36C25725Q0505 0004.pdf

PDF 471 KB Posted

Attached to
SPS Steam Water Testing Federal contract opportunity
Solicitation number
Not on record
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17

About this file

This document is a contract amendment (Standard Form 30) for a water quality testing contract with the Department of Veterans Affairs, specifically for the North Texas Healthcare System. The amendment (number 0004) serves to post additional questions and answers, provide an updated delivery/schedule, and update the Statement of Work (SOW) with highlighted changes.

The contract involves steam water quality testing at the Harlingen VA Facility, focusing on ensuring water quality monitoring requirements are met under ANSI/AAMI ST108 standards. Key requirements include monthly testing of utility, critical, and steam water at various points of use, with provisions for up to 15 re-testing actions per year and emergency 3-day performance testing when critical water lines experience changes or damages. The base contract period is 12 months with four optional year periods, covering water sampling, testing, and reporting activities to confirm water and steam used in sterilization processes meet specified specifications. The testing will be performed at the Harlingen Care Center located at 2601 Veterans Dr., Harlingen, TX 78559.

View the file

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5. PROJECT NUMBER (if applicable)

CODE 7. ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER 3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE OF PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO. 1. CONTRACT ID CODE

FACILITY CODE CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office. is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER 16A. NAME AND TITLE OF CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30 PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243

(Type or print) (Type or print)

(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code)

(If other than Item 6)

(Specify type of modification and authority)

(such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer)

1 14

0004 05-13-2025

36C257

Department of Veterans Affairs NCO 17 North Texas Healthcare System Regional Procurement Office West (RPO-W) 124 E. Hwy 67, Suite 100 Duncanville TX 75137

36C257

NCO 17

Department of Veterans Affairs North Texas Veterans Health Care Center 124 E. Hwy 67, Suite 100 Duncanville TX 75137

36C25725Q0505

X

X X

See CONTINUATION Page

X 1

The purpose of this amendment is to:

Post additional questions & answers Provide updated delivery/schedule Provide updated SOW with highlighted changes.

CONTINUATION PAGE

Questions & Answers

1. Is this a bacteria sample re-test or a system water quality re-test?

2. Are we to assume re-testing at all sample ports for each re-test?

Answer:

The purpose of this solicitation is to perform water & steam (as condensate) testing to ensure the water quality monitoring requirements are met under ST-108.

The purpose of CLIN 0002 is to account for any re-testing that may be required up to 15 per year( Please note the SOW has been updated to 15 per year instead of 10 per year). Re- Testing would only be required for the ports that failed.

CLIN 0003 will be added for emergency 3 days performance testing. The VA can request for emergency or on-call testing to allow for performance qualification testing (IAW Table 2) in the event of any changes or modifications to the critical water system such as: addition or deduction of SPS equipment which use critical water, changes to critical water lines, or breaks or damages to the critical water line which exposes the water loop to open air (no longer a closed loop).

Performance qualification testing is demonstrated below for the three days of testing. Water sample locations shall comply with Section 9.3 of ANSI / AAMI ST-108.

3. We are interpreting section 3.2 and have estimated the testing panels for critical, utility and steam. Each require a different test panel and that is not shown on the price/cost schedule on the two item numbers in the government pricing schedule.

Answer:

You can price individually on your end but please roll it up into the one CLIN for the monthly cost for Testing.

Updated Delivery/Schedule

ITEM INFORMATION

ITEM

NUMBER

DESCRIPTION OF

SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT

12.00 MO __________________ __________________

Steam Water Quality testing at Harlingen VA Facility. See SOW for testing points.

Contract Period: Base POP Begin: 07-01-2025 POP End: 06-30-2026 PRINCIPAL NAICS CODE: 541380 - Testing Laboratories and Services PRODUCT/SERVICE CODE: J046 - Maintenance, Repair, and Rebuilding of Equipment - Water Purification and Sewage Treatment Equipment

1.00 YR __________________ __________________

re-testing for up to 15 actions per year

Contract Period: Base POP Begin: 07-01-2025 POP End: 06-30-2026 PRINCIPAL NAICS CODE: 541380 - Testing Laboratories and Services PRODUCT/SERVICE CODE: J046 - Maintenance, Repair, and

Emergency Performance testing- for Three days of testing. Please reference SOW Contract Period: Base POP Begin: 07-01-2025 POP End: 06-30-2026 testing points.

Contract Period: Option 1 POP Begin: 07-01-2026 POP End: 06-30-2027 PRINCIPAL NAICS CODE: 541380 - Testing Laboratories and Services PRODUCT/SERVICE CODE: J046 - Maintenance, Repair, and

Contract Period: Option 1 POP Begin: 07-01-2026 POP End: 06-30-2027 PRINCIPAL NAICS CODE: 541380 - Testing Laboratories and Services PRODUCT/SERVICE CODE: J046 - Maintenance, Repair, and reference SOW Contract Period: Option 1 POP Begin: 07-01-2026 POP End: 06-30-2027 testing points.

Contract Period: Option 2 POP Begin: 07-01-2027 POP End: 06-30-2028 PRINCIPAL NAICS CODE: 541380 - Testing Laboratories and Services PRODUCT/SERVICE CODE: J046 - Maintenance, Repair, and

Contract Period: Option 2 POP Begin: 07-01-2027 POP End: 06-30-2028 PRINCIPAL NAICS CODE: 541380 - Testing Laboratories and Services PRODUCT/SERVICE CODE: J046 - Maintenance, Repair, and reference SOW Contract Period: Option 2 POP Begin: 07-01-2027 POP End: 06-30-2028 testing points.

Contract Period: Option 3 POP Begin: 07-01-2028 POP End: 06-30-2029 PRINCIPAL NAICS CODE: 541380 - Testing Laboratories and Services PRODUCT/SERVICE CODE: J046 - Maintenance, Repair, and Rebuilding of Equipment - Water Purification and Sewage Treatment

LOCAL STOCK NUMBER: 600

Contract Period: Option 3 POP Begin: 07-01-2027 POP End: 06-30-2028 PRINCIPAL NAICS CODE: 541380 - Testing Laboratories and Services PRODUCT/SERVICE CODE: J046 - Maintenance, Repair, and reference SOW Contract Period: Option 3 testing points.

Contract Period: Option 4 POP Begin: 07-01-2029 POP End: 06-30-2030 PRINCIPAL NAICS CODE: 541380 - Testing Laboratories and Services PRODUCT/SERVICE CODE: J046 - Maintenance, Repair, and Rebuilding of Equipment - Water Purification and Sewage Treatment

LOCAL STOCK NUMBER: 600

Contract Period: Option 4 POP Begin: 07-01-2027 POP End: 06-30-2028 PRINCIPAL NAICS CODE: 541380 - Testing Laboratories and Services PRODUCT/SERVICE CODE: J046 - Maintenance, Repair, and reference SOW Contract Period: Option 4

GRAND TOTAL __________________

Updated Statement of Work

1. BACKGROUND. Texas Valley Coastal Bend Health Care System (TVCBHCS) is required to complete testing on all water and steam systems utilized in the reprocessing of reusable medical devices. Water impurities can have adverse effects on medical devices and patient outcomes. The requirements of Association for the Advancement of Medical Instrumentation (AAMI) ST108: Water for the Processing of Medical Devices are intended to mitigate the risks associated with water identified to be in improper quality. The TVCBHCS requires water quality testing to meet the standards of ANSI/AAMI ST108 for reprocessing of reusable medical equipment. This Sterile Processing Service is located at 2601 Veterans Dr., Harlingen, TX, 78559. Services shall be in accordance with the provisions listed in the contract.

1.1 ANSI/AAMI ST108 Standard (Current Edition), which governs the processes and requirements for Sterile Processing, added requirements to the roster of locations needing monthly critical water sampling and daily conductivity monitoring. Per the standard, the requirement is to test critical water at “every point of use” each month.

2. SCOPE OF WORK. The purpose of this service is to provide for the sampling and testing of water and provide a report for the analysis of the results to ensure effective water quality for processing medical devices. The testing shall include testing of critical water and steam, as condensate, per guidance published in ANSI/AAMI ST108: Water for the Processing of Medical Devices. The Contractor shall use the current edition of this standard for the life of the contract unless informed differently.

2.1 ANSI/AAMI ST108 covers the minimum requirements for the quality of water and steam condensate necessary to effectively process medical devices.

2.3 The Contractor will perform testing and verification of water and steam condensate used in the VA's sterile processing departments to ensure compliance with ANSI/AAMI ST108 standards. The services will include sampling, testing, and reporting activities to confirm that water and steam used in sterilization processes meet the required specifications. It is the responsibility of the contractor to bring all the appropriate equipment and/or supplies necessary to complete the work; the VA shall not furnish any supplies or equipment for the performance of the contract

2.4 PERIOD OF PERFORMANCE. Base Year for a period of 12 months with 4 option year period. (TBD upon contract award)

2.5 SITE VISIT. A site visit will be scheduled to view areas that require testing for location 2601 Veterans Dr., Harlingen TX 78559.

3. CONTRACTOR RESPONSIBILITY. The Contractor shall perform water and steam condensate testing in accordance with Table 5 & Table 6 at every point of use. The locations for these services are listed in subsequent section of this SOW.

3.1 The Contractor shall provide all labor, materials, tools, equipment, applicable state licenses and permits to accomplish the requirements.

3.1.1 The Contractor shall provide all testing requirements as outlined by ANSI/AAMI ST108 for testing quantity guides.

3.1.2 The Contractor shall provide a fully qualified Laboratory for processing of water samples to meet all metrics of ANSI/AAMI ST108. The Laboratories shall be accredited by the Texas Commission on Environmental Quality (TECQ) and National Environmental Laboratory Accreditation Program (NELAP). The Contractor shall ensure all laboratory certificates, credentials and capabilities are provided to the Contracting Officers Representative (COR).

3.1.3 The Contractor shall follow testing frequencies in Tables 5 & 6 as described in ANSI/AAMI ST108. For any testing completed, provide the results/reports back to the VHA as soon as possible after completion but no later than seven (7) calendar days.

3.1.4 The Contractor shall perform water and steam testing & monitoring program as described for the following locations:

3.1.4.1 Harlingen Care Center (HCC) – 2601 Veterans Dr., Harlingen, TX

• Perform all testing per the reference Table 4 in ANSI/AAMI ST108.

• Perform all tests to comply with the frequencies required and listed in the associated

ANSI/AAMI ST108 Tables 5 & 6.

• Provide Report of Analysis within seven (7) calendar days of sampling. Identify all results which are in compliance with ANSI/AAMI ST108 standards in green and all results which are out of tolerance in red.

• Allow up to 15 re-testing actions per year.

• Emergency 3-day testing when changes to critical water lines, or breaks, damages to the critical waterline which exposes the water loop to open air a Performance qualification testing (IAW Table 2) will be required. Allow Up to 3, Three-day Testing’s per year.( See Performance Testing Table)

3.2 WATER TEST POINTS OF USE BY LOCATION

3.2.1 Harlingen Care Center (HCC). Testing points shall be in SPS Areas:

• Two decontamination sinks with each having hot and cold lines, and one critical water.

• One decontamination sink with hot and cold lines.

• Two washer-disinfector with hot and cold lines, and one critical water.

• One cart washer with hot and cold lines, and one critical water.

• Two ultrasonics with each having hot lines and one critical water.

• Two medivators with utility water.

• Three Sterilizers with steam sample ports (steam as condensate).

3.3 The Contractor shall provide a rapid means of immediate shipping of all water samples to the approved laboratory.

3.4 The Contractor shall provide a final report of all findings (i.e. sample locations, results, parameters) and compliance status within seven calendar days of sampling.

3.6 The Contractor shall provide immediate notification of any positive samples over the bacteria and endotoxin threshold per ANSI/AAMI ST108 no later than 24 hours of the finding by both telephone and email.

3.7 The Contractor shall provide an annual balance of Emergency / On-call tests for any locations that require re-testing or per direction of VA.

3.8 The Contractor shall ensure Contractor staff adhere to all PPE requirements when testing in PPE required areas.

3.9 Contractor shall submit a sampling procedure for concurrence and compliance with flushing and sampling per Annex H.

3.10 The Contractor shall enforce a strict chain of custody of sampling so that samples are secured and shipped by one dedicated technician.

3.11 The Contractor shall immediately notify VA of any breach in chain of custody or shipping issues that would render the samples un-usable.

3.12 The Contractor shall coordinate with VA on providing re-tests.

3.13 The Contractor’s personnel shall obtain a short-term identification badge issued by the VA designee.

3.13.1 The badge shall be worn by the individual and prominently displayed while on VA property.

3.13.2 No employee of the Contractor shall enter the project site without a valid identification badge issued by the VA.

3.13.3 To obtain a short-term identification badge, Contractor personnel shall present to the VA designee a valid (non-expired) photo identification issued by a US federal, State, or local government agency.

3.14 The Contractor shall deliver sufficient technical documentation with all data deliverables to permit the VA to use the data.

3.15 The Contractor shall only follow guidance as provided by the Contracting Officer assigned and coordinate all work with the Contracting Officer’s Representative (COR).

4. CONTRACTOR COMMUNICATION. The Contractor shall be available for servicing equipment during normal hours of operations. The Contractor shall reply and respond to routine communications within 48 hours and emergency communication within four (4) hours. The Contractor shall communicate any results that are out of compliance within 24 hours of the finding by both telephone and email. The Contractor shall provide a schedule at the beginning of each option year, specifying pre-planned dates for routine monitoring and testing. This schedule must be submitted for review and acceptance by the COR. Any changes to the approved dates must be communicated no later than 48 hours in advance. Please note that communications cannot be performed over weekends, or federal holidays.

5. SAMPLING REQUIREMENTS. The Contractor shall refer to the below tables for sampling requirements required by ANSI/AAMI ST108 testing for utility water, critical water, and steam.

5.1 Three (3) categories of water quality per ANSI/AAMI ST 108. Three (3) categories of water quality in terms of the characteristics that are important for medical device processing and the level of treatment that may be needed.

5.1.1 Utility Water: Water as it comes from the tap that can require further treatment at the facility to achieve water quality measurement values outlined in Table 2. This water is mainly used for flushing, washing, and intermediate rinsing (e.g., rinsing between cleaning and disinfection).

5.1.2 Critical Water: Water that meets the water quality measurement values detailed in Table 1; to achieve these values, the water generally requires extensive treatment by a multi-step process that can include a pretreatment, does include primary treatment (e.g., RO and/or DI), storage, distribution, and can include final treatment to provide a level of assurance that microorganisms and inorganic and organic material are removed from the water. This water is mainly used for the final rinse after high-level disinfection, for the final rinse for critical devices prior to sterilization and feedwater for process steam production.

5.1.3 Steam: vaporized water that is produced by a centralized boiler or a generator/heat exchanger near the sterilizer. When the steam is tested as a condensate, it should meet the specified criteria as defined in Table 2 below.

Table 2 ANSI/AAMI ST108 Categories and performance qualification levels of water quality for medical device processing

Water Quality Measurement

Units

Utility Water

Critical Water

Steam* pH @ 25 °C: pH 6.5 – 9.5 5.0 – 7.5 5.0 – 9.2** Total Alkalinity mg CaCO3/L <400 <8 <8 Bacteria CFU/mL <500*** <10 N/A Endotoxin EU/mL N/A*** <10 N/A Total Organic Carbon (TOC) mg/L (ppm) N/A <1.0 N/A

Color and Turbidity

Visual Colorless, clear, without sediment

Colorless, clear, without sediment

Colorless, clear, without sediment

Ionic Contaminants Aluminum mg/L <0.1 <0.1 <0.1

Water Quality Measurement

Units

Utility Water

Critical Water

Steam*

Chloride mg/L <250 <1 <1 Conductivity μS/cm <500 <10 <10 Copper mg/L <0.1 <0.1 <0.1 Iron mg/L <0.1 <0.1 <0.1 Manganese mg/L <0.1 <0.1 <0.1 Nitrate mg/L <10 <1 <1 Phosphate mg/L <5 <1 <1 Sulfate mg/L <150 <1 <1 Silicate mg/L <50 <1 <1 Total Hardness mg CaCO3/L <150**** <1 <1 Zinc mg/L <0.1 <0.1 <0.1

* Steam parameters are for monitoring as steam condensate ** For local steam generation, the condensate pH should be 5.0 to 7.5. For boiler-treated steam, most boilers should be treated to maintain a condensate pH of 7.5 to 9.2 *** When Utility Water is used after chemical high-level disinfection as a final rinse, the bacteria should be <10 CFU/mL and endotoxin <10 EU/mL **** If hardness is greater than 150 mg/L a water softener is recommended unless used for washing where the cleaning chemistry is capable of handling higher levels of hardness NOTE: See ANSI/AAMI ST108, Annex D for additional information.

5.2 Water Quality Routine Monitoring.

5.2.1 The Contractor shall ensure water quality and equipment maintenance requirements are compliant with the guidelines and parameters established by ANSI/AAMI ST108.

5.2.2 The Contractor shall provide for routine monitoring to ensure compliance with the defined compliance parameters as defined in Table 4.

Table 4 ANSI/AAMI ST108 Table for Water Quality monitoring requirements.

Water Quality Measurement

Units Utility Water Critical Water Steam* pH @ 25 °C: pH 6.5 – 9.5 5.0 – 7.5 5.0 – 9.2** Conductivity μS/cm <500 <10 <10 Total Alkalinity mg CaCO3/L <400 <8 <8 Total Hardness mg CaCO3/L <150 <1 <1 Bacteria CFU/mL <500 <10 N/A Endotoxin EU/mL N/A <10 N/A Color and Turbidity

Visual Colorless, clear, without sediment

Colorless, clear, without sediment

Colorless, clear, without sediment

*NOTE 1 Sampled as Steam condensate.

**NOTE 2 The pH range for steam is wider than for Critical Water as some steam may not be generated locally but from a centralized/facility system. The need to add chemicals to the boiler and the steam to travel distances over black iron piping may result in higher pH requirements. A pH <7.5 in these systems should be avoided.

5.3 The Contractor shall comply with the frequency of testing and monitoring as defined in Table 5 & Table 6.

Table 5 ANSI/AAMI ST108 Frequency for water quality monitoring.

Minimum frequency of testing* Water Quality Measurement

Type of Testing Routine monitoring sample site

Utility Water Critical Water pH pH meter** of Colorimetric dipsticks (sample tested within 15 minutes)

After the last treatment step

Quarterly Monthly

Conductivity Conductivity meter (in line or by measurement of a collected sample)

After the last treatment step, Storage tanks (if used)

Quarterly Monthly

Total Alkalinity

Colorimetric dipsticks Alkalinity test kit**

After the last treatment step, Storage tanks (if used)

Quarterly Monthly

Total Hardness Determination of PPM as CaCO3 by Colorimetric dipsticks, Titration kit**, or Handheld meter**

After the last treatment step

Quarterly Monthly

Bacteria Heterotrophic plate count (see Annex H)

Loop out and loop return points

N/A Monthly

Endotoxin LAL text (see Annex H)

Loop out and loop return points

N/A Monthly

*NOTE 1 The recommendations for frequency of testing in this table are the recommended minimum frequency. If problems or issues arise with the water quality, it may be necessary to increase the frequency until they are resolved.

**NOTE 2 When using these tests, the user should carefully follow the manufacturer’s written IFU for accurate results. When measuring Critical Water levels, the water sample must be filled to the brim of these test kits, sealed, and if the sample is hot, allowed to cool to room temperature before testing. Testing within 15 minutes of sample collection prevents carbon dioxide absorption that can result in an accurate pH.

Table 6 ANSI/AAMI ST108 Frequency for water quality monitoring at point-of-water use

Minimum frequency of testing*

Water Quality Measurement

Type of Testing Routine monitoring sample site

Utility Water

Critical Water

Steam pH pH meter** of Colorimetric dipsticks (sample tested within 15 minutes)

After the point the distribution loop enters the processing area or first POU on the distribution loop

Quarterly Monthly Quarterly

Conductivity Conductivity meter (in line or by measurement of a collected sample)

After the point the distribution loop enters the processing area or first POU on the distribution loop

Quarterly Monthly Quarterly

Total Alkalinity

Colorimetric dipsticks Alkalinity test kit**

After the point the distribution loop enters the processing area or first POU on the distribution loop

Quarterly Monthly Quarterly

Total Hardness Determination of PPM as CaCO3 by Colorimetric dipsticks, Titration kit**, or Handheld meter**

After the point the distribution loop enters the processing area or first POU on the distribution loop

Quarterly Monthly Quarterly

Bacteria Heterotrophic plate count (see Annex H)

Each location of point-of-use in department

Quarterly Monthly N/A

Endotoxin LAL text (see Annex H) Each location of point-of-use in department

N/A Monthly N/A

Visual Inspection Visual inspection of inside of equipment - Look for residue, staining, scaling and discoloration (Annex I)

Spray Arms/Inside Chamber Walls/Inside Interior of Machine

Daily Daily Daily

*NOTE 1 The recommendations for frequency of testing in this table are the recommended minimum frequency. If problems or issues arise with the water quality, it may be necessary to increase the frequency until they are resolved.

**NOTE 2 Test type need to measure Critical Water and Steam levels. Steam condensate must be filled to the brim, sealed, and allowed to cool before testing to prevent carbon dioxide absorption.

6. SAMPLING PER ANSI/AAMI ST108 GUIDANCE.

6.1 Sample Collection: The Contractor shall perform sample collections per Annex H of

ANSI/AAMI ST108.

6.2 Performance Testing: The contractor shall perform sample collections for three consecutive days for emergency’s only when there are changes to critical waterlines or breaks or damages to the critical water line which exposes the water loop to open air.

Sample Performance testing

7. HOURS OF OPERATION. Normal duty hours are 8:00 a.m. through 4:30 p.m., Monday through Friday, not including federal holidays.

The Government observes the listed days as holidays. If the holiday falls on a Saturday, the Friday before is the holiday. If the holiday falls on a Sunday, the Monday after is the holiday:

New Year's Day January 1st Martin Luther King's Birthday Third Monday in January Washington’s Birthday Third Monday in February Memorial Day Last Monday in May Juneteenth June 19th Independence Day July 4th Labor Day First Monday in September Columbus Day Second Monday in October Veterans Day November 11th Thanksgiving Day Fourth Thursday in November Christmas December 25th

In addition to the days designated as holidays, the Government observes the following days:

• Any other day designated by Federal Statute

• Any other day designated by Executive Order

• Any other day designated by the President’s Proclamation

The observance of such days by Contractor personnel shall not otherwise be a reason for an additional period of performance, or entitlement of compensation. In the event the Contractor’s personnel work during the holiday, they may be reimbursed by the Contractor, however, no form of holiday or other premium compensation will be reimbursed either as a direct or indirect cost, other than their normal compensation for the time worked.

8. SAFETY PLAN. The Contractor shall be required to provide a safety plan for the work to be performed under this contract before starting physical work. The plan shall include an Activity Hazard Analysis (AHA) focused on the essential areas of work where risks must be addressed.

The Contractor shall provide Personal Protective Equipment (PPE) for the Contractor’s employees and ensure all Contractor employees to include sub-contractors have and properly use the PPE. The Contractor shall follow all OSHA (Office of Safety and Health Administration) and VHA Safety Guidelines and ensure their contracted personnel and all sub-contractors adhere to OSHA safety guidelines. The contractor shall be responsible to follow OSHA guidelines

9. TUBERCULOSIS (TB) SCREENING.

9.1 The Contractor shall provide written certification that all Contractor employees assigned to the worksite have had a pre-placement negative tuberculin screening within 90 days prior to assignment.

9.2 The Contractors shall be required to show documentation of negative TB screening for any additional workers who are added after the 90-day requirement before Contractor employees are allowed to work on the work site. NOTE: This can be the Center for Disease Control (CDC) and Prevention and two-step skin testing or a Food and Drug Administration (FDA)-approved blood test.

9.3 Contract employees manifesting positive screening reactions to the tuberculin shall be examined according to current CDC guidelines prior to working on VHA property. If a Contractors employee is found without evidence of active (infectious) pulmonary TB, a statement documenting examination by a physician shall be on file with the Contractor noting that the employee with a positive tuberculin screening test is without evidence of active (infectious) pulmonary TB. If the employee is found with evidence of active (infectious) pulmonary TB, the Contractor employee shall be required to obtain treatment with a subsequent statement to the fact on file with the employer before being allowed to return to work on VHA property.

(End Statement of Work)

End of Document

ITEM INFORMATION

File details come from the government source that posted it. Updated .