36C25018B0808-034.pdf

PDF 6 MB Posted

Attached to
Loading Dock and Warehouse Improvements 539-19-202 Federal contract opportunity
Solicitation number
36C25018B0808
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

36C25018B0808 Attachment 2 539-19-202 Final Drawings 01-24-2018 - Original.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Loading Dock and Warehouse Improvements 539-19-202, newest first.
File Type Posted
36C25018B0808-0003001.docx DOCX document
36C25018B0808-0004001.docx DOCX document
36C25018B0808-0004000.docx DOCX document
36C25018B0808-0002001.docx DOCX document
36C25018B0808-0001002.docx DOCX document
36C25018B0808-033.pdf PDF
36C25018B0808-036.docx DOCX document
36C25018B0808-032.docx DOCX document
36C25018B0808-035.docx DOCX document
36C25018B0808-000.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

LOADING DOCK AND

WAREHOUSECOVER SHEET

GI001

539-19-202

Cincinnati VAMC

PH JK

BLDG 1

DRAWING SHEET INDEX

Drawing Sequence Sheet

Number Sheet Name Sheet Discipline

1 GI001 COVER SHEET GENERAL

2 AD101 DEMO PLAN ARCHITECTURAL

3 A101 NEW WORK PLAN ARCHITECTURAL

4 A102 CEILING PLANS ARCHITECTURAL

5 A104 INTERIOR ELEVATIONS ARCHITECTURAL

6 AS600 DOOR SCHEDULE AND DETAILS ARCHITECTURAL

7 AF101 Finish Plan ARCHITECTURAL

8 FP 101 FIRE SUPPRESSION PLAN FIRE PROTECTION

9 PL101 PLUMBING PLANS PLUMBING

10 MD 101 LOAD DOCK - DEMOLITION PLAN MECHANICAL

11 MH101 LOADING DOCK - NEW WORK MECHANICAL

12 MH501 DETAILS AND SCHEDULES MECHANICAL

13 MP101 LOADING DOCK - NEW PIPING MECHANICAL

14 EDL100 PARTIAL BASEMENT LIGHTING DEMOLITION

PLAN

ELECTRICAL

15 EDP100 PARTIAL BASEMENT POWER DEMOLITION

PLAN

ELECTRICAL

16 EL100 PARTIAL BASEMENT LIGHTING PLAN ELECTRICAL

17 EP100 PARTIAL BASEMENT POWER PLAN ELECTRICAL

18 FA100 PARTIAL BASEMENT FIRE ALARM PLAN ELECTRICAL

LOADING DOCK AND

WAREHOUSE

CINCINNATI VA MEDICAL CENTER

3200 VINE STREET CINCINNATI OHIO 45220

PROJECT NO. 539-19-202

AREA MAP

PROJECT LOCATION

*** R.I.D. = RESIDENT INTERIOR DESIGNER. ***

** U.N.O. = UNLESS NOTED OTHERWISE.**

* C.O.R. = CONTRACTING OFFICER'S REPRESENTATIVE. THIS IS USED IN LIEU OF THE TERM OWNER.

1. ALL WORK SHALL COMPLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL CODES, RULES, ORDINANCES AND REGULATIONS INCLUDING THE AMERICAN DISABILITIES ACT (ADA), ARCHITECTURAL BARRIERS ACT(ABA), THE VA BARRIER FREE DESIGN GUIDELINES AND THE

AMERICAN NATIONALSTANDARDS INSTITUTE (ANSI) GUIDELINES.

2. THE C.O.R. SHALL WORK WITH THE CONTRACTOR TO PROVIDE ACCESS TO TEMPORARY SERVICES

REQUIRED TO PROVIDE THE WORK INDICATED. SEE SPECIFICATION SECTION 01 00 00 FOR

ADDITIONAL REQUIREMENTS ON TEMPORARY ACCESS TO VA UTILITIES.

3. THE GENERAL CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE PROVISIONS OF THE

SPECIFICATIONS, INCLUDING ALL GENERAL CONDITIONS, SUPPLEMENTARY GENERAL CONDITIONS, AND MATERIAL AND CONSTRUCTION PROVISIONS, WHICH APPLY TO MATERIALS OR

CONSTRUCTION METHODS REQUIRED BY THIS PROJECT.

4. PRIOR TO BIDDING, THE GENERAL CONTRACTOR SHALL VISIT THE SITE, EXAMINE, AND ACCEPT

ALL EXISTING CONDITIONS. DATES FOR SITE VISITS WILL BE POSTED IN THE CONTRACT

DOCUMENTS AS POSTED ON THE FEDERAL BUSINESS OPPURTUNITIES WEBPAGE FOR THIS

PROJECT. UNSCHEDULED VISITS WILL NOT BE ALLOWED.

5. DO NOT PAINT ANY CAULKING OR SEALANTS WHICH ARE SUBJECT TO MOVEMENT - CONTROL

JOINTS SHALL BE CAULKED AFTER PAINT AND SPECIAL COATING APPLICATIONS. PROVIDE

CAULKING OR SEALANTS IN COLORS WHICH MATCH ADJACENT FINISHED SURFACE COLORS.

6. VERIFY ALL CONDITIONS AND DIMENSIONS IN THE FIELD BEFORE FABRICATING ANY MATERIALS.

7. IT IS THE INTENT OF THE DOCUMENTS TO INDICATE COMPLETE AND OPERATIONAL SYSTEMS (I.E.

STRUCTURAL, HVAC, PLUMBING, ELECTRICAL, ETC.) THE CONTRACTOR SHALL PROVIDE THE

SYSTEMS AS OPERATIONAL SYSTEMS WHICH COMPLY WITH APPLICABLE CODES AND

REGULATIONS. THIS NOTE SHALL BE LIMITED TO THE SYSTEMS AS INDICATED BY THE

DOCUMENTS AND SHALL NOT INCLUDE CHANGES TO THE SYSTEMS WHICH ALTER INDICATED

CAPACITIES, OPERATIONAL CHARACTERISTICS, ETC.

8. THE GENERAL CONTRACTOR SHALL VERIFY THE SIZES OF ALL EQUIPMENT OR FIXTURES TO BE

INSTALLED IN THE BUILDING THROUGH THE SUBMITTAL PROCESS, AND SHALL MAKE SPECIAL

PROVISIONS FOR INSTALLATION OF ANY EQUIPMENT WHICH IS TOO LARGE TO FIT THROUGH A

FINISHED OPENING.

9. ALL CONTRACTORS SHALL BE RESPONSIBLE TO PATCH AND REPAIR ALL SURFACES WHERE

EXISTING CONSTRUCTION IS REMOVED OR DISTURBED BY WORK UNDER THEIR CONTRACT.

10. ALL SUSPENDED ITEMS SUCH AS CEILINGS, DUCTS, PIPES, CONDUITS, ETC., SHALL BE SUSPENDED (ATTACHED) DIRECTLY TO STRUCTURE AND SHALL NOT BE ATTACHED OR ANCHORED TO EXISTING

PLASTER, ACOUSTIC TILE, ETC.

11. NEW PENETRATIONS SUCH AS DUCTS, CONDUITS, PIPING, ELECTRICAL OUTLETS, LIGHT SWITCHES, RECESSED DEVICES OR ITEMS, HOLES, VOIDS, CRACKS, ETC. IN MODIFIED AND NEW CORRIDOR WALLS, SMOKE PARTITIONS, AND FLOOR SLABS SHALL BE SEALED TO PREVENT PASSAGE OF ANY

SMOKE, FLAME, GASES, ETC. AS INDICATED IN THE CONTRACT DOCUMENTS.

12. WHERE NEW CONSTRUCTION REQUIRES CORE DRILLING THROUGH EXISTING STRUCTURAL

CONCRETE FLOOR SLABS, AND WALLS THE CONTRACTOR SHALL COORDINATE HIS DRILLING WORK TO AVOID DRILLING INTO A STRUCTURAL ELEMENT, INCLUDING JOISTS, BEAMS, COLUMNS, ETC.

ALSO SEE ELECTRICAL. DRAWINGS AND SPECIFICATIONS.

13. WHERE NEW CONSTRUCTION IS INDICATED TO BE INSTALLED IN EXISTING CONSTRUCTION, THE

CONTRACTOR SHALL VERIFY ALL DIMENSIONS FOR PROPER FIT AND FOR ACCESS INTO THE

BUILDING PRIOR TO SHOP DRAWING SUBMITTAL, ORDERING AND DELIVERING TO THE SITE.

14. FOR INFECTION CONTROL REASONS, WORK CONDUCTED IN THE CORRIDOR THAT DOES NOT

GENERATE DUST MAY ONLY REMOVE UP TO 16 SQUARE FEET OF CEILING TILE AT ONCE. AS LONG

AS THIS STANDARD IS FOLLOWED NEGATIVE AIR AND BARRIERS ARE NOT REQUIRED BY THE

INFECTION CONTROL NURSES. IF DUST IS GENERATED AND GREATER THAN 16 SF OF CEILING TILES

ARE DISTURBED AT ONCE THEN THE WORK AREA SHALL BE SEALED OFF WITH 6 MIL FIRE

RETARDANT POLYETHYLENE AND NEGATIVE AIR PROVIDED. MAINTAIN 5' MINIMUM ACCESS IN

CORRIDORS AT ALL TIMES. CLEAN THOROUGHLY PRIOR TO COMPLETION OF A GIVEN WORK AREA

BY HEPA VACUUM AND WET MOP. REFER TO SPECIFICATION 01 35 26 FOR ADDITIONAL

INFORMATION.

NO PARKING ON VA CAMPUS.

Revisions Date 01/26/18

DN DN

Corridor C-B-1a

Serv. Lobby C-B-1b

Forms Rm.

A013D

Ref. Equip.

Rm.

A013A

Mech. Rm.

A013B

Corridor A14

Loading Dock A017

Office A014B

Canteen Storage

A014C

Stor.

A016

PM&R Stor.

A018

Elec.

A109

Room A208

Mech Stor.

A013

Room A213

Room A233

Room A253

Stor.

A022C

Room A419

Room A475

Room A503

Room A504

Room A507

Room A567

Room A583

Stor.

A021

Hazard Chem. Stor.

A007B Stor.

A007A

Mail Rm.

B022A

Mail Rm.

B022a

Warehouse Receiving &

Check-in

A014A Distribution

A014

RELOCATE REFRIGERATOR

RELOCATE

REFRIGERATOR

RELOCATE COPIER

BACKUP REFRIGERATOR

TO REMAIN

CHEMICAL SPILL KIT

TO REMAIN

EXIST.

EYE WASH STATION

DEMO TACK BOARD TYP.

DEMO KEY LOCKEREXIST.

FIRE EXTINGUISHER

DEMO TOWEL DISPENSER

DEMO SOAP DISPENSER

FIRE EXTINGUISHER

DEMO TACK BOARD

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

LOADING DOCK AND

WAREHOUSEDEMO PLAN

AD101

539-19-202

Cincinnati VAMC

PH JK

1/8" = 1'-0"

BASEMENT DEMO PLAN

KEY PLAN

DEMO KEYNOTES

1. REMOVE DOOR AND FRAME

2. REMOVE PORTION OF WALL FOR NEW OPENING

3. REMOVE EXISTING CMU WALL

4. REMOVE EXISTING DRINKING FOUNTAIN

5. REMOVE EXISTING CASEWORK

6. REMOVE ONE OF TWO DOORS FOR REPLACING WITH DUTCH

DOOR.

7. TEMPORARY WALL T-1

8. TEMPORARY DOOR

SELF LATCHING + SELF CLOSING

W/ CORBIN ROSSWIN LOCK KEYED BY VA LOCKSMITH

GENERAL NOTES

1. ALL DEMOLISHED WALL MOUTED ITEMS TO BE TURNED OVER TO

OWNER. IF REFUSED - TO BE DISPOSED OF BY CONTRCTOR.

2. INSTALL TEMPORARY WALLS AS SHOWN - 1 HOUR RATED 3 5/8"

METAL STUDS WITH GYPSUM BOARD ON BOTH SIDES TO

STRUCTURE ABOVE.

3. TURN OVER ALL VA SIGNS TO VA INTERIOR DESIGNER.

4. PROVIDE NOTIFICATION TO STATE EPA PRIOR TO ANY DEMILITION

WORK.

5. TURN OVER ALL ELECTRONIC DEVICES TO VA. FOR EXAMPLE

WIRELESS ACCESS POINTS, PA SPEAKERS, CHECKPOINT

SENSORS, CHECKPOINT REPEATERS, CHECKPOINT MODEMS,

ETC.

Revisions Date 01/26/18

Loading Dock A017

Office A014B

Canteen Storage

A014C

Corridor A14

Room A580

Stor.

A022C

Corridor C-B-1a

Stor.

A016

PM&R Stor.

A018

Elec.

A109

Serv. Lobby C-B-1b

Forms Rm.

A013D

Mech Stor.

A013

Mail Rm.

B022A

Mail Rm.

B022a

Stor.

A007A

Hazard Chem. Stor.

A007B

Mech. Rm.

A013B

Ref. Equip.

Rm.

A013A

Warehouse Receiving &

Check-in

A014A

Distribution A014

A104

A104

014AA 014A

014B

014C

86 9

1.4

1.5

1.6

71.1 1.2

1.3311

12 12

CIRCULATION LANES

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

LOADING DOCK AND

WAREHOUSENEW WORK PLAN

A101

539-19-202

Cincinnati VAMC

PH JK

Scale: 3/32" = 1'-0"1

BASEMENT PLAN - NEW WORK

GENERAL NOTESKEYNOTES

1. WORKSTATION BY VA (DECIMAL IS ID)

2. EXISTING COPIER

3. EXISTING REFRIGERATOR

4. CORNER GUARD BOTH SIDES OF DOOR OPENING

5. PATCH AND PAINT WALL FROM INSTALLATION OF

DRINNKING FOUNTAIN.

6. WIRE SHELVING BY VA

7. WASTE RECEPTACLE BY VA

8. FLATBED BY VA

9. TASK STOOL BY VA

10. EXIST. BACK UP REFRIGERATOR

11. EXIST. DESCREPANCY AREA

12. TABLE AND PRINTER BY VA

13. VERTICAL FILE CABINET BY VA

14. SUPPORT EQUIPMENT AREA

KEY PLAN

1. MAINTAIN ACCESS TO REMAINING LOADING LOADING

DOCK DOORS AT ALL TIMES.

Scale: 3/32" = 1'-0"3

BASEMENT PLAN - FURNITURE

STRUCTURAL BEAMS 7' - 10"

ABOVE ASSOCIATED LEVEL

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

LOADING DOCK AND

WAREHOUSECEILING PLANS

A102

539-19-202

Cincinnati VAMC

PH JK

KEYNOTES

1. EXISTING LIGHTING TO REMAIN.

2. UPGRADE EXISTING LIGHTING.

3. NEW LIGHTING. SEE ELECTRICAL.

4. EXPOSED STRUCTURE TO REMAIN AS IS.

5. PAINT EXPOSED STRUCTURE CEILING AND BEAMS.

6. PATCH CEILING AT WALL DEMO.

1/8" = 1'-0"

CEILING PLAN

1/8" = 1'-0"

CEILING PLAN EXISTING

GENERAL NOTES

KEY PLAN

1. REMOVE ABANDONED CLIPS, WIRES, ETC.

2. PAINT CEIINGS, CONDUIT AND STRUCTURE WHERE

SHOWN TO BE PAINTED

OFOI FURNITURE AND EQUIPMENT

COORDINATE DATA AND POWER OUTLET

LOCATIONS.

NEW BASE AND WALL PAINT CORNER TO CORNER

NEW DOOR IN

EXISTING MASONRY

OPENING

CUT IN NEW DOOR OPENING

IN EXISTING MASONRY WALL

NEW BASE & PAINT

FROM CORNER

TO CORNER

NEW DOOR IN EXISTING

MASONRY OPENING

A104

A104

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

LOADING DOCK AND

WAREHOUSEINTERIOR ELEVATIONS

A104

539-19-202

Cincinnati VAMC

PH JK

1/4" = 1'-0"

ELEVATION 1

1/4" = 1'-0"

ELEVATION 2

1/4" = 1'-0"

ELEVATION 3

1/4" = 1'-0"

ELEVATION 4

1/4" = 1'-0"

ELEVATION 5

1/4" = 1'-0"

ELEVATION 6

1/4" = 1'-0"

ELEVATION 7

1/4" = 1'-0"

ELEVATION 8

GENERAL NOTES

3/32" = 1'-0"A104

9 BASEMENT PLAN - NEW WORK

S E

E S

C H

E D

U L E

6' - 0" OPG. WIDTH

DOOR TYPE B

HOLLOW METAL FLUSH DOOR

2"

S E

E S

C H

E D

U L E

6' - 4" FRAME WIDTH

FRAME TYPE 1

HOLLOW METAL FRAME FLUSH WITH WALL

SURFACE. SEE DETAILS THIS SHEET.

S E

E S

C H

E D

U L E

6' - 0" OPG. WIDTH

DOOR TYPE A

HOLLOW METAL FLUSH DOOR

INACTIVE LEAF

DUTCH DOOR

(NEW DOOR IN

EXIST. FRAME)

INACTIVE LEAF

DUTCH DOOR

(NEW DOOR IN

EXIST. FRAME)

SHELF

INACTIVE LEAF

DUTCH DOOR

(NEW DOOR IN

EXIST. FRAME)

INACTIVE LEAF

DUTCH DOOR

(NEW DOOR IN

EXIST. FRAME)

ALIGN

HOLLOW METAL DOOR.

SEE SCHEDULE.

1 15/16" 1 1/8" 1 15/16"

/8

/8

FULLY-GROUTED HOLLOW

METAL FRAME FLUSH WITH

EXTERIOR FACE OF WALL.

EXISTING CMU. VERIFY

OPENING HEIGHT IN FIELD AND

REINFORCE AS NECESSARY

FOR NEW DOOR.

NEW DOUBLE-ANGLE STEEL

LINTEL. PROVIDE

ENGINEERED SHOP

DRAWINGS FOR LINTEL.

ALIGN

HOLLOW METAL DOOR.

SEE SCHEDULE.

/1

/8

/1

5/8" 2"

FULLY-GROUTED HOLLOW

METAL FRAME FLUSH WITH

EXTERIOR FACE OF WALL.

EXISTING CMU. VERIFY

OPENING HEIGHT IN FIELD AND

REINFORCE AS NECESSARY

FOR NEW DOOR.

3/8"

SEAL FULL PERIMETER

OF DOOR BOTH SIDES.

G1: TYPICAL

6"X8"X16" NOM. CMU

PARTITION TO EXTEND TO

DECK ABOVE

A. DIMENSIONS ON PLANS AND SCHEDULES ARE NOMINAL. GENERAL CONTRACTOR AND DOOR/FRAME MANUFACTURERS ARE TO COORDINATE ALL DIMENSIONS IN THE FIELD CONCERNING FRAME AND ROUGH

OPENINGS PRIOR TO FABRICATION AND CONSTRUCTION.

B. SEAL ALL EDGES OF METAL FRAMES IN CONTACT WITH ADJACENT WALL SURFACES.

C. WHERE TWO DOORS ARE INDICATED ON FLOOR PLAN FOR AN OPENING, BOTH LEAVES ARE EQUAL WIDTH

UNLESS INDICATED OTHERWISE.

D. FRAMES TO BE WELDED WITH HOSPITAL STOPS

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

LOADING DOCK AND

WAREHOUSEDOOR SCHEDULE AND DETAILS

AS600

539-19-202

Cincinnati VAMC

PH JK

1/2" = 1'-0"AS600

1 DOOR AND FRAME TYPES

3" = 1'-0"AS600

2 DOOR HEAD

3" = 1'-0"AS600

3 DOOR JAMB

NOTES:

1. WHERE EXISTING PARTITIONS (OR PORTIONS THEREOF) ARE TO REMAIN, CONTRACTOR SHALL

VERIFY PARTITION TYPE AND CONSTRUCT INFILL OR CONTINUATION OF WALL TO MATCH

EXISTING.

DOOR SCHEDULE

DOOR

NUMBER

FROM

ROOM TO ROOM

OPG.

WIDTH

OPG.

HEIGHT THK

DR.

MATERIAL

DOOR

TYPE

FRAME

MATERIAL

FIRE

RATING HW SET COMMENTS

014A A14 A014 3' - 0" 7' - 0" 1 3/4" HM B EX. HM NONE HW-1 REPLACE DOORS WITH DUTCH DOORS.

014AA A017 A014A 3' - 0" 7' - 0" 1 3/4" HM A EX. HM NONE HW-2 REPLACE DOORS IN EXISTING FRAME, MODIFY FRAME FOR

NEW HARDWARE

014B A014 C-B-1a 3' - 0" 7' - 0" 1 3/4" HM B HM NONE HW-3 NEW DOOR OPENING WITH CARD READER

014C A014A A014 3' - 0" 7' - 0" 1 3/4" HM A HM NONE HW-4 NEW DOOR OPENING WITH CARD READER

PARTITION TYPES FINISH LISTING

GENERAL NOTES - DOORS

STRUCTURE ABOVE

LAMIFLOW LN102

NEGATIVE PRESSURE

MONITOR

3 5/8" METAL STUDS

@ 16" OC

5/8" GYPSUM BD

BOTH SIDES,

TAPED.

T-1

TEMPORARY WALL

1HR RATED

Revisions Date 01/26/18

16 GA. 304 #3/4 FINISH

STAINLESS STEEL.

DUTCH DOOR SHELF DETAIL

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

FFE, Inc.

420 Springfield Pike Cincinnati OH, 45215 513-522-0956

Cincinnati, Ohio

LOADING DOCK AND

WAREHOUSE

01/26/18

Finish Plan

AF101

539-19-202

PH PH

FINISH SCHEDULE

ROOM

NUMBER ROOM NAME

FLOOR

FINISH WALL BASE

NORTH

WALL

FINISH

EAST WALL

FINISH

SOUTH

WALL

FINISH

WEST

WALL

FINISH CEILING COMMENTS

MB-0A-BASEMENT

A014 Distribution EXISTING EXIST/B-1 P-1 EXISTING P-1 EXISTING EXISTING PAINT DOOR FRAMES P-2

A014A Warehouse Receiving & Check-in

F-1 B-1 P-1 P-1 P-1 P-1 P-3 PAINT DOOR FRAMES P-2

FINISH NOTES:

A. ALL FINISHES TO BE INSTALLED PER MANUFACTURER'S DIRECTIONS.

B. ALL ACCESS PANEL DOORS, GRILLES, ETC. ARE TO BE PAINTED TO MATCH WALL COLOR.

C. ALL HOLLOW METAL DOOR FRAMES WITHIN THE AREA TO BE PAINTED TO MATCH WALL COLOR. ALL HOLLOW METAL FRAMES ON MAIN BUILDING CORRIDOR SIDE ONLY ARE TO BE PAINTED TO MATCH EXISTING WALL COLOR.

D. ALL ADJACENT CORNER GUARDS, BUMPER RAILS AND SHEET WALL PROTECTION TO BE WALL PROTECTION IN MATCHING COLOR TO ADJACENT WALL COLOR, UNLESS OTHERWISE NOTED. SEE FINISH LEGEND.

E. ALL FINISHES SHALL COMPLY WITH THE OHIO BUILDING CODE, SECTION 8, INTERIOR FINISHES.

F. DEMO EXISTING BASE AT LOCATIONS SHOWN TO RECIEVE NEW BASE.

F. REFER TO SPECIFICATIONS SECTION 09260 FOR DRYWALL LEVEL INFORMATION.

Floors for Rooms: F-1 Sealed/Topping Concrete Sherwin Williams 3479 Water-Based Epoxy Coating, Color: SW 6236 Grays Harbor 222-C6

Wall Base Replacement for Rooms: B-1 6” Johnsonite Contoured Wall Base Mandalay MX-49-H6, 6” Height, Color: 49 Beige.

Wall Paint and Trim for Rooms:

P-1 Wall Paint: Water Chestnut 30YY 62/127, Semi-Gloss Finish. Sherwin Williams: Pro Industrial Pre-Catalyzed Water Based Epoxy.

P-2 HM Doors and Frame: ICI, 20YY 55/151 Mushroom Cap, Semi-Gloss Finish.

P-3 Ceiling Paint: Sherwin Williams SW 7005 Pure White, 255-C1

Wall Protection & Corner Guards for Rooms:

CG-1 CS Acrovyn Full Length Stainless Corner Guards, Leg Length 3-1/2”, Beveled Vertical Edges, Gauge: 16. Option to Mount with hardware or use CS Acrovyn Recommended Adhesive.

BASE AREAQR; K=5.6 OR K=8.030 MIN100 GPM.10 GPM/SF OVER 1,500 SFLIGHT HAZARD

NOTESSPRINKLERDURATIONHOSECRITERIACLASSIFICATION

FIRE SPRINKLER HAZARD SCHEDULE

ORDINARY HAZARD GROUP I .15 GPM/SF OVER 1,500 SF 250 GPM 60 MIN QR; K=5.6 OR K=8.0 BASE AREA

.20 GPM/SF OVER 1,500 SF 250 GPM 90 MIN QR; K=5.6 OR K=8.0 BASE AREAORDINARY HAZARD GROUP II

N

N

O

O

P

P

Q

Q

R

R

10 10

11 11

12 12

Loading Dock

A017

Corridor

A14

Distribution

A014

Warehouse Receiving &

Check-in

A014A

OH-2 OH-2

1 1

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

FFE, Inc.

438 Springfield Pike Cincinnati OH, 45215 513-522-0956

LOADING DOCK AND

WAREHOUSE

01/26/18

FIRE SUPPRESSION PLAN

FX101

539-16-101

Cincinnati, Ohio

GP GP

A. PROVIDE COMPLETE AUTOMATIC FIRE SPRINKLER

SYSTEMS IN RENOVATED AREAS IN

ACCORDANCE WITH NFPA 13. THE AREA BEING

RENOVATED IS CURRENTLY PROTECTED WITH

AUTOMATIC SPRINKLERS. REWORK PIPING AS

NECESSARY TO ACCOMMODATE RENOVATION.

RAISE SPRINKLER HEADS AS HIGH AS POSSIBLE.

SPRINKLERS SHALL BE QUICK RESPONSE.

B. FURNISH PIPING OFFSETS, FITTINGS, AND ANY

OTHER ACCESSORIES AS REQUIRED TO PROVIDE

A COMPLETE INSTALLATION AND TO ELIMINATE

INTERFERENCE WITH OTHER CONSTRUCTION.

C. INSTALL SPRINKLER SYSTEM OVER AND UNDER

OBSTRUCTIONS WHEN SUCH OBSTRUCTIONS CAN

NEGATIVELY EFFECT OR DISRUPT THE

SPRINKLER DISCHARGE PATTERN AND

COVERAGE.

D. PIPE SIZES SHALL BE DETERMINED BY

HYDRAULICCALCULATION.

E. DESIGN ANY PORTIONS OF THE SPRINKLER

SYSTEM THAT ARE NOT INDICATED ON THE

DRAWINGS INCLUDING LOCATING SPRINKLERS,

PIPING, AND EQUIPMENT, AND SIZE PIPING AND

EQUIPMENT WHEN THIS INFORMATION IS NOT

INDICATED ON THE DRAWINGS OR IS NOT

SPECIFIED HEREIN.

F. AFTER BECOMING FAMILIAR WITH ALL DETAILS

OF THE WORK, VERIFY ALL DIMENSIONS AND

LOCATIONS IN THE FIELD AND ADVISE THE

ENGINEER OF RECORD OF ANY DISCREPANCY

BEFORE PERFORMING THE WORK.

G. COMPLETELY COORDINATE WITH STRUCTURE,

ARCHITECTURE, AND ALL TRADES. CONTENT

SHOWN ON THIS DRAWING IS TO CONVEY DESIGN

INTENT AND DOES NOT DICTATE THE MEANS

AND METHODS OF IMPLEMENTATION. ADHERE TO

ALL HAZARD CLASSIFICATIONS SHOWN.

H. CONTRACTOR TO CONDUCT FIRE WATER FLOW

TEST AND SUBMIT RESULTS AND SPRINKLER

DESIGN.

GENERAL NOTES:

1. INSTALL NEW SPRINKLER HEADS IN THIS

AREA TO ACCOMMODATE NEW FLOOR PLAN.

FOLLOW NFPA CODES FOR SPACING AND

FLOW REQUIREMENTS.

DRAWING NOTES:

SCALE: 1/8" = 1'-0"

FIRE SUPPRESSION PLAN

1 N

LIGHT HAZARD

ORDINARY HAZARD GROUP I

ORDINARY HAZARD GROUP II

SPRINKLER HAZARDS:

LH

OH-1

OH-2

----NON/A0.250.5--[ 10 ]0.375[ 40 ]1.5[ 40 ]1.5ELECTRIC WATER COOLER, WALL HUNGP-604

[mm]IN[mm]IN[mm]IN[mm]IN

REMARKSELECTRIC

SENSOR

WRIST BLADE

HANDLES

WATER

FIXTURE UNITS

WASTE

FIXTURE UNITS

HOT WATERCOLD WATERVENT PIPEWASTE PIPEDESCRIPTIONMARK

PLUMBING FIXTURE SCHEDULE

N

SANITARY & VENT ISOMETRIC

NOT TO SCALE

BASEMENT

FLOOR

P-604

(E ) 3

" S

AN

1-1/2" V(E) 1-1/2" V

1-1/2"

(E ) 3

" S

AN

1-1/2" V

TO VTR

N

N

O

O

P

P

Q

Q

R

R

10 10

11 11

12 12

(E) SSEW

(E) 3/4" DCW

(E) HB

(E) 3/4" DCW

(E) 1-1/2" V

1/2" DCW

(E) 3" SAN DNP-6041-1/2" V

N

N

O

O

P

P

Q

Q

R

R

10 10

11 11

12 12

(E) SSEW

D1

(E) 3/4" DCW

(E) HB

D1

(E) 3/4" DCW

EWCD2

SINK

D2

(E) 1-1/2" V

(E) 1" DCW DN

(E) 1-1/2" SAN DN

D3

D3

(E) 3" SAN DN

(E) EXISTING

DCW DOMESTIC COLD WATER

DN DOWN

EWC ELECTRIC WATER COOLER

HB HOSE BIBB

SAN SANITARY

SSEW SAFETY SHOWER AND EYEWASH

V VENT

VTR VENT THROUGH ROOF

POINT OF CONNECTION

POINT OF REMOVAL

DIRECTION OF FLOW IN PIPING

DEMOLITION DRAWING NOTES:

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

FFE, Inc.

438 Springfield Pike Cincinnati OH, 45215 513-522-0956

LOADING DOCK AND

WAREHOUSE

01/26/18

PLUMBING PLANS

PL101

539-16-101

Cincinnati, Ohio

GP KG

SCALE: 1/8" = 1'-0"

PLUMBING NEW WORK PLAN

SCALE: 1/8" = 1'-0"

PLUMBING DEMOLITION PLAN

A. LOCATIONS AND SIZES OF EXISTING PIPING AND

EQUIPMENT HAVE BEEN DETERMINED FROM A

REVIEW OF EXISTING DRAWINGS AND/OR SITE

INVESTIGATION WHERE POSSIBLE. ANY

DISCREPANCIES BETWEEN EXISTING

CONDITIONS AND THE WORK SHOWN ON THE

CONTRACT DRAWINGS WHICH MAY IMPACT THE

PROGRESS OF THE WORK SHALL BE BROUGHT

TO THE ATTENTION OF THE VA IN WRITING

BEFORE PROCEEDING WITH THE WORK.

GENERAL NOTES:

1. CONNECT 1/2" DCW PIPING TO EXISTING AT

POINT SHOWN. PROVIDE ISOLATION BALL

VALVE.

2. CONNECT 1-1/2" VENT PIPING TO EXISITNG AT

POINT SHOWN.

3. CONNECT 1-1/2" SANITARY PIPING TO EXISTING

3" VERTICAL SANITARY PIPING AT POINT

SHOWN.

4. RE-ROUTE DCW PIPING TO AVOID NEW

DOORWAY. COORDINATE WITH ARCHITECTUAL

PLANS. CORE DRILL FLOOR AS NECESSARY.

DRAWING NOTES:

D1. FIXTURE TO REMAIN

D2. REMOVE PLUMBING FIXTURE AND ALL

ASSOCIATED PIPING BACK TO MAINS AND CAP.

RETURN TO COR FOR FINAL DISPOSAL OR

REUSE.

D3. REMOVE WATER, SANITARY, AND VENT PIPING

SO THAT THE PIPING DOES NOT OBSTRUCT THE

DOORWAY SHOWN ON THE NEW WORK PLAN.

COORDINATE WITH ARCHITECTURAL PLANS.

WATER PIPING TO BE RE-ROUTED IN NEW

WORK PHASE. CAP SANITARY PIPING BELOW

FLOOR. PATCH FLOOR PENETRATIONS TO

MATCH EXISTING.

DEMOLITION DRAWING NOTES:

N

N

AH-2

EF-3

N

N

O

O

P

P

Q

Q

R

R

10 10

11 11

12 12

13 13

14 14

15 15

Nb

Nb

Pb

Pb

Qb

Qb

Rb

Rb

T

DEMO DRAWING NOTES

1 REMOVE EXISTING HEATING AND VENTILATING SUPPLY DUCTWORK FROM POINT

INDICATED, INCLUDING AIR DEVICES AND HANGERS. CAP OPEN END FOR CONNECTION

TO NEW EQUIPMENT.

2 REMOVE EXISTING STEAM UNIT HEATER, INCLUDING HANGERS, WALL THERMOSTAT

AND RACEWAYS. REMOVE STEAM CONDENSATE PIPING AND SPECIALTIES. REMOVE

STEAM SUPPLY PIPING. CAP STEAM AND STEAM CONDENSATE AT BRANCH MAINS FOR

RECONNECTION TO NEW EQUIPMENT.

3 REMOVE EXISTING BRANCH EXHAUST DUCTWORK FROM POINT INDICATED, INCLUDING

AIR DEVICE AND HANGERS. CAP OPEN END FOR CONNECTION TO NEW EQUIPMENT.

4 REMOVE EXISTING CEILING HUNG CHILLED WATER FAN COIL UNIT, INCLUDING

HARDWARE, CONDENSATE DRAIN PIPING AND CONTROL. REMOVE CHILLED WATER

AND CAP BEHIND WALL.

5 EXISTING HEATING AND VENTILATING UNIT AH-2 TO REMAIN.

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

FFE, Inc.

438 Springfield Pike Cincinnati OH, 45215 513-522-0956

LOADING DOCK AND

WAREHOUSE

01/26/18

LOADING DOCK - DEMOLITION

PLAN

MD101

539-16-101

Cincinnati, Ohio

Designer Author

SCALE: 3/16" = 1'-0"

Basement-DEMO

EF-3

AH-2

350 CFM

350 CFM

350 CFM

580 CFM

580 CFM

580 CFM

12"x12"16"x12"24"x12"

500 CFM

EG-1

500 CFM

SG-1

(TYP. 3)

16"x10"

FD

N

N

O

O

P

P

Q

Q

R

R

10 10

11 11

12 12

13 13

14 14

15 15

Nb

Nb

Pb

Pb

Qb

Qb

Rb

Rb

NEW DRAWING NOTES

1 PROVIDE NEW HEATING AND VENTILATING SUPPLY DUCTWORK AND SUPPLY GRILLES AS

SHOWN, CONNECTING TO THE EXISTING. ADJUST AIRFLOW RATES TO THOSE SHOWN.

2 ADJUST AIRFLOW RATES FOR EXISTING SUPPLY GRILLES TO THOSE SHOWN. MAKE

ADJUSTMENTS TO FAN SPEED AT EXISTING HEATING AND VENTILATING UNIT AS

NEEDED FOR OVERALL PERFORMANCE LISTED.

3 PROVIDE NEW EXHAUST GRILLE IN WALL, AND NEW FIRE DAMPER WITHIN WALL;

CONNECTING TO EXISTING 18 X 8 BRANCH EXHAUST DUCT. ADJUST AIR FLOW RATE TO

THAT SHOWN.

4 ADJUST AIRFLOW RATE FOR EXISTING EXHAUST GRILLE TO THAT SHOWN.

5 EXISTING IN0LINE EXHAUST FAN TO REMAIN.

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

FFE, Inc.

438 Springfield Pike Cincinnati OH, 45215 513-522-0956

LOADING DOCK AND

WAREHOUSE

01/26/18

LOADING DOCK - NEW WORK

MH101

539-16-101

Cincinnati, Ohio

Designer Author

SCALE: 3/16" = 1'-0"

Basement-New

HOT WATER LINEAR RADIATION PANEL SCHEDULE

MARK LOCATION AREA

SERVED

TYPE ENCLOSURE TYPE MOUNTING PASSES CONNECTIONS ENCLOSURE LENGTH ENCLOSURE WIDTH CAPACITY TEMPERATURES FLOW MAX WPD REMARKS

EWT LWT

FT [M] INCHES [MM] BTUH/FT TOTAL BTUH [W] °F [°C] °F [°C] GPM [L/s] FT [Pa]

RAD-1 OVERHEAD DOCK PANEL RADIATIVE HORIZONTAL 6 SAME END 8 [ 2 ] 36 [ 900 ] 560 4,480 [ 1300 ] 180 [ 82 ] 160 [ 71 ] 1.0 0.06 4 [ 12 ] - -

RAD-2 OVERHEAD DOCK PANEL RADIATIVE HORIZONTAL 6 SAME END 6 [ 2 ] 36 [ 900 ] 560 3,360 [ 980 ] 180 [ 82 ] 160 [ 71 ] 1.0 0.06 4 [ 12 ] - -

STEAM HEATED DOOR AIR CURTAIN UNIT SCHEDULE

MARK LOCATION AREA/ROOM OR UNIT

SERVED

HEATING

COIL

NOMINAL

LENGTH (FT)

AIR FLOW FAN DATA HEATING COIL FILTER THICKNESS

(INCH)

FILTER TYPE REMARKS

MAX NOZZLE VELOCITY (FPM) MOTOR UNIT ELECTRICAL EAT LAT CAPACITY CONNS. ROWS

CFM [L/s] MAX AVE. QUAN. HP [Kw] VOLT FLA F F BTUH (INCH)

DAC-1 OVERHEAD LOGISTICS DOCK STEAM (15 LB) 10 4300 [ 2000 ] 4650 2050 3 .5 0.40 120 15.3 60.0 95.0 18,300 1.5 1 2 WASHABLE - -

PIPING CONNECTIONS

A

NTS

TEST PLUG (TYP.)

MANUAL AIR VENT

(TYP.)

UNION CONNECTIONS

(TYP.)

RADIANT HEATERS HOT WATER COILS -

DRAIN WITH HOSE

CONNECTION (TYP.)

MV

MODULATING

CONTROL VALVE

MV

RADIANT

HEATER

B

NTS

STEAM HEATING COIL

STEAM

CONDENSATE

RETURN

INVERTED

BUCKET TRAP

STEAM SUPPLY

[1 m m

SCALE POCKET

STEAM CONTROL VALVE

PIPING CONNECTIONS

M

IN

M

IN

[1 m m

DRAIN WITH HOSE

CONNECTION (TYP.)

DOOR AIR CURTAIN

BALANCING

VALVE

BALANCING

VALVE

STRAINER

RADIANT

HEATER

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

FFE, Inc.

438 Springfield Pike Cincinnati OH, 45215 513-522-0956

LOADING DOCK AND

WAREHOUSE

01/26/18

DETAILS AND SCHEDULES

MH501

539-16-101

Cincinnati, Ohio

Designer Author

SEQUENCE OF OPERATION FOR RAD-1, RAD-2 AND DAC-1 - BUILDING 1 – BASEMENT LEVEL – LOGISTICS DOCK

1. GENERAL

1.1 RADIATION HOT WATER HEATERS RAD-1, RAD-2 INSTALLED NEAR THE CEILING OF DOCK AREA PROVIDE

HEAT IN WINTER TO THE DOCK AREA FOR GENERAL COMFORT. STEAM HEATED DOOR CURTAIN DAC-1

OPERATES WHEN THE DOCK DOOR IS OPEN TO CREATE AND AIR CURTAIN TO DETER ENTRY OF

INSECTS, WITH INTEGRAL STEAM HEATING COIL TO HEAT THAT CURTAIN OF AIR IN WINTER TO HELP

PREVENT LOSS OF SPACE HEAT TO THE OPEN DOCK DOOR.

1.2 PROGRAM THE SYSTEM AND EXISTING ECC TO PROVIDE THE FOLLOWING SEQUENCES, INCLUDING NEW

GRAPHICS PAGES, TRENDS.

2. TEMPERATURE CONTROL

2.1 THE RADIATION HOT WATER HEATERS SHALL BE ENABLED DURING WINTER (WHEN OUTDOOR

TEMPERATURE IS BELOW 50 F, ADJUSTABLE).

2.2 WHEN ENABLED, MODULATING HOT WATER CONTROL VALVE FOR THE HOT WATER RADIATION HEATERS

SHALL MODULATE TO MAINTAIN SETPOINT TEMPERATURE IN THE DOCK AREA BASED ON SPACE

TEMPERATURE SENSOR (BLANK COVER, NO ADJUSTMENT).

2.3 DOCK AREA SPACE TEMPERATURE SETPOINT SHALL BE 65 F (ADJUSTABLE) DURING OCCUPIED HOURS, AND 55 F (ADJUSTABLE) DURING UNOCCUPIED HOURS. SETPOINT ESTABLISHED AT ECC.

2.4 DOOR SWITCH SHALL DETERMINE THAT DOCK DOOR IS OPEN AND INDEX DOOR AIR CURTAIN FAN TO OPERATE. DOOR SWITCH SHALL DISABLE DOOR AIR CURTAIN FAN WHEN DOOR IS NO LONGER OPEN.

2.5 DOOR AIR CURTAIN STEAM HEATING SHALL BE ENABLED ONLY WHEN ECC DETERMINES OUTDOOR

TEMPERATURE IS BELOW 45 F (ADJUSTABLE).

2.6 WHENEVER DOOR AIR CURTAIN FAN IS ENABLED, AND HEATING IS ENABLED BY ECC, STEAM HEATING IN

THE DOOR AIR CURTAIN SHALL BE ENABLED.

2.7 STEAM SUPPLY CONTROL VALVE SHALL CYCLE STEAM FLOW TO DOOR AIR CURTAIN COIL TO MAINTAIN TEMPERATURE AT WALL MOUNTED THERMOSTAT NEAR DOCK DOOR OPENING (50 F, ADJUSTABLE).

2.8 INTEGRAL FACTORY TIME DELAY SHALL MAINTAIN HEATING ALREADY IN OPERATION FOR 1 MINUTE AFTER

DOOR HAS CLOSED.

3. SCHEDULE

3.1 PROGRAM OCCUPIED AND UNOCCUPIED SCHEDULE FOR THIS SYSTEM AT THE ECC.

4. SAFETY

4.1 WHEN LOCAL FIRE ALARM SYSTEM IS ACTIVATED, DAC-1 SHALL BE STOPPED.

4.2 PROGRAM ALARMS FOR LOW SPACE TEMPERATURE (SPACE SENSOR 10 F BELOW SETPOINT,

ADJ), HIGH SPACE TEMPERATURE (SENSOR ABOVE 100 F, ADJ),

4.3 IN THE EVENT OF FAILURE (SUCH AS POWER FAILURE), BOTH UNITS SHALL BE DISABLED AND CONTROL

VALVES CLOSED.

1" HWS/RRAD-1

RAD-1

3/4" HWS/R

3/4" STM

3/4" STC

T

DAC-1

S T

C

S T

M

N

N

O

O

P

P

Q

Q

R

R

10 10

11 11

12 12

13 13

14 14

15 15

Nb

Nb

Pb

Pb

Qb

Qb

Rb

Rb

RAD-2

RAD-2

NEW PIPING DRAWING NOTES

1 PROVIDE NEW STEAM HEATED DOOR AIR CURTAIN ABOVE EXISTING DOCK DOOR

OPENING, LOCATED AS CLOSE AS PRACTICAL TO THE DOOR OPENING. PROVIDE DOOR

SWITCH TO ENABLE UNIT WHEN DOCK DOOR IS OPENED.

2 PROVIDE NEW STEAM AND STEAM CONDENSATE PIPING, INCLUDING SPECIALTIES AND

INSULATION, EXTENDED FROM THE CONNECTIONS REMAINING ON THE EXISTING

BRANCH MAINS. REFER TO PIPING DIAGRAMS.

3 PROVIDE NEW HOT WATER HEATING RADIATION UNITS CLOSE TO CEILING. PROVIDE

SPACE TEMPERATURE SENSOR FOR CONTROL OF RADIATORS ON THE BACK SIDE OF THE

EXISTING COLUMN.

4 PROVIDE NEW HEATING HOT WATER SUPPLY AND RETURN PIPING, INCLUDING

SPECIALTIES AND INSULATION, EXTENDED FROM THE FLOOR BELOW. REFER TO PIPING

DIAGRAMS.

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

FFE, Inc.

438 Springfield Pike Cincinnati OH, 45215 513-522-0956

LOADING DOCK AND

WAREHOUSE

01/26/18

LOADING DOCK - NEW PIPING

MP101

539-16-101

Cincinnati, Ohio

Designer Author

SCALE: 3/16" = 1'-0"

LOADING DOCK - NEW PIPING

RELOCATE EXISTING WALL LIGHT

8" WEST FOR NEW DOOR OPENING

DEMO WALL LIGHTS

72"

EXIT SIGN

ALT-1

Rb

Qb O N Ma

8a

AREA OF PROJECT

GENERAL NOTES - DEMOLITION

A. FOR EXISTING LIGHTING FIXTURES, WIRING DEVICES, CONDUITS, ETC., SHOWN ON

PLANS TO BE REMOVED, MAINTAIN CONDUIT AND WIRE SERVING FIXTURES, DEVICES

OR EQUIPMENT TO REMAIN AND REMOVE FIXTURE, DEVICE OR EQUIPMENT. MAKE

SAFE ALL WIRING THROUGH PROPER LOCK-OUT TAGOUT PROCEDURES BEFORE

COMMENCING WORK. REMOVE PORTIONS OF CONDUIT AND WIRE AS ABANDONED OR

LEFT IN PLACE DUE FIXTURE(S), DEVICE(S) AND EQUIPMENT THAT ARE TO BE REMOVED.

REFER TO EL100 FOR CONNECTION TO NEW LIGHTING.

B. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES BACK TO THE OVERCURRENT

PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING.

C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS PASSING

THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.

DEMO DRAWING NOTES

1. DISCONNECT & PERMANENTLY REMOVE EXISTING LIGHTING. DISCARD LIGHTING

FIXTURE. MAINTAIN CONDUIT & WIRING FOR RECONNECTION.

2. EXISTING LIGHTS TO REMAIN.

3. DISCONNECT AND REMOVE EXISTING LIGHT SWITCH. DISCONNECT AND REMOVE

CONDUIT AND WIRE SERVING INACTIVE DEVICE(S)

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

LOADING DOCK AND

WAREHOUSE

PARTIAL BASEMENT LIGHTING

DEMOLITION PLAN

EDL100

539-19-202

Cincinnati VAMC

MM

SCALE: 3/16" = 1'-0"

ENLARGED DEMO LIGHTING PLAN

KEY PLAN

AREA OF PROJECT

Rb Qb O N Ma

DOOR CONTACT

FIRE ALARM / PA SPEAKERS

TO REMAIN, TYPICAL

DEVICE TO REMAIN,

TYPICAL UNLESS NOTED

OTHERWISE

4 5

7 8

GENERAL NOTES

A. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO ANY FABRICATION OR

CONSTRUCTION.

B. CONTRACTOR TO NOTIFY OWNER REPRESENTATIVE OF ANY DISCREPANCIES AND OBTAIN

OWNER APPROVAL FOR ANY CHANGES.

C. ELECTRICAL DEVICE LOCATIONS ARE APPROXIMATE. COORDINATE WITH EQUIPMENT IN

AREA AND OWNER FOR FINAL DEVICE LOCATIONS.

D. CONDUIT TO BE FIELD ROUTED. PROVIDE PULL BOXES AS REQUIRED PER NEC OR

CONSTRUCTION CONDITIONS.

E. CONTRACTOR TO SIZE CONDUIT AND CONDUCTORS BASED UPON MAXIMUM ALLOWABLE

LOAD FOR CIRCUIT BREAKER SIZE SHOWN AND DERATING FACTORS REQUIRED FOR FILL AND

VOLTAGE DROP.

F. PROVIDE SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTOR WITHIN EACH

FEEDER AND BRANCH CIRCUIT RACEWAY. TERMINATE EACH END ON SUITABLE LUG, BUS

OR BUSHING.

G. CONTRACTOR TO PROVIDE ALL NECESSARY SUPPORTS TO FACILITATE INSTALLATION OF

THEIR DISCIPLINE EQUIPMENT, INDEPENDENT OF OTHER DISCIPLINES.

DRAWING NOTES

1. DEMOLISH CONDUIT ALONG WALL. PULL EXISTING CONDUIT BACK TO CEILING AND

MAKE SAFE. MAINTAIN OUTLETS AND DEVICES ALONG WALL, REFER TO EP100 FOR

REFEED.

2. DEMOLISH FAN, ASSOCIATED RECEPTACLE, CONDUIT AND WIRE BACK TO SOURCE OR

LAST ACTIVE DEVICE.

3. DEMOLISH CONDUIT ALONG WALL. FOR CONDUIT SERVING DEVICES TO REMAIN:

PROVIDE NEW CONDUIT, SUPPORTED FROM THE CEILING. EXTEND OR REFEED

CABLING FROM LAST ACTIVE DEVICE.

4. DEMOLISH CAMERA, CONDUIT AND WIRE BACK TO SOURCE.

5. DEMOLISH RECEPTACLE, CONDUIT AND WIRE TO LAST ACTIVE DEVICE.

6. RELOCATE WIRELESS ACCESS POINT TO CEILING. EXTEND CONDUIT AND WIRE TO NEW

LOCATION.

7. DEMOLISH SENSOR ABOVE DOOR, CONDUIT AND WIRE BACK TO SOURCE OR LAST

ACTIVE DEVICE.

8. DEMOLISH HORN, CONDUIT AND WIRE BACK TO SOURCE OR LAST ACTIVE DEVICE.

9. DEMOLISH INTRUSION ALARM SYSTEM CONTROLS FROM WITHIN ROOM TO LAST

ACTIVE DEVICE.

10. DEMOLISH INTRUSION ALARM KEYPAD.

GENERAL POWER DEMO NOTES

A. TERMINATE CONDUIT AND WIRING AT NEAREST JUNCTION BOX IN AREAS TO REMAIN AND

LABEL WITH CIRCUIT DESIGNATION. MAINTAIN CIRCUITING TO WIRING DEVICES WHICH

ARE TO REMAIN. REWORK BRANCH CIRCUITS AS REQUIRED WHERE DEMOLISHED WIRING

DEVICES FEED THROUGH TO OTHER DEVICES WHICH ARE TO REMAIN.

B. ALL DEMOLISHED MATERIAL SHALL BE REMOVED FROM SITE UNLESS NOTED TO BE RE-USED

OR TO BE SALVAGED AND TURNED OVER TO OWNER.

C. IF CIRCUITING IS NOT RE-USED, REMOVE CONDUIT & WIRING BACK TO PANELBOARD &

MARK CIRCUIT BREAKER AS 'SPARE'.

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

LOADING DOCK AND

WAREHOUSE

PARTIAL BASEMENT POWER

DEMOLITION PLAN

EDP100

539-19-202

Cincinnati VAMC

MM

KEY PLAN

3/16" = 1'-0"

ENLARGED DEMOLITION POWER PLAN

S

RELOCATE EXISTING LIGHT 8"

FOR NEW DOOR OPENING

NEW 120V LINE VOLTAGE

OCCUPANCY SENSOR

A

AE

A

A

A

AE A A A

A

A

A A

A A A A

AAE

A A

EX

EX

EX

EX EX

EX

EX EX

EX

EX EX

EX

EX EX

EX

EX

EXEXEX

EX EX EX

EX

ALT-1

Rb

Qb

O N Ma

8a

EXISTING LIGHT SWITCHES

EXISTING EXIT SIGN

Warehouse

Receiving &

Check-in

A014A

1031 SF

Distribution

A014

1159 SF

Loading Dock

A017

949 SF

GENERAL NOTES

A. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE OBTAINED

FROM THE ARCHITECTURAL REFLECTED CEILING PLAN.

B. LIGHTING FIXTURES WITH MORE THAN TWO LAMPS SHALL HAVE TWO OUTER LAMPS

CONTROLLED WITH ONE SWITCH AND INNER LAMP(S) CONTROLLED BY A SECOND SWITCH.

C. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH

BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED EQUIPMENT

GROUNDING CONDUCTOR. IF EXISTING CIRCUITRY DOES NOT MEET THIS REQUIREMENT,

REPLACE ALL PORTIONS OF WIRING THAT DO NOT COMPLY.

D. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND

NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.

E. FOR TYPE 'A' AND 'AE' FIXTURES: REPLACE LIGHTING IN KIND. LIGHTING INSTALLATIONS

ARE INTENDED TO BE INSTALLED TO MATCH EXISTING LIGHTING FIXTURE LOCATIONS AND

EXACT QUANTITIES. NOTE DISCREPANCIES, CLASHES AND SUBMIT WHERE REQUIRED BY

MAJOR DIFFERENCES IN THE LAYOUT.

DRAWING NOTES

1. UNLESS NOTED OTHERWISE, RECONNECT LIGHTING IN THIS ROOM TO EXISTING 120V

CIRCUITRY MADE AVAILABLE THROUGH LIGHTING DEMOLITION. LIGHTING TO BE

CONTROLLED BY EXISTING LIGHT SWITCHES.

2. RECIRCUIT LIGHT FROM LOCAL EMERGENCY LIGHTING CIRCUITRY. POWER FROM UN-

SWITCHED EXISTING 120V CIRCUIT FROM PANEL LSAB IN ROOM A019.

3. PROVIDE CEILING MOUNTED 120V 20A 1P OCCUPANCY SENSOR WITH 360 DEGREE

SENSING CAPABILITY. SENSOR TO BE DESIGNED FOR A 10' SPACE AND SHALL BE DUAL

TECHNOLOGY PIR/ULTRASONIC.

4. UNLESS NOTED OTHERWISE, RECONNECT LIGHTING IN THIS ROOM TO EXISTING

CIRCUITRY MADE AVIALABLE THROUGH LIGHTING DEMOLITION. LIGHTING TO BE

CONTROLLED BY OCCUPANCY SENSOR REFEED FROM DEMOLISHED LIGHT SWITCHING

TO LINE VOLTAGE OCCUPANCY SWITCH.

AREA OF PROJECT

LIGHT SWITCH

LIGHT FIXTURE, 1 x 4

LIGHTING LEGEND

OCCUPANCY SENSOR, CEILING MOUNTED 360° COVERAGEOC

A

EMERGENCY LIGHT FIXTURE, 1 x 4

AE

EX

EX

EXISTING WALL LIGHT FIXTURE

EXISTING LIGHT FIXTURE

FIXTURE SCHEDULE

MARK DESCRIPTION LAMPS VOLTAGE MOUNTING

A

1X4 LED WRAPAROUND FIXTURE; 4000K COLOR

TEMP.

(1) LED, 62W, 7336 LUMENS 120-277V SURFACE

MOUNT

AE 1X4 LED WRAPAROUND FIXTURE; 4000K COLOR

TEMP.

(1) LED, 62W, 7336 LUMENS 120-277V SURFACE

MOUNT

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

LOADING DOCK AND

WAREHOUSE

PARTIAL BASEMENT LIGHTING

PLAN

EL100

539-19-202

Cincinnati VAMC

MM

SCALE: 3/16" = 1'-0"

ENLARGED NEW WORK LIGHTING PLAN

KEY PLAN

GFI

42"

10' - 1"

CONDUIT, RELOCATED

TO CEILING

WAP, RELOCATED TO CEILING

REROUTED CONDUIT AROUND

NEW OPENING - MANTAIN

DEVICES ON BOTH SIDES

Qb O N Ma

8a

42" 42"

Warehouse

Receiving &

Check-in

A014A

1031 SF

Loading Dock

A017

949 SF

Corridor

A14

122 SF

Distribution

A014

1159 SF

DAC-1

BC2

PROVIDE CARD

ACCESS. REF 2/EP100

PROVIDE CARD

ACCESS. REF 2/EP100

42" 42"42"

42"

42"

42"

42"

42"

18"

18" 18"

42"

014AA

014C

A014A

014B

GENERAL NOTES

A. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO ANY FABRICATION OR

CONSTRUCTION.

B. CONTRACTOR TO NOTIFY OWNER REPRESENTATIVE OF ANY DISCREPANCIES AND OBTAIN

OWNER APPROVAL FOR ANY CHANGES.

C. ELECTRICAL DEVICE LOCATIONS ARE APPROXIMATE. COORDINATE WITH EQUIPMENT IN

AREA AND OWNER FOR FINAL DEVICE LOCATIONS.

D. CONDUIT TO BE FIELD ROUTED. PROVIDE PULL BOXES AS REQUIRED PER NEC OR

CONSTRUCTION CONDITIONS.

E. CONTRACTOR TO SIZE CONDUIT AND CONDUCTORS BASED UPON MAXIMUM ALLOWABLE

LOAD FOR CIRCUIT BREAKER SIZE SHOWN AND DERATING FACTORS REQUIRED FOR FILL

AND VOLTAGE DROP.

F. PROVIDE SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTOR WITHIN EACH

FEEDER AND BRANCH CIRCUIT RACEWAY. TERMINATE EACH END ON SUITABLE LUG, BUS

OR BUSHING.

G. CONTRACTOR TO PROVIDE ALL NECESSARY SUPPORTS TO FACILITATE INSTALLATION OF

THEIR DISCIPLINE EQUIPMENT, INDEPENDENT OF OTHER DISCIPLINES.

H. PROVIDE MARKUPS TO AS-BUILT SET. MARKUPS SHALL INCLUDE EXISTING CIRCUIT

INFORMATION ON INDICATING HOME-RUNS AND TIE-INS.

DRAWING NOTES

1. PROVIDE 1" EMT CONDUIT AND ACCESS CONTROL PLENUM RATED MULTICABLE

ASSEMBLY FROM DOOR CONNECTIONS BACK TO CARD READER CONTROL PANEL IN ROOM

A001D. MAKE TERMINATIONS TO SYSTEM TERMINAL MODULE.

2. PROVIDE CARD READER ON UNSECURE SIDE OF DOOR(S) TO CONTROL ACCESS TO STORAGE

ROOMS A014A. CARD READER TO RELEASE ELECTRONIC MORTISE LOCKSET UPON

ACTIVATION. PROVIDE A NEW NETWORK CONTROLLER IN EXISTING CARD READER CONTROL

PANEL IN ROOM A001D & AN ADDITIONAL TERMINAL MODULE IN THE EXISTING CARD READER

MODULE PANEL ALSO IN ROOM A001D.

3. ELECTRONIC MORTISE LOCKSET AND POWER TRANSFER UNIT CONNECTED TO DOOR

HANDLE ASSEMBLY. CONCEAL WIRING TO ELECTRONIC LOCKSET AND TRANSFER UNIT

WITHIN FRAMES. CABLING SHALL NOT BE EXPOSED.

4. PROVIDE 120V 1P POWER TO POWER MODULE FROM PANEL LASB-7. ELECTRIC DOOR

LOCK SHALL BE TIED TO CONTROLLER WITH CONTROL MODULES LOCATED IN ELECTRIC

ROOM A001D. SYSTEM SHALL BE FAIL SECURE - UPON LOSS OF POWER TO POWER MODULE,

KEYED ENTRY IS THE ONLY WAY TO ENTER THE SECURED SPACE.

5. PROVIDE POWER FROM CIRCUITS MADE AVAILABLE THROUGH DEMOLITION OF EXISTING

WALK-IN COOLER UNDER VAMC PROJECT 539-16-101. PROVIDE #12, #12N, #12G, 3/4"

CONDUIT FROM SOURCE. PROVIDE 20A 1P, 120V BREAKER WITHIN PANEL TO REPLACE

EXISTING.

6. PROVIDE MOTION SENSITIVE EXIT DEVICE ON SECURE SIDE.

7. CIRCUIT DUPLEX RECEPTACLE TO LOCAL 120V RECEPTACLE CIRCUIT GIVEN SPARE CAPACITY

THROUGH DEMOLITION.

8. PROVIDE (4) CAT 6 CABLES FROM DATA OUTLET TO TELECOMMUNICATIONS EQUIPMENT

ROOM A035. PROVIDE (4) PORT DEVICE AND ALL TERMINATIONS. COORDINATE IP

ADDRESSING WITH OWNER REQUIREMENTS.

9. CIRCUIT TO SPARE 120V 1P 20A BREAKER IN BC2.

10. COORDINATE ELEVATION OF DRINKING FOUNTAIN RECEPTACLE WITH INSTALLATION OF

DRINKING FOUNTAIN. RECEPTACLE TO BE CONCEALED BY DRINKING FOUNTAIN.

11. REPLACE DUPLEX RECEPTACLE WITH QUADRUPLEX RECEPTACLE. RECONNECT POWER AS

REQUIRED.

12. CONNECT DOCK DOOR INTRUSION SYSTEM DOOR CONTACT INTO ACCESS CONTROL

SYSTEM. PROVIDE CONDUIT AND WIRE TO NEAREST INPUT.

13. PROVIDE DOOR CONTACTS AT DUTCH DOOR TIED INTO THE ACCESS CONTROL SYSTEM.

3 2

JBCEILING

FLOOR

AREA OF PROJECT

JUNCTION BOX

CARD READER

J

CR

POWER LEGEND

120V 1P 20A DUPLEX RECEPTACLE

120V 1P 20A 30mA GFI RECEPTACLEGFI

DATA OUTLET WITH (4) DATA JACKS,

PROVIDE (4) CAT 6 CABLES PER PLAN.

PROVIDE TERMINATIONS.

DOOR CONTACTDC

DOOR TAG101

O

BC1

BC2

DPC CBC

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

LOADING DOCK AND

WAREHOUSE

PARTIAL BASEMENT POWER

PLAN

EP100

539-19-202

Cincinnati VAMC

MM

SCALE: 3/16" = 1'-0"

ENLARGED BASEMENT - NEW ELECTRICAL FLOOR PLAN

SCALE: 1/2" = 1'-0"

DOOR CARD READER / HARDWARE ELEVATION

KEY PLAN

ELECTRICAL

CLOSET

TELECOMMUNICATIONS

EQUIPMENT ROOM

SCALE: 3/16" = 1'-0"

ENLARGED BASEMENT - NEW ELECTRICAL FLOOR PLAN

AREA OF PROJECT

GENERAL NOTES

A. THIS WORK INCLUDES COMPLETION OF LAYOUT AND PROVIDING COMPLETE FIRE

ALARM COVERAGE THROUGHOUT THE RENOVATED AREAS IN ACCORDANCE WITH (BUT

NOT LIMITED TO) NFPA 70, NFPA 72, AND THE VA FIRE PROTECTION MANUAL.

B. PROVIDE WIRING, RACEWAYS, PULL BOXES, TERMINAL CABINETS, OUTLET AND

MOUNTING BOXES, CONTROL EQUIPMENT, ALARM AND SUPERVISORY SIGNAL INITIATING

DEVICES, ALARM NOTIFICATION APPLIANCES, SUPERVISING STATIONS INTERFACE

EQUIPMENT, AND OTHER ACCESSORIES AND MISCELLANEOUS ITEMS REQUIRED FOR A

COMPLETE OPERATING SYSTEM EVEN THOUGH EACH ITEM IS NOT SPECIFICALLY

MENTIONED OR DESCRIBED. PROVIDE SYSTEM COMPLETE AND READY FOR

OPERATION.

C. SUBMIT PLAN VIEW DRAWING SHOWING DEVICE LOCATIONS, TERMINAL CABINET

LOCATIONS, JUNCTION BOXES, OTHER RELATED EQUIPMENT, CONDUIT ROUTING, WIRE

COUNTS, CIRCUIT IDENTIFICATION IN EACH CONDUIT, AND CIRCUIT LAYOUTS.

DRAWINGS SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 170. FINAL

QUANTITY, SYSTEM LAYOUT, AND COORDINATION ARE THE RESPONSIBILITY OF THE

CONTRACTOR.

D. MAINTAIN EXISTING SYSTEM FUNCTIONALITY, DO NOT ALTER INPUTS / OUTPUTS.

E. EXISTING SYSTEM IS HONEYWELL, FIRE ALARM WORK SHALL BE SOLE SOURCED TO

HONEYWELL.

DRAWING NOTES

1. EXISTING WALL MOUNTED SPEAKER MOUNTED 84" A.F.F. CONNECT TO EXISTING

CENTER NORTH DSDC STROBE CIRCUIT. CIRCUIT IDENTIFICATION - CONTROL: 1,

SOURCE: 2, RELAY NO.: 164. RELOCATE FOR NEW DOOR OPENING.

2. FIRE ALARM MONITOR MODULE. PROVIDE CUTOUT AT EQUIPMENT DURING FIRE ALARM

CONDITIONS. TIE MONITOR MODULE INTO FIRE ALARM LOOP. PROVIDE WIRING AND

TERMINATIONS, (2)#14 FROM MONITOR MODULE TO DAC-1.

EX

Qb O N Ma

8a

RELOCATE

CONNECT TO LOCAL

FIRE ALARM LOOP

M

DAC-1

Warehouse

Receiving &

Check-in

A014A

1031 SF

Distribution

A014

1159 SF

HORN STROBE

FIRE ALARM LEGEND

CANDELA RATING

M RELAY MONITOR MODULE

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

LOADING DOCK AND

WAREHOUSE

PARTIAL BASEMENT FIRE ALARM

PLAN

FA100

539-19-202

Cincinnati VAMC

MM

KEY PLAN

SCALE: N.T.S.

ENLARGED BASEMENT - NEW ELECTRICAL FLOOR PLAN

1 539-19-202 B01 Main Building - Sheet - GI001 - COVER SHEET
Sheets
A101 - NEW WORK PLAN
A102 - CEILING PLANS
A104 - INTERIOR ELEVATIONS
AD101 - DEMO PLAN
AF101 - Finish Plan
AS600 - DOOR SCHEDULE AND DETAILS
GI001 - COVER SHEET
2 539-19-202 B01 Main Building - Sheet - AD101 - DEMO PLAN
Sheets
A101 - NEW WORK PLAN
A102 - CEILING PLANS
A104 - INTERIOR ELEVATIONS
AD101 - DEMO PLAN
AF101 - Finish Plan
AS600 - DOOR SCHEDULE AND DETAILS
GI001 - COVER SHEET
3 539-19-202 B01 Main Building - Sheet - A101 - NEW WORK PLAN
Sheets
A101 - NEW WORK PLAN
A102 - CEILING PLANS
A104 - INTERIOR ELEVATIONS
AD101 - DEMO PLAN
AF101 - Finish Plan
AS600 - DOOR SCHEDULE AND DETAILS
GI001 - COVER SHEET
4 539-19-202 B01 Main Building - Sheet - A102 - CEILING PLANS
Sheets
A101 - NEW WORK PLAN
A102 - CEILING PLANS
A104 - INTERIOR ELEVATIONS
AD101 - DEMO PLAN
AF101 - Finish Plan
AS600 - DOOR SCHEDULE AND DETAILS
GI001 - COVER SHEET
5 539-19-202 B01 Main Building - Sheet - A104 - INTERIOR ELEVATIONS
Sheets
A101 - NEW WORK PLAN
A102 - CEILING PLANS
A104 - INTERIOR ELEVATIONS
AD101 - DEMO PLAN
AF101 - Finish Plan
AS600 - DOOR SCHEDULE AND DETAILS
GI001 - COVER SHEET
6 539-19-202 B01 Main Building - Sheet - AS600 - DOOR SCHEDULE AND DETAILS
Sheets
A101 - NEW WORK PLAN
A102 - CEILING PLANS
A104 - INTERIOR ELEVATIONS
AD101 - DEMO PLAN
AF101 - Finish Plan
AS600 - DOOR SCHEDULE AND DETAILS
GI001 - COVER SHEET
7 539-19-202 B01 Main Building - Sheet - AF101 - Finish Plan
Sheets
A101 - NEW WORK PLAN
A102 - CEILING PLANS
A104 - INTERIOR ELEVATIONS
AD101 - DEMO PLAN
AF101 - Finish Plan
AS600 - DOOR SCHEDULE AND DETAILS
GI001 - COVER SHEET
8 539-19-202 Mechanical_razvan - Sheet - FX101 - FIRE SUPPRESSION PLAN
Sheets
FX101 - FIRE SUPPRESSION PLAN
MD101 - LOADING DOCK - DEMOLITION PLAN
MH101 - LOADING DOCK - NEW WORK
MH501 - DETAILS AND SCHEDULES
MP101 - LOADING DOCK - NEW PIPING
PL101 - PLUMBING PLANS
9 539-19-202 Mechanical_razvan - Sheet - PL101 - PLUMBING PLANS
Sheets
FX101 - FIRE SUPPRESSION PLAN
MD101 - LOADING DOCK - DEMOLITION PLAN
MH101 - LOADING DOCK - NEW WORK
MH501 - DETAILS AND SCHEDULES
MP101 - LOADING DOCK - NEW PIPING
PL101 - PLUMBING PLANS
10 539-19-202 Mechanical_razvan - Sheet - MD101 - LOADING DOCK - DEMOLITION PLAN
Sheets
FX101 - FIRE SUPPRESSION PLAN