36C25020B0025-0001002.pdf
PDF Posted
- Attached to
- Y1DA--VA Site Prep for Intevo Project 541-18-505 (Construction) Federal contract opportunity
- Solicitation number
- 36C25020B0025
About this file
36C25020B0025 0001 S02. Drawings.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25020B0025-0006000.docx | DOCX document | |
| 36C25020B0025-0005000.docx | DOCX document | |
| 36C25020B0025-0005001.pdf | ||
| 36C25020B0025-0004000.docx | DOCX document | |
| 36C25020B0025-0003000.docx | DOCX document | |
| 36C25020B0025-0002001.docx | DOCX document | |
| 36C25020B0025-0001009.pdf | ||
| 36C25020B0025-0001005.pdf | ||
| 36C25020B0025-0001010.docx | DOCX document | |
| 36C25020B0025-0001008.docx | DOCX document | |
| 36C25020B0025-0001007.docx | DOCX document | |
| 36C25020B0025-0001001.pdf | ||
| 36C25020B0025-0001000.docx | DOCX document | |
| 36C25020B0025-0001003.pdf | ||
| 36C25020B0025-0001006.pdf | ||
| 36C25020B0025-0001011.pdf | ||
| 36C25020B0025-0001004.pdf | ||
| 36C25020B0025-008.docx | DOCX document |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
V
20'-0"±
E X
C
O N
C R
E T
E
B
E A
M
EX. CONCRETE BEAM
3'-0"±3'-0"±
EX. CONCRETE
JOIST
E X
C
O N
C R
E T
E
J O
I S
T
L6x6x5/16 BELOW ANCHORAGE
LOCATIONS - SEE DETAILS (THIS
SHEET) FOR MORE INFORMATION
(TYP.)
EXISTING BASEMENT FRAMING PARTIAL PLAN
1/4"=1'-0"
GANTRY (8,650 LBS.)
FRONT PHS (2,750 LBS.)
REAR PHS (385 LBS.)
EX. CONCRETE
JOIST
NOTE:
CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND
CONDITIONS IN FIELD PRIOR TO FABRICATION.
LEGEND:
INDICATES 12" DEEP CONCRETE
JOISTS WITH 3" FLANGE.
MEDICAL UNIT ANCHORAGE
LOCATION - COORDINATE WITH
MEDICAL UNIT SUPPLIER (TYP.)
E X
C
O N
C R
E T
E
B
E A
M
8"± 2'-6"± 8"±
TYPICAL ANCHORAGE DETAIL AT JOIST FLANGE
1 1/2"=1'-0"
8"±
TYPICAL ANCHORAGE DETAIL AT JOIST STEM
1 1/2"=1'-0"
ANCHORS TO OCCUR WITHIN
THE TAPERED EDGES OF THE
JOIST STEM
TYPICAL ANCHORAGE DETAIL AT CONCRETE BEAM
1 1/2"=1'-0"
/2
MEDICAL UNIT - COORDINATE
WITH ARCH. & UNIT SUPPLIER
DRAWINGS
L6x6x5/16 - TAPER
ENDS TO MATCH
SLOPE OF JOIST
STEM PROFILE
(2) 1/2"ø HILTI KWIK BOLT TZ
WITH 3 5/8" MIN. EMBED (TYP.)
L3x3x5/16 x 6" LONG WITH
(2) 3/4"ø (A325) BOLTS TO
L6x6 (TYP.)
PROVIDE 3"x3"
SQUARE PLATE
WASHER SHIM
PLATES AS
REQUIRED
EX. CONCRETE JOIST
THRU-BOLT (A325) - SEE
MEDICAL UNIT DRAWINGS FOR
REQUIRED BOLT DIAMTER
EX. CONCRETE JOIST
MEDICAL UNIT - COORDINATE
WITH ARCH. & UNIT SUPPLIER
DRAWINGS
HILTI HY-200 ADHESIVE
ANCHOR WITH 2 3/4"EMBED &
MIN. SPACING OF 1 7/8" WHERE
MULTIPLE ANCHORS OCCUR -
SEE MEDICAL UNIT DRAWINGS
FOR BOLT DIAMETERS
HILTI HY-200 ADHESIVE
ANCHOR WITH 8" EMBED - SEE
MEDICAL UNIT DRAWINGS FOR
BOLT DIAMETERS
MEDICAL UNIT - COORDINATE
WITH ARCH. & UNIT SUPPLIER
DRAWINGS
EX. CONCRETE JOIST
EX. WIRE MESHEX. WIRE MESHEX. WIRE MESH
3'-0"±
GENERAL
1. All new construction shall comply with the Contract Documents and the Building
Code.
2. Typical details and general notes apply to all parts of the work except where specifically detailed or unless otherwise noted.
3. The structural drawings illustrate structural members. Refer to architectural, mechanical, and electrical drawings for non-structural items which require special provisions during the construction of the structural members.
4. Drawings are not to be scaled.
5. The Contractor shall verify and be responsible for all dimensions and conditions which impact the work. Field verify sizes, elevations, hole locations, etc., prior to fabrication.
6. The Contractor shall carefully review the drawings to identify the scope of work required, visit the site to relate the scope of work to existing conditions and determine the extent to which those conditions and physical surroundings will impact the work.
7. Existing conditions as shown on these plans are for reference only. The Contractor is required to field verify all existing conditions prior to construction.
8. The Contractor shall resolve any conflicts on the drawings with the
Architect/Engineer before proceeding with the work.
9. Any deviation, modification, or substitution from the approved set of structural drawings shall be submitted to the Owner, Architect, and Engineer for review/approval prior to its use or inclusion on the shop drawings.
10. The Contractor shall provide means, method, techniques, sequence, and procedure of construction as required.
11. The Contractor shall protect all work, materials, and equipment from damage and shall provide proper storage facilities for materials and equipment during construction.
DESIGN STRESSES
Structural steel other shapes (ASTM A36) -------------------------------------------- Fy = 36,000 psi
DESIGN LOADS (OBC 2017)
Floor live load --------------------------------------------------------------------------------- 50 psf
Equipment loads ----------------------------------------------------------------------------- As Noted
CODES AND STANDARDS
1. New construction has been designed to, and shall be constructed in accordance with the following building codes and standards:
A. 2017 Ohio Building Code (OBC 2017)
B. City of Cleveland, Ohio, Code of Ordinances
C. ASCE 7-10, Minimum Design Loads for Buildings and Other Structures
2. Unless explicitly modified in the Contract Drawings and Specifications, the Contractor shall comply with provisions of:
A. ACI 301-10, Specifications for Structural Concrete
B. ACI 318-14, Building Code Requirements for Structural Concrete
C. AISC 360-10, Specification for Structural Steel Buildings
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
1-S1
PARTIAL FRAMING PLAN,
SECTIONS, & NOTES
A
F i l e
P a t h
P
M
FINAL CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT OF RECORD: STAMPCONSULTANTS:
321 4 5 6 7 8 9 10
CLEVELAND, OHIO
541-18-505
Project Director
10/11/2019 JTL MCDRevisions: Date:
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF
THIS DESIGN AND THESE CONSTRUCTION
DOCUMENTS FOR PURPOSES OTHER THAN
THE SPECIFIC PROJECT NAMED HEREIN IS
STRICTLY PROHIBITED WITHOUT THE
EXPRESSED WRITTEN CONSENT OF
PERSPECTUS ARCHITECTURE.
13212 Shaker Square Suite Cleveland, Ohio 44120
P. 216.752.1800 F.216.752.3833
Consulting Engineers
BARBER & HOFFMAN, INC.
2217 East 9th Street, Suite 350
Cleveland OH 44115-1257
216-875-0100/ (F) 216-875-0111 barberhoffman.com
100% Construction Document Submission 9/13/19
PROJECT
SCOPE
KEY PLAN - BASEMENT
Scale = None
B
A
C
B
A
C
B-B2
B-B3
B-B4
B-B5
B-C2
B-C3
B-C4
B-C5
B-D2
B-D3
B-D4
B-E3
B-E4
B-E2
B-F3
B-F4
TRUE
NORTH
C:\ArchiComp\Chrisprjold\PhilNew\VAMU\FromTim\Logos\FFH ICON (GRAY).tif
VA SITE PREP FOR
INTEVO
Final Construction Document Submission 10/11/19
BARBER & HOFFMAN, INC.
S
T
A
T
E
O
F
O
H
I
O
P R
O
F
E
S
S
I
O
N A
L
E
N
G
I
N
E
E
R
R
E
G
I
S
T
E
R
E
D
JON T.
LEUTHAEUSER
E-65601
AutoCAD SHX Text
TEL. (440) 546-9696
AutoCAD SHX Text
BROADVIEW HTS., OHIO 44147
AutoCAD SHX Text
672 EAST ROYALTON ROAD
AutoCAD SHX Text
FAX: (440) 546-9699
AutoCAD SHX Text
FREDRICK, FREDRICK & HELLER
AutoCAD SHX Text
ENGINEERS, INC.
BC-446A
Nuc Med
BC-474
0B
BC-446
Hot LabRad Waste
Nuc Med
BC-475
Thyroid Uptake
BC-448
Inject
BC-461
A. LOCATIONS AND ROUTING OF EXISTING PIPING, DUCTWORK AND EQUIPMENT IS PRESUMED FROM
EXISTING DRAWINGS. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ALL PRIOR TO COMMENCEMENT
OF CONSTRUCTION. NOTIFY ENGINEER OF ANY CONDITIONS WHICH WILL NOT PERMIT THE WORK TO BE
PERFORMED AS INDICATED ON THESE DRAWINGS.
B. REFER TO SPECIFICATIONS FOR SHUTDOWN NOTIFICATION REQUIREMENTS.
C. PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW WALL MOUNTED DEVICES WITH OWNER AND
ARCHITECT. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR PRECISE LOCATION OF CEILING
MOUNTED DEVICES.
D. PROVIDE ADEQUATE SERVICE CLEARANCE FOR ALL EQUIPMENT. REFER TO INSTRUCTIONS FROM THE
EQUIPMENT MANUFACTURER.
E. NEW PIPING SHALL NOT BE ROUTED ABOVE ELECTRICAL PANELS. REFER TO ELECTRICAL DRAWINGS FOR
LOCATION OF PANELS.
F. THE FIRE SUPPRESSION CONTRACTOR SHALL PROVIDE DETAILED DESIGN OF THE SPRINKLER SYSTEM.
REFER TO SPECIFICATIONS.
G. UNLESS OTHERWISE NOTED NEW SPRINKLERS SHALL BE AS FOLLOWS:
G.1. AREAS WITH CEILINGS: SEMI-RECESSED WITH CHROME ESCUTCHEONS.
G.2. EXPOSED STRUCTURE: UPRIGHT OR PENDENT TYPE.
H. THE FIRE PROTECTION SYSTEM IS PERFORMANCE SPECIFIED. ALL SPRINKLER PIPE SIZES SHALL BE
DETERMINED BY FIRE PROTECTION CONTRACTOR, BASED ON HYDRAULIC CALCULATIONS.
I. PROVIDE SUPPLEMENTAL DRAINS AS NECESSARY TO PROVIDE 100% SYSTEM DRAINAGE. LOCATE DRAINS
ABOVE ACCESSIBLE CEILINGS.
J. REFER TO ARCHITECTURAL PLANS FOR EXACT PHASING REQUIREMENTS.
K. REFER TO SPECIFICATIONS FOR FIRE SUPPRESSION HAZARD OCCUPANCY CLASSIFICATIONS.
L. SPRINKLER PIPING SHALL BE A MINIMUM OF ONE INCH.
M. UNLESS OTHERWISE STATED ON DRAWINGS OR IN THE SPECIFICATIONS, ALL SPRINKLER HEADS SHALL BE
QUICK RESPONSE.
N. ALL HEADS SHALL BE UL LISTED AND FM APPROVED.
O. ALL SPRINKLER HEADS LOCATED IN CEILING TILES SHALL BE LOCATED IN CENTER OF THE CEILING TILE.
P. ALL SPRINKLER ZONES SHALL MATCH SMOKE COMPARTMENTS. REFER TO ARCHITECTURAL PLANS FOR
INFORMATION ON SMOKE COMPARTMENTS, SMOKE PARTITIONS AND FIRE BARRIERS.
Q. CONTRACTOR SHALL REMOVE AND REPLACE CEILING TILES AND GRID AS REQUIRED TO COMPLETE
DEMOLITION AND NEW WORK IN AREAS OUTSIDE OF RENOVATION PROJECT. CONTRACTOR SHALL BE
RESPONSIBLE FOR REPLACING ANY TILES OR GRID DAMAGED DUE TO THIS WORK.
FIRE SUPPRESSION GENERAL NOTES:
FIRE SUPPRESSION PIPING LEGEND
F FIRE SUPPRESSION PIPING
FR FIRE RISER
SP STAND PIPE
FDV FIRE DEPARTMENT VALVE
EXISTING TO REMAIN
EXISTING TO BE REMOVED
X
XR
EC ELECTRICAL CONTRACTOR
HC HVAC CONTRACTOR
FSC FIRE SUPPRESSION CONTRACTOR
GC GENERAL CONTRACTOR
A. THIS PROJECT CONSISTS OF MULTIPLE TRADES OF WORK PERFORMED WITHIN AN EXISTING BUILDING, ALL OF WHICH ALLOWS VERY LITTLE PERMISSIBLE RANGE OF VARIATION. THE CONTRACTOR SHALL
TAKE CAREFUL CONSIDERATION WITH THE COORDINATION AND INSTALLATION OF THE MULTITUDE OF
NEW SYSTEMS WHILE ALSO ACCOMMODATING ANY EXISTING SYSTEMS TO REMAIN.
B. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL TRADES ASSOCIATED WITH THIS
PROJECT AND ISSUING COORDINATION PLANS PRIOR TO COMMENCEMENT OF EACH PHASE OF
CONSTRUCTION.
C. THE COORDINATION DRAWINGS SHALL ILLUSTRATE ALL SYSTEMS IN PLACE. NO EXCEPTIONS! THE
CONTRACTOR SHALL SHOW ALL NECESSARY OFFSETS, TRANSITIONS, ETC. AS REQUIRED IN ORDER TO
ACCOMMODATE CONDITIONS IDENTIFIED IN THE FIELD.
D. IF CONFLICTS ARE IDENTIFIED DURING THE DEVELOPMENT OF COORDINATION PLANS, THE
CONTRACTOR SHALL NOTIFY THE VA COTR, ARCHITECT, AND/OR ENGINEER OF ANY CONDITIONS WHICH
WILL NOT PERMIT THE WORK TO BE PERFORMED AS INDICATED ON THE PROJECT PLANS.
E. A COMPLETED SET OF COORDINATION PLANS ISSUED FOR REVIEW SHALL CONFIRM THAT THE
CONTRACTOR FULLY UNDERSTANDS THE PROJECT CONSTRAINTS AND ALL KNOWN CONFLICTS HAVE
BEEN ADDRESSED.
REWORK EXISTING SPRINKLER MAIN AS REQUIRED TO ACCOMMODATE
RENOVATION IN OUTLINED AREA. REFER TO OTHER TRADES FOR WORK IN
OUTLINED AREA. OUTLINED AREA SHALL BE SPRINKLERED BY EXISTING
SPRINKLER ZONE. SPRINKLER ZONE VALVE IS LOCATED IN STAIR #8 (ROOM
BB420). PROVIDE ALL NEW SPRINKLER BRANCH PIPING AND HEADS IN
OUTLINED AREA.
FIRE SUPPRESSION LEGEND
ALL OUTLINED AREAS SHALL BE 100% FULLY SPRINKLERED WITH A
WET-TYPE SPRINKLER SYSTEM IN ACCORDANCE WITH NFPA 13 AND
VA SPECIFICATIONS. SPRINKLER HEADS SHALL BE INSTALLED SO AS
TO ACCOMMODATE ANY NEW CEILINGS. COORDINATE SPRINKLER
HEAD LAYOUT WITH ARCHITECTURAL REFLECTED CEILING PLAN.
REFER TO MECHANICAL SPECIFICATIONS AND FIRE SUPPRESSION
NOTES FOR ADDITIONAL INFORMATION.
A
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
3 4 5 6 7 8 9 10
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF
THIS DESIGN AND THESE CONSTRUCTION
DOCUMENTS FOR PURPOSES OTHER THAN
THE SPECIFIC PROJECT NAMED HEREIN IS
STRICTLY PROHIBITED WITHOUT THE
EXPRESSED WRITTEN CONSENT OF
PERSPECTUS ARCHITECTURE.13212 Shaker Square Suite Cleveland, Ohio 44120
P. 216.752.1800 F.216.752.3833 Consulting Engineers
2217 East 9th Street, Suite 350
Cleveland OH 44115-1257
216-875-0100/ (F) 216-875-0111 barberhoffman.com
B-AC-3
B-AC-2
Louis Stokes Cleveland
VA Medical Center
S
74490
L.D. HENDRIX, JR
R E
S
O F
I
R
GE
NOIS
P
E
N E
D
ERT
L EA
E I N
G
R
T
S
TE
A H
F OO
IO
19057
U.S. Department of Veterans Affairs
FINAL CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
541-18-505
10/11/2019
VA SITE PREP FOR
INTEVO
F ile
P a th
Drawing Title
Approved: Project Director
ARCHITECT OF RECORD: STAMPCONSULTANTS:
Final Construction Document Submission 10/11/19
Project Number
Building Number
Drawing Number
Project Title
Location
Phase
Issue Date Checked Drawn
CLEVELAND, OHIO
Revisions: Date:
FIRE PROTECTION PLAN
0'
SCALE: 1/4" = 1'0"
2' 4' 8' 16'
PARTIAL BASEMENT FIRE
PROTECTION PLAN
V
LDH LDH
PLUMBING GENERAL NOTES:
A. LOCATIONS AND ROUTING OF EXISTING PIPING, DUCTWORK AND EQUIPMENT IS PRESUMED FROM
EXISTING DRAWINGS. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ALL PRIOR TO COMMENCEMENT
OF CONSTRUCTION. NOTIFY ENGINEER OF ANY CONDITIONS WHICH WILL NOT PERMIT THE WORK TO BE
PERFORMED AS INDICATED ON THESE DRAWINGS.
B. COORDINATE ALL SHUT-DOWNS OF EXISTING MECHANICAL SYSTEMS WITH OWNER A MINIMUM OF TEN
WORKING DAYS IN ADVANCE.
C. PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW WALL MOUNTED DEVICES WITH VA AND
ARCHITECT.
D. PROVIDE ADEQUATE SERVICE CLEARANCE FOR ALL MECHANICAL EQUIPMENT. REFER TO INSTRUCTIONS
FROM THE EQUIPMENT MANUFACTURER.
E. NEW PIPING SHALL NOT BE ROUTED ABOVE ELECTRICAL PANELS. REFER TO ELECTRICAL DRAWINGS FOR
LOCATION OF PANELS.
F. WHERE EXISTING FIXTURES ARE TO BE REMOVED, REMOVE ALL ASSOCIATED BRANCH PIPING WHICH IS
NOT TO BE REUSED. REMOVE PIPING TO MAINS AND CAP.
G. CONTRACTOR SHALL REMOVE AND REPLACE CEILING TILES AND GRID AS REQUIRED TO COMPLETE
DEMOLITION AND NEW WORK IN AREAS OUTSIDE OF RENOVATION PROJECT. CONTRACTOR SHALL BE
RESPONSIBLE FOR REPLACING ANY TILES OR GRID DAMAGED DUE TO THIS WORK.
H. CONTRACTOR SHALL PROVIDE NEW CHASE ENCLOSURES WHERE EXISTING STORM, SANITARY, WATER, VENT RISERS ARE TO REMAIN, BUT ARE UNCOVERED/EXPOSED DURING CONSTRUCTION. ENCLOSURES
SHALL FULLY CONCEAL PIPING. COORDINATE REQUIREMENTS WITH GENERAL TRADES.
I. PLUMBING PIPING SYSTEMS SHALL BE SUPPORTED FROM STRUCTURE INDEPENDENTLY OF OTHER
SYSTEMS.
FAUCET SEE
SPECIFICATIONS
LAMINAR FLOW
CONTROL DEVICE
OFFSET
WASTE
TRAP PARALLEL TO WALL.
PROVIDE PROTECTIVE TRAP
COVER PER SPECIFICATIONS.
LOOSE KEY
STOP
ESCUTCHEON
FINISHED
FLOOR
34"
8"
10 3/4"±
F O
R F
IX
T
U R
E H
E
IG
H T
S
S E
E A
R C
H
IT
E C
T U
R A
L
D R
A W
IN
G
S
NOT TO SCALE
TYPICAL ADA LAVATORY DETAIL
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
MAXIMUM PIPE/TUBING SUPPORT SPACING
TYPICAL PIPE HANGERS
TUBING 5 FT
NOM. SIZE
PIPE
THRU (20)
6 8 10
(32)(25) (40)
(65)
(50)
(75)
ADJUSTABLE CLEVIS HANGER
TYPE 43 - SEE SPECIFICATIONS
SADDLE
WELD
1312 14 16
(125)(100)
(150)
(200)
TO 1000 LB. (453 KG) UNIFORM LOAD
TRAPEZE HANGER FOR UP
PROVIDE INSULATION SHIELD
SIDE VIEW
1 5/8" (43 MM) 12 GAGE1" (25 MM) MAX.
STRENGTH INSULATION
PROVIDE HIGH COMPRESSIVE
TYPE 1 - SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER
HANGER ROD
UNDER INSULATION SHIELD
AT HANGER
INSULATION SHIELD
TEMPERATURE PIPE)
REQUIRED FOR LOW
BARRIER TYPE IS
INSULATION (VAPOR
SPACING ON
36" (900 MM) MAX.
BAND
(9 PCF MIN. DENSITY)
HANGER RODS WITH
(8" (200 MM) MIN.)
CHANNEL OR 2"x2"x1/4"
(50x50x8 MM) ANGLE
864 532 2 1/21 1/21 1 1/4IN.
(MM)
(M)
FT.
FT.
(M)
(5.8)(5.2)(4.1) (4.9)(3.7)(3.0) (3.4)(2.7)(2.1)
(4.9)(4.1)(3.7) (4.0)(3.0)(2.4)(1.8)5 FT
THRU 3/4
(2.1) (2.1)
(2.1)
(2.7)
(2.4)
1/2" (15 MM) DIA.
EACH CHANNEL
AND INSERT FOR ALL PIPING
STEEL EXPANSION SHIELD FOR
THIS TYPE SHALL BE USED ONLY
INSERTS FOR NEW CONSTRUCTION
FOR EXISTING CONSTRUCTION AND
3/8" (10 MM) MIN DIA EXPANSION BOLTS
TYPICAL METHOD OF SECURING
NUTS & WASHERS
HANGER RODS
3/8" (10 MM) MIN DIA
FLOOR SLAB
CLIP
ANGLE
HANGER RODS
3/8" (10 MM) MIN DIA
TURNBUCKLE
NEW CONSTRUCTION ONLY.
3/8" (10 MM) MIN DIA INSERTS
IN SLABS OR BEAMS OF
INSERTS FOR NEW CONSTRICTION
EXISTING CONSTRUCTION AND
HANGER RODS IN CONCRETE
4" (100 MM) MIN DEPTH
CONCRETE
SLABS AND BEAMS.
NOT TO SCALE
NOT TO SCALE
MEDICAL GAS SYMBOLS:
PIPE DOWN
PIPE RISE UP
PIPE CAP
BRANCH CONNECTION
EXISTING TO BE REMAIN
EXISTING TO BE REMOVED
ISOLATION VALVE
OX MEDICAL OXYGEN
MA MEDICAL AIR
MV MEDICAL VACUUM
X
XR
L
LOCKABLE VALVE (INLINE/SERVICE)
MEDICAL GAS CONNECTION WITH OUTLET/INLET
MEDICAL GAS VACUUM SLIDE
MEDICAL GAS VALVE BOX
MEDICAL GAS GENERAL NOTES:
1. PROVIDE MEDICAL GAS PIPING SYSTEMS AND PIPE LABELS COMPLYING WITH REQUIREMENTS OF NFPA
99 "STANDARD FOR HEALTH CARE FACILITIES".
2. INSTALLATION AND CERTIFICATION SHALL COMPLY WITH ASSE/ANSI SERIES 6000, "PROFESSIONAL
QUALIFICATIONS STANDARDS FOR MEDICAL GAS SYSTEMS INSTALLERS, INSPECTORS AND VERIFIERS".
3. PROVIDE COMPATIBLE ACCESSORIES, TUBE, FITTING, AND VALVES FOR EACH SYSTEM.
A. OUTLET / INLET STYLE:
DISS
B. MEDICAL GAS TUBE, FITTINGS AND JOINTS: PRE-CLEANED AND SEALED COPPER TUBE: ASTM B 88, TYPE K OR TYPE L, WATER TUBE, SEAMLESS, DRAWN TEMPER, CLEANED FOR MEDICAL GAS USE, PURGED, AND WITH ENDS SEALED.
C. MEDICAL SYSTEM ACCESSORIES: PROVIDE THE MEDICAL GAS SYSTEM ACCESSORIES FROM
MANUFACTURER OF EXISTING ACCESSORIES, COMPATIBLE WITH EXISTING SYSTEMS.
D. SERVICE OUTLETS: INCLUDE BRASS VALVE AND BODY BLOCK WITH SEALS IN ROUGH-IN AND
FINISHING ASSEMBLIES, STEEL OUTLET BOX AND COVER PLATE; 3/8 INCH TYPE K OR L COPPER
TUBE BRAZED TO VALVE; AND PRESSURE OUTLETS WITH AUTOMATIC SECONDARY SERVICE VALVE TO PREVENT GAS FLOW WHEN PRIMARY VALVE IS REMOVED. DISS COUPLING SHALL BE INDEXED
TO PREVENT INTERCHANGE BETWEEN SERVICES, CONSTRUCTED TO PERMIT ONE HANDED
CONNECTION AND REMOVAL OF EQUIPMENT WITH POSITIVE LOCKING RING WHICH RETAINS
EQUIPMENT STEM IN VALVE DURING USE. OUTLET/INLET TYPE OF CONNECTION SHALL BE
COORDINATED WITH THE OWNER PRIOR TO ORDERING EQUIPMENT.
4. INSTALL LABELING ON VALVES, VALVE BOX COVERS, AND ALARM PANELS IN ACCORDANCE WITH
REQUIREMENTS OF NFPA 99 AND VA STANDARDS. CAPTIONS AND COLOR CODING: PER THE
REQUIREMENTS OF NFPA 99 AND VA STANDARDS.
5. LOCATIONS AND ROUTING OF EXISTING PIPING, DUCTWORK AND EQUIPMENT IS PRESUMED FROM
EXISTING DRAWINGS. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ALL PRIOR TO COMMENCEMENT OF CONSTRUCTION. NOTIFY ENGINEER OF ANY CONDITIONS WHICH WILL NOT PERMIT THE WORK TO BE
PERFORMED AS INDICATED ON THESE DRAWINGS.
6. COORDINATE ALL SHUT-DOWNS IF EXISTING MEDICAL GAS AND VACUUM SYSTEMS WITH OWNER A
MINIMUM OF TEN WORKING DAYS IN ADVANCE.
7. PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW WALL MOUNTED DEVICES WITH OWNER
AND ARCHITECT.
8. PROVIDE ADEQUATE SERVICE CLEARANCE FOR ALL EQUIPMENT. REFER TO INSTRUCTIONS FROM THE
EQUIPMENT MANUFACTURER.
9. NEW PIPING SHALL NOT BE ROUTED ABOVE ELECTRICAL PANELS. REFER TO ELECTRICAL DRAWINGS
FOR LOCATION OF PANELS.
10. WHERE EXISTING FIXTURES ARE TO BE REMOVED, REMOVE ALL ASSOCIATED BRANCH PIPING WHICH IS
NOT TO BE REUSED. REMOVE PIPING TO MAINS AND CAP REMAINING PIPES.
11. MEDICAL GAS MATERIALS, EQUIPMENT AND INSTALLATION SHALL COMPLY WITH NFPA 99, HEALTH CARE
FACILITIES”, LATEST EDITION. INSTALLATION PERSONNEL SHALL BE QUALIFIED IN ACCORDANCE WITH
ASSE SERIES 6000, “PROFESSIONAL QUALIFICATIONS FOR MEDICAL GAS SYSTEMS
INSTALLERS, INSPECTORS AND VERIFIERS”.
PLUMBING SYMBOLS:
ACCESS SIDE OF VALVE BOX OR ALARM PANEL
AS
REFER TO ARCHITECTURAL PLANS FOR DESIGNATED WALLS IN THE PROJECT AREA TO BE LINED WITH LEAD
SHIELDING BY THE CONTRACTOR. FOR EXISTING MECHANICAL DEVICES THAT ARE INDICATED TO REMAIN, THE MECHANICAL CONTRACTOR SHALL REMOVE AND RE-INSTALL OR RELOCATE THESE DEVICES. THE GC
SHALL PROVIDE NEW LEAD SHIELDING FOR ALL SUCH DEVICES. FOR NEW MECHANICAL DEVICES, THE GC SHALL PROVIDE ALL LEAD SHIELDING FOR EACH DEVICE. THE MECHANICAL CONTRACTOR SHALL COORDINATE
ALL SUCH WORK WITH THE GENERAL CONTRACTOR, AND SHALL ASSIST THE GENERAL CONTRACTOR IN THE
PERFORMANCE OF THIS WORK. IN ANY CASE, ALL PLUMBING DEVICES, HVAC DEVICES, FIRE PROTECTION
DEVICES, ETC. INSTALLED IN THESE WALLS SHALL BE SHIELDED WITH LEAD.
LEAD SHIELDING NOTE
PLUMBING FIXTURE
CONNECTION SCHEDULE
A. THIS PROJECT CONSISTS OF MULTIPLE TRADES OF WORK PERFORMED WITHIN AN EXISTING BUILDING, ALL OF WHICH ALLOWS VERY LITTLE PERMISSIBLE RANGE OF VARIATION. THE CONTRACTOR SHALL TAKE CAREFUL CONSIDERATION WITH THE COORDINATION AND INSTALLATION OF THE MULTITUDE OF
NEW SYSTEMS WHILE ALSO ACCOMMODATING ANY EXISTING SYSTEMS TO REMAIN.
B. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL TRADES ASSOCIATED WITH THIS
PROJECT AND ISSUING COORDINATION PLANS PRIOR TO COMMENCEMENT OF EACH PHASE OF
CONSTRUCTION.
C. THE COORDINATION DRAWINGS SHALL ILLUSTRATE ALL SYSTEMS IN PLACE. NO EXCEPTIONS! THE
CONTRACTOR SHALL SHOW ALL NECESSARY OFFSETS, TRANSITIONS, ETC. AS REQUIRED IN ORDER TO
ACCOMMODATE CONDITIONS IDENTIFIED IN THE FIELD.
D. IF CONFLICTS ARE IDENTIFIED DURING THE DEVELOPMENT OF COORDINATION PLANS, THE
CONTRACTOR SHALL NOTIFY THE VA COTR, ARCHITECT, AND/OR ENGINEER OF ANY CONDITIONS WHICH
WILL NOT PERMIT THE WORK TO BE PERFORMED AS INDICATED ON THE PROJECT PLANS.
E. A COMPLETED SET OF COORDINATION PLANS ISSUED FOR REVIEW SHALL CONFIRM THAT THE
CONTRACTOR FULLY UNDERSTANDS THE PROJECT CONSTRAINTS AND ALL KNOWN CONFLICTS HAVE
BEEN ADDRESSED.
PROJECT COORDINATION NOTES:
NOTE:
INSTALL IN AN ACCESSIBLE LOCATION.
MIXING VALVE DETAIL
NOT TO SCALE
H W
C W
ADJUSTABLE THERMOSTATIC
MIXING VALVE
105 DEGREE DHW TO FAUCET HW
SUPPLY IN LAVATORIES AND SINKS.
1/2" 1/2"
1/2"
H W
CHECK VALVE
NOTE:
1. APPLICABLE TO PENETRATIONS OF ALL
FIRE RATED MEMBRANES, IN
ACCORDANCE WITH NFPA 101. REFER
TO SPECIFICATIONS SECTION FOR FIRE
STOPPING SYSTEMS.
INSULATED PIPE
OR DUCT
FLOOR
FIRESTOP MATERIAL
3/4" [19mm] APPROVED
FIRESTOP INSULATION
WITH VAPOR BARRIER
PIPE SLEEVE WHERE
SPECIFIED
1/4" [6mm]Ø ANCHOR
ROD FOR NEW
CONSTRUCTION
WELD
FLOOR OR DECK PENETRATION
PARTITION OR CHASE PENETRATION
[152mm] [152mm]
MASONRY
PARTITION
PARTITION SUPPORT
FIRESTOP
MATERIAL
[152mm] [152mm]
3/4" [19mm] APPROVED
FIRESTOP INSULATION WITH
VAPOR BARRIER
DRYWALL PARTITION
INSULATED
PIPE OR
DUCT
A
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
3 4 5 6 7 8 9 10
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF
THIS DESIGN AND THESE CONSTRUCTION
DOCUMENTS FOR PURPOSES OTHER THAN
THE SPECIFIC PROJECT NAMED HEREIN IS
STRICTLY PROHIBITED WITHOUT THE
EXPRESSED WRITTEN CONSENT OF
PERSPECTUS ARCHITECTURE.13212 Shaker Square Suite Cleveland, Ohio 44120
P. 216.752.1800 F.216.752.3833 Consulting Engineers
2217 East 9th Street, Suite 350
Cleveland OH 44115-1257
216-875-0100/ (F) 216-875-0111 barberhoffman.com
B-AC-3
B-AC-2
Louis Stokes Cleveland
VA Medical Center
S
74490
L.D. HENDRIX, JR
R E
S
O F
I
R
GE
NOIS
P
E
N E
D
ERT
L EA
E I N
G
R
T
S
TE
A H
F OO
IO
19057
U.S. Department of Veterans Affairs
FINAL CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
541-18-505
10/11/2019
VA SITE PREP FOR
INTEVO
F ile
P a th
Drawing Title
Approved: Project Director
ARCHITECT OF RECORD: STAMPCONSULTANTS:
Final Construction Document Submission 10/11/19
Project Number
Building Number
Drawing Number
Project Title
Location
Phase
Issue Date Checked Drawn
CLEVELAND, OHIO
Revisions: Date:
PLUMBING LEGEND, SCHEDULE,
DETAILS, AND GENERAL NOTES
Hall
BC-460
BC-446A
Nuc Med
BC-474
70B
BC-446
Hot Lab
Rad Waste
Nuc Med
BC-475
Thyroid Uptake
BC-448
Inject
BC-461
X-3/4"
X-3/4"
P-418
L
X-OX
X-MV
X-3/4"
X-1/2"
X-3/4"
X-1/2"
X-1/2"
X-3/4"
X-MA
X -M
A
L
L
X-3" X-4"
X-4"
X-3"
X-3"
X-4"
X-3"
3/4"
1/2"
X-MVB
1-1/2"
V
U S
A N
ROUTE (APPROXIMATELY 20
FEET) 1-1/2" SANITARY
WITHIN SUB-BASEMENT TO
SANITARY MAIN.
REMOVE SANITARY
BRANCH BACK TO MAIN
AND CAP.
3/4"
X-HW
X-CW
X -S
A N
X-SAN
A
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
3 4 5 6 7 8 9 10
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF
THIS DESIGN AND THESE CONSTRUCTION
DOCUMENTS FOR PURPOSES OTHER THAN
THE SPECIFIC PROJECT NAMED HEREIN IS
STRICTLY PROHIBITED WITHOUT THE
EXPRESSED WRITTEN CONSENT OF
PERSPECTUS ARCHITECTURE.13212 Shaker Square Suite Cleveland, Ohio 44120
P. 216.752.1800 F.216.752.3833 Consulting Engineers
2217 East 9th Street, Suite 350
Cleveland OH 44115-1257
216-875-0100/ (F) 216-875-0111 barberhoffman.com
B-AC-3
B-AC-2
Louis Stokes Cleveland
VA Medical Center
S
74490
L.D. HENDRIX, JR
R E
S
O F
I
R
GE
NOIS
P
E
N E
D
ERT
L EA
E I N
G
R
T
S
TE
A H
F OO
IO
19057
U.S. Department of Veterans Affairs
FINAL CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
541-18-505
10/11/2019
VA SITE PREP FOR
INTEVO
F ile
P a th
Drawing Title
Approved: Project Director
ARCHITECT OF RECORD: STAMPCONSULTANTS:
Final Construction Document Submission 10/11/19
Project Number
Building Number
Drawing Number
Project Title
Location
Phase
Issue Date Checked Drawn
CLEVELAND, OHIO
Revisions: Date:
PARTIAL BASEMENT PLUMBING AND
MEDICAL GAS PLAN
0'
SCALE: 1/4" = 1'0"
2' 4' 8' 16'
PARTIAL BASEMENT PLUMBING
AND MEDICAL GAS PLAN
V
CALL OUTS:
MANUAL BALANCING DAMPER ON DUCT
ROUND DUCT SIZE12"Ø
RECTANGULAR DUCT SIZE24x18
REFERENCE TO CODED NOTE#
SUPPLY AIR DUCT
TO BE MOUNTED OVER ACCESSIBLE CEILING
SUPPLY AIR DIFFUSER
SHADING INDICATES TO PROVIDE QUADRANT BLANK-OFF
IN NECK OF DIFFUSER. TO BE FURNISHED WITH DIFFUSER.
AIR CONDITIONING CONDENSATE
HHWS
HHWR
CD
HEATING HOT WATER SUPPLY
HEATING HOT WATER RETURN
F FIRE SUPPRESSION PIPE
STRAINER
FLEXIBLE PIPE CONNECTOR
THERMOMETER IN PIPE WELL
BALANCING VALVE
HVAC PIPING:
SHUTOFF VALVE
REDUCER
UNION
CHECK VALVE
3-WAY CONTROL VALVE
GAUGE PORT (PETE'S PLUG)
2-WAY CONTROL VALVE
DUCTWORK SYMBOLS:
CONTROL SYMBOLS:
DDC THERMOSTATT
NORMALLY OPENNO
NORMALLY CLOSEDNC
RETURN AIR DUCT
EXHAUST AIR DUCT
EXISTING TO REMAIN
EXISTING TO BE REMOVED
X
XR
EQUIPMENT OR FIXTURE MARK
AIR DISTRIBUTION DEVICE
UNIT NUMBER
EQUIPMENT
TYPE
CONNECTION SIZE AT
DEVICE
TYPE
LIMIT OF DEMOLITION
DN
DN
UP
UP
SUPPLY DUCT (UP & DOWN)
RETURN DUCT (UP & DOWN)
CONNECT NEW DUCT TO EXISTING DUCT
AC
AD
AFF
AHU
AP
BIW
CC
CF
CO
CW
Db dB
Dp
DX
AIR CONDITIONING UNIT
ACCESS DOOR
ABOVE FINISHED FLOOR
AIR HANDLING UNIT
ACCESS PANEL
BACKWARD INCLINED WHEEL
COOLING COIL
CENTRIFUGAL FAN
CLEAN OUT
COLD WATER
DRY BULB TEMPERATURE
DECIBELS
DEW POINT TEMPERATURE
DIRECT EXPANSION
EA
EER
EF
EX.
FC
FLR.
HC
HP
EXHAUST AIR
ENERGY EFFICIENCY RATIO
EXHAUST FAN
EXISTING
FORWARD CURVED FAN
FLOOR
HEATING COIL
HORSEPOWER
MAX.
MIN.
NOM.
OA
PD
RA
RF
RH
Rh
SA
Sp. Gr.
SH
SP
MAXIMUM
MINIMUM
NOMINAL
OUTDOOR AIR
PRESSURE DROP
RETURN AIR
RETURN FAN
REHEAT COIL
RELATIVE HUMIDITY
SUPPLY AIR
SPECIFIC GRAVITY
STEAM HUMIDIFIER
STATIC PRESSURE
V
VD
Wb
VALVE
VOLUME DAMPER
WET BULB TEMPERATURE
ABBREVIATIONS:
MECHANICAL SYMBOLS:
LIMIT OF DEMOLITION
AND EXISTING WORK
POINT OF CONNECTION BETWEEN NEW
GENERAL SYMBOLS:
DIRECTION OF FLOW
EXISTING TO BE RELOCATEDXRL
RETURN AIR GRILLE
EXHAUST AIR GRILLE
A. LOCATIONS AND ROUTING OF EXISTING PIPING, DUCTWORK AND EQUIPMENT IS PRESUMED FROM
EXISTING DRAWINGS. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ALL PRIOR TO
COMMENCEMENT OF CONSTRUCTION. NOTIFY ENGINEER OF ANY CONDITIONS WHICH WILL NOT
PERMIT THE WORK TO BE PERFORMED AS INDICATED ON THESE DRAWINGS.
B. COORDINATE ALL SHUT-DOWNS OF EXISTING MECHANICAL SYSTEMS WITH OWNER A MINIMUM OF
TEN (10) WORKING DAYS IN ADVANCE.
C. PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW WALL MOUNTED DEVICES WITH
OWNER AND ARCHITECT. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR PRECISE
LOCATION OF CEILING MOUNTED DEVICES.
D. PROVIDE ADEQUATE SERVICE CLEARANCE FOR ALL MECHANICAL EQUIPMENT. REFER TO
INSTRUCTIONS FROM THE EQUIPMENT MANUFACTURER. MAINTAIN A MINIMUM OF 18 INCH
CLEARANCE AT CONTROLS FOR VARIABLE AIR VOLUME TERMINALS AND FAN POWERED
TERMINALS ABOVE CEILINGS.
E. NEW DUCTS OR PIPING SHALL NOT BE ROUTED ABOVE ELECTRICAL PANELS. REFER TO
ELECTRICAL DRAWINGS FOR LOCATION OF PANELS.
F. UNLESS NOTED OTHERWISE, BRANCH DUCTS TO DIFFUSERS SHALL BE THE SAME SIZE AS THE
NECK OF THE DIFFUSER.
G. PIPE SHALL NOT BE PVC PLASTIC AND ALL WIRING SHALL BE INSTALLED IN CONDUIT OR SHALL BE
PLENUM RATED.
H. NO TEMPERATURE SENSING CONTROL DEVICES SHALL BE LOCATED OVER HEAT PRODUCING
DEVICES.
I. INSTALL ALL EQUIPMENT TO BE DEAD LEVEL.
J. EXTREMELY TIGHT CLEARANCES OCCUR IN THE EXISTING BUILDING. CONTRACTOR SHALL
PREPARE SHEET METAL SHOP DRAWINGS FOR APPROVAL PRIOR TO FABRICATING SHEET METAL.
COORDINATE WITH ALL OTHER TRADES.
K. MECHANICAL DRAWINGS ARE DIAGRAMMATICAL WHERE DUCT SIZE SHOWN IS IN CONFLICT WITH
STRUCTURE OR OTHER BUILDING SYSTEM, CONTRACTOR MAY MODIFY DUCT SIZE AND PROVIDE
EQUIVALENT FREE AREA DUCT.
HVAC GENERAL NOTES:
470R1
12x10
AIR FLOW
Db SUMMER
OUTDOOR DESIGN
Wb SUMMER
Db WINTER
DESIGN ALTITUDE: 800 FT.
INDOOR AREA
SUMMER
Db Db
°F
TEMPERATURES
89.4°F
73.9°F
-4.0°F
WINTER
°F
70 70 40
DESIGN CONDITIONS
MAX.
RELATIVE
HUMIDITY (%)
MIN RELATIVE
HUMIDITY (%)
HVAC DESIGN DATA
NUCLEAR MEDICINE CT ROOM 5570 70 40
CONTROL ROOM
REFER TO ARCHITECTURAL PLANS FOR DESIGNATED WALLS IN THE PROJECT AREA TO BE LINED WITH LEAD
SHIELDING BY THE CONTRACTOR. FOR EXISTING MECHANICAL DEVICES THAT ARE INDICATED TO REMAIN, THE MECHANICAL CONTRACTOR SHALL REMOVE AND RE-INSTALL OR RELOCATE THESE DEVICES. THE GC
SHALL PROVIDE NEW LEAD SHIELDING FOR ALL SUCH DEVICES. FOR NEW MECHANICAL DEVICES, THE GC
SHALL PROVIDE ALL LEAD SHIELDING FOR EACH DEVICE. THE MECHANICAL CONTRACTOR SHALL COORDINATE
ALL SUCH WORK WITH THE GENERAL CONTRACTOR, AND SHALL ASSIST THE GENERAL CONTRACTOR IN THE PERFORMANCE OF THIS WORK. IN ANY CASE, ALL PLUMBING DEVICES, HVAC DEVICES, FIRE PROTECTION
DEVICES, ETC. INSTALLED IN THESE WALLS SHALL BE SHIELDED WITH LEAD.
LEAD SHIELDING NOTE
A. THIS PROJECT CONSISTS OF MULTIPLE TRADES OF WORK PERFORMED WITHIN AN EXISTING BUILDING, ALL OF WHICH ALLOWS VERY LITTLE PERMISSIBLE RANGE OF VARIATION. THE CONTRACTOR SHALL
TAKE CAREFUL CONSIDERATION WITH THE COORDINATION AND INSTALLATION OF THE MULTITUDE OF
NEW SYSTEMS WHILE ALSO ACCOMMODATING ANY EXISTING SYSTEMS TO REMAIN.
B. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL TRADES ASSOCIATED WITH THIS
PROJECT AND ISSUING COORDINATION PLANS PRIOR TO COMMENCEMENT OF EACH PHASE OF
CONSTRUCTION.
C. THE COORDINATION DRAWINGS SHALL ILLUSTRATE ALL SYSTEMS IN PLACE. NO EXCEPTIONS! THE
CONTRACTOR SHALL SHOW ALL NECESSARY OFFSETS, TRANSITIONS, ETC. AS REQUIRED IN ORDER TO
ACCOMMODATE CONDITIONS IDENTIFIED IN THE FIELD.
D. IF CONFLICTS ARE IDENTIFIED DURING THE DEVELOPMENT OF COORDINATION PLANS, THE
CONTRACTOR SHALL NOTIFY THE VA COTR, ARCHITECT, AND/OR ENGINEER OF ANY CONDITIONS WHICH
WILL NOT PERMIT THE WORK TO BE PERFORMED AS INDICATED ON THE PROJECT PLANS.
E. A COMPLETED SET OF COORDINATION PLANS ISSUED FOR REVIEW SHALL CONFIRM THAT THE
CONTRACTOR FULLY UNDERSTANDS THE PROJECT CONSTRAINTS AND ALL KNOWN CONFLICTS HAVE
BEEN ADDRESSED.
PROJECT COORDINATION NOTES:
CD COOLING COIL CONDENSATE (IN. W.G.)
(DEG. F.)
FACTORY DISCONNECT SWITCH
FACTORY CONDENSATE PUMP
MICROPROCESSOR CONTROL WITH WALL MOUNTED DISPLAY
ACCESSORIES
RETURN AIRSIDE SMOKE DETECTOR
MANUFACTURER'S STARTUP
WIRE SIZING AMPS
MAX. OVERCURRENT PROTECTIVE DEVICE
ELECTRICAL DATA - AIR CONDITIONER
VOLTS-PHASE-HERTZ
FULL LOAD AMPS
TYPE
FILTERS
AIR FLOW
OUTDOOR AIR
MOTOR SIZE
EXTERNAL STATIC PRESSURE
COOLING PERFORMANCE (CHILLED WATER COIL)
TOTAL COOLING CAPACITY
SENSIBLE COOLING CAPACITY
ENTERING AIR TEMP. DB/WB
AIR HANDLER CONFIGURATION
SUPPLY FAN PERFORMANCE
MARK
(HP)
(MBH)
(MBH)
(CFM)
SPACE SERVED
(AMPS)
3-WAY CHILLED WATER MODULATING VALVE
HIGH STATIC BLOWER MODULE
BACnet INTERFACE
REMOTE TEMPERATURE & HUMIDITY SENSORS
AC-5
YES
12.8
460-3-60
11.2
2" STANDARD
HORIZONTAL
1,250
0.3
0.5
72/60
NO
YES
YES
YES
CT ROOM
NO
YES
NO
YES
YES
(DEG. F.)
WATER FLOW/PRESSURE DROP
EWT/LWT
(GPM/FT. HD)
(DEG. F.)LEAVING AIR TEMP. DB/WB 53.9/52.2
24.2
22.2
45.0/55.0
5.2/7.2
AC UNIT (CHILLED WATER) -
AC
NOTES:
1. UNITS SHALL BE SUPPORTED FROM STRUCTURE WITH THREADED RODS AND
VIBRATION ISOLATORS.
ELECTRIC HUMIDIFIER
TOTAL CAPACITY
KW
(LB/HR) 4.3
1.5
SUPPLY AIR PLENUM WITH CEILING FASCIA NO
2-WAY CHILLED WATER MODULATING VALVE
MARK TYPE
S1
AIR DISTRIBUTION DEVICE (DIFFUSERS, REGISTERS AND GRILLES)
(INCHES)
FACE SIZE
24x24 LAY-IN
COLORSTYLE
ALUMINUMWHITE
MATERIAL
1,2
NOTES
(INCHES)
NECK SIZE
SEE TAGSUPPLY
DIFFUSER
R1 RETURN
WHITE
GRILLE
24x12 PERFORATED FACE
LAY-IN
SEE TAG 1,2ALUMINUM
R2 24x24 WHITE 1,2SEE TAG ALUMINUM
PERFORATED FACE
LAY-IN
RETURN
GRILLE
CFMS1
NECK
NOTES:
1. PROVIDE TRANSITIONS FROM NECK SIZE TO BRANCH DUCTS.
2. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
A
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
3 4 5 6 7 8 9 10
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF
THIS DESIGN AND THESE CONSTRUCTION
DOCUMENTS FOR PURPOSES OTHER THAN
THE SPECIFIC PROJECT NAMED HEREIN IS
STRICTLY PROHIBITED WITHOUT THE
EXPRESSED WRITTEN CONSENT OF
PERSPECTUS ARCHITECTURE.13212 Shaker Square Suite Cleveland, Ohio 44120
P. 216.752.1800 F.216.752.3833 Consulting Engineers
2217 East 9th Street, Suite 350
Cleveland OH 44115-1257
216-875-0100/ (F) 216-875-0111 barberhoffman.com
B-AC-3
B-AC-2
Louis Stokes Cleveland
VA Medical Center
S
74490
L.D. HENDRIX, JR
R E
S
O F
I
R
GE
NOIS
P
E
N E
D
ERT
L EA
E I N
G
R
T
S
TE
A H
F OO
IO
19057
U.S. Department of Veterans Affairs
FINAL CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
541-18-505
10/11/2019
VA SITE PREP FOR
INTEVO
F ile
P a th
Drawing Title
Approved: Project Director
ARCHITECT OF RECORD: STAMPCONSULTANTS:
Final Construction Document Submission 10/11/19
Project Number
Building Number
Drawing Number
Project Title
Location
Phase
Issue Date Checked Drawn
CLEVELAND, OHIO
Revisions: Date:
HVAC LEGEND, SCHEDULES, AND
GENERAL NOTES
PENETRATION OF FIRE/SMOKE BARRIERS
NOTE:
1. APPLICABLE TO PENETRATIONS OF ALL
FIRE RATED MEMBRANES, IN
ACCORDANCE WITH NFPA 101. REFER
TO SPECIFICATIONS SECTION 078400,
FIRE STOPPING SYSTEMS.
INSULATED PIPE
OR DUCT
FLOOR
FIRESTOP MATERIAL
3/4" [19mm] APPROVED
FIRESTOP INSULATION
WITH VAPOR BARRIER
PIPE SLEEVE WHERE
SPECIFIED
1/4" [6mm]Ø ANCHOR
ROD FOR NEW
CONSTRUCTION
WELD
FLOOR OR DECK PENETRATION
PARTITION OR CHASE PENETRATION
PIPE/DUCT
6" [152mm]
6" [152mm]
MASONRY
PARTITION
PARTITION SUPPORT
FIRESTOP
MATERIAL
6"
[152mm]
6" [152mm]
3/4" [19mm] APPROVED
FIRESTOP INSULATION WITH
VAPOR BARRIER
DRYWALL PARTITION
INSULATED
PIPE OR
DUCT
TYPICAL PIPE HANGERS
VOLUME DAMPER DETAIL
NOTE:
1.
2.
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR
MULTI-BLADE DAMPERS & ROUND DAMPERS.
INSULATION
DAMPER BLADE
1/8" [6mm]
CLEARANCE
ALL AROUND
OUTSIDE END BEARING
INSIDE END BEARING
HANDLE WITH
LOCKING
QUADRANT
2" INSULATION
STAND-OFF
1/2" [15mm] ROUND
ROD PIN
DUCT
STIFFEN BLADE
AS REQUIRED
SIDE ELEVATION SECTION
DUCTWORK RADIUS ELBOWS
NOTE:
1.
2.
3.
THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
ALL STANDARD RADIUS ELBOWS SHOWN ON FLOOR PLANS MAY BE MADE SHORT RADIUS
ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE
CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.
PROVIDE DUCT ACCESS DOORS BEFORE AND AFTER EACH ELBOW.
R SHALL
EQUAL OR
BE
GREATER
THAN W.
R SHALL
EQUAL OR
BE
GREATER
THAN
1/3W.
W
R
R
2/3W
/3
W
R SHALL
EQUAL OR
BE
GREATER
THAN
1/6W.
STANDARD RADIUS ELBOW
SHORT RADIUS ELBOW
WITH ONE VANE
SHORT RADIUS ELBOW
WITH TWO VANES
W W
1/2W
/3
W
1/6W
R
SUPPLY DUCTWORK TAKE-OFFS
NOTE:
1.
2.
THE SUPPLY REGISTER TAKE-OFF MAY BE USED FOR UP UP TO
25% OF THE MAIN DUCT CFM. THE BRANCH DUCT TAKE-OFF
MAY BE USED FOR UP TO 15% OF THE MAIN DUCT CFM
ANYTIME AND UP TO 40% WHEN THE MAIN DUCT VELOCITY IS
1000 FPM [5 M/S] OR LESS. THE AIR SPLIT DUCT TAKE-OFF
SHALL BE USED IN ALL OTHER CASES AND MAY BE USED AT
ANYTIME.
SHOW VOLUME DAMPERS ON FLOOR PLANS.
AIR SPLIT DUCT TAKE-OFF PLAN
VIEW
BRANCH DUCT TAKE-OFF PLAN
VIEW
AIR
FLOW
AIR
FLOW
A
IR
F L O
W
SUPPLY REGISTER
OR BRANCH DUCT
TURNING VANES
MAIN
SUPPLY
DUCT
SEE FLOOR PLAN FOR
SPLIT DIMENSION
SQUARE ELBOW SHOWN.
PROVIDE ROUND ELBOW
WHEN SHOWN ON FLOOR
PLANS
PROVIDE VOLUME
DAMPER WHEN SHOWN
ON FLOOR PLANS
PROVIDE VOLUME
DAMPER WHEN
SHOWN ON FLOOR
PLANS
1/4 W OR 4" MIN.
AIR
FLOW
MAIN SUPPLY
DUCT
W
A
IR
F L O
W
WITH EQUIPMENT MOUNTED IN DUCT
TYPICAL DUCTWORK TRANSITION
NOTE:
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.
0°
M A
X
M
AX.
0°
M A
X
M A
X
E Q
U
IP
M E
N T
AIR
FLOW
AIR
FLOW
TYPICAL DUCTWORK TRANSITION
PLAN OR SIDE VIEWTYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
M
AX.
M A
X
DUCTWORK SQUARE VANED ELBOWS
NOTE:
1.
2.
3.
4.
5.
ALL VANED ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE VANE TYPE REGARDLESS OF W
DIMENSION.
ALL SINGLE VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.
WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE DOUBLE VANE
TYPE.
PROVIDE DUCT ACCESS DOORS BEFORE AND AFTER EACH ELBOW.
W
W1
COIL
TEST PLUG (TYP.)
REDUCER, IF REQUIRED
WATER RETURN
SCREWHEAD VENT
UNIONS OR SOLDER
CONNECTION (TYP.)
WATER SUPPLY
AC-5
TYPICAL COIL PIPING CONNECTIONS
2-WAY VALVE
1.
NOTES:
BRANCH PIPING VALVES SHALL BE PROVIDED WITH PACKING GLANDS.
TYPICAL METHOD OF SECURING HANGER
RODS IN CONCRETE SLABS AND BEAMS.
AC UNIT TEMPERATURE CONTROLS AND SEQUENCE OF OPERATION
SCALE = NTS
A
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
3 4 5 6 7 8 9 10
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF
THIS DESIGN AND THESE CONSTRUCTION
DOCUMENTS FOR PURPOSES OTHER THAN
THE SPECIFIC PROJECT NAMED HEREIN IS
STRICTLY PROHIBITED WITHOUT THE
EXPRESSED WRITTEN CONSENT OF
PERSPECTUS ARCHITECTURE.13212 Shaker Square Suite Cleveland, Ohio 44120
P. 216.752.1800 F.216.752.3833 Consulting Engineers
2217 East 9th Street, Suite 350
Cleveland OH 44115-1257
216-875-0100/ (F) 216-875-0111 barberhoffman.com
B-AC-3
B-AC-2
Louis Stokes Cleveland
VA Medical Center
S
74490
L.D. HENDRIX, JR
R E
S
O F
I
R
GE
NOIS
P
E
N E
D
ERT
L EA
E I N
G
R
T
S
TE
A H
F OO
IO
19057
U.S. Department of Veterans Affairs
FINAL CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
541-18-505
10/11/2019
VA SITE PREP FOR
INTEVO
F ile
P a th
Drawing Title
Approved: Project Director
ARCHITECT OF RECORD: STAMPCONSULTANTS:
Final Construction Document Submission 10/11/19
Project Number
Building Number
Drawing Number
Project Title
Location
Phase
Issue Date Checked Drawn
CLEVELAND, OHIO
Revisions: Date:
HVAC DETAILS
RH-1NC
Hall
BC-460
BC-446A
Nuc Med
BC-474
0B
BC-446
Hot LabRad Waste
Nuc Med
BC-475
Thyroid Uptake
BC-448
Inject
BC-461
Hall
T
T
T
X-VAV-30
X-VAV-20
X-VAV-21
1CAP
NC
Hall
BC-460
BC-446A
Nuc Med
BC-474
0B
BC-446
Hot LabRad Waste
Nuc Med
BC-475
Thyroid Uptake
BC-448
Inject
BC-461
Hall
T
X-VAV-30
X-VAV-20
X-VAV-21
350S1
10"Ø
350S1
10"Ø
12"Ø
350R1
10"Ø2 x
18x8
18x8
625S1
14"Ø
625S1
14"Ø
350R1
10"Ø
250S1
10"Ø
250S1
10"Ø
T
500R2
12"Ø
T
T x
1-1/4"
6 180
CFM
CFM
CFM
CFM
1"
C.O.
X-FD
EXISTING THERMOSTAT TO BE RELOCATED.
RE-BALANCE X-VAV-30 TO 500 CFM MAX AND 500 CFM MIN.
RE-BALANCE X-VAV-21 TO 330 CFM MAX AND 330 CFM MIN.
RE-BALANCE X-VAV-20 TO 700 CFM MAX AND 400 CFM MIN.
REMOVE AND REINSTALL CEILING TILE AND GRID AND LIGHTING AS REQUIRED FOR INSTALLATION OF AC-5.
HANG UNIT FROM STRUCTURE WITH THREADED ROD AND VIBRATION ISOLATORS. INSTALL SUPPLY AND
RETURN PLENUMS ON UNIT.
RE-BALANCE DIFFUSER/GRILLE TO INDICATED AIR FLOW.
RELOCATE THERMOSTAT TO LOCATION INDICATED. CUT AND PATCH WALL FOR INSTALLATION.
1-1/4" PCWS/R DOWN TO SUB-BASEMENT.
1" CD DOWN. SPILL TO FLOOR DRAIN.
1-1/4" PCWS/R UP TO BASEMENT.
X -P
C W
R
X -P
C W
S
X-4"
X-2-1/2"
X-1-1/2"
X-1-1/4"
X-1-1/4"
X-1"
X-1" PCHWS&R
X-6"
A
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
3 4 5 6 7 8 9 10
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF
THIS DESIGN AND THESE CONSTRUCTION
DOCUMENTS FOR PURPOSES OTHER THAN
THE SPECIFIC PROJECT NAMED HEREIN IS
STRICTLY PROHIBITED WITHOUT THE
EXPRESSED WRITTEN CONSENT OF
PERSPECTUS ARCHITECTURE.13212 Shaker Square Suite Cleveland, Ohio 44120
P. 216.752.1800 F.216.752.3833 Consulting Engineers
2217 East 9th Street, Suite 350
Cleveland OH 44115-1257
216-875-0100/ (F) 216-875-0111 barberhoffman.com
B-AC-3
B-AC-2
Louis Stokes Cleveland
VA Medical Center
S
74490
L.D. HENDRIX, JR
R E
S
O F
I
R
GE
NOIS
P
E
N E
D
ERT
L EA
E I N
G
R
T
S
TE
A H
F OO
IO
19057
U.S. Department of Veterans Affairs
FINAL CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
541-18-505
10/11/2019
VA SITE PREP FOR
INTEVO
F ile
P a th
Drawing Title
Approved: Project Director
ARCHITECT OF RECORD: STAMPCONSULTANTS:
Final Construction Document Submission 10/11/19
Project Number
Building Number
Drawing Number
Project Title
Location
Phase
Issue Date Checked Drawn
CLEVELAND, OHIO
Revisions: Date:
0'
SCALE: 1/4" = 1'0"
2' 4' 8' 16'
PARTIAL BASEMENT HVAC DEMOLITION
PLAN
PARTIAL BASEMENT HVAC PLANS
V
LDH LDH
0'
SCALE: 1/4" = 1'0"
2' 4' 8' 16'
PARTIAL BASEMENT HVAC PLAN
V
0'
SCALE: 1/4" = 1'0"
2' 4' 8' 16'
PARTIAL SUB-BASEMENT HVAC PLAN
V
27 29 30
BRANCH CIRCUIT HOME RUN TO PANEL - ARROWHEADS INDICATE CIRCUITS. WIRE INDICATED ARE GREEN GROUND, SEPARATE NEUTRALS (SHARED NEUTRALS ARE NOT PERMITTED FOR BRANCH CIRCUITS) AND THREE HOT LEGS (A
DIFFERENT PHASE FOR EACH CIRCUIT) MAXIMUM THREE CIRCUITS PER CONDUIT. 3/4" MINIMUM CONDUIT WITH WIRE
SIZE INDICATED ON DRAWING ("XX" INDICATES AWG SIZE). ALL POWER WIRING SHALL BE STRANDED COPPER
CONDUCTORS WITH THHN/THWN INSULATION. PROVIDE SEPARATE EQUIPMENT GROUNDING CONDUCTOR (SAME SIZE AS PHASE AND NEUTRAL, UNLESS OTHERWISE NOTED) FOR EACH CONDUIT. CONDUIT WIRE FILLS SHALL BE IN
ACCORDANCE WITH LATEST NATIONAL ELECTRIC CODE.
WIRE SIZE
(MIN. #12AWG)
NO. OF CCTS
IN CONDUIT
PHASE
CONDUCTORS
NEUTRALS
GROUND CONDUIT UP
CONDUIT DOWN
MOTOR - NUMBER DENOTES HORSEPOWER3
TEMPERATURE CONTROL PANEL FURNISHED AND INSTALLED BY OTHERS. EC SHALL PROVIDE 120V CONNECTION (HARDWIRED OR
RECEPTACLE, AS REQUIRED).
TCP
EC SHALL PROVIDE 20A-120V CIRCUIT IN ABOVE FINISHED CEILING MOUNTED JUNCTION BOX FOR VAV TERMINALS. CONNECT ALL
VAV'S IN AREA TO CIRCUIT INDICATED. MC SHALL PROVIDE CONTROL TRANSFORMER AND CONTROL WIRING FOR 24VAC VAV
TERMINALS. VERIFY LOCATION OF ALL ADJACENT VAV'S WITH MECHANICAL DRAWINGS.
VAV
JUNCTION BOX, CEILING OR WALL MOUNTED, 4" SQ. WITH GROUND LUG, UNLESS OTHERWISE NOTED. COORDINATE MOUNTING
LOCATION WITH EQUIPMENT.
SC - SINK STATION CONTROLS. CONNECT PER MANUFACTURES WIRING DIAGRAM.
JUNCTION BOX, ABOVE CEILING FOR CONNECTION TO 120V AUTOMATIC DOOR. ELECTRICAL CONTRACTOR SHALL CONNECT
AUTOMATIC DOOR INCLUDING PUSH PAD OPERATORS PER MANUFACTURER'S INSTRUCTIONS TO 120V EMERGENCY LIFE SAFETY
CIRCUIT. GENERAL CONTRACTOR SHALL FURNISH AND INSTALL AUTOMATIC DOOR.
JUNCTION BOX MOUNTED AT 48" AFF FOR CONNECTION TO AUTOMATIC DOOR PUSH PAD DEVICE. PROVIDE 3/4"C TO DOOR
CONTROLLER WITH WIRING PER MANUFACTURER'S REQUIREMENTS.
AD
20A-125V, HOSPITAL GRADE, GROUND FAULT INTERRUPTER RECEPTACLE, MOUNT AT 18" AFF UNLESS OTHERWISE NOTED.
20A-125V, HOSPITAL GRADE, GROUNDED DUPLEX RECEPTACLE, MOUNT AT 18" AFF UNLESS OTHERWISE NOTED.
DOUBLE 20A-125V, HOSPITAL GRADE, GROUNDED DUPLEX RECEPTACLE, MOUNT AT 18" AFF UNLESS OTHERWISE NOTED.
SAME DEVICE TYPES AS INDICATED ABOVE EXCEPT CONNECTED TO EMERGENCY CRITICAL CIRCUIT.
TR
BRANCH CIRCUIT WIRING
LED LIGHTING FIXTURE, CONNECT TO EMERGENCY CRITICAL CIRCUIT - TYPE AS SPECIFIED IN SCHEDULE.
LED LIGHTING FIXTURE, CONNECTED TO NORMAL CIRCUIT - TYPE AS SPECIFIED IN SCHEDULE.
LED LIGHTING FIXTURE CONNECTED TO NORMAL CIRCUIT AS INDICATED - TYPE AS SPECIFIED IN SCHEDULE. "A" INDICATES TYPE, "3" INDICATES CIRCUIT NUMBER ASSIGNMENT, "a" INDICATES LOCAL SWITCHING CONTROL. CONNECT FIXTURES SO THAT FIXTURES ARE
CONTROLLED BY
A
A
480/277V-3Ø-4W PANELBOARD UNLESS OTHERWISE NOTED. MOUNT AT 78" AFF TO TOP OF PANEL.
208/120V-3Ø-4W PANELBOARD UNLESS OTHERWISE NOTED. MOUNT AT 78" AFF TO TOP OF PANEL.
GENERAL PURPOSE, 3 PHASE DRY-TYPE TRANSFORMER - TYPE AS NOTED ON PLANS.
FUSED DISCONNECT SWITCH OR ENCLOSED CIRCUIT BREAKER - SIZE AND TYPE AS NOTED. PROVIDE CLASS RK1 FUSES UNLESS
OTHERWISE NOTED. NEMA 1 ENCLOSURE UNLESS OTHERWISE NOTED.
LIGHTING FIXTURES AND CONTROLS
POWER DISTRIBUTION EQUIPMENT (FLOOR PLAN VIEW)
WIRING TERMINATIONS
WIRING DEVICES GENERAL ELECTRICAL INSTALLATION NOTES:
1. ALL MOUNTING HEIGHTS ARE TO CENTER OF DEVICE UNLESS OTHERWISE NOTED.
2. ALL NEW WALL MOUNTED ELECTRICAL DEVICES ARE TO BE INSTALLED FLUSH IN WALL UNLESS OTHERWISE NOTED. ALL ELECTRICAL CONDUIT SHALL BE CONCEALED BEHIND FINISHED WALLS AND ABOVE FINISHED CEILING UNLESS OTHERWISE NOTED. THE COST TO CUT AND PATCH WALLS SHALL BE THE
RESPONSIBILITY OF THE TRADE REQUIRING THE CUTTING.
3. CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS REQUIRED FOR ELECTRICAL WORK. CONTRACTOR SHALL REPLACE ANY
DAMAGED CEILING TILES.
4. PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW OR RELOCATED WALL OR CEILING MOUNTED DEVICES WITH ARCHITECTURAL ELEVATIONS
AND REFLECTED CEILING PLANS.
5. COORDINATE ALL SHUT-DOWNS OF EXISTING ELECTRICAL SYSTEMS WITH OWNER A MINIMUM OF FOURTEEN (14) WORKING DAYS IN ADVANCE. ALL
SHUT-DOWNS SHALL OCCUR DURING WEEKENDS OR BETWEEN 8:00PM AND 7:00AM ON WEEKDAYS ("OFF-HOURS"). INCLUDE ALL PREMIUM TIME CHARGES
IN BID.
6. ALL NOISE GENERATING OPERATIONS, INCLUDING CUTTING OF CEILINGS, WALLS AND FLOORS, CORING, DRILLING, ETC. SHALL BE SCHEDULED IN
ACCORDANCE WITH PROJECT SPECIFICATIONS (SECTION 01 00 00). INCLUDE ALL PREMIUM TIME CHARGES IN BID.
7. CONTRACTOR SHALL CONNECT ALL MECHANICAL EQUIPMENT COMPLETE PER MANUFACTURER'S WIRING DIAGRAMS AND INSTRUCTIONS. COORDINATE
WITH MECHANICAL CONTRACTOR AND VERIFY LOCATION, VOLTAGE, AMPS, NO. OF WIRES, AND PROTECTION REQUIREMENTS PRIOR TO ROUGH-IN.
CONTACT ENGINEER WITH ANY DISCREPANCIES FROM DESIGN DRAWINGS.
8. PROVIDE LIQUID-TIGHT FLEXIBLE METAL CONDUIT FOR FINAL CONNECTION TO MECHANICAL EQUIPMENT OR OTHER EQUIPMENT WHICH MAY PROPAGATE
VIBRATION.
9. ALL FLUORESCENT LAMPS THAT WILL NOT BE REUSED SHALL BE DISPOSED OF IN ACCORDANCE WITH EPA STANDARDS, AND WRITTEN EVIDENCE OF
PROPER DISPOSAL SHALL BE FURNISHED TO THE OWNER.
10. ALL WORK SHALL BE PERFORMED IN STRICT CONFORMANCE WITH THE PHASING REQUIREMENTS OF THE PROJECT. ALL COSTS ASSOCIATED WITH THESE
REQUIREMENTS SHALL BE INCLUDED IN THE BID SUBMITTAL.
11. CONTRACTOR IS RESPONSIBLE FOR PROVIDING TEMPORARY LIGHTING TO ADEQUATELY LIGHT ALL CONSTRUCTION AREAS, TEMPORARILY PARTITIONED
AREAS, AND EXIT CORRIDORS MAINTAINED DURING CONSTRUCTION.
12. DEFINITION: "PROVIDE" - FURNISH, INSTALL AND CONNECT COMPLETE.
13. PROJECT AND PHASING SCOPE LINES INDICATE WHERE GENERAL CONSTRUCTION BOUNDARIES OCCUR. ELECTRICAL WORK AND UTILITY TIE-INS MAY
OCCUR OUTSIDE OF SCOPE LINES.
A
GROUNDING BUSBAR
GB
LED LIGHTING FIXTURE CONNECTED TO EMERGENCY CRITICAL CIRCUIT - TYPE AS SPECIFIED IN SCHEDULE, "A" INDICATES TYPE, "3" INDICATES CIRCUIT NUMBER ASSIGNMENT. CONNECT FIXTURES SO THAT FIXTURES ARE CONTROLLED BY a
3,a
A
DUAL TECHNOLOGY OCCUPANCY/VACANCY SENSOR - CONNECTS TO ROOM CONTROLLER VIA CAT6A CABLING. PROVIDE COMPLETE
SYSTEM INDCLUDING SENSOR, ROOM CONTROLLERS, AND LOW-VOLTAGE OVER-RIDE SWITCH. REFER TO OCCUPANCY SENSOR PROGRAM SCHEDULE AND OCCUPANCY SENSOR DIAGRAM FOR ADDITIONAL INFORMATION. PROVIDE FORM C RELAY IN RELAY UNIT IN ALL
OCCUPANCY SENSOR FOR HVAC SWITCHING.
LIGHTING ROOM CONTROLLER - INTEGRATES LOW-VOLTAGE DIMMING SWITCH, SWITCH, AND OCCUPANCY SENSOR. PROVIDES DIMMING
AND CONTROL OUTPUT TO LIGHTING FIXTURES. UTILIZES CAT6A CABLING TO CONNECT TO SWITCHING AND OCCUPANCY SENSORS AND
UTILIZES STANDARD LOW-VOLTAGE CLING TO CONNECT TO FIXTURES DIMMING DRIVER. REFER TO OCCUPANCY SENSOR DIAGRAM FOR
ADDITON INFORMATION . ROOM CONTROLLER, OCCUPANCY SENSOR, AND OVER09RIDE SWITCH SHALL BE A COMPLETE SYSTEM FROM A
SINGLE MANUFACTURER.
OS
LIGHTING CONTROLS SYSTEM GENERAL NOTES:
1. ALL COMPONENTS FOR OCCUPANCY AND DAYLIGHT HARVESTING SYSTEM SHALL BE FROM A SINGLE MANUFACTURER AND UL LABELED.
2. SENSORS (OCCUPANCY/VACANCY, DAYLIGHT HARVESTING, ETC.) MAY BE STAND ALONE, COMBINATION, OR INTEGRATED WITH LIGHTING
FIXTURES.
3. PROVIDE ALL ADDITIONAL COMPONENTS NECESSARY FOR COMPLETE SYSTEM PER MANUFACTURER'S REQUIREMENTS.
4. SUBMIT WIRING DIAGRAMS SHOWING COMPLETE LIGHTING CONTROLS CONNECTIONS TO ENGINEER FOR REVIEW WITH SHOP DRAWINGS.
5. PROVIDE POWER SUPPLY FOR LOW-VOLTAGE SWITCHES AS REQUIRED.
24V SINGLE POLE, LARGE BUTTON SWITCH WITH INTEGRAL DIMMING FUNCTION - MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED.
PROVIDE SINGLE GANG BACK BOX AND 1"C FROM BACK BOX TO ABOVE FINISHED CEILING TO ROUTE LOW-VOLTAGE CABLING. CONNECT
COMPLETE TO ROOM CONTROLLER VIA CAT6A CABLING. SWITCH SHALL BE CAPABLE OF 3-WAY AND 4-WAY OPERATION BY INSTALLATION OF
ADDITIONAL SWITCHES VIA CONNECTION TO ROOM CONTROLLER OR DAISY-CHAINED.
DLV DS
EMERGENCY POWER OFF PUSHBUTTON "EPO" - MOUNTED AT 48" AFF. REFER TO ELECTRICAL PLANS FOR TYPE.
DOOR SWITCH - NORMALLY OPEN/NORMALLY CLOSED CONTACTS. MOUNT IN DOOR FRAME.
DUCT DETECTOR - ADDRESSABLE INTELLIGENT PHOTOELECTRIC DETECTOR (MATCH EXISTING TYPE), SAMPLING TUBES AND PROGRAMMABLE RELAY BASE. PROVIDE DUCT DETECTOR TEST/RESET SWITCH (MATCH EXISTING TYPE) WITH REMOTE INDICATOR
LAMP FOR EACH DUCT DETECTOR - WALL MOUNTED AT 7'-6" AFF.
ADDRESSABLE FIRE ALARM CONTROL PANEL (MANUFACTURER NOTIFIER).
STROBE ONLY DEVICE (ADA TYPE) (MATCH EXISTING TYPE) - RED HOUSING WITH WHITE "FIRE" LETTERING. MOUNTED AT 80" AFF.
FACP
F
FIRE ALARM REMOTE ANNUNCIATOR - FLUSH MOUNTED AT 5'-0" AFF TO TOP OF DEVICE.FARA
FIRE ALARM POWER SUPPLY EXTENDER - CONNECT TO 120V LIFE SAFETY CIRCUIT. SURFACE MOUNTED AT 5'-0" AFF TO TOP OF
DEVICE.
FPS
FIRE ALARM SYSTEM NOTES:
F1. PROVIDE A 2-GANG MINIMUM SIZE BACKBOX FOR ALL OF THE ABOVE FIRE ALARM DEVICES. ALL FIRE ALARM SYSTEM
CONDUCTORS SHALL BE INSTALLED IN 3/4" MINIMUM SIZE COMPLETE CONDUIT SYSTEM WITH COLOR CODED WIRING AS
INDICATED ON SHOP DRAWINGS PREPARED BY NOTIFIER - MAINTAIN HOSPITAL COLOR CODING. ALL NETWORK AND IDNET CABLES SHALL BE "COMMUNICATION GRADE" TYPE CABLE. FURNISH, INSTALL AND CONNECT ALL FIRE ALARM DEVICES IN
ACCORDANCE WITH WIRING DIAGRAMS AS PREPARED BY NOTIFER.
FIRE ALARM SYSTEM
TYPE
QUANTITY WATTS TYPE COLOR TEMP.
FIXTURE INFORMATION
QUANTITY TYPE VOLTAGE
DRIVER INFORMATION
GENERAL LIGHTING INSTALLATION NOTES:
L1. REFER TO ELECTRICAL SPECIFICATIONS FOR FIXTURE COLOR TEMPERATURE AND DRIVER TYPE.
L2. ELECTRICAL CONTRACTOR SHALL COORDINATE LIGHTING FIXTURE TYPE (GRID OR FLANGE) WITH ACTUAL CEILING TYPE PRIOR TO ORDERING FIXTURES. CONTACT ENGINEER IF QUESTIONS SHOULD ARISE CONCERNING CEILING
TYPES.
L3. ELECTRICAL CONTRACTOR SHALL VERIFY ALL DRIVER QUANTITIES WITH SWITCHING SHOWN ON PLANS PRIOR TO ORDERING FIXTURES. ADJUST BALLAST QUANTITIES AS REQUIRED TO MATCH SWITCHING.
L4. VERIFY LIGHTING CIRCUIT VOLTAGE (277V-1Ø OR 120V-1Ø) PRIOR TO ORDERING LIGHTING FIXTURES OR STARTING ROUGH-IN OF BRANCH CIRCUITS. IMMEDIATELY CONTACT ENGINEER WITH ANY DISCREPANCIES. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ORDERING THE PROPER VOLTAGE FOR LIGHTING FIXTURES, REGARDLESS OF VOLTAGE SHOWN ON LIGHTING FIXTURE SCHEDULE.
L5. ELECTRICAL CONTRACTOR SHALL VERIFY ALL FIXTURES TO BE CONTROLLED BY DIMMER SWITCHES AS SHOWN ON PLANS PRIOR TO ORDERING FIXTURES.
1 15.5W 120/ 277V
LED
0-10V
DIMMING
(100-1%) 14000°K
LED WARNING LIGHT - 120/277V DUAL VOLTAGE INPUT, LED TYPE, AC ONLY, UNIVERSAL MOUNTING, SINGLE
FACE, DIECAST ALUMINUM HOUSING WITH WHITE FINISH, RED STENCIL LETTERS ON WHITE FACE. PROVIDE
"CT EQUIPMENT IN USE" SIGNAGE FOR CT SCAN PROCEDURE ROOM
6" DIA RECESSED DOWNLIGHT, SEMI SPECULAR CLEAR REFLECTOR AND WHITE POLYMER TRIM
RING, 1500 LUMEN OUTPUT, MINIMUM CRI OF 90, MEDIUM DISTRIBUTION, LED BOARD AND DRIVER
ACCESSIBLE FROM BELOW, CONVEX TRANSITIONAL LENS, FUSED.
A
DESCRIPTION
1 LED N/A 1 N/A
120/ 277V
4WW
RC
24V SINGLE POLE, LARGE BUTTON SWITCH - MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED. PROVIDE SINGLE GANG BACK BOX AND 1"C
FROM BACK BOX TO ABOVE FINISHED CEILING TO ROUTE LOW-VOLTAGE CABLING. CONNECT COMPLETE TO ROOM CONTROLLER VIA CAT6A
CABLING. SWITCH SHALL BE CAPABLE OF 3-WAY AND 4-WAY OPERATION BY INSTALLATION OF ADDITIONAL SWITCHES VIA CONNECTION TO
ROOM CONTROLLER OR DAISY-CHAINED.
LV
3,a a
SD
HORN ONLY DEVICE (ADA TYPE) (MATCH EXISTING TYPE) - RED HOUSING WITH WHITE "FIRE" LETTERING. MOUNTED AT 80" AFF.F
FIRE ALARM TERMINAL CABINET (MANUFACTURER NOTIFIER).FATP
ELECTRICAL LEGEND AND GENERAL
NOTES
A
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
3 4 5 6 7 8 9 10
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF
THIS DESIGN AND THESE CONSTRUCTION
DOCUMENTS FOR PURPOSES OTHER THAN
THE SPECIFIC PROJECT NAMED HEREIN IS
STRICTLY PROHIBITED WITHOUT THE
EXPRESSED WRITTEN CONSENT OF
PERSPECTUS…