36C25020Q0783 0002.docx
DOCX document 218 KB Posted
- Attached to
- 6530--AUDIOLOGY BOOTHS Federal contract opportunity
- Solicitation number
- 36C25020Q0783
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25020Q0783 0001.docx | DOCX document | |
| 36C25020Q0783.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Contract Opportunity Amendment to a Previous Combined Solicitation
PRODUCT SERVICE CODE
SUBJECT
CONTRACTING OFFICE'S
ZIP-CODE
SOLICITATION NUMBER
BASE NOTICE TYPE
RESPONSE DATE/TIME/ZONE
ARCHIVE
DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
SET-ASIDE
NAICS CODE
CONTRACTING OFFICE
ADDRESS
POINT OF CONTACT
(POC Information Automatically Filled from User Profile Unless Entered)
DESCRIPTION
See Attachment
AGENCY'S URL
URL DESCRIPTION
AGENCY CONTACT'S EMAIL
ADDRESS
EMAIL DESCRIPTION
ADDRESS
POSTAL CODE
COUNTRY
ADDITIONAL INFORMATION
GENERAL INFORMATION
PLACE OF PERFORMANCE
* = Required Field Contract Opportunity Amendment to a Previous Combined Solicitation
AUDIOLOGY BOOTHS
46240 36C25020Q0783 09-07-2020 17:00
EASTERN TIME, NEW YORK, USA
N
SDVOSBC
334510 Department of Veterans Affairs Network Contracting Office 10 8888 Keystone Crossing Suite 1100 Indianapolis IN 46240 Erik Fallo Erik.Fallo@va.gov Marion VAMC Bldg 138 1700 E 38th St Marion
IN
46953
USA
Q&A
1. Will there being ventilation to the roof? (Yes) No exhaust.
1. Booth & Control in the same area? (Yes) yes.
1. How many drops for HVAC, intact and exhaust, and locations? (Qty of 6 – 2 above each booth, location TBD). Supply and return for each section, attached sheet indicates 2 supplies and 1 return though.
1. HVAC locations of supply and return, and qty into the booths? (John to mark on drawings and provide). Location doesn’t matter just mark them either return or supply.
1. Elevator height for booths and location? (Eng.) 92”
1. Door to booth comes to the platform? The platform was built based on the attached drawing which called for a 4 ¾ rise.
1. Carpet and padding total thickness into booths? To ensure flush with doors or will shimmy needed? Ramp floor covering is to be Luxury Vinyl Tile.
1. Height & width of booth door standard spec for ADA? VA follows Architectural Building Act (ABA).
1. Will each booth be on own electrical circuit? Lighting power outside of booth? Pigtail? Dedicated 20 amp circuit to each suite pig tail.
1. Carpet needed in the booth? Attached sample of carpeting being used in the rest of 4th floor.
1. Phone and Data Lines into control room, number of cables? 4 data cables to each suite, phones will run thru the computer port.
12.) Width of platform at window isn’t wide enough for booth doors to open properly. The platform area at the window will be extended to match (the wall on left side of picture).