About this file

36C25020B0025 0001 S02. Drawings.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--VA Site Prep for Intevo Project 541-18-505 (Construction), newest first.
File Type Posted
36C25020B0025-0006000.docx DOCX document
36C25020B0025-0005000.docx DOCX document
36C25020B0025-0005001.pdf PDF
36C25020B0025-0004000.docx DOCX document
36C25020B0025-0003000.docx DOCX document
36C25020B0025-0002001.docx DOCX document
36C25020B0025-0001009.pdf PDF
36C25020B0025-0001005.pdf PDF
36C25020B0025-0001010.docx DOCX document
36C25020B0025-0001008.docx DOCX document
36C25020B0025-0001007.docx DOCX document
36C25020B0025-0001001.pdf PDF
36C25020B0025-0001000.docx DOCX document
36C25020B0025-0001003.pdf PDF
36C25020B0025-0001006.pdf PDF
36C25020B0025-0001011.pdf PDF
36C25020B0025-0001004.pdf PDF
36C25020B0025-008.docx DOCX document
Show all 18

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

V

20'-0"±

E X

C

O N

C R

E T

E

B

E A

M

EX. CONCRETE BEAM

3'-0"±3'-0"±

EX. CONCRETE

JOIST

E X

C

O N

C R

E T

E

J O

I S

T

L6x6x5/16 BELOW ANCHORAGE

LOCATIONS - SEE DETAILS (THIS

SHEET) FOR MORE INFORMATION

(TYP.)

EXISTING BASEMENT FRAMING PARTIAL PLAN

1/4"=1'-0"

GANTRY (8,650 LBS.)

FRONT PHS (2,750 LBS.)

REAR PHS (385 LBS.)

EX. CONCRETE

JOIST

NOTE:

CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND

CONDITIONS IN FIELD PRIOR TO FABRICATION.

LEGEND:

INDICATES 12" DEEP CONCRETE

JOISTS WITH 3" FLANGE.

MEDICAL UNIT ANCHORAGE

LOCATION - COORDINATE WITH

MEDICAL UNIT SUPPLIER (TYP.)

E X

C

O N

C R

E T

E

B

E A

M

8"± 2'-6"± 8"±

TYPICAL ANCHORAGE DETAIL AT JOIST FLANGE

1 1/2"=1'-0"

8"±

TYPICAL ANCHORAGE DETAIL AT JOIST STEM

1 1/2"=1'-0"

ANCHORS TO OCCUR WITHIN

THE TAPERED EDGES OF THE

JOIST STEM

TYPICAL ANCHORAGE DETAIL AT CONCRETE BEAM

1 1/2"=1'-0"

/2

MEDICAL UNIT - COORDINATE

WITH ARCH. & UNIT SUPPLIER

DRAWINGS

L6x6x5/16 - TAPER

ENDS TO MATCH

SLOPE OF JOIST

STEM PROFILE

(2) 1/2"ø HILTI KWIK BOLT TZ

WITH 3 5/8" MIN. EMBED (TYP.)

L3x3x5/16 x 6" LONG WITH

(2) 3/4"ø (A325) BOLTS TO

L6x6 (TYP.)

PROVIDE 3"x3"

SQUARE PLATE

WASHER SHIM

PLATES AS

REQUIRED

EX. CONCRETE JOIST

THRU-BOLT (A325) - SEE

MEDICAL UNIT DRAWINGS FOR

REQUIRED BOLT DIAMTER

EX. CONCRETE JOIST

MEDICAL UNIT - COORDINATE

WITH ARCH. & UNIT SUPPLIER

DRAWINGS

HILTI HY-200 ADHESIVE

ANCHOR WITH 2 3/4"EMBED &

MIN. SPACING OF 1 7/8" WHERE

MULTIPLE ANCHORS OCCUR -

SEE MEDICAL UNIT DRAWINGS

FOR BOLT DIAMETERS

HILTI HY-200 ADHESIVE

ANCHOR WITH 8" EMBED - SEE

MEDICAL UNIT DRAWINGS FOR

BOLT DIAMETERS

MEDICAL UNIT - COORDINATE

WITH ARCH. & UNIT SUPPLIER

DRAWINGS

EX. CONCRETE JOIST

EX. WIRE MESHEX. WIRE MESHEX. WIRE MESH

3'-0"±

GENERAL

1. All new construction shall comply with the Contract Documents and the Building

Code.

2. Typical details and general notes apply to all parts of the work except where specifically detailed or unless otherwise noted.

3. The structural drawings illustrate structural members. Refer to architectural, mechanical, and electrical drawings for non-structural items which require special provisions during the construction of the structural members.

4. Drawings are not to be scaled.

5. The Contractor shall verify and be responsible for all dimensions and conditions which impact the work. Field verify sizes, elevations, hole locations, etc., prior to fabrication.

6. The Contractor shall carefully review the drawings to identify the scope of work required, visit the site to relate the scope of work to existing conditions and determine the extent to which those conditions and physical surroundings will impact the work.

7. Existing conditions as shown on these plans are for reference only. The Contractor is required to field verify all existing conditions prior to construction.

8. The Contractor shall resolve any conflicts on the drawings with the

Architect/Engineer before proceeding with the work.

9. Any deviation, modification, or substitution from the approved set of structural drawings shall be submitted to the Owner, Architect, and Engineer for review/approval prior to its use or inclusion on the shop drawings.

10. The Contractor shall provide means, method, techniques, sequence, and procedure of construction as required.

11. The Contractor shall protect all work, materials, and equipment from damage and shall provide proper storage facilities for materials and equipment during construction.

DESIGN STRESSES

Structural steel other shapes (ASTM A36) -------------------------------------------- Fy = 36,000 psi

DESIGN LOADS (OBC 2017)

Floor live load --------------------------------------------------------------------------------- 50 psf

Equipment loads ----------------------------------------------------------------------------- As Noted

CODES AND STANDARDS

1. New construction has been designed to, and shall be constructed in accordance with the following building codes and standards:

A. 2017 Ohio Building Code (OBC 2017)

B. City of Cleveland, Ohio, Code of Ordinances

C. ASCE 7-10, Minimum Design Loads for Buildings and Other Structures

2. Unless explicitly modified in the Contract Drawings and Specifications, the Contractor shall comply with provisions of:

A. ACI 301-10, Specifications for Structural Concrete

B. ACI 318-14, Building Code Requirements for Structural Concrete

C. AISC 360-10, Specification for Structural Steel Buildings

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

1-S1

PARTIAL FRAMING PLAN,

SECTIONS, & NOTES

A

F i l e

P a t h

P

M

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Louis Stokes Cleveland

VA Medical Center

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT OF RECORD: STAMPCONSULTANTS:

321 4 5 6 7 8 9 10

CLEVELAND, OHIO

541-18-505

Project Director

10/11/2019 JTL MCDRevisions: Date:

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF

THIS DESIGN AND THESE CONSTRUCTION

DOCUMENTS FOR PURPOSES OTHER THAN

THE SPECIFIC PROJECT NAMED HEREIN IS

STRICTLY PROHIBITED WITHOUT THE

EXPRESSED WRITTEN CONSENT OF

PERSPECTUS ARCHITECTURE.

13212 Shaker Square Suite Cleveland, Ohio 44120

P. 216.752.1800 F.216.752.3833

Consulting Engineers

BARBER & HOFFMAN, INC.

2217 East 9th Street, Suite 350

Cleveland OH 44115-1257

216-875-0100/ (F) 216-875-0111 barberhoffman.com

100% Construction Document Submission 9/13/19

PROJECT

SCOPE

KEY PLAN - BASEMENT

Scale = None

B

A

C

B

A

C

B-B2

B-B3

B-B4

B-B5

B-C2

B-C3

B-C4

B-C5

B-D2

B-D3

B-D4

B-E3

B-E4

B-E2

B-F3

B-F4

TRUE

NORTH

C:\ArchiComp\Chrisprjold\PhilNew\VAMU\FromTim\Logos\FFH ICON (GRAY).tif

VA SITE PREP FOR

INTEVO

Final Construction Document Submission 10/11/19

BARBER & HOFFMAN, INC.

S

T

A

T

E

O

F

O

H

I

O

P R

O

F

E

S

S

I

O

N A

L

E

N

G

I

N

E

E

R

R

E

G

I

S

T

E

R

E

D

JON T.

LEUTHAEUSER

E-65601

AutoCAD SHX Text

TEL. (440) 546-9696

AutoCAD SHX Text

BROADVIEW HTS., OHIO 44147

AutoCAD SHX Text

672 EAST ROYALTON ROAD

AutoCAD SHX Text

FAX: (440) 546-9699

AutoCAD SHX Text

FREDRICK, FREDRICK & HELLER

AutoCAD SHX Text

ENGINEERS, INC.

BC-446A

Nuc Med

BC-474

0B

BC-446

Hot LabRad Waste

Nuc Med

BC-475

Thyroid Uptake

BC-448

Inject

BC-461

A. LOCATIONS AND ROUTING OF EXISTING PIPING, DUCTWORK AND EQUIPMENT IS PRESUMED FROM

EXISTING DRAWINGS. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ALL PRIOR TO COMMENCEMENT

OF CONSTRUCTION. NOTIFY ENGINEER OF ANY CONDITIONS WHICH WILL NOT PERMIT THE WORK TO BE

PERFORMED AS INDICATED ON THESE DRAWINGS.

B. REFER TO SPECIFICATIONS FOR SHUTDOWN NOTIFICATION REQUIREMENTS.

C. PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW WALL MOUNTED DEVICES WITH OWNER AND

ARCHITECT. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR PRECISE LOCATION OF CEILING

MOUNTED DEVICES.

D. PROVIDE ADEQUATE SERVICE CLEARANCE FOR ALL EQUIPMENT. REFER TO INSTRUCTIONS FROM THE

EQUIPMENT MANUFACTURER.

E. NEW PIPING SHALL NOT BE ROUTED ABOVE ELECTRICAL PANELS. REFER TO ELECTRICAL DRAWINGS FOR

LOCATION OF PANELS.

F. THE FIRE SUPPRESSION CONTRACTOR SHALL PROVIDE DETAILED DESIGN OF THE SPRINKLER SYSTEM.

REFER TO SPECIFICATIONS.

G. UNLESS OTHERWISE NOTED NEW SPRINKLERS SHALL BE AS FOLLOWS:

G.1. AREAS WITH CEILINGS: SEMI-RECESSED WITH CHROME ESCUTCHEONS.

G.2. EXPOSED STRUCTURE: UPRIGHT OR PENDENT TYPE.

H. THE FIRE PROTECTION SYSTEM IS PERFORMANCE SPECIFIED. ALL SPRINKLER PIPE SIZES SHALL BE

DETERMINED BY FIRE PROTECTION CONTRACTOR, BASED ON HYDRAULIC CALCULATIONS.

I. PROVIDE SUPPLEMENTAL DRAINS AS NECESSARY TO PROVIDE 100% SYSTEM DRAINAGE. LOCATE DRAINS

ABOVE ACCESSIBLE CEILINGS.

J. REFER TO ARCHITECTURAL PLANS FOR EXACT PHASING REQUIREMENTS.

K. REFER TO SPECIFICATIONS FOR FIRE SUPPRESSION HAZARD OCCUPANCY CLASSIFICATIONS.

L. SPRINKLER PIPING SHALL BE A MINIMUM OF ONE INCH.

M. UNLESS OTHERWISE STATED ON DRAWINGS OR IN THE SPECIFICATIONS, ALL SPRINKLER HEADS SHALL BE

QUICK RESPONSE.

N. ALL HEADS SHALL BE UL LISTED AND FM APPROVED.

O. ALL SPRINKLER HEADS LOCATED IN CEILING TILES SHALL BE LOCATED IN CENTER OF THE CEILING TILE.

P. ALL SPRINKLER ZONES SHALL MATCH SMOKE COMPARTMENTS. REFER TO ARCHITECTURAL PLANS FOR

INFORMATION ON SMOKE COMPARTMENTS, SMOKE PARTITIONS AND FIRE BARRIERS.

Q. CONTRACTOR SHALL REMOVE AND REPLACE CEILING TILES AND GRID AS REQUIRED TO COMPLETE

DEMOLITION AND NEW WORK IN AREAS OUTSIDE OF RENOVATION PROJECT. CONTRACTOR SHALL BE

RESPONSIBLE FOR REPLACING ANY TILES OR GRID DAMAGED DUE TO THIS WORK.

FIRE SUPPRESSION GENERAL NOTES:

FIRE SUPPRESSION PIPING LEGEND

F FIRE SUPPRESSION PIPING

FR FIRE RISER

SP STAND PIPE

FDV FIRE DEPARTMENT VALVE

EXISTING TO REMAIN

EXISTING TO BE REMOVED

X

XR

EC ELECTRICAL CONTRACTOR

HC HVAC CONTRACTOR

FSC FIRE SUPPRESSION CONTRACTOR

GC GENERAL CONTRACTOR

A. THIS PROJECT CONSISTS OF MULTIPLE TRADES OF WORK PERFORMED WITHIN AN EXISTING BUILDING, ALL OF WHICH ALLOWS VERY LITTLE PERMISSIBLE RANGE OF VARIATION. THE CONTRACTOR SHALL

TAKE CAREFUL CONSIDERATION WITH THE COORDINATION AND INSTALLATION OF THE MULTITUDE OF

NEW SYSTEMS WHILE ALSO ACCOMMODATING ANY EXISTING SYSTEMS TO REMAIN.

B. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL TRADES ASSOCIATED WITH THIS

PROJECT AND ISSUING COORDINATION PLANS PRIOR TO COMMENCEMENT OF EACH PHASE OF

CONSTRUCTION.

C. THE COORDINATION DRAWINGS SHALL ILLUSTRATE ALL SYSTEMS IN PLACE. NO EXCEPTIONS! THE

CONTRACTOR SHALL SHOW ALL NECESSARY OFFSETS, TRANSITIONS, ETC. AS REQUIRED IN ORDER TO

ACCOMMODATE CONDITIONS IDENTIFIED IN THE FIELD.

D. IF CONFLICTS ARE IDENTIFIED DURING THE DEVELOPMENT OF COORDINATION PLANS, THE

CONTRACTOR SHALL NOTIFY THE VA COTR, ARCHITECT, AND/OR ENGINEER OF ANY CONDITIONS WHICH

WILL NOT PERMIT THE WORK TO BE PERFORMED AS INDICATED ON THE PROJECT PLANS.

E. A COMPLETED SET OF COORDINATION PLANS ISSUED FOR REVIEW SHALL CONFIRM THAT THE

CONTRACTOR FULLY UNDERSTANDS THE PROJECT CONSTRAINTS AND ALL KNOWN CONFLICTS HAVE

BEEN ADDRESSED.

REWORK EXISTING SPRINKLER MAIN AS REQUIRED TO ACCOMMODATE

RENOVATION IN OUTLINED AREA. REFER TO OTHER TRADES FOR WORK IN

OUTLINED AREA. OUTLINED AREA SHALL BE SPRINKLERED BY EXISTING

SPRINKLER ZONE. SPRINKLER ZONE VALVE IS LOCATED IN STAIR #8 (ROOM

BB420). PROVIDE ALL NEW SPRINKLER BRANCH PIPING AND HEADS IN

OUTLINED AREA.

FIRE SUPPRESSION LEGEND

ALL OUTLINED AREAS SHALL BE 100% FULLY SPRINKLERED WITH A

WET-TYPE SPRINKLER SYSTEM IN ACCORDANCE WITH NFPA 13 AND

VA SPECIFICATIONS. SPRINKLER HEADS SHALL BE INSTALLED SO AS

TO ACCOMMODATE ANY NEW CEILINGS. COORDINATE SPRINKLER

HEAD LAYOUT WITH ARCHITECTURAL REFLECTED CEILING PLAN.

REFER TO MECHANICAL SPECIFICATIONS AND FIRE SUPPRESSION

NOTES FOR ADDITIONAL INFORMATION.

A

/1

/2

:3

:0

P

M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

3 4 5 6 7 8 9 10

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF

THIS DESIGN AND THESE CONSTRUCTION

DOCUMENTS FOR PURPOSES OTHER THAN

THE SPECIFIC PROJECT NAMED HEREIN IS

STRICTLY PROHIBITED WITHOUT THE

EXPRESSED WRITTEN CONSENT OF

PERSPECTUS ARCHITECTURE.13212 Shaker Square Suite Cleveland, Ohio 44120

P. 216.752.1800 F.216.752.3833 Consulting Engineers

2217 East 9th Street, Suite 350

Cleveland OH 44115-1257

216-875-0100/ (F) 216-875-0111 barberhoffman.com

B-AC-3

B-AC-2

Louis Stokes Cleveland

VA Medical Center

S

74490

L.D. HENDRIX, JR

R E

S

O F

I

R

GE

NOIS

P

E

N E

D

ERT

L EA

E I N

G

R

T

S

TE

A H

F OO

IO

19057

U.S. Department of Veterans Affairs

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

541-18-505

10/11/2019

VA SITE PREP FOR

INTEVO

F ile

P a th

Drawing Title

Approved: Project Director

ARCHITECT OF RECORD: STAMPCONSULTANTS:

Final Construction Document Submission 10/11/19

Project Number

Building Number

Drawing Number

Project Title

Location

Phase

Issue Date Checked Drawn

CLEVELAND, OHIO

Revisions: Date:

FIRE PROTECTION PLAN

0'

SCALE: 1/4" = 1'0"

2' 4' 8' 16'

PARTIAL BASEMENT FIRE

PROTECTION PLAN

V

LDH LDH

PLUMBING GENERAL NOTES:

A. LOCATIONS AND ROUTING OF EXISTING PIPING, DUCTWORK AND EQUIPMENT IS PRESUMED FROM

EXISTING DRAWINGS. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ALL PRIOR TO COMMENCEMENT

OF CONSTRUCTION. NOTIFY ENGINEER OF ANY CONDITIONS WHICH WILL NOT PERMIT THE WORK TO BE

PERFORMED AS INDICATED ON THESE DRAWINGS.

B. COORDINATE ALL SHUT-DOWNS OF EXISTING MECHANICAL SYSTEMS WITH OWNER A MINIMUM OF TEN

WORKING DAYS IN ADVANCE.

C. PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW WALL MOUNTED DEVICES WITH VA AND

ARCHITECT.

D. PROVIDE ADEQUATE SERVICE CLEARANCE FOR ALL MECHANICAL EQUIPMENT. REFER TO INSTRUCTIONS

FROM THE EQUIPMENT MANUFACTURER.

E. NEW PIPING SHALL NOT BE ROUTED ABOVE ELECTRICAL PANELS. REFER TO ELECTRICAL DRAWINGS FOR

LOCATION OF PANELS.

F. WHERE EXISTING FIXTURES ARE TO BE REMOVED, REMOVE ALL ASSOCIATED BRANCH PIPING WHICH IS

NOT TO BE REUSED. REMOVE PIPING TO MAINS AND CAP.

G. CONTRACTOR SHALL REMOVE AND REPLACE CEILING TILES AND GRID AS REQUIRED TO COMPLETE

DEMOLITION AND NEW WORK IN AREAS OUTSIDE OF RENOVATION PROJECT. CONTRACTOR SHALL BE

RESPONSIBLE FOR REPLACING ANY TILES OR GRID DAMAGED DUE TO THIS WORK.

H. CONTRACTOR SHALL PROVIDE NEW CHASE ENCLOSURES WHERE EXISTING STORM, SANITARY, WATER, VENT RISERS ARE TO REMAIN, BUT ARE UNCOVERED/EXPOSED DURING CONSTRUCTION. ENCLOSURES

SHALL FULLY CONCEAL PIPING. COORDINATE REQUIREMENTS WITH GENERAL TRADES.

I. PLUMBING PIPING SYSTEMS SHALL BE SUPPORTED FROM STRUCTURE INDEPENDENTLY OF OTHER

SYSTEMS.

FAUCET SEE

SPECIFICATIONS

LAMINAR FLOW

CONTROL DEVICE

OFFSET

WASTE

TRAP PARALLEL TO WALL.

PROVIDE PROTECTIVE TRAP

COVER PER SPECIFICATIONS.

LOOSE KEY

STOP

ESCUTCHEON

FINISHED

FLOOR

34"

8"

10 3/4"±

F O

R F

IX

T

U R

E H

E

IG

H T

S

S E

E A

R C

H

IT

E C

T U

R A

L

D R

A W

IN

G

S

NOT TO SCALE

TYPICAL ADA LAVATORY DETAIL

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

MAXIMUM PIPE/TUBING SUPPORT SPACING

TYPICAL PIPE HANGERS

TUBING 5 FT

NOM. SIZE

PIPE

THRU (20)

6 8 10

(32)(25) (40)

(65)

(50)

(75)

ADJUSTABLE CLEVIS HANGER

TYPE 43 - SEE SPECIFICATIONS

SADDLE

WELD

1312 14 16

(125)(100)

(150)

(200)

TO 1000 LB. (453 KG) UNIFORM LOAD

TRAPEZE HANGER FOR UP

PROVIDE INSULATION SHIELD

SIDE VIEW

1 5/8" (43 MM) 12 GAGE1" (25 MM) MAX.

STRENGTH INSULATION

PROVIDE HIGH COMPRESSIVE

TYPE 1 - SEE SPECIFICATIONS

ADJUSTABLE CLEVIS HANGER

HANGER ROD

UNDER INSULATION SHIELD

AT HANGER

INSULATION SHIELD

TEMPERATURE PIPE)

REQUIRED FOR LOW

BARRIER TYPE IS

INSULATION (VAPOR

SPACING ON

36" (900 MM) MAX.

BAND

(9 PCF MIN. DENSITY)

HANGER RODS WITH

(8" (200 MM) MIN.)

CHANNEL OR 2"x2"x1/4"

(50x50x8 MM) ANGLE

864 532 2 1/21 1/21 1 1/4IN.

(MM)

(M)

FT.

FT.

(M)

(5.8)(5.2)(4.1) (4.9)(3.7)(3.0) (3.4)(2.7)(2.1)

(4.9)(4.1)(3.7) (4.0)(3.0)(2.4)(1.8)5 FT

THRU 3/4

(2.1) (2.1)

(2.1)

(2.7)

(2.4)

1/2" (15 MM) DIA.

EACH CHANNEL

AND INSERT FOR ALL PIPING

STEEL EXPANSION SHIELD FOR

THIS TYPE SHALL BE USED ONLY

INSERTS FOR NEW CONSTRUCTION

FOR EXISTING CONSTRUCTION AND

3/8" (10 MM) MIN DIA EXPANSION BOLTS

TYPICAL METHOD OF SECURING

NUTS & WASHERS

HANGER RODS

3/8" (10 MM) MIN DIA

FLOOR SLAB

CLIP

ANGLE

HANGER RODS

3/8" (10 MM) MIN DIA

TURNBUCKLE

NEW CONSTRUCTION ONLY.

3/8" (10 MM) MIN DIA INSERTS

IN SLABS OR BEAMS OF

INSERTS FOR NEW CONSTRICTION

EXISTING CONSTRUCTION AND

HANGER RODS IN CONCRETE

4" (100 MM) MIN DEPTH

CONCRETE

SLABS AND BEAMS.

NOT TO SCALE

NOT TO SCALE

MEDICAL GAS SYMBOLS:

PIPE DOWN

PIPE RISE UP

PIPE CAP

BRANCH CONNECTION

EXISTING TO BE REMAIN

EXISTING TO BE REMOVED

ISOLATION VALVE

OX MEDICAL OXYGEN

MA MEDICAL AIR

MV MEDICAL VACUUM

X

XR

L

LOCKABLE VALVE (INLINE/SERVICE)

MEDICAL GAS CONNECTION WITH OUTLET/INLET

MEDICAL GAS VACUUM SLIDE

MEDICAL GAS VALVE BOX

MEDICAL GAS GENERAL NOTES:

1. PROVIDE MEDICAL GAS PIPING SYSTEMS AND PIPE LABELS COMPLYING WITH REQUIREMENTS OF NFPA

99 "STANDARD FOR HEALTH CARE FACILITIES".

2. INSTALLATION AND CERTIFICATION SHALL COMPLY WITH ASSE/ANSI SERIES 6000, "PROFESSIONAL

QUALIFICATIONS STANDARDS FOR MEDICAL GAS SYSTEMS INSTALLERS, INSPECTORS AND VERIFIERS".

3. PROVIDE COMPATIBLE ACCESSORIES, TUBE, FITTING, AND VALVES FOR EACH SYSTEM.

A. OUTLET / INLET STYLE:

DISS

B. MEDICAL GAS TUBE, FITTINGS AND JOINTS: PRE-CLEANED AND SEALED COPPER TUBE: ASTM B 88, TYPE K OR TYPE L, WATER TUBE, SEAMLESS, DRAWN TEMPER, CLEANED FOR MEDICAL GAS USE, PURGED, AND WITH ENDS SEALED.

C. MEDICAL SYSTEM ACCESSORIES: PROVIDE THE MEDICAL GAS SYSTEM ACCESSORIES FROM

MANUFACTURER OF EXISTING ACCESSORIES, COMPATIBLE WITH EXISTING SYSTEMS.

D. SERVICE OUTLETS: INCLUDE BRASS VALVE AND BODY BLOCK WITH SEALS IN ROUGH-IN AND

FINISHING ASSEMBLIES, STEEL OUTLET BOX AND COVER PLATE; 3/8 INCH TYPE K OR L COPPER

TUBE BRAZED TO VALVE; AND PRESSURE OUTLETS WITH AUTOMATIC SECONDARY SERVICE VALVE TO PREVENT GAS FLOW WHEN PRIMARY VALVE IS REMOVED. DISS COUPLING SHALL BE INDEXED

TO PREVENT INTERCHANGE BETWEEN SERVICES, CONSTRUCTED TO PERMIT ONE HANDED

CONNECTION AND REMOVAL OF EQUIPMENT WITH POSITIVE LOCKING RING WHICH RETAINS

EQUIPMENT STEM IN VALVE DURING USE. OUTLET/INLET TYPE OF CONNECTION SHALL BE

COORDINATED WITH THE OWNER PRIOR TO ORDERING EQUIPMENT.

4. INSTALL LABELING ON VALVES, VALVE BOX COVERS, AND ALARM PANELS IN ACCORDANCE WITH

REQUIREMENTS OF NFPA 99 AND VA STANDARDS. CAPTIONS AND COLOR CODING: PER THE

REQUIREMENTS OF NFPA 99 AND VA STANDARDS.

5. LOCATIONS AND ROUTING OF EXISTING PIPING, DUCTWORK AND EQUIPMENT IS PRESUMED FROM

EXISTING DRAWINGS. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ALL PRIOR TO COMMENCEMENT OF CONSTRUCTION. NOTIFY ENGINEER OF ANY CONDITIONS WHICH WILL NOT PERMIT THE WORK TO BE

PERFORMED AS INDICATED ON THESE DRAWINGS.

6. COORDINATE ALL SHUT-DOWNS IF EXISTING MEDICAL GAS AND VACUUM SYSTEMS WITH OWNER A

MINIMUM OF TEN WORKING DAYS IN ADVANCE.

7. PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW WALL MOUNTED DEVICES WITH OWNER

AND ARCHITECT.

8. PROVIDE ADEQUATE SERVICE CLEARANCE FOR ALL EQUIPMENT. REFER TO INSTRUCTIONS FROM THE

EQUIPMENT MANUFACTURER.

9. NEW PIPING SHALL NOT BE ROUTED ABOVE ELECTRICAL PANELS. REFER TO ELECTRICAL DRAWINGS

FOR LOCATION OF PANELS.

10. WHERE EXISTING FIXTURES ARE TO BE REMOVED, REMOVE ALL ASSOCIATED BRANCH PIPING WHICH IS

NOT TO BE REUSED. REMOVE PIPING TO MAINS AND CAP REMAINING PIPES.

11. MEDICAL GAS MATERIALS, EQUIPMENT AND INSTALLATION SHALL COMPLY WITH NFPA 99, HEALTH CARE

FACILITIES”, LATEST EDITION. INSTALLATION PERSONNEL SHALL BE QUALIFIED IN ACCORDANCE WITH

ASSE SERIES 6000, “PROFESSIONAL QUALIFICATIONS FOR MEDICAL GAS SYSTEMS

INSTALLERS, INSPECTORS AND VERIFIERS”.

PLUMBING SYMBOLS:

ACCESS SIDE OF VALVE BOX OR ALARM PANEL

AS

REFER TO ARCHITECTURAL PLANS FOR DESIGNATED WALLS IN THE PROJECT AREA TO BE LINED WITH LEAD

SHIELDING BY THE CONTRACTOR. FOR EXISTING MECHANICAL DEVICES THAT ARE INDICATED TO REMAIN, THE MECHANICAL CONTRACTOR SHALL REMOVE AND RE-INSTALL OR RELOCATE THESE DEVICES. THE GC

SHALL PROVIDE NEW LEAD SHIELDING FOR ALL SUCH DEVICES. FOR NEW MECHANICAL DEVICES, THE GC SHALL PROVIDE ALL LEAD SHIELDING FOR EACH DEVICE. THE MECHANICAL CONTRACTOR SHALL COORDINATE

ALL SUCH WORK WITH THE GENERAL CONTRACTOR, AND SHALL ASSIST THE GENERAL CONTRACTOR IN THE

PERFORMANCE OF THIS WORK. IN ANY CASE, ALL PLUMBING DEVICES, HVAC DEVICES, FIRE PROTECTION

DEVICES, ETC. INSTALLED IN THESE WALLS SHALL BE SHIELDED WITH LEAD.

LEAD SHIELDING NOTE

PLUMBING FIXTURE

CONNECTION SCHEDULE

A. THIS PROJECT CONSISTS OF MULTIPLE TRADES OF WORK PERFORMED WITHIN AN EXISTING BUILDING, ALL OF WHICH ALLOWS VERY LITTLE PERMISSIBLE RANGE OF VARIATION. THE CONTRACTOR SHALL TAKE CAREFUL CONSIDERATION WITH THE COORDINATION AND INSTALLATION OF THE MULTITUDE OF

NEW SYSTEMS WHILE ALSO ACCOMMODATING ANY EXISTING SYSTEMS TO REMAIN.

B. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL TRADES ASSOCIATED WITH THIS

PROJECT AND ISSUING COORDINATION PLANS PRIOR TO COMMENCEMENT OF EACH PHASE OF

CONSTRUCTION.

C. THE COORDINATION DRAWINGS SHALL ILLUSTRATE ALL SYSTEMS IN PLACE. NO EXCEPTIONS! THE

CONTRACTOR SHALL SHOW ALL NECESSARY OFFSETS, TRANSITIONS, ETC. AS REQUIRED IN ORDER TO

ACCOMMODATE CONDITIONS IDENTIFIED IN THE FIELD.

D. IF CONFLICTS ARE IDENTIFIED DURING THE DEVELOPMENT OF COORDINATION PLANS, THE

CONTRACTOR SHALL NOTIFY THE VA COTR, ARCHITECT, AND/OR ENGINEER OF ANY CONDITIONS WHICH

WILL NOT PERMIT THE WORK TO BE PERFORMED AS INDICATED ON THE PROJECT PLANS.

E. A COMPLETED SET OF COORDINATION PLANS ISSUED FOR REVIEW SHALL CONFIRM THAT THE

CONTRACTOR FULLY UNDERSTANDS THE PROJECT CONSTRAINTS AND ALL KNOWN CONFLICTS HAVE

BEEN ADDRESSED.

PROJECT COORDINATION NOTES:

NOTE:

INSTALL IN AN ACCESSIBLE LOCATION.

MIXING VALVE DETAIL

NOT TO SCALE

H W

C W

ADJUSTABLE THERMOSTATIC

MIXING VALVE

105 DEGREE DHW TO FAUCET HW

SUPPLY IN LAVATORIES AND SINKS.

1/2" 1/2"

1/2"

H W

CHECK VALVE

NOTE:

1. APPLICABLE TO PENETRATIONS OF ALL

FIRE RATED MEMBRANES, IN

ACCORDANCE WITH NFPA 101. REFER

TO SPECIFICATIONS SECTION FOR FIRE

STOPPING SYSTEMS.

INSULATED PIPE

OR DUCT

FLOOR

FIRESTOP MATERIAL

3/4" [19mm] APPROVED

FIRESTOP INSULATION

WITH VAPOR BARRIER

PIPE SLEEVE WHERE

SPECIFIED

1/4" [6mm]Ø ANCHOR

ROD FOR NEW

CONSTRUCTION

WELD

FLOOR OR DECK PENETRATION

PARTITION OR CHASE PENETRATION

[152mm] [152mm]

MASONRY

PARTITION

PARTITION SUPPORT

FIRESTOP

MATERIAL

[152mm] [152mm]

3/4" [19mm] APPROVED

FIRESTOP INSULATION WITH

VAPOR BARRIER

DRYWALL PARTITION

INSULATED

PIPE OR

DUCT

A

/1

/2

:3

:0

P

M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

3 4 5 6 7 8 9 10

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF

THIS DESIGN AND THESE CONSTRUCTION

DOCUMENTS FOR PURPOSES OTHER THAN

THE SPECIFIC PROJECT NAMED HEREIN IS

STRICTLY PROHIBITED WITHOUT THE

EXPRESSED WRITTEN CONSENT OF

PERSPECTUS ARCHITECTURE.13212 Shaker Square Suite Cleveland, Ohio 44120

P. 216.752.1800 F.216.752.3833 Consulting Engineers

2217 East 9th Street, Suite 350

Cleveland OH 44115-1257

216-875-0100/ (F) 216-875-0111 barberhoffman.com

B-AC-3

B-AC-2

Louis Stokes Cleveland

VA Medical Center

S

74490

L.D. HENDRIX, JR

R E

S

O F

I

R

GE

NOIS

P

E

N E

D

ERT

L EA

E I N

G

R

T

S

TE

A H

F OO

IO

19057

U.S. Department of Veterans Affairs

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

541-18-505

10/11/2019

VA SITE PREP FOR

INTEVO

F ile

P a th

Drawing Title

Approved: Project Director

ARCHITECT OF RECORD: STAMPCONSULTANTS:

Final Construction Document Submission 10/11/19

Project Number

Building Number

Drawing Number

Project Title

Location

Phase

Issue Date Checked Drawn

CLEVELAND, OHIO

Revisions: Date:

PLUMBING LEGEND, SCHEDULE,

DETAILS, AND GENERAL NOTES

Hall

BC-460

BC-446A

Nuc Med

BC-474

70B

BC-446

Hot Lab

Rad Waste

Nuc Med

BC-475

Thyroid Uptake

BC-448

Inject

BC-461

X-3/4"

X-3/4"

P-418

L

X-OX

X-MV

X-3/4"

X-1/2"

X-3/4"

X-1/2"

X-1/2"

X-3/4"

X-MA

X -M

A

L

L

X-3" X-4"

X-4"

X-3"

X-3"

X-4"

X-3"

3/4"

1/2"

X-MVB

1-1/2"

V

U S

A N

ROUTE (APPROXIMATELY 20

FEET) 1-1/2" SANITARY

WITHIN SUB-BASEMENT TO

SANITARY MAIN.

REMOVE SANITARY

BRANCH BACK TO MAIN

AND CAP.

3/4"

X-HW

X-CW

X -S

A N

X-SAN

A

/1

/2

:3

:0

P

M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

3 4 5 6 7 8 9 10

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF

THIS DESIGN AND THESE CONSTRUCTION

DOCUMENTS FOR PURPOSES OTHER THAN

THE SPECIFIC PROJECT NAMED HEREIN IS

STRICTLY PROHIBITED WITHOUT THE

EXPRESSED WRITTEN CONSENT OF

PERSPECTUS ARCHITECTURE.13212 Shaker Square Suite Cleveland, Ohio 44120

P. 216.752.1800 F.216.752.3833 Consulting Engineers

2217 East 9th Street, Suite 350

Cleveland OH 44115-1257

216-875-0100/ (F) 216-875-0111 barberhoffman.com

B-AC-3

B-AC-2

Louis Stokes Cleveland

VA Medical Center

S

74490

L.D. HENDRIX, JR

R E

S

O F

I

R

GE

NOIS

P

E

N E

D

ERT

L EA

E I N

G

R

T

S

TE

A H

F OO

IO

19057

U.S. Department of Veterans Affairs

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

541-18-505

10/11/2019

VA SITE PREP FOR

INTEVO

F ile

P a th

Drawing Title

Approved: Project Director

ARCHITECT OF RECORD: STAMPCONSULTANTS:

Final Construction Document Submission 10/11/19

Project Number

Building Number

Drawing Number

Project Title

Location

Phase

Issue Date Checked Drawn

CLEVELAND, OHIO

Revisions: Date:

PARTIAL BASEMENT PLUMBING AND

MEDICAL GAS PLAN

0'

SCALE: 1/4" = 1'0"

2' 4' 8' 16'

PARTIAL BASEMENT PLUMBING

AND MEDICAL GAS PLAN

V

CALL OUTS:

MANUAL BALANCING DAMPER ON DUCT

ROUND DUCT SIZE12"Ø

RECTANGULAR DUCT SIZE24x18

REFERENCE TO CODED NOTE#

SUPPLY AIR DUCT

TO BE MOUNTED OVER ACCESSIBLE CEILING

SUPPLY AIR DIFFUSER

SHADING INDICATES TO PROVIDE QUADRANT BLANK-OFF

IN NECK OF DIFFUSER. TO BE FURNISHED WITH DIFFUSER.

AIR CONDITIONING CONDENSATE

HHWS

HHWR

CD

HEATING HOT WATER SUPPLY

HEATING HOT WATER RETURN

F FIRE SUPPRESSION PIPE

STRAINER

FLEXIBLE PIPE CONNECTOR

THERMOMETER IN PIPE WELL

BALANCING VALVE

HVAC PIPING:

SHUTOFF VALVE

REDUCER

UNION

CHECK VALVE

3-WAY CONTROL VALVE

GAUGE PORT (PETE'S PLUG)

2-WAY CONTROL VALVE

DUCTWORK SYMBOLS:

CONTROL SYMBOLS:

DDC THERMOSTATT

NORMALLY OPENNO

NORMALLY CLOSEDNC

RETURN AIR DUCT

EXHAUST AIR DUCT

EXISTING TO REMAIN

EXISTING TO BE REMOVED

X

XR

EQUIPMENT OR FIXTURE MARK

AIR DISTRIBUTION DEVICE

UNIT NUMBER

EQUIPMENT

TYPE

CONNECTION SIZE AT

DEVICE

TYPE

LIMIT OF DEMOLITION

DN

DN

UP

UP

SUPPLY DUCT (UP & DOWN)

RETURN DUCT (UP & DOWN)

CONNECT NEW DUCT TO EXISTING DUCT

AC

AD

AFF

AHU

AP

BIW

CC

CF

CO

CW

Db dB

Dp

DX

AIR CONDITIONING UNIT

ACCESS DOOR

ABOVE FINISHED FLOOR

AIR HANDLING UNIT

ACCESS PANEL

BACKWARD INCLINED WHEEL

COOLING COIL

CENTRIFUGAL FAN

CLEAN OUT

COLD WATER

DRY BULB TEMPERATURE

DECIBELS

DEW POINT TEMPERATURE

DIRECT EXPANSION

EA

EER

EF

EX.

FC

FLR.

HC

HP

EXHAUST AIR

ENERGY EFFICIENCY RATIO

EXHAUST FAN

EXISTING

FORWARD CURVED FAN

FLOOR

HEATING COIL

HORSEPOWER

MAX.

MIN.

NOM.

OA

PD

RA

RF

RH

Rh

SA

Sp. Gr.

SH

SP

MAXIMUM

MINIMUM

NOMINAL

OUTDOOR AIR

PRESSURE DROP

RETURN AIR

RETURN FAN

REHEAT COIL

RELATIVE HUMIDITY

SUPPLY AIR

SPECIFIC GRAVITY

STEAM HUMIDIFIER

STATIC PRESSURE

V

VD

Wb

VALVE

VOLUME DAMPER

WET BULB TEMPERATURE

ABBREVIATIONS:

MECHANICAL SYMBOLS:

LIMIT OF DEMOLITION

AND EXISTING WORK

POINT OF CONNECTION BETWEEN NEW

GENERAL SYMBOLS:

DIRECTION OF FLOW

EXISTING TO BE RELOCATEDXRL

RETURN AIR GRILLE

EXHAUST AIR GRILLE

A. LOCATIONS AND ROUTING OF EXISTING PIPING, DUCTWORK AND EQUIPMENT IS PRESUMED FROM

EXISTING DRAWINGS. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ALL PRIOR TO

COMMENCEMENT OF CONSTRUCTION. NOTIFY ENGINEER OF ANY CONDITIONS WHICH WILL NOT

PERMIT THE WORK TO BE PERFORMED AS INDICATED ON THESE DRAWINGS.

B. COORDINATE ALL SHUT-DOWNS OF EXISTING MECHANICAL SYSTEMS WITH OWNER A MINIMUM OF

TEN (10) WORKING DAYS IN ADVANCE.

C. PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW WALL MOUNTED DEVICES WITH

OWNER AND ARCHITECT. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR PRECISE

LOCATION OF CEILING MOUNTED DEVICES.

D. PROVIDE ADEQUATE SERVICE CLEARANCE FOR ALL MECHANICAL EQUIPMENT. REFER TO

INSTRUCTIONS FROM THE EQUIPMENT MANUFACTURER. MAINTAIN A MINIMUM OF 18 INCH

CLEARANCE AT CONTROLS FOR VARIABLE AIR VOLUME TERMINALS AND FAN POWERED

TERMINALS ABOVE CEILINGS.

E. NEW DUCTS OR PIPING SHALL NOT BE ROUTED ABOVE ELECTRICAL PANELS. REFER TO

ELECTRICAL DRAWINGS FOR LOCATION OF PANELS.

F. UNLESS NOTED OTHERWISE, BRANCH DUCTS TO DIFFUSERS SHALL BE THE SAME SIZE AS THE

NECK OF THE DIFFUSER.

G. PIPE SHALL NOT BE PVC PLASTIC AND ALL WIRING SHALL BE INSTALLED IN CONDUIT OR SHALL BE

PLENUM RATED.

H. NO TEMPERATURE SENSING CONTROL DEVICES SHALL BE LOCATED OVER HEAT PRODUCING

DEVICES.

I. INSTALL ALL EQUIPMENT TO BE DEAD LEVEL.

J. EXTREMELY TIGHT CLEARANCES OCCUR IN THE EXISTING BUILDING. CONTRACTOR SHALL

PREPARE SHEET METAL SHOP DRAWINGS FOR APPROVAL PRIOR TO FABRICATING SHEET METAL.

COORDINATE WITH ALL OTHER TRADES.

K. MECHANICAL DRAWINGS ARE DIAGRAMMATICAL WHERE DUCT SIZE SHOWN IS IN CONFLICT WITH

STRUCTURE OR OTHER BUILDING SYSTEM, CONTRACTOR MAY MODIFY DUCT SIZE AND PROVIDE

EQUIVALENT FREE AREA DUCT.

HVAC GENERAL NOTES:

470R1

12x10

AIR FLOW

Db SUMMER

OUTDOOR DESIGN

Wb SUMMER

Db WINTER

DESIGN ALTITUDE: 800 FT.

INDOOR AREA

SUMMER

Db Db

°F

TEMPERATURES

89.4°F

73.9°F

-4.0°F

WINTER

°F

70 70 40

DESIGN CONDITIONS

MAX.

RELATIVE

HUMIDITY (%)

MIN RELATIVE

HUMIDITY (%)

HVAC DESIGN DATA

NUCLEAR MEDICINE CT ROOM 5570 70 40

CONTROL ROOM

REFER TO ARCHITECTURAL PLANS FOR DESIGNATED WALLS IN THE PROJECT AREA TO BE LINED WITH LEAD

SHIELDING BY THE CONTRACTOR. FOR EXISTING MECHANICAL DEVICES THAT ARE INDICATED TO REMAIN, THE MECHANICAL CONTRACTOR SHALL REMOVE AND RE-INSTALL OR RELOCATE THESE DEVICES. THE GC

SHALL PROVIDE NEW LEAD SHIELDING FOR ALL SUCH DEVICES. FOR NEW MECHANICAL DEVICES, THE GC

SHALL PROVIDE ALL LEAD SHIELDING FOR EACH DEVICE. THE MECHANICAL CONTRACTOR SHALL COORDINATE

ALL SUCH WORK WITH THE GENERAL CONTRACTOR, AND SHALL ASSIST THE GENERAL CONTRACTOR IN THE PERFORMANCE OF THIS WORK. IN ANY CASE, ALL PLUMBING DEVICES, HVAC DEVICES, FIRE PROTECTION

DEVICES, ETC. INSTALLED IN THESE WALLS SHALL BE SHIELDED WITH LEAD.

LEAD SHIELDING NOTE

A. THIS PROJECT CONSISTS OF MULTIPLE TRADES OF WORK PERFORMED WITHIN AN EXISTING BUILDING, ALL OF WHICH ALLOWS VERY LITTLE PERMISSIBLE RANGE OF VARIATION. THE CONTRACTOR SHALL

TAKE CAREFUL CONSIDERATION WITH THE COORDINATION AND INSTALLATION OF THE MULTITUDE OF

NEW SYSTEMS WHILE ALSO ACCOMMODATING ANY EXISTING SYSTEMS TO REMAIN.

B. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL TRADES ASSOCIATED WITH THIS

PROJECT AND ISSUING COORDINATION PLANS PRIOR TO COMMENCEMENT OF EACH PHASE OF

CONSTRUCTION.

C. THE COORDINATION DRAWINGS SHALL ILLUSTRATE ALL SYSTEMS IN PLACE. NO EXCEPTIONS! THE

CONTRACTOR SHALL SHOW ALL NECESSARY OFFSETS, TRANSITIONS, ETC. AS REQUIRED IN ORDER TO

ACCOMMODATE CONDITIONS IDENTIFIED IN THE FIELD.

D. IF CONFLICTS ARE IDENTIFIED DURING THE DEVELOPMENT OF COORDINATION PLANS, THE

CONTRACTOR SHALL NOTIFY THE VA COTR, ARCHITECT, AND/OR ENGINEER OF ANY CONDITIONS WHICH

WILL NOT PERMIT THE WORK TO BE PERFORMED AS INDICATED ON THE PROJECT PLANS.

E. A COMPLETED SET OF COORDINATION PLANS ISSUED FOR REVIEW SHALL CONFIRM THAT THE

CONTRACTOR FULLY UNDERSTANDS THE PROJECT CONSTRAINTS AND ALL KNOWN CONFLICTS HAVE

BEEN ADDRESSED.

PROJECT COORDINATION NOTES:

CD COOLING COIL CONDENSATE (IN. W.G.)

(DEG. F.)

FACTORY DISCONNECT SWITCH

FACTORY CONDENSATE PUMP

MICROPROCESSOR CONTROL WITH WALL MOUNTED DISPLAY

ACCESSORIES

RETURN AIRSIDE SMOKE DETECTOR

MANUFACTURER'S STARTUP

WIRE SIZING AMPS

MAX. OVERCURRENT PROTECTIVE DEVICE

ELECTRICAL DATA - AIR CONDITIONER

VOLTS-PHASE-HERTZ

FULL LOAD AMPS

TYPE

FILTERS

AIR FLOW

OUTDOOR AIR

MOTOR SIZE

EXTERNAL STATIC PRESSURE

COOLING PERFORMANCE (CHILLED WATER COIL)

TOTAL COOLING CAPACITY

SENSIBLE COOLING CAPACITY

ENTERING AIR TEMP. DB/WB

AIR HANDLER CONFIGURATION

SUPPLY FAN PERFORMANCE

MARK

(HP)

(MBH)

(MBH)

(CFM)

SPACE SERVED

(AMPS)

3-WAY CHILLED WATER MODULATING VALVE

HIGH STATIC BLOWER MODULE

BACnet INTERFACE

REMOTE TEMPERATURE & HUMIDITY SENSORS

AC-5

YES

12.8

460-3-60

11.2

2" STANDARD

HORIZONTAL

1,250

0.3

0.5

72/60

NO

YES

YES

YES

CT ROOM

NO

YES

NO

YES

YES

(DEG. F.)

WATER FLOW/PRESSURE DROP

EWT/LWT

(GPM/FT. HD)

(DEG. F.)LEAVING AIR TEMP. DB/WB 53.9/52.2

24.2

22.2

45.0/55.0

5.2/7.2

AC UNIT (CHILLED WATER) -

AC

NOTES:

1. UNITS SHALL BE SUPPORTED FROM STRUCTURE WITH THREADED RODS AND

VIBRATION ISOLATORS.

ELECTRIC HUMIDIFIER

TOTAL CAPACITY

KW

(LB/HR) 4.3

1.5

SUPPLY AIR PLENUM WITH CEILING FASCIA NO

2-WAY CHILLED WATER MODULATING VALVE

MARK TYPE

S1

AIR DISTRIBUTION DEVICE (DIFFUSERS, REGISTERS AND GRILLES)

(INCHES)

FACE SIZE

24x24 LAY-IN

COLORSTYLE

ALUMINUMWHITE

MATERIAL

1,2

NOTES

(INCHES)

NECK SIZE

SEE TAGSUPPLY

DIFFUSER

R1 RETURN

WHITE

GRILLE

24x12 PERFORATED FACE

LAY-IN

SEE TAG 1,2ALUMINUM

R2 24x24 WHITE 1,2SEE TAG ALUMINUM

PERFORATED FACE

LAY-IN

RETURN

GRILLE

CFMS1

NECK

NOTES:

1. PROVIDE TRANSITIONS FROM NECK SIZE TO BRANCH DUCTS.

2. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

A

/1

/2

:3

:0

P

M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

3 4 5 6 7 8 9 10

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF

THIS DESIGN AND THESE CONSTRUCTION

DOCUMENTS FOR PURPOSES OTHER THAN

THE SPECIFIC PROJECT NAMED HEREIN IS

STRICTLY PROHIBITED WITHOUT THE

EXPRESSED WRITTEN CONSENT OF

PERSPECTUS ARCHITECTURE.13212 Shaker Square Suite Cleveland, Ohio 44120

P. 216.752.1800 F.216.752.3833 Consulting Engineers

2217 East 9th Street, Suite 350

Cleveland OH 44115-1257

216-875-0100/ (F) 216-875-0111 barberhoffman.com

B-AC-3

B-AC-2

Louis Stokes Cleveland

VA Medical Center

S

74490

L.D. HENDRIX, JR

R E

S

O F

I

R

GE

NOIS

P

E

N E

D

ERT

L EA

E I N

G

R

T

S

TE

A H

F OO

IO

19057

U.S. Department of Veterans Affairs

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

541-18-505

10/11/2019

VA SITE PREP FOR

INTEVO

F ile

P a th

Drawing Title

Approved: Project Director

ARCHITECT OF RECORD: STAMPCONSULTANTS:

Final Construction Document Submission 10/11/19

Project Number

Building Number

Drawing Number

Project Title

Location

Phase

Issue Date Checked Drawn

CLEVELAND, OHIO

Revisions: Date:

HVAC LEGEND, SCHEDULES, AND

GENERAL NOTES

PENETRATION OF FIRE/SMOKE BARRIERS

NOTE:

1. APPLICABLE TO PENETRATIONS OF ALL

FIRE RATED MEMBRANES, IN

ACCORDANCE WITH NFPA 101. REFER

TO SPECIFICATIONS SECTION 078400,

FIRE STOPPING SYSTEMS.

INSULATED PIPE

OR DUCT

FLOOR

FIRESTOP MATERIAL

3/4" [19mm] APPROVED

FIRESTOP INSULATION

WITH VAPOR BARRIER

PIPE SLEEVE WHERE

SPECIFIED

1/4" [6mm]Ø ANCHOR

ROD FOR NEW

CONSTRUCTION

WELD

FLOOR OR DECK PENETRATION

PARTITION OR CHASE PENETRATION

PIPE/DUCT

6" [152mm]

6" [152mm]

MASONRY

PARTITION

PARTITION SUPPORT

FIRESTOP

MATERIAL

6"

[152mm]

6" [152mm]

3/4" [19mm] APPROVED

FIRESTOP INSULATION WITH

VAPOR BARRIER

DRYWALL PARTITION

INSULATED

PIPE OR

DUCT

TYPICAL PIPE HANGERS

VOLUME DAMPER DETAIL

NOTE:

1.

2.

DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR

MULTI-BLADE DAMPERS & ROUND DAMPERS.

INSULATION

DAMPER BLADE

1/8" [6mm]

CLEARANCE

ALL AROUND

OUTSIDE END BEARING

INSIDE END BEARING

HANDLE WITH

LOCKING

QUADRANT

2" INSULATION

STAND-OFF

1/2" [15mm] ROUND

ROD PIN

DUCT

STIFFEN BLADE

AS REQUIRED

SIDE ELEVATION SECTION

DUCTWORK RADIUS ELBOWS

NOTE:

1.

2.

3.

THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.

ALL STANDARD RADIUS ELBOWS SHOWN ON FLOOR PLANS MAY BE MADE SHORT RADIUS

ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE

CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.

PROVIDE DUCT ACCESS DOORS BEFORE AND AFTER EACH ELBOW.

R SHALL

EQUAL OR

BE

GREATER

THAN W.

R SHALL

EQUAL OR

BE

GREATER

THAN

1/3W.

W

R

R

2/3W

/3

W

R SHALL

EQUAL OR

BE

GREATER

THAN

1/6W.

STANDARD RADIUS ELBOW

SHORT RADIUS ELBOW

WITH ONE VANE

SHORT RADIUS ELBOW

WITH TWO VANES

W W

1/2W

/3

W

1/6W

R

SUPPLY DUCTWORK TAKE-OFFS

NOTE:

1.

2.

THE SUPPLY REGISTER TAKE-OFF MAY BE USED FOR UP UP TO

25% OF THE MAIN DUCT CFM. THE BRANCH DUCT TAKE-OFF

MAY BE USED FOR UP TO 15% OF THE MAIN DUCT CFM

ANYTIME AND UP TO 40% WHEN THE MAIN DUCT VELOCITY IS

1000 FPM [5 M/S] OR LESS. THE AIR SPLIT DUCT TAKE-OFF

SHALL BE USED IN ALL OTHER CASES AND MAY BE USED AT

ANYTIME.

SHOW VOLUME DAMPERS ON FLOOR PLANS.

AIR SPLIT DUCT TAKE-OFF PLAN

VIEW

BRANCH DUCT TAKE-OFF PLAN

VIEW

AIR

FLOW

AIR

FLOW

A

IR

F L O

W

SUPPLY REGISTER

OR BRANCH DUCT

TURNING VANES

MAIN

SUPPLY

DUCT

SEE FLOOR PLAN FOR

SPLIT DIMENSION

SQUARE ELBOW SHOWN.

PROVIDE ROUND ELBOW

WHEN SHOWN ON FLOOR

PLANS

PROVIDE VOLUME

DAMPER WHEN SHOWN

ON FLOOR PLANS

PROVIDE VOLUME

DAMPER WHEN

SHOWN ON FLOOR

PLANS

1/4 W OR 4" MIN.

AIR

FLOW

MAIN SUPPLY

DUCT

W

A

IR

F L O

W

WITH EQUIPMENT MOUNTED IN DUCT

TYPICAL DUCTWORK TRANSITION

NOTE:

UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.

0°

M A

X

M

AX.

0°

M A

X

M A

X

E Q

U

IP

M E

N T

AIR

FLOW

AIR

FLOW

TYPICAL DUCTWORK TRANSITION

PLAN OR SIDE VIEWTYPICAL DUCTWORK TRANSITION WITH

EQUIPMENT MOUNTED IN DUCT

PLAN OR SIDE VIEW

M

AX.

M A

X

DUCTWORK SQUARE VANED ELBOWS

NOTE:

1.

2.

3.

4.

5.

ALL VANED ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.

WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE VANE TYPE REGARDLESS OF W

DIMENSION.

ALL SINGLE VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.

WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE DOUBLE VANE

TYPE.

PROVIDE DUCT ACCESS DOORS BEFORE AND AFTER EACH ELBOW.

W

W1

COIL

TEST PLUG (TYP.)

REDUCER, IF REQUIRED

WATER RETURN

SCREWHEAD VENT

UNIONS OR SOLDER

CONNECTION (TYP.)

WATER SUPPLY

AC-5

TYPICAL COIL PIPING CONNECTIONS

2-WAY VALVE

1.

NOTES:

BRANCH PIPING VALVES SHALL BE PROVIDED WITH PACKING GLANDS.

TYPICAL METHOD OF SECURING HANGER

RODS IN CONCRETE SLABS AND BEAMS.

AC UNIT TEMPERATURE CONTROLS AND SEQUENCE OF OPERATION

SCALE = NTS

A

/1

/2

:3

:0

P

M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

3 4 5 6 7 8 9 10

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF

THIS DESIGN AND THESE CONSTRUCTION

DOCUMENTS FOR PURPOSES OTHER THAN

THE SPECIFIC PROJECT NAMED HEREIN IS

STRICTLY PROHIBITED WITHOUT THE

EXPRESSED WRITTEN CONSENT OF

PERSPECTUS ARCHITECTURE.13212 Shaker Square Suite Cleveland, Ohio 44120

P. 216.752.1800 F.216.752.3833 Consulting Engineers

2217 East 9th Street, Suite 350

Cleveland OH 44115-1257

216-875-0100/ (F) 216-875-0111 barberhoffman.com

B-AC-3

B-AC-2

Louis Stokes Cleveland

VA Medical Center

S

74490

L.D. HENDRIX, JR

R E

S

O F

I

R

GE

NOIS

P

E

N E

D

ERT

L EA

E I N

G

R

T

S

TE

A H

F OO

IO

19057

U.S. Department of Veterans Affairs

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

541-18-505

10/11/2019

VA SITE PREP FOR

INTEVO

F ile

P a th

Drawing Title

Approved: Project Director

ARCHITECT OF RECORD: STAMPCONSULTANTS:

Final Construction Document Submission 10/11/19

Project Number

Building Number

Drawing Number

Project Title

Location

Phase

Issue Date Checked Drawn

CLEVELAND, OHIO

Revisions: Date:

HVAC DETAILS

RH-1NC

Hall

BC-460

BC-446A

Nuc Med

BC-474

0B

BC-446

Hot LabRad Waste

Nuc Med

BC-475

Thyroid Uptake

BC-448

Inject

BC-461

Hall

T

T

T

X-VAV-30

X-VAV-20

X-VAV-21

1CAP

NC

Hall

BC-460

BC-446A

Nuc Med

BC-474

0B

BC-446

Hot LabRad Waste

Nuc Med

BC-475

Thyroid Uptake

BC-448

Inject

BC-461

Hall

T

X-VAV-30

X-VAV-20

X-VAV-21

350S1

10"Ø

350S1

10"Ø

12"Ø

350R1

10"Ø2 x

18x8

18x8

625S1

14"Ø

625S1

14"Ø

350R1

10"Ø

250S1

10"Ø

250S1

10"Ø

T

500R2

12"Ø

T

T x

1-1/4"

6 180

CFM

CFM

CFM

CFM

1"

C.O.

X-FD

EXISTING THERMOSTAT TO BE RELOCATED.

RE-BALANCE X-VAV-30 TO 500 CFM MAX AND 500 CFM MIN.

RE-BALANCE X-VAV-21 TO 330 CFM MAX AND 330 CFM MIN.

RE-BALANCE X-VAV-20 TO 700 CFM MAX AND 400 CFM MIN.

REMOVE AND REINSTALL CEILING TILE AND GRID AND LIGHTING AS REQUIRED FOR INSTALLATION OF AC-5.

HANG UNIT FROM STRUCTURE WITH THREADED ROD AND VIBRATION ISOLATORS. INSTALL SUPPLY AND

RETURN PLENUMS ON UNIT.

RE-BALANCE DIFFUSER/GRILLE TO INDICATED AIR FLOW.

RELOCATE THERMOSTAT TO LOCATION INDICATED. CUT AND PATCH WALL FOR INSTALLATION.

1-1/4" PCWS/R DOWN TO SUB-BASEMENT.

1" CD DOWN. SPILL TO FLOOR DRAIN.

1-1/4" PCWS/R UP TO BASEMENT.

X -P

C W

R

X -P

C W

S

X-4"

X-2-1/2"

X-1-1/2"

X-1-1/4"

X-1-1/4"

X-1"

X-1" PCHWS&R

X-6"

A

/1

/2

:3

:0

P

M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

3 4 5 6 7 8 9 10

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF

THIS DESIGN AND THESE CONSTRUCTION

DOCUMENTS FOR PURPOSES OTHER THAN

THE SPECIFIC PROJECT NAMED HEREIN IS

STRICTLY PROHIBITED WITHOUT THE

EXPRESSED WRITTEN CONSENT OF

PERSPECTUS ARCHITECTURE.13212 Shaker Square Suite Cleveland, Ohio 44120

P. 216.752.1800 F.216.752.3833 Consulting Engineers

2217 East 9th Street, Suite 350

Cleveland OH 44115-1257

216-875-0100/ (F) 216-875-0111 barberhoffman.com

B-AC-3

B-AC-2

Louis Stokes Cleveland

VA Medical Center

S

74490

L.D. HENDRIX, JR

R E

S

O F

I

R

GE

NOIS

P

E

N E

D

ERT

L EA

E I N

G

R

T

S

TE

A H

F OO

IO

19057

U.S. Department of Veterans Affairs

FINAL CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

541-18-505

10/11/2019

VA SITE PREP FOR

INTEVO

F ile

P a th

Drawing Title

Approved: Project Director

ARCHITECT OF RECORD: STAMPCONSULTANTS:

Final Construction Document Submission 10/11/19

Project Number

Building Number

Drawing Number

Project Title

Location

Phase

Issue Date Checked Drawn

CLEVELAND, OHIO

Revisions: Date:

0'

SCALE: 1/4" = 1'0"

2' 4' 8' 16'

PARTIAL BASEMENT HVAC DEMOLITION

PLAN

PARTIAL BASEMENT HVAC PLANS

V

LDH LDH

0'

SCALE: 1/4" = 1'0"

2' 4' 8' 16'

PARTIAL BASEMENT HVAC PLAN

V

0'

SCALE: 1/4" = 1'0"

2' 4' 8' 16'

PARTIAL SUB-BASEMENT HVAC PLAN

V

27 29 30

BRANCH CIRCUIT HOME RUN TO PANEL - ARROWHEADS INDICATE CIRCUITS. WIRE INDICATED ARE GREEN GROUND, SEPARATE NEUTRALS (SHARED NEUTRALS ARE NOT PERMITTED FOR BRANCH CIRCUITS) AND THREE HOT LEGS (A

DIFFERENT PHASE FOR EACH CIRCUIT) MAXIMUM THREE CIRCUITS PER CONDUIT. 3/4" MINIMUM CONDUIT WITH WIRE

SIZE INDICATED ON DRAWING ("XX" INDICATES AWG SIZE). ALL POWER WIRING SHALL BE STRANDED COPPER

CONDUCTORS WITH THHN/THWN INSULATION. PROVIDE SEPARATE EQUIPMENT GROUNDING CONDUCTOR (SAME SIZE AS PHASE AND NEUTRAL, UNLESS OTHERWISE NOTED) FOR EACH CONDUIT. CONDUIT WIRE FILLS SHALL BE IN

ACCORDANCE WITH LATEST NATIONAL ELECTRIC CODE.

WIRE SIZE

(MIN. #12AWG)

NO. OF CCTS

IN CONDUIT

PHASE

CONDUCTORS

NEUTRALS

GROUND CONDUIT UP

CONDUIT DOWN

MOTOR - NUMBER DENOTES HORSEPOWER3

TEMPERATURE CONTROL PANEL FURNISHED AND INSTALLED BY OTHERS. EC SHALL PROVIDE 120V CONNECTION (HARDWIRED OR

RECEPTACLE, AS REQUIRED).

TCP

EC SHALL PROVIDE 20A-120V CIRCUIT IN ABOVE FINISHED CEILING MOUNTED JUNCTION BOX FOR VAV TERMINALS. CONNECT ALL

VAV'S IN AREA TO CIRCUIT INDICATED. MC SHALL PROVIDE CONTROL TRANSFORMER AND CONTROL WIRING FOR 24VAC VAV

TERMINALS. VERIFY LOCATION OF ALL ADJACENT VAV'S WITH MECHANICAL DRAWINGS.

VAV

JUNCTION BOX, CEILING OR WALL MOUNTED, 4" SQ. WITH GROUND LUG, UNLESS OTHERWISE NOTED. COORDINATE MOUNTING

LOCATION WITH EQUIPMENT.

SC - SINK STATION CONTROLS. CONNECT PER MANUFACTURES WIRING DIAGRAM.

JUNCTION BOX, ABOVE CEILING FOR CONNECTION TO 120V AUTOMATIC DOOR. ELECTRICAL CONTRACTOR SHALL CONNECT

AUTOMATIC DOOR INCLUDING PUSH PAD OPERATORS PER MANUFACTURER'S INSTRUCTIONS TO 120V EMERGENCY LIFE SAFETY

CIRCUIT. GENERAL CONTRACTOR SHALL FURNISH AND INSTALL AUTOMATIC DOOR.

JUNCTION BOX MOUNTED AT 48" AFF FOR CONNECTION TO AUTOMATIC DOOR PUSH PAD DEVICE. PROVIDE 3/4"C TO DOOR

CONTROLLER WITH WIRING PER MANUFACTURER'S REQUIREMENTS.

AD

20A-125V, HOSPITAL GRADE, GROUND FAULT INTERRUPTER RECEPTACLE, MOUNT AT 18" AFF UNLESS OTHERWISE NOTED.

20A-125V, HOSPITAL GRADE, GROUNDED DUPLEX RECEPTACLE, MOUNT AT 18" AFF UNLESS OTHERWISE NOTED.

DOUBLE 20A-125V, HOSPITAL GRADE, GROUNDED DUPLEX RECEPTACLE, MOUNT AT 18" AFF UNLESS OTHERWISE NOTED.

SAME DEVICE TYPES AS INDICATED ABOVE EXCEPT CONNECTED TO EMERGENCY CRITICAL CIRCUIT.

TR

BRANCH CIRCUIT WIRING

LED LIGHTING FIXTURE, CONNECT TO EMERGENCY CRITICAL CIRCUIT - TYPE AS SPECIFIED IN SCHEDULE.

LED LIGHTING FIXTURE, CONNECTED TO NORMAL CIRCUIT - TYPE AS SPECIFIED IN SCHEDULE.

LED LIGHTING FIXTURE CONNECTED TO NORMAL CIRCUIT AS INDICATED - TYPE AS SPECIFIED IN SCHEDULE. "A" INDICATES TYPE, "3" INDICATES CIRCUIT NUMBER ASSIGNMENT, "a" INDICATES LOCAL SWITCHING CONTROL. CONNECT FIXTURES SO THAT FIXTURES ARE

CONTROLLED BY

A

A

480/277V-3Ø-4W PANELBOARD UNLESS OTHERWISE NOTED. MOUNT AT 78" AFF TO TOP OF PANEL.

208/120V-3Ø-4W PANELBOARD UNLESS OTHERWISE NOTED. MOUNT AT 78" AFF TO TOP OF PANEL.

GENERAL PURPOSE, 3 PHASE DRY-TYPE TRANSFORMER - TYPE AS NOTED ON PLANS.

FUSED DISCONNECT SWITCH OR ENCLOSED CIRCUIT BREAKER - SIZE AND TYPE AS NOTED. PROVIDE CLASS RK1 FUSES UNLESS

OTHERWISE NOTED. NEMA 1 ENCLOSURE UNLESS OTHERWISE NOTED.

LIGHTING FIXTURES AND CONTROLS

POWER DISTRIBUTION EQUIPMENT (FLOOR PLAN VIEW)

WIRING TERMINATIONS

WIRING DEVICES GENERAL ELECTRICAL INSTALLATION NOTES:

1. ALL MOUNTING HEIGHTS ARE TO CENTER OF DEVICE UNLESS OTHERWISE NOTED.

2. ALL NEW WALL MOUNTED ELECTRICAL DEVICES ARE TO BE INSTALLED FLUSH IN WALL UNLESS OTHERWISE NOTED. ALL ELECTRICAL CONDUIT SHALL BE CONCEALED BEHIND FINISHED WALLS AND ABOVE FINISHED CEILING UNLESS OTHERWISE NOTED. THE COST TO CUT AND PATCH WALLS SHALL BE THE

RESPONSIBILITY OF THE TRADE REQUIRING THE CUTTING.

3. CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS REQUIRED FOR ELECTRICAL WORK. CONTRACTOR SHALL REPLACE ANY

DAMAGED CEILING TILES.

4. PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW OR RELOCATED WALL OR CEILING MOUNTED DEVICES WITH ARCHITECTURAL ELEVATIONS

AND REFLECTED CEILING PLANS.

5. COORDINATE ALL SHUT-DOWNS OF EXISTING ELECTRICAL SYSTEMS WITH OWNER A MINIMUM OF FOURTEEN (14) WORKING DAYS IN ADVANCE. ALL

SHUT-DOWNS SHALL OCCUR DURING WEEKENDS OR BETWEEN 8:00PM AND 7:00AM ON WEEKDAYS ("OFF-HOURS"). INCLUDE ALL PREMIUM TIME CHARGES

IN BID.

6. ALL NOISE GENERATING OPERATIONS, INCLUDING CUTTING OF CEILINGS, WALLS AND FLOORS, CORING, DRILLING, ETC. SHALL BE SCHEDULED IN

ACCORDANCE WITH PROJECT SPECIFICATIONS (SECTION 01 00 00). INCLUDE ALL PREMIUM TIME CHARGES IN BID.

7. CONTRACTOR SHALL CONNECT ALL MECHANICAL EQUIPMENT COMPLETE PER MANUFACTURER'S WIRING DIAGRAMS AND INSTRUCTIONS. COORDINATE

WITH MECHANICAL CONTRACTOR AND VERIFY LOCATION, VOLTAGE, AMPS, NO. OF WIRES, AND PROTECTION REQUIREMENTS PRIOR TO ROUGH-IN.

CONTACT ENGINEER WITH ANY DISCREPANCIES FROM DESIGN DRAWINGS.

8. PROVIDE LIQUID-TIGHT FLEXIBLE METAL CONDUIT FOR FINAL CONNECTION TO MECHANICAL EQUIPMENT OR OTHER EQUIPMENT WHICH MAY PROPAGATE

VIBRATION.

9. ALL FLUORESCENT LAMPS THAT WILL NOT BE REUSED SHALL BE DISPOSED OF IN ACCORDANCE WITH EPA STANDARDS, AND WRITTEN EVIDENCE OF

PROPER DISPOSAL SHALL BE FURNISHED TO THE OWNER.

10. ALL WORK SHALL BE PERFORMED IN STRICT CONFORMANCE WITH THE PHASING REQUIREMENTS OF THE PROJECT. ALL COSTS ASSOCIATED WITH THESE

REQUIREMENTS SHALL BE INCLUDED IN THE BID SUBMITTAL.

11. CONTRACTOR IS RESPONSIBLE FOR PROVIDING TEMPORARY LIGHTING TO ADEQUATELY LIGHT ALL CONSTRUCTION AREAS, TEMPORARILY PARTITIONED

AREAS, AND EXIT CORRIDORS MAINTAINED DURING CONSTRUCTION.

12. DEFINITION: "PROVIDE" - FURNISH, INSTALL AND CONNECT COMPLETE.

13. PROJECT AND PHASING SCOPE LINES INDICATE WHERE GENERAL CONSTRUCTION BOUNDARIES OCCUR. ELECTRICAL WORK AND UTILITY TIE-INS MAY

OCCUR OUTSIDE OF SCOPE LINES.

A

GROUNDING BUSBAR

GB

LED LIGHTING FIXTURE CONNECTED TO EMERGENCY CRITICAL CIRCUIT - TYPE AS SPECIFIED IN SCHEDULE, "A" INDICATES TYPE, "3" INDICATES CIRCUIT NUMBER ASSIGNMENT. CONNECT FIXTURES SO THAT FIXTURES ARE CONTROLLED BY a

3,a

A

DUAL TECHNOLOGY OCCUPANCY/VACANCY SENSOR - CONNECTS TO ROOM CONTROLLER VIA CAT6A CABLING. PROVIDE COMPLETE

SYSTEM INDCLUDING SENSOR, ROOM CONTROLLERS, AND LOW-VOLTAGE OVER-RIDE SWITCH. REFER TO OCCUPANCY SENSOR PROGRAM SCHEDULE AND OCCUPANCY SENSOR DIAGRAM FOR ADDITIONAL INFORMATION. PROVIDE FORM C RELAY IN RELAY UNIT IN ALL

OCCUPANCY SENSOR FOR HVAC SWITCHING.

LIGHTING ROOM CONTROLLER - INTEGRATES LOW-VOLTAGE DIMMING SWITCH, SWITCH, AND OCCUPANCY SENSOR. PROVIDES DIMMING

AND CONTROL OUTPUT TO LIGHTING FIXTURES. UTILIZES CAT6A CABLING TO CONNECT TO SWITCHING AND OCCUPANCY SENSORS AND

UTILIZES STANDARD LOW-VOLTAGE CLING TO CONNECT TO FIXTURES DIMMING DRIVER. REFER TO OCCUPANCY SENSOR DIAGRAM FOR

ADDITON INFORMATION . ROOM CONTROLLER, OCCUPANCY SENSOR, AND OVER09RIDE SWITCH SHALL BE A COMPLETE SYSTEM FROM A

SINGLE MANUFACTURER.

OS

LIGHTING CONTROLS SYSTEM GENERAL NOTES:

1. ALL COMPONENTS FOR OCCUPANCY AND DAYLIGHT HARVESTING SYSTEM SHALL BE FROM A SINGLE MANUFACTURER AND UL LABELED.

2. SENSORS (OCCUPANCY/VACANCY, DAYLIGHT HARVESTING, ETC.) MAY BE STAND ALONE, COMBINATION, OR INTEGRATED WITH LIGHTING

FIXTURES.

3. PROVIDE ALL ADDITIONAL COMPONENTS NECESSARY FOR COMPLETE SYSTEM PER MANUFACTURER'S REQUIREMENTS.

4. SUBMIT WIRING DIAGRAMS SHOWING COMPLETE LIGHTING CONTROLS CONNECTIONS TO ENGINEER FOR REVIEW WITH SHOP DRAWINGS.

5. PROVIDE POWER SUPPLY FOR LOW-VOLTAGE SWITCHES AS REQUIRED.

24V SINGLE POLE, LARGE BUTTON SWITCH WITH INTEGRAL DIMMING FUNCTION - MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED.

PROVIDE SINGLE GANG BACK BOX AND 1"C FROM BACK BOX TO ABOVE FINISHED CEILING TO ROUTE LOW-VOLTAGE CABLING. CONNECT

COMPLETE TO ROOM CONTROLLER VIA CAT6A CABLING. SWITCH SHALL BE CAPABLE OF 3-WAY AND 4-WAY OPERATION BY INSTALLATION OF

ADDITIONAL SWITCHES VIA CONNECTION TO ROOM CONTROLLER OR DAISY-CHAINED.

DLV DS

EMERGENCY POWER OFF PUSHBUTTON "EPO" - MOUNTED AT 48" AFF. REFER TO ELECTRICAL PLANS FOR TYPE.

DOOR SWITCH - NORMALLY OPEN/NORMALLY CLOSED CONTACTS. MOUNT IN DOOR FRAME.

DUCT DETECTOR - ADDRESSABLE INTELLIGENT PHOTOELECTRIC DETECTOR (MATCH EXISTING TYPE), SAMPLING TUBES AND PROGRAMMABLE RELAY BASE. PROVIDE DUCT DETECTOR TEST/RESET SWITCH (MATCH EXISTING TYPE) WITH REMOTE INDICATOR

LAMP FOR EACH DUCT DETECTOR - WALL MOUNTED AT 7'-6" AFF.

ADDRESSABLE FIRE ALARM CONTROL PANEL (MANUFACTURER NOTIFIER).

STROBE ONLY DEVICE (ADA TYPE) (MATCH EXISTING TYPE) - RED HOUSING WITH WHITE "FIRE" LETTERING. MOUNTED AT 80" AFF.

FACP

F

FIRE ALARM REMOTE ANNUNCIATOR - FLUSH MOUNTED AT 5'-0" AFF TO TOP OF DEVICE.FARA

FIRE ALARM POWER SUPPLY EXTENDER - CONNECT TO 120V LIFE SAFETY CIRCUIT. SURFACE MOUNTED AT 5'-0" AFF TO TOP OF

DEVICE.

FPS

FIRE ALARM SYSTEM NOTES:

F1. PROVIDE A 2-GANG MINIMUM SIZE BACKBOX FOR ALL OF THE ABOVE FIRE ALARM DEVICES. ALL FIRE ALARM SYSTEM

CONDUCTORS SHALL BE INSTALLED IN 3/4" MINIMUM SIZE COMPLETE CONDUIT SYSTEM WITH COLOR CODED WIRING AS

INDICATED ON SHOP DRAWINGS PREPARED BY NOTIFIER - MAINTAIN HOSPITAL COLOR CODING. ALL NETWORK AND IDNET CABLES SHALL BE "COMMUNICATION GRADE" TYPE CABLE. FURNISH, INSTALL AND CONNECT ALL FIRE ALARM DEVICES IN

ACCORDANCE WITH WIRING DIAGRAMS AS PREPARED BY NOTIFER.

FIRE ALARM SYSTEM

TYPE

QUANTITY WATTS TYPE COLOR TEMP.

FIXTURE INFORMATION

QUANTITY TYPE VOLTAGE

DRIVER INFORMATION

GENERAL LIGHTING INSTALLATION NOTES:

L1. REFER TO ELECTRICAL SPECIFICATIONS FOR FIXTURE COLOR TEMPERATURE AND DRIVER TYPE.

L2. ELECTRICAL CONTRACTOR SHALL COORDINATE LIGHTING FIXTURE TYPE (GRID OR FLANGE) WITH ACTUAL CEILING TYPE PRIOR TO ORDERING FIXTURES. CONTACT ENGINEER IF QUESTIONS SHOULD ARISE CONCERNING CEILING

TYPES.

L3. ELECTRICAL CONTRACTOR SHALL VERIFY ALL DRIVER QUANTITIES WITH SWITCHING SHOWN ON PLANS PRIOR TO ORDERING FIXTURES. ADJUST BALLAST QUANTITIES AS REQUIRED TO MATCH SWITCHING.

L4. VERIFY LIGHTING CIRCUIT VOLTAGE (277V-1Ø OR 120V-1Ø) PRIOR TO ORDERING LIGHTING FIXTURES OR STARTING ROUGH-IN OF BRANCH CIRCUITS. IMMEDIATELY CONTACT ENGINEER WITH ANY DISCREPANCIES. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ORDERING THE PROPER VOLTAGE FOR LIGHTING FIXTURES, REGARDLESS OF VOLTAGE SHOWN ON LIGHTING FIXTURE SCHEDULE.

L5. ELECTRICAL CONTRACTOR SHALL VERIFY ALL FIXTURES TO BE CONTROLLED BY DIMMER SWITCHES AS SHOWN ON PLANS PRIOR TO ORDERING FIXTURES.

1 15.5W 120/ 277V

LED

0-10V

DIMMING

(100-1%) 14000°K

LED WARNING LIGHT - 120/277V DUAL VOLTAGE INPUT, LED TYPE, AC ONLY, UNIVERSAL MOUNTING, SINGLE

FACE, DIECAST ALUMINUM HOUSING WITH WHITE FINISH, RED STENCIL LETTERS ON WHITE FACE. PROVIDE

"CT EQUIPMENT IN USE" SIGNAGE FOR CT SCAN PROCEDURE ROOM

6" DIA RECESSED DOWNLIGHT, SEMI SPECULAR CLEAR REFLECTOR AND WHITE POLYMER TRIM

RING, 1500 LUMEN OUTPUT, MINIMUM CRI OF 90, MEDIUM DISTRIBUTION, LED BOARD AND DRIVER

ACCESSIBLE FROM BELOW, CONVEX TRANSITIONAL LENS, FUSED.

A

DESCRIPTION

1 LED N/A 1 N/A

120/ 277V

4WW

RC

24V SINGLE POLE, LARGE BUTTON SWITCH - MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED. PROVIDE SINGLE GANG BACK BOX AND 1"C

FROM BACK BOX TO ABOVE FINISHED CEILING TO ROUTE LOW-VOLTAGE CABLING. CONNECT COMPLETE TO ROOM CONTROLLER VIA CAT6A

CABLING. SWITCH SHALL BE CAPABLE OF 3-WAY AND 4-WAY OPERATION BY INSTALLATION OF ADDITIONAL SWITCHES VIA CONNECTION TO

ROOM CONTROLLER OR DAISY-CHAINED.

LV

3,a a

SD

HORN ONLY DEVICE (ADA TYPE) (MATCH EXISTING TYPE) - RED HOUSING WITH WHITE "FIRE" LETTERING. MOUNTED AT 80" AFF.F

FIRE ALARM TERMINAL CABINET (MANUFACTURER NOTIFIER).FATP

ELECTRICAL LEGEND AND GENERAL

NOTES

A

/1

/2

:3

:0

P

M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

3 4 5 6 7 8 9 10

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF

THIS DESIGN AND THESE CONSTRUCTION

DOCUMENTS FOR PURPOSES OTHER THAN

THE SPECIFIC PROJECT NAMED HEREIN IS

STRICTLY PROHIBITED WITHOUT THE

EXPRESSED WRITTEN CONSENT OF

PERSPECTUS…

This is the start of the file's text. The full file is on GovTribe.