36C25018B0806-003.pdf
PDF 3 MB Posted
- Attached to
- Re-Solicitation - Upgrade UPS and AC Federal contract opportunity
- Solicitation number
- 36C25018B0806
About this file
36C25018B0806 Attachment 2 Upgrade UPS and AC in Computer Room Drawings 02-16-2018.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25018B0806-0002000.docx | DOCX document | |
| 36C25018B0806-0001000.docx | DOCX document | |
| 36C25018B0806-002.pdf | ||
| 36C25018B0806-001.docx | DOCX document | |
| 36C25018B0806-004.docx | DOCX document | |
| 36C25018B0806-005.docx | DOCX document | |
| 36C25018B0806-006.docx | DOCX document | |
| 36C25018B0806-000.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Drawing Title
Approved: Project Director
Location
Building Number
Project Tit le
Checked DrawnDate
Project No.
Drawing Number
D w g . o f o n e -e ig h th i n c h o n e f o o t o n e
-q u a rt e r in c h o n e f o o t th re e
-e ig h th s i n c h o n e f o o t o n e
-h a lf i n c h o n e f o o t th re e
-q u a rt e rs i n c h o n e fo o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
FFE, Inc.
420 Springfield Pike Cincinnati OH, 45215 513-522-0956
Cincinnati, Ohio
Upgrade UPS and AC in Computer Room
06/09/17
COVER SHEET
GI001
539-18-202
RG JK
BLDG 1
1 13
DRAWING SHEET INDEX
Sheet Number Sheet Name
Sheet Discipline
GI001 COVER SHEET GENERAL
E001 ELECTRICAL LEGENDS ELECTRICAL
EP101 PARTIAL FIRST FLOOR PLAN ELECTRICAL
EP102 PHASE 1 PARTIAL THIRD FLOOR PLAN ELECTRICAL
EP103 POWER PLAN - PHASE 1 PARTIAL FOURTH
FLOOR IT ROOM A437C
ELECTRICAL
EP104 POWER PLAN - PHASE 2 PARTIAL FOURTH
FLOOR IT ROOM A437C
ELECTRICAL
EP105 POWER PLAN - PHASE 3 PARTIAL FOURTH
FLOOR IT ROOM A437C
ELECTRICAL
EP301 NORMAL & EMERGENCY POWER BRANCHES -
80kVA UPS - "1E7" / ATS-"1E7" SINGLE LINE
DIAGRAM
ELECTRICAL
EP302 POWER BRANCH - 100kVA UPS2, PANEL
EDPEQ3 SINGLE LINE DIAGRAM
ELECTRICAL
EP501 ELECTRICAL DETAILS ELECTRICAL
EP601 EXISTING UPS1 POWER PANEL SCHEDULES ELECTRICAL
EP602 NEW WORK - EDPEQ3 POWER PANEL
SCHEDULE
ELECTRICAL
EP603 NEW UPS1 AND UPS2 POWER PANEL
SCHEDULES
ELECTRICAL
UPGRADE UPS AND AC IN
COMPUTER ROOM
CINCINNATI VA MEDICAL CENTER
3200 VINE STREET CINCINNATI OHIO 45220
PROJECT NO. 539-18-202
AREA MAP
PROJECT LOCATION
Revisions Date
0 ISSUED FOR CONSTRUCTION 06-09-2017
1 ADDENDUM 1 11-03-2017
*** R.I.D. = RESIDENT INTERIOR DESIGNER. ***
** U.N.O. = UNLESS NOTED OTHERWISE.**
* C.O.R. = CONTRACTING OFFICER'S REPRESENTATIVE. THIS IS USED IN LIEU OF THE TERM OWNER.*
1. ALL WORK SHALL COMPLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL CODES, RULES, ORDINANCES AND REGULATIONS INCLUDING THE AMERICAN DISABILITIES ACT (ADA), ARCHITECTURAL
BARRIERS ACT(ABA), THE VA BARRIER FREE DESIGN GUIDELINES AND THE AMERICAN
NATIONALSTANDARDS INSTITUTE (ANSI) GUIDELINES.
2. THE C.O.R. SHALL WORK WITH THE CONTRACTOR TO PROVIDE ACCESS TO TEMPORARY SERVICES REQUIRED TO PROVIDE THE WORK INDICATED. SEE SPECIFICATION SECTION 01 00 00 FOR ADDITIONAL
REQUIREMENTS ON TEMPORARY ACCESS TO VA UTILITIES.
3. THE GENERAL CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE PROVISIONS OF THE SPECIFICATIONS, INCLUDING ALL GENERAL CONDITIONS, SUPPLEMENTARY GENERAL CONDITIONS, AND MATERIAL AND CONSTRUCTION PROVISIONS, WHICH APPLY TO MATERIALS OR CONSTRUCTION METHODS REQUIRED BY
THIS PROJECT.
4. PRIOR TO BIDDING, THE GENERAL CONTRACTOR SHALL VISIT THE SITE, EXAMINE, AND ACCEPT ALL EXISTING CONDITIONS. DATES FOR SITE VISITS WILL BE POSTED IN THE CONTRACT DOCUMENTS AS POSTED ON THE FEDERAL BUSINESS OPPURTUNITIES WEBPAGE FOR THIS PROJECT. UNSCHEDULED VISITS
WILL NOT BE ALLOWED.
5. DO NOT PAINT ANY CAULKING OR SEALANTS WHICH ARE SUBJECT TO MOVEMENT - CONTROL JOINTS SHALL BE CAULKED AFTER PAINT AND SPECIAL COATING APPLICATIONS. PROVIDE CAULKING OR
SEALANTS IN COLORS WHICH MATCH ADJACENT FINISHED SURFACE COLORS.
6. VERIFY ALL CONDITIONS AND DIMENSIONS IN THE FIELD BEFORE FABRICATING ANY MATERIALS.
7. IT IS THE INTENT OF THE DOCUMENTS TO INDICATE COMPLETE AND OPERATIONAL SYSTEMS (I.E.
STRUCTURAL, HVAC, PLUMBING, ELECTRICAL, ETC.) THE CONTRACTOR SHALL PROVIDE THE SYSTEMS AS OPERATIONAL SYSTEMS WHICH COMPLY WITH APPLICABLE CODES AND REGULATIONS. THIS NOTE SHALL BE LIMITED TO THE SYSTEMS AS INDICATED BY THE DOCUMENTS AND SHALL NOT INCLUDE CHANGES TO
THE SYSTEMS WHICH ALTER INDICATED CAPACITIES, OPERATIONAL CHARACTERISTICS, ETC.
8. THE GENERAL CONTRACTOR SHALL VERIFY THE SIZES OF ALL EQUIPMENT OR FIXTURES TO BE INSTALLED IN THE BUILDING THROUGH THE SUBMITTAL PROCESS, AND SHALL MAKE SPECIAL PROVISIONS FOR INSTALLATION OF ANY EQUIPMENT WHICH IS TOO LARGE TO FIT THROUGH A FINISHED OPENING.
9. ALL CONTRACTORS SHALL BE RESPONSIBLE TO PATCH AND REPAIR ALL SURFACES WHERE EXISTING
CONSTRUCTION IS REMOVED OR DISTURBED BY WORK UNDER THEIR CONTRACT.
10. ALL SUSPENDED ITEMS SUCH AS CEILINGS, DUCTS, PIPES, CONDUITS, ETC., SHALL BE SUSPENDED (ATTACHED) DIRECTLY TO STRUCTURE AND SHALL NOT BE ATTACHED OR ANCHORED TO EXISTING
PLASTER, ACOUSTIC TILE, ETC.
11. NEW PENETRATIONS SUCH AS DUCTS, CONDUITS, PIPING, ELECTRICAL OUTLETS, LIGHT SWITCHES, RECESSED DEVICES OR ITEMS, HOLES, VOIDS, CRACKS, ETC. IN MODIFIED AND NEW CORRIDOR WALLS, SMOKE PARTITIONS, AND FLOOR SLABS SHALL BE SEALED TO PREVENT PASSAGE OF ANY SMOKE, FLAME, GASES, ETC. AS INDICATED IN THE CONTRACT DOCUMENTS.
12. WHERE NEW CONSTRUCTION REQUIRES CORE DRILLING THROUGH EXISTING STRUCTURAL CONCRETE FLOOR SLABS, AND WALLS THE CONTRACTOR SHALL COORDINATE HIS DRILLING WORK TO AVOID DRILLING INTO A STRUCTURAL ELEMENT, INCLUDING JOISTS, BEAMS, COLUMNS, ETC. ALSO SEE
ELECTRICAL. DRAWINGS AND SPECIFICATIONS.
13. WHERE NEW CONSTRUCTION IS INDICATED TO BE INSTALLED IN EXISTING CONSTRUCTION, THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS FOR PROPER FIT AND FOR ACCESS INTO THE BUILDING
PRIOR TO SHOP DRAWING SUBMITTAL, ORDERING AND DELIVERING TO THE SITE.
14. FOR INFECTION CONTROL REASONS, WORK CONDUCTED IN THE CORRIDOR THAT DOES NOT GENERATE DUST MAY ONLY REMOVE UP TO 16 SQUARE FEET OF CEILING TILE AT ONCE. AS LONG AS THIS STANDARD IS FOLLOWED NEGATIVE AIR AND BARRIERS ARE NOT REQUIRED BY THE INFECTION CONTROL NURSES. IF DUST IS GENERATED AND GREATER THAN 16 SF OF CEILING TILES ARE DISTURBED AT ONCE THEN THE WORK AREA SHALL BE SEALED OFF WITH 6 MIL FIRE RETARDANT POLYETHYLENE AND NEGATIVE AIR PROVIDED. MAINTAIN 5' MINIMUM ACCESS IN CORRIDORS AT ALL TIMES. CLEAN THOROUGHLY PRIOR TO COMPLETION OF A GIVEN WORK AREA BY HEPA VACUUM AND WET MOP. REFER TO SPECIFICATION 01 35
26 FOR ADDITIONAL INFORMATION.
D P # _ _
LP
PB
R
T
PB
S
S
R
VFD
ELECTRICAL ABBREVIATIONS
IMC INTERMEDIATE METAL CONDUIT
J-BOX JUNCTION BOX
kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWH KILOWATT HOUR kWHM KILOWATT HOUR METER
LV LOW VOLTAGE
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NEUT OR N NEUTRAL
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OL OVERLOAD
PB PANELBOARD
PH PHASE
PNL PANEL
PT POTENTIAL TRANSFORMER
PWR POWER
REC RECESSED
RECPT RECEPTACLE
SCC SHORT CIRCUIT CAPACITY
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VOLT VOLTAGE
W WATT
WP WEATHERPROOF
XFMR TRANSFORMER
FUSE WITH RATING
NORMALLY CLOSED RELAY CONTACT
NORMALLY OPEN RELAY CONTACT
MOLDED CASE CIRCUIT BREAKER
LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER
SWITCH AND FUSE UNIT
FUSED DRAWOUT POTENTIAL TRANSFORMER
ELECTRICAL SYMBOLS - DIAGRAM
MOTOR, SINGLE-PHASE
MOTOR, THREE-PHASE
DELTA CONNECTION
TRANSFORMER
WYE CONNECTION
EARTH GROUND
JUNCTION BOX
PULL BOX
FUSIBLE LINK
BATTERY
RELAY
50 = INSTANTANEOUS OVERCURRENT OR RATE-OF-RISE
51 = AC-TIME OVERCURRENT
67 = AC-DIRECTIONAL OVERCURRENT
86 LOCKING OUT
DISCONNECT SWITCH, FUSED
DISCONNECT SWITCH, UNFUSED
STARTER, COMBINATION WITH DISCONNECT SWITCH
STARTER OR MOTOR CONTROLLER
METER
AMMETER
VOLTMETER
WATTMETER
WATT-HOUR METER
DISCONNECT SWITCH, FUSED
DISCONNECT SWITCH, UNFUSED
STARTER, COMBINATION WITH DISCONNECT SWITCH
STARTER OR MOTOR CONTROLLER
CONDUIT TERMINATED 6" [152mm] AFF IN STANDARD BOX FOR
EXTENSION TO EQUIPMENT AS DIRECTED.
CONDUIT TERMINATED W/COUPLING (FLUSH W/FINISHED FLOOR)
FOR EXTENSION TO EQUIPMENT AS DIRECTED.
ELECTRICAL SYMBOLS - POWER PLAN
JUNCTION BOX
TRANSFORMER, PLAN
MOTOR, SINGLE-PHASE
MOTOR, THREE-PHASE
WYE CONNECTION
DUCT, CELL FLOOR HEADER
DUCT, TROLLEY
DUCT, UNDERFLOOR JUNCTION BOX
EARTH GROUND
LADDER CABLE TRAY
BRANCH CIRCUIT HOMERUN. LINES INDICATE NUMBER OF
CIRCUITS, NEUTRAL, AND SWITCH LEG CONDUCTORS. ONE
SEPARATE GREEN GROUNDING CONDUCTOR SHALL BE PROVIDED
FOR EACH HOMERUN; NOT SHOWN
PULL BOX
WIREWAY
RIGID CONDUIT LINE = RC
BUSWAY
FLOOR OUTLET, DATA COMMUNICATION
OUTLET, DATA COMMUNICATION
PUSH BUTTON
DISTRIBUTION PANEL
LIGHTING PANEL
PANELBOARD CABINET, FLUSH MOUNTED
PANELBOARD CABINET, SURFACE MOUNTED
RECEPTACLE, CLOCK HANGER
RECEPTACLE, DUPLEX
RECEPTACLE, DUPLEX ON EMERGENCY POWER
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER
RECEPTACLE, QUADRAPLEX
RECEPTACLE, SINGLE
RECEPTACLE, SINGLE WITH SWITCH
RECEPTACLE, SPECIAL PURPOSE
A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.
B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.
C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.
D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.
E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.
F = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.
G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R.
H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.
RECEPTACLE, SWITCHED DUPLEX
DIRECT BURIAL CABLE = DB
POWER DUCT = P
DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE, GROUNDING
TYPE, 20A, W/#12 CONDUCTORS IN FLEXIBLE CORD (CENTER LINE
OF OUTLET: 6'-6" [1981mm] AFF. MINIMUM).
ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" [610mm] CENTERS OR AS DESIGNATED ON DRAWINGS), MTD 3'-6" [1067mm] AFF OR AS
INDICATED.
3-GANG COMPARTMENT BOX IN FLOOR FOR TELEPHONE, DATA &
RECEPTACLE.
RELAY; LETTER INDICATES RELAY TYPE
50 = INSTANTANEOUS OVERCURRENT OR RATE-OF-RISE
51 = AC-TIME OVERCURRENT
67 = AC-DIRECTIONAL OVERCURRENT
86 = LOCK OUT
ELECTRICAL SYMBOLS - POWER PLAN
SWITCH
F = FUSED SWITCH K = KEY OPERATED
L = LOCK LM= LOW VOLTAGE MASTER
M = MANUAL MOTOR STARTING MC= MOMENTARY CONTACT
MP= MOTOR SNAP WITH PILOT LIGHT P = WITH PILOT LIGHT
(THERMAL TYPE)
PB= PUSH BUTTON STATION RC= REMOTE CONTROL
WP= WEATHER PROOF X = EXPLOSION PROOF
VARIABLE FREQUENCY DRIVE
A. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE
CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE
GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.
B. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF
EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE
DIVIDERS BETWEEN DEVICES.
C. COORDINATE ALL SHUT-DOWNS OF EXISTING ELECTRICALSYSTEMS WITH
OWNER A MINIMUM OF FOURTEEN (14) WORKING DAYS IN ADVANCE. ALL
SHUT-DOWNS SHALL OCCUR DURING WEEKENDS OR UNOCCUPIED TIMES,
INCLUDE ALL PREMIUM TIME CHARGES IN BID.
D. ALL NOISE GENERATING OPERATIONS, INCLUDING CUTTING OF CEILINGS,
WALLS AND FLOORS, CORING, DRILLING,ETC. SHALL BE SCHEDULED ON
WEEKENDS OR BETWEEN 8:00PM AND 7:00AM ON WEEKDAYS. INCLUDE
ALL PREMIUM TIME CHARGES IN BID.
E. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND
REPLACEMENT OF CEILINGS REQUIRED FOR ELECTRICAL WORK.
ELECTRICAL CONTRACTOR SHALL REPLACE ANY DAMAGED CEILING
MATERIAL.
F. ALL NEW WALL MOUNTED ELECTRICAL DEVICES ARE TO BE INSTALLED
FLUSH IN WALL UNLESS OTHERWISE NOTED. ALL ELECTRICAL CONDUIT
SHALL BE CONCEALED BEHIND FINISHED WALLS AND ABOVE FINISHED
CEILING UNLESS OTHERWISE NOTED. THE COST TO CUT AND PATCH
WALLS SHALL BE THE RESPONSIBILITY OF THE TRADE REQUIRING THE
CUTTING.
G. ALL WORK SHALL BE PERFORMED IN STRICT CONFORMANCE WITH THE
PHASING REQUIREMENTS OF THE PROJECT. ALL COSTS ASSOCIATED
WITH THESE REQUIREMENTS SHALL BE INCLUDED IN THE BID SUBMITTAL.
REFER TO ARCHITECTURAL PLANS FOR PHASING AND AREAS
DESIGNATED AS "OFF HOURS" CONSTRUCTION AREAS.
H. DEFINITION: "PROVIDE" - FURNISH, INSTALL AND CONNECT COMPLETE.
A. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING
DEVICES, CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED,
COMPLETELY CUT/CAP CONDUITS AT THE AREA OF WORK PERIMETER
AND REMOVE CONDUIT WITHIN THE WORK AREA, DISCONNECT WIRING AT
THE OVERCURRENT PROTECTIVE DEVICE AND REMOVE WIRING
COMPLETELY FROM THE ABANDONED CONDUITS.
B. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE
OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL
ABANDONED WIRING.
C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND
CONDUCTORS PASSING THROUGH RENOVATED AREAS AND SERVICING
UNDISTURBED AREAS.
GENERAL NOTES
GENERAL NOTES - DEMOLITION
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
AFC ABOVE FINISHED COUNTER,
AUTOMATIC FREQUENCY CONTROL, OR
AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
AMP AMPERE
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
BAT BATTERY
BC BARE COPPER
BFF BELOW FINISH FLOOR
BRKR BREAKER
BYP BY PASS
C CONDUIT
CAB CABINET
CAP CAPACITY
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CPT CONTROL POWER TRANSFORMER
CT CURRENT TRANSFORMER
CU COPPER
CU FT CUBIC FEET
CUR CURRENT
DC DIRECT CURRENT
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
EG EQUIPMENT GROUND
ELEV ELEVATOR
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EXIST EXISTING
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FU SW FUSED SWITCH
G GROUND
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
Drawing Title
Approved: Project Director
Location
Building Number
Project Tit le
Checked DrawnDate
Project No.
Drawing Number
D w g . o f o n e -e ig h th i n c h o n e f o o t o n e
-q u a rt e r in c h o n e f o o t th re e
-e ig h th s i n c h o n e f o o t o n e
-h a lf i n c h o n e f o o t th re e
-q u a rt e rs i n c h o n e fo o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
FFE, Inc.
420 Springfield Pike Cincinnati OH, 45215 513-522-0956
Cincinnati, Ohio
Upgrade UPS and AC in Computer Room
06/09/17
ELECTRICAL LEGENDS
E001
539-18-202
RG JK 2 13
Revisions Date
0 ISSUED FOR CONSTRUCTION 06-09-2017
NFPA 2017
CHAPTER 6 - SPECIAL EQUIPMENT
ARTICLE 645 - INFORMATION TECHNOLOGY EQUIPMENT
645.5 SUPPLY CIRCUITS AND INTERCONNECTING CABLES
645.5(A) BRANCH CIRCUIT CONDUCTORS SHALL HAVE AN AMPACITY OF NOT
LESS THAN 125% OF THE TOTAL CONNECTED LOAD.
645.5(B)(1) POWER SUPPLY CORDS SHALL NOT EXCEED 15 FEET IN LENGTH.
645.5(B)(2) POWER CORDS SHALL BE LISTED AND OF A TYPE PERMITTED FOR
USE ON LISTED IT EQUIPMENT OR CONSTRUCTED FROM LISTED
CORD WITH LISTED ATTACHMENT PLUGS AND CORD CONNECTORS
OF A TYPE PERMITTED FOR IT EQUIPMENT.
645.5(C) INTERCONNECTING CABLES SHALL BE LISTED CABLES OR
ASSEMBLIES.
645.5(D) WHERE EXPOSED TO PHYSICAL DAMAGE, SUPPLY CIRCUITS AND
INTERCONNECTING CABLES SHALL BE PROTECTED FROM HARM.
645.5(E) FLOOR OPENINGS SHALL MINIMIZE THE ENTRANCE OF DEBRIS
BENEATH THE FLOOR.
645.5(E)(1)(A) BRANCH CIRCUIT SUPPLY CONDUCTORS SHALL BE INSTALLED IN
ACCORDANCE WITH THE REQUIREMENTS OF 300.11.
645.5(E)(1)(B) IN ADDITION TO THE WIRING METHODS OF 300.22(C), THE
FOLLOWING WIRING METHODS ARE ALSO PERMITTED: (1) RIGID
METAL CONDUIT, (2) RIGID NONMETALLIC CONDUIT, (3)
INTERMEDIATE METAL CONDUIT, (4) ELECTRICAL METALLIC
TUBING, (5) ELECTRICAL NONMETALLIC TUBING, (6) METAL WIREWAY,
(7) NONMETALLIC WIREWAY, (8) SURFACE METAL RACEWAY
WITH METAL COVER, (9) SURFACE NONMETALLIC RACEWAY, (10)
FLEXIBLE METAL CONDUIT, (11) LIQUIDTIGHT FLEXIBLE METAL
CONDUIT, (12) LIQUIDTIGHT NONMETALLIC CONDUIT, (13) TYPE MI
CABLE, (14) TYPE MC CABLE, (15) TYPE AC CABLE, (16) ASSOCIATED
METALLIC AND NONMETALLIC BOXES OR ENCLOSURES, (17) TYPE TC
POWER AND CONTROL TRAY CABLE.
645.10 DISCONNECTING MEANS
645.10(B) REMOTE DISCONNECTING CONTROLS SHALL NOT BE REQUIRED FOR
CRITICAL OPERATIONS DATA SYSTEMS WHEN ALL OF THE
FOLLOWING ARE MET:
(1) AN APPROVED PROCEDURE HAS BEEN ESTABLISHED AND
MAINTAINED FOR REMOVING POWER AND AIR MOVEMENT WITHIN
THE ROOM OR ZONE. (2) QUALIFIED PERSONNEL ARE
CONTINUOUSLY AVAILABLE TO ADVISE EMERGENCY RESPONDERS
AND TO INSTRUCT THEM OF DISCONNECTING METHODS. (3) A
SMOKE-SENSING FIRE DETECTION SYSTEM IS IN PLACE. (4) AN
APPROVED FIRE SUPPRESSION SYSTEM SUITABLE FOR THE
APPLICATION IS IN PLACE. (5) CABLES INSTALLED UNDER A RAISED
FLOOR, OTHER THAN BRANCH CIRCUIT WIRING, AND POWER CORDS
ARE INSTALLED IN COMPLIANCE WITH 645.5(E)(2) OR (E)(3), OR IN
COMPLIANCE WITH TABLE 645.10(B)(5).
645.11 UPS SYSTEMS INSTALLED WITHIN THE INFORMATION TECHNOLOGY
EQUIPMENT ROOM, AND THEIR SUPPLY AND OUTPUT CIRCUITS,
SHALL COMPLY WITH 645.10. THE DISCONNECTING MEANS SHALL
ALSO DISCONNECT THE BATTERY FROM ITS LOAD.
645.15 ALL EXPOSED NON-CURRENT CARRYING METAL PARTS OF AN IT
SYSTEM SHALL BE BONDED TO THE EQUIPMENT GROUNDING
CONDUCTOR IN ACCORDANCE WITH PARTS I, V, VI, VII, AND VIII OF
ARTICLE 250 OR SHALL BE DOUBLE INSULATED.
645.16 EACH UNIT OF AN IT SYSTEM SUPPLIED BY A BRANCH CIRCUIT SHALL
BE PROVIDED WITH A MANUFACTURER'S NAMEPLATE, WHICH SHALL
ALSO INCLUDE THE INPUT POWER REQUIREMENTS FOR VOLTAGE,
FREQUENCY, AND MAXIMUM RATED LOAD IN AMPERES.
645.18 SURGE PROTECTION SHALL BE PROVIDED FOR CRITICAL
OPERATIONS DATA SYSTEMS.
645.27 OVERCURRENT DEVICES FOR CRITICAL OPERATION DATA SYSTEMS
SHALL BE SELECTIVELY COORDINATED WITH ALL SUPPLY-SIDE
OVERCURRENT PROTECTIVE DEVICES.
CODE COMPLIENCE
CHAPTER 7 - SPECIAL CONDITIONS
ARTICLE 700 EMERGENCY SYSTEMS
700.8 A LISTED SURGE PROTECTION DEVICE SHALL BE INSTALLED IN ALL
EMERGENCY SYSTEM SWITCHBOARDS AND PANELBOARDS.
700.32 EMERGENCY SYSTEM OVERCURRENT DEVICES SHALL BE SELECTIVELY
COORDINATED WITH ALL SUPPLY-SIDE OVERCURRENT PROTECTIVE
DEVICES.
DN
3 1/2"ø
3 1/2"ø
IE3 IE7
EXISTING 3-1/2" C.
NOTE: EXISTING SUB-FLOOR CONDUIT
ROUTING FROM 1E7 TO 80kVA UPS
(APPROXIMATE).
B013B
TRANSFORMER ROOM
B013A
ELECTRIC ROOM
C-1-7
CORRIDOR
B107A
TELE CLOS.
C-1-9A
CORRIDOR
C-1-7A
CORRIDOR
B101
RETAIL STORE
A128
FOOD SERVICE
A. ALL ELECTRIC WIRING & CONDUITS SHALL BE INSTALLED PER LOCAL CODES AND AS DIRECTED BY
THE LOCAL ELECTRIC CODE OFFICIAL. VERIFY ALL REQUIREMENTS PRIOR TO ROUGH-IN.
B. SUPPLY ARC FAULT WARNING LABELS AS REQUIRED BY N.E.C. 110.16
C. ALL MULTI-WIRE CIRCUITS SHALL HAVE COMMON TRIP OVER-CURRENT PROTECTION DEVICES.
D. ROUTING OF CONDUIT IS ESTIMATED. FIELD VERIFICATION OF CONDUIT ROUTING & PULLBOX
LOCATIONS IS REQUIRED.
E. PROVIDE FIRESTOPPING AT ALL RATED WALL PENETRATIONS - SEE PLANS FOR RATED WALLS.
PROVIDE ACOUSTICAL WALL SEALANT AT ALL OTHER WALL PENETRATIONS.
F. CONTRACTOR TO PROTECT EXISTING INSTALLATIONS FROM DAMAGE. ANY DAMAGE TO EXISTING
FACILITY WILL BE REPAIRED AT CONTRACTOR'S EXPENSE.
GENERAL POWER NOTES:
Drawing Title
Approved: Project Director
Location
Building Number
Project Tit le
Checked DrawnDate
Project No.
Drawing Number
D w g . o f o n e -e ig h th i n c h o n e f o o t o n e
-q u a rt e r in c h o n e f o o t th re e
-e ig h th s i n c h o n e f o o t o n e
-h a lf i n c h o n e f o o t th re e
-q u a rt e rs i n c h o n e fo o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
FFE, Inc.
420 Springfield Pike Cincinnati OH, 45215 513-522-0956
Cincinnati, Ohio
Upgrade UPS and AC in Computer Room
06/09/17
PARTIAL FIRST FLOOR PLAN
EP101
539-18-202
RG JK
SCALE: 1/8" = 1'-0"
PARTIAL FIRST FLOOR ELECTRIC PLAN - EXISTING UPS POWER (REFERENCE ONLY)
3 13 Revisions Date
0 ISSUED FOR CONSTRUCTION 06-09-2017
UP
A. ALL ELECTRIC WIRING & CONDUITS SHALL BE INSTALLED PER LOCAL CODES AND AS DIRECTED BY
THE LOCAL ELECTRIC CODE OFFICIAL. VERIFY ALL REQUIREMENTS PRIOR TO ROUGH-IN.
B. SUPPLY ARC FAULT WARNING LABELS AS REQUIRED BY N.E.C. 110.16
C. ALL MULTI-WIRE CIRCUITS SHALL HAVE COMMON TRIP OVER-CURRENT PROTECTION DEVICES.
D. ROUTING OF CONDUIT IS ESTIMATED. FIELD VERIFICATION OF CONDUIT ROUTING & PULLBOX
LOCATIONS IS REQUIRED.
E. PROVIDE FIRESTOPPING AT ALL RATED WALL PENETRATIONS - SEE PLANS FOR RATED WALLS.
PROVIDE ACOUSTICAL WALL SEALANT AT ALL OTHER WALL PENETRATIONS.
F. CONTRACTOR TO PROTECT EXISTING INSTALLATIONS FROM DAMAGE. ANY DAMAGE TO EXISTING
FACILITY WILL BE REPAIRED AT CONTRACTOR'S EXPENSE.
GENERAL POWER NOTES:
PHASING NOTES:
L
L
M
M
N
N
3 3
4a 4a
5 5
6 6
7 7
J
J
Jb
Jb
UP TO ELECTRIC
ROOM A436B
A338B
ELECTRIC
A338
SERVICE LOBBY
CORE ABANDONED WINDOW
HEADER - DO NOT PENETRATE BEAM
SEAL PENETRATION AT
EXISTING FIRE WALLS
TRANSITION TO CENTER OF CORRIDOR
AND TIGHT TO STRUCTURE BEFORE
EXISTING FIRE DOORS
RUN BETWEEN CABLE TRAY
AND CHILLED WATER PIPING
RUN PARALLEL TO EXISTING BANK OF CONDUIT.
SEAL PENETRATION AT
EXISTING FIRE WALLS
MATCH LINE
BB
6 7
4.7
4.7
AA
A.6A.6
7'-8"B.O.C.
10' 0"B.O.S.
8'-0"B.O.C.
10'-6"B.O.S.
9'-0"B.O.C.
11 '-9"B.O.S.
M
M
2 2
3 3
(4) 600 MCM, (1) #1 GND. IN 3" CONDUIT
- REUSE EXISTING CONDUIT SUPPORTS
WHERE PRACTICABLE
- VERIFY STRUCTURAL CAPACITY PRIOR
EXISTING CONDUIT
CORE DRILL NEAR EXISTING PENETRATION
EXISTING 12" CONCRETE WALL
RUN CONDUIT TIGHT TO
EXISTING STRUCTURE
100KVA UPS/BATTERY PACK
A3002-2
MECHANICAL-2
TRANSFORMER
DPF3
EDPEQ3
CDP3
DPLF3
EEQM3
1-EF5
1-EF4
1-EF3
1-EF2
DISCONNECT
TR-UPS2
MATCH LINE
EDPLEQ3
UPS2
BB
CC
4.7
4.7
AA
A.6A.6
2" HOUSEKEEPING PAD
21'-7"B.O.S.21'-7"B.O.S.
10'-5"B.O.S.
EDPEQ3 PANEL
UPS2
TR-UPS2 DISCONNECT
FROM TO
UPS2
TR-UPS2
UPS2 PANEL 1
CABLE SIZE
REFER TO SINGLE LINE
REFER TO SINGLE LINE
REFER TO SINGLE LINE
CABLE TYPE
THWN-2
THWN-2
THWN-2
CABLE LENGTH
35'
25'
210'
CABLE SCHEDULE
UPS2 PANEL 1 UPS2 PANEL 2 REFER TO SINGLE LINE THWN-2 5'
Drawing Title
Approved: Project Director
Location
Building Number
Project Tit le
Checked DrawnDate
Project No.
Drawing Number
D w g . o f o n e -e ig h th i n c h o n e f o o t o n e
-q u a rt e r in c h o n e f o o t th re e
-e ig h th s i n c h o n e f o o t o n e
-h a lf i n c h o n e f o o t th re e
-q u a rt e rs i n c h o n e fo o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
FFE, Inc.
420 Springfield Pike Cincinnati OH, 45215 513-522-0956
Cincinnati, Ohio
Upgrade UPS and AC in Computer Room
06/09/17
PHASE 1 PARTIAL THIRD FLOOR
PLAN
EP102
539-18-202
RG JK
PHASE 1
1. PROVIDE 100KVA UPS AND ASSOCIATED TRANSFORMER. INSTALL UPON 2" POURED CONCRETE PAD WITHIN MECHANICAL ROOM A3002-2.
FURNISH ALL ASSOCIATED COMPONENTS AND PROVIDE INSTALLATION, PROGRAMMING, STARTUP, ASSOCIATED CONTROL WIRING AND ALL
ASSOCIATED TERMINATIONS.
2. PROVIDE 200A CIRCUIT BREAKER IN PANEL EDPEQ3 - VERIFY CAPACITY. ROUTE FEEDER IN CONDUIT FROM NEW CIRCUIT BREAKER TO UPS.
3. PROVIDE 125kVA, 480V-208Y/120V TRANSFORMER IN MECHANICAL ROOM A3002-2.
4. PROVIDE 600V 200A 3P NON-FUSED DISCONNECT (14,000AIC RATED). ROUTE CONDUIT AND WIRE TO SERVE TR-UPS2 PRIMARY.
5. PROVIDE CONDUIT AND WIRE FROM TRANSFORMER TO UPS INPUT BREAKER.
6. PROVIDE CONDUIT AND WIRE FROM UPS SHUNT TRIP OUTPUT BREAKER TO DISTRIBUTION PANELS IN ROOM A4037C ON THE 4TH FLOOR.
REFER TO SHEET EP103.
4 13
SCALE: 1/4" = 1'-0"
ELECTRICAL POWER THIRD FLOOR PLAN - PANEL EDPEQ3
Revisions Date
0 ISSUED FOR CONSTRUCTION 06-09-2017
1 ADDENDUM 1 11-03-2017
06-09-2017
ABBREVIATIONS
B.O.C. = BOTTOM OF CEILING
B.O.S. = BOTTOM OF STRUCTURE
A. ALL ELECTRIC WIRING & CONDUITS SHALL BE INSTALLED PER LOCAL CODES AND AS DIRECTED BY
THE LOCAL ELECTRIC CODE OFFICIAL. VERIFY ALL REQUIREMENTS PRIOR TO ROUGH-IN.
B. SUPPLY ARC FAULT WARNING LABELS AS REQUIRED BY N.E.C. 110.16
C. ALL MULTI-WIRE CIRCUITS SHALL HAVE COMMON TRIP OVER-CURRENT PROTECTION DEVICES.
D. ROUTING OF CONDUIT IS ESTIMATED. FIELD VERIFICATION OF CONDUIT ROUTING & PULLBOX
LOCATIONS IS REQUIRED.
E. PROVIDE FIRESTOPPING AT ALL RATED WALL PENETRATIONS - SEE PLANS FOR RATED WALLS.
PROVIDE ACOUSTICAL WALL SEALANT AT ALL OTHER WALL PENETRATIONS.
F. CONTRACTOR TO PROTECT EXISTING INSTALLATIONS FROM DAMAGE. ANY DAMAGE TO EXISTING
FACILITY WILL BE REPAIRED AT CONTRACTOR'S EXPENSE.
GENERAL POWER NOTES:
PHASING NOTES:
L
L
M
M
7 7
10 10
11 11
12 12
Kb
Kb
AC
SW
LAN RACK 3
LAN RACK 2
LAN RACK 1
PLASMA
CRAC-3
C R
A C
-2
PLASMA
PLASMA
WAN 2
WAN 1
EXISTING
80kVA UPS1
EXISTING 3-1/2"C. FROM SWITCHBOARD "1E7"
4A1
4A2
E4A
A436B
ELECTRIC CL
A437C
COMPUTER RM
NEW
PANELBOARD AND
DISTRIBUTION PANEL
UPS2 PANEL1
UPS2 PANEL 2
EX. PANEL #1
EX. PANEL #2
TO PANEL EPEDQ3 ON
LEVEL 3 MECHANICAL ROOM A3002-2, SEE
SHEET EP102 FOR CONTINUATION
SEAL PENETRATION AT
EXISTING FIRE WALLS
SEAL PENETRATION AT
EXISTING FIRE WALLS
NEW
CABLE
SUPPORTS
EPSMS
Drawing Title
Approved: Project Director
Location
Building Number
Project Tit le
Checked DrawnDate
Project No.
Drawing Number
D w g . o f o n e -e ig h th i n c h o n e f o o t o n e
-q u a rt e r in c h o n e f o o t th re e
-e ig h th s i n c h o n e f o o t o n e
-h a lf i n c h o n e f o o t th re e
-q u a rt e rs i n c h o n e fo o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
FFE, Inc.
420 Springfield Pike Cincinnati OH, 45215 513-522-0956
Cincinnati, Ohio
Upgrade UPS and AC in Computer Room
06/09/17
POWER PLAN - PHASE 1 PARTIAL
FOURTH FLOOR IT ROOM A437C
EP103
539-18-202
RG JK
PHASE 1
1. PROVIDE AND INSTALL NEW DISTRIBUTION PANEL AND PANELBOARD AS INDICATED ON EP603.
2. PROVIDE AND INSTALL CONDUIT AND WIRE FROM UPS OUTPUT BREAKER TO NEW DISTRIBUTION PANELS AS INDICATED ON EP102.
3. PROVIDE AND INSTALL APPROXIMATELY 24" LONG SECTIONS OF UNISTRUT TO SUPPORT AND ORGANIZE THE POWER CABLES. UNISTRUT IS TO BE
SUPPORTED FROM THE RAISED FLOOR SUPPORTS. INSTALL ON APPROXIMATELY 4'-0" CENTERS.
SCALE: 1/4" = 1'-0"
PHASE 1 FOURTH FLOOR COMPUTER ROOM POWER PLAN
5 13 Revisions Date
0 ISSUED FOR CONSTRUCTION 06-09-2017
1 ADDENDUM 1 11-03-2017
AC
SW
LAN RACK 3
LAN RACK 2
LAN RACK 1
PLASMA
AC-2
A C
-1
PLASMA
PLASMA
WAN 2
WAN 1
EXISTING
80kVA UPS1
EXISTING 3-1/2"C. FROM SWITCHBOARD "1E7"
A436B
ELECTRIC CL
A437C
COMPUTER RM
NEW
CABLE SUPPORT
ROUTING
RACK 1 ATS-A
UPS2 PANEL 2
UPS2 PANEL1
RACK 2 ATS-A
RACK 3 ATS
RACK 5 ATS-A
RACK 7 ATS-B
RACK 21 ATS-C
RACK 20 ATS-C
RACK 19 ATS-D
RACK 16 ATS-A
RACK 11 ATS-A
RACK 10 ATS-A
RACK 4 ATS
RACK 6 ATS-A
RACK 7 ATS-A
RACK 9 ATS-B
RACK 23 ATS-A
RACK 22 ATS-A
RACK 19 ATS-C
RACK 17 ATS
RACK 16 ATS-B
RACK 15 ATS
RACK 14 ATS
RACK 12 ATS-A
RACK 6 ATS-B
RACK 1 ATS-B
RACK 5 ATS-B
RACK 9 ATS-A
RACK 9 ATS-C
RACK 9 ATS-D
RACK 10 ATS-B
RACK 11 ATS-B
RACK 12 ATS-B
RACK 12 ATS-C
RACK 20 ATS-B
RACK 20 ATS-A
RACK 19 ATS-A
RACK 19 ATS-B
RACK 21 ATS-B
RACK 22 ATS-B
RACK 23 ATS-B
RACK 24 ATS
RACK 25 ATS-A
RACK 25 ATS-D
RACK 25 ATS-B
RACK 25 ATS-C
RACK 7 ATS-C
RACK 7 ATS-D
RACK 16 ATS-C
RACK 16 ATS-D
RACK 2 ATS-B
RACK 8 ATS
RACK 21 ATS-A
1 2 3 4 5 6 7 8 (TYP)
A. ALL ELECTRIC WIRING & CONDUITS SHALL BE INSTALLED PER LOCAL CODES AND AS DIRECTED BY
THE LOCAL ELECTRIC CODE OFFICIAL. VERIFY ALL REQUIREMENTS PRIOR TO ROUGH-IN.
B. SUPPLY ARC FAULT WARNING LABELS AS REQUIRED BY N.E.C. 110.16
C. ALL MULTI-WIRE CIRCUITS SHALL HAVE COMMON TRIP OVER-CURRENT PROTECTION DEVICES.
D. ROUTING OF CONDUIT IS ESTIMATED. FIELD VERIFICATION OF CONDUIT ROUTING & PULLBOX
LOCATIONS IS REQUIRED.
E. PROVIDE FIRESTOPPING AT ALL RATED WALL PENETRATIONS - SEE PLANS FOR RATED WALLS.
PROVIDE ACOUSTICAL WALL SEALANT AT ALL OTHER WALL PENETRATIONS.
F. CONTRACTOR TO PROTECT EXISTING INSTALLATIONS FROM DAMAGE. ANY DAMAGE TO EXISTING
FACILITY WILL BE REPAIRED AT CONTRACTOR'S EXPENSE.
GENERAL POWER NOTES:
PHASING NOTES:
RACK 1 ATS-A
RACK 1 ATS-B
RACK 2 ATS-A
RACK 2 ATS-B
RACK 4 ATS-A
RACK 5 ATS-A
RACK 5 ATS-B
RACK 6 ATS-A
RACK 6 ATS-B
RACK 7 ATS-A
RACK 7 ATS-B
RACK 7 ATS-C
RACK 7 ATS-D
RACK 8 ATS
RACK 9 ATS-A
ATS NAME VOLTAGE PANEL
RACK 9 ATS-B
RACK 9 ATS-C
RACK 9 ATS-D
RACK 10 ATS-A
RACK 10 ATS-B
RACK 11 ATS-A
RACK 11 ATS-B
RACK 12 ATS-A
RACK 12 ATS-B
RACK 12 ATS-C
RACK 14 ATS
RACK 15 ATS
RACK 16 ATS-A
RACK 16 ATS-B
RACK 16 ATS-C
RACK 16 ATS-D
RACK 17 ATS
RACK 19 ATS-A
RACK 19 ATS-B
RACK 19 ATS-C
RACK 19 ATS-D
RACK 20 ATS-A
RACK 20 ATS-B
RACK 20 ATS-C
RACK 21 ATS-A
RACK 21 ATS-B
RACK 22 ATS-A
RACK 22 ATS-B
RACK 23 ATS-A
RACK 23 ATS-B
208V
208V
208V
208V
120V
208V
208V
120V
208V
120V
208V
120V
120V
120V
120V
120V
120V
120V
208V
208V
208V
208V
120V
120V
120V
120V
120V
208V
120V
208V
120V
120V
208V
208V
208V
120V
208V
208V
208V
120V
208V
120V
120V
120V
120V
UPS2 PANEL 1
UPS2 PANEL 1
UPS2 PANEL 1
UPS2 PANEL 2
UPS2 PANEL 1
UPS2 PANEL 1
UPS2 PANEL 2
UPS2 PANEL 1
UPS2 PANEL 2
UPS2 PANEL 2
UPS2 PANEL 1
UPS2 PANEL 1
UPS2 PANEL 2
UPS2 PANEL 2
UPS2 PANEL 2
UPS2 PANEL 1
UPS2 PANEL 1
UPS2 PANEL 2
UPS2 PANEL 1
UPS2 PANEL 2
UPS2 PANEL 1
UPS2 PANEL 2
UPS2 PANEL 1
UPS2 PANEL 2
UPS2 PANEL 1
UPS2 PANEL 2
UPS2 PANEL 2
UPS2 PANEL 1
UPS2 PANEL 1
RACK 24 ATS
RACK 25 ATS-A
RACK 25 ATS-B
RACK 25 ATS-C
120V
120V
120V
120V
RACK 25 ATS-D 120V
UPS2 PANEL 2
UPS2 PANEL 2
UPS2 PANEL 2
UPS2 PANEL 2
UPS2 PANEL 1
UPS2 PANEL 2
UPS2 PANEL 1
UPS2 PANEL 1
UPS2 PANEL 2
UPS2 PANEL 2
UPS2 PANEL 1
UPS2 PANEL 1
UPS2 PANEL 1
UPS2 PANEL 2
UPS2 PANEL 1
UPS2 PANEL 2
UPS2 PANEL 2
UPS2 PANEL 1
UPS2 PANEL 2
UPS2 PANEL 2
UPS2 PANEL 2
CIRCUIT
21, 23
37,39
30, 32
18, 20
34, 36
39, 41
36, 38
24, 26
8, 10
4, 6
8, 10
4, 6
40, 42
17, 19
7, 9
13, 15
31, 33
16, 18
28, 30
35, 37
31, 33
RECEPTACLE
NEMA L6-30
NEMA L6-30
NEMA L6-30
NEMA L6-30
NEMA L5-20
NEMA L6-30
NEMA L6-30
NEMA L5-30
NEMA L6-30
NEMA L5-20
NEMA L6-30
NEMA L5-30
NEMA L5-20
NEMA L5-20
NEMA L5-30
NEMA L5-30
NEMA L5-30
NEMA L5-30
NEMA L6-30
NEMA L6-30
NEMA L6-30
NEMA L6-30
NEMA L5-20
NEMA L5-30
NEMA L5-30
NEMA L5-20
NEMA L5-20
NEMA L6-30
NEMA L5- 20
NEMA L6-30
NEMA L5-20
NEMA L5-20
NEMA L6-20
NEMA L6-20
NEMA L6-20
NEMA L5-30
NEMA L6-20
NEMA L6-20
NEMA L6-20
NEMA L5-20
NEMA L6-30
NEMA L5-30
NEMA L5-30
NEMA L5-30
NEMA L5-30
NEMA L5-20
NEMA L5-30
NEMA L5-30
NEMA L5-30
NEMA L5-30
CABLE SIZE
(2) #10 AWG / # 8 GND
(2) #12 AWG / #10 GND
CABLE TYPE
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
CABLE LENGTH
47' - 10"
47' - 2"
45' - 10"
44' - 11"
36' - 4"
26' - 1"
26' - 4"
27' - 8"
28' - 11"
30' - 0"
30' - 0"
30' - 7"
30' - 7"
31' - 9"
40' - 0"
40' - 0"
40' - 0"
40' - 0"
37' - 4"
36' - 7"
35' - 3"
34' - 5"
33' - 3"
33' - 3"
33' - 3"
22' - 11"
20' - 0"
9' - 5"
9' - 5"
9' - 5"
9' - 5"
7' - 3"
9' - 10"
9' - 10"
9' - 10"
9' - 10"
12' - 0"
12' - 0"
12' - 0"
13' - 11"
13' - 11"
13' - 11"
15' - 10"
15' - 10"
17' - 10"
21' - 2"
23' - 5"
23' - 5"
23' - 5"
23' - 5"
RACK 21 ATS-C 208V UPS2 PANEL 2 32, 34 NEMA L6-30 MC
17' - 10"
UPS2 PANELS 1 AND 2 CABLE SCHEDULE
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #12 AWG / #10 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #12 AWG / #10 GND
(2) #12 AWG / #10 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #12 AWG / #10 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #12 AWG / #10 GND
(2) #12 AWG / #10 GND
(2) #10 AWG / # 8 GND
(2) #12 AWG / #10 GND
(2) #10 AWG / # 8 GND
(2) #12 AWG / #10 GND
(2) #12 AWG / #10 GND
(2) #12 AWG / #10 GND
(2) #12 AWG / #10 GND
(2) #12 AWG / #10 GND
(2) #10 AWG / # 8 GND
(2) #12 AWG / #10 GND
(2) #12 AWG / #10 GND
(2) #12 AWG / #10 GND
(2) #12 AWG / #10 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #12 AWG / #10 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
Drawing Title
Approved: Project Director
Location
Building Number
Project Tit le
Checked DrawnDate
Project No.
Drawing Number
D w g . o f o n e -e ig h th i n c h o n e f o o t o n e
-q u a rt e r in c h o n e f o o t th re e
-e ig h th s i n c h o n e f o o t o n e
-h a lf i n c h o n e f o o t th re e
-q u a rt e rs i n c h o n e fo o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
FFE, Inc.
420 Springfield Pike Cincinnati OH, 45215 513-522-0956
Cincinnati, Ohio
Upgrade UPS and AC in Computer Room
06/09/17
POWER PLAN - PHASE 2 PARTIAL
FOURTH FLOOR IT ROOM A437C
EP104
539-18-202
RG JK
SCALE: 1/4" = 1'-0"
PHASE 2 FOURTH FLOOR COMPUTER ROOM POWER PLAN
PHASE 2
1. PROVIDE AND INSTALL NEW RACK AUTO TRANSFER SWITCHES AND POWER DISTRIBUTION UNITS IN EACH RACK. (SEE HEX NOTE 1 ON
PLANS)
2. PROVIDE AND INSTALL NEW CABLE FROM PANELS UPS2-1 AND UPS2-2 TO EACH RACK ATS IN ACCORDANCE WITH THE ASSOCIATED PANEL SCHEDULE. INSTALL NEW POWER CIRCUITS IN A NEAT AND ORGANIZED MANNER. SECURE TO NEW CABLE SUPPORTS USING CABLE ACCESSORIES THAT ARE EITHER METAL OR THAT ARE LISTED AS HAVING LOW SMOKE OR HEAT RELEASE PROPERTIES.
CONNECT NEW CIRCUITS TO ATS SECONDARY INPUT. (SEE HEX NOTE 2 ON PLANS)
3. VERIFY SECONDARY POWER IS AVAILABLE AT EACH ATS. (SEE HEX NOTE 3 ON PLANS)
4. CONNECT CONTROL CIRCUIT FROM EACH ATS AND EACH PDU TO LOCAL NETWORK. (SEE HEX NOTE 4 ON PLANS)
5. INSTALL ATS AND PDU MONITORING SOFTWARE IN HMI DESIGNATED BY VA IT DEPARTMENT. (SEE HEX NOTE 5 ON PLANS)
6. VERIFY CONTROL AND POWER FUNCTIONS FOR EACH ATS AND EACH PDU. (SEE HEX NOTE 6 ON PLANS)
7. COORDINATE WITH VA IT DEPARTMENT FOR SEQUENCING OF SWITCHING RACK EQUIPMENT OVER TO NEW RACK PDUs. (SEE HEX NOTE 7
ON PLANS)
8. AS EACH DEVICE IS ADDED TO A PDU, CHECK THE PDU POWER METER TO ENSURE THE CIRCUIT IS NOT OVERLOADED. IF THE LOAD
EXCEEDS 80% OF THE CAPACITY OF THE CIRCUIT, ADD AN ADDITIONAL CIRCUIT INCLUDING ATS AND PDU. FOR BIDDING PURPOSES, ASSUME NO MORE THAN TWO ADDITIONAL 120V, 30 AMP CIRCUITS. (SEE HEX NOTE 8 ON PLANS)
9. RACK 3 POWER FEED FROM UPS1 ONLY. EXISTING TO REMAIN. (SEE HEX NOTE 9 ON PLANS)
Revisions Date
6 13
PHASING NOTES:
A. ALL ELECTRIC WIRING & CONDUITS SHALL BE INSTALLED PER LOCAL CODES AND AS DIRECTED BY
THE LOCAL ELECTRIC CODE OFFICIAL. VERIFY ALL REQUIREMENTS PRIOR TO ROUGH-IN.
B. SUPPLY ARC FAULT WARNING LABELS AS REQUIRED BY N.E.C. 110.16
C. ALL MULTI-WIRE CIRCUITS SHALL HAVE COMMON TRIP OVER-CURRENT PROTECTION DEVICES.
D. ROUTING OF CONDUIT IS ESTIMATED. FIELD VERIFICATION OF CONDUIT ROUTING & PULLBOX
LOCATIONS IS REQUIRED.
E. PROVIDE FIRESTOPPING AT ALL RATED WALL PENETRATIONS - SEE PLANS FOR RATED WALLS.
PROVIDE ACOUSTICAL WALL SEALANT AT ALL OTHER WALL PENETRATIONS.
F. CONTRACTOR TO PROTECT EXISTING INSTALLATIONS FROM DAMAGE. ANY DAMAGE TO EXISTING
FACILITY WILL BE REPAIRED AT CONTRACTOR'S EXPENSE.
GENERAL POWER NOTES:
AC
SW
LAN RACK 3
LAN RACK 2
LAN RACK 1
PLASMA
AC-2
A C
-1
PLASMA
PLASMA
WAN 2
WAN 1
EXISTING
80kVA UPS1
EXISTING 3-1/2"C. FROM SWITCHBOARD "1E7"
DISTRIBUTION
A436B
ELECTRIC CL
A437C
COMPUTER RM
NEW
DISTRIBUTION
PANEL
NEW
CABLE SUPPORT
ROUTING
1 2 3 4 5 (TYP)
Drawing Title
Approved: Project Director
Location
Building Number
Project Tit le
Checked DrawnDate
Project No.
Drawing Number
D w g . o f o n e -e ig h th i n c h o n e f o o t o n e
-q u a rt e r in c h o n e f o o t th re e
-e ig h th s i n c h o n e f o o t o n e
-h a lf i n c h o n e f o o t th re e
-q u a rt e rs i n c h o n e fo o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
FFE, Inc.
420 Springfield Pike Cincinnati OH, 45215 513-522-0956
Cincinnati, Ohio
Upgrade UPS and AC in Computer Room
06/09/17
POWER PLAN - PHASE 3 PARTIAL
FOURTH FLOOR IT ROOM A437C
EP105
539-18-202
RG JK
PHASE 3
1. AFTER RACK EQUIPMENT IS SWITCHED OVER TO UPS2 RECONFIGURE UPS1 CIRCUITS TO MATCH NEW SCHEDULE ON SHEET EP602.
2. ROUTE UPS1 WIRING IN A NEAT AND ORGANIZED MANNER. SECURE TO NEW CABLE SUPPORTS USING CABLE ACCESSORIES THAT ARE EITHER METAL
OR THAT ARE LISTED AS HAVING LOW SMOKE OR HEAT RELEASE PROPERTIES. (EXHIBIT A MAXIMUM PEAK OPTICAL DENSITY OF 0.5 OR LESS, AN AVERAGE OPTICAL DENSITY OF 0.15 OR LESS, AND A PEAK HEAT RELEASE RATE OF 100kW OR LESS WHEN TESTED IN ACCORDANCE WITH ANSI/UL 2043-2008)
3. REMOVE UNUSED RECEPTACLES AND CABLES. INSTALL NEW RECEPTACLES AND CONNECT TO NEW RACK ATS UNITS.
4. VERIFY ATS SWITCHES TO PRIMARY POWER WHEN UPS1 CIRCUIT IS ENERGIZED.
5. CLOSE ALL FLOOR PENETRATIONS WITH 1" THICK, FIRE RETARDANT, FLEXIBLE FOAM SHEETING, FOAM TO MEET UL94, HF1 RATING.
SCALE: 1/4" = 1'-0"
PHASE 3 FOURTH FLOOR COMPUTER ROOM POWER PLAN
7 13 Revisions Date
E NE NE NE NE NE N
400A 400A 600A 400A 800A 200A
A.T.S.
"1E15"
BLDG. 15
A.T.S.
"1E15""TO 1E8"
TO
A.T.S.
"1E3" 600A
CRITICAL
BRANCH
A.T.S.
1E4
400A
EQUIPMENT
BRANCH
1000 AMP BUS, 65 KAIC
"ESB" 1000 AMP, 208Y/120V, 3 PH, 4W, GENERAL ELECTRIC SPECTRA SERIES, RM B13B
EMERGENCY POWER
2000A
800A800A800A800A
1000 AMP BUS, 65 KAIC
"US1B" 3000 AMP, 208Y/120V, 3 PH, 4W,
GENERAL ELECTRIC MICRO VERSA TRIP, RM B13B
NORMAL POWER
SWBD
METERING
400A
SPD
32 4 5 6 7
12,470V, 750KVA LF OIL
-208Y/120V,3P,4W
32,000A
400A
800A
600A
400A
800A
SPARESPARE
#600
50ASELECTOR
SWITCH
A
B
TO US-1A
SPARE
TO 400A TIE-BUS
SPARE
TO
PANELS
"PP-1"
800A
800A
800A
SPARE SPARE
TO
"DPP"
TO
"DPE"
TO
PANEL
"IE5"
TO
WIREWAY
BLDG. 15
34651515
TO FIRE
PUMP &
JOCKEY
PUMP
TO SWBD
"1E3"
E N
600A
A.T.S.
1E5
400A
EQUIPMENT
BRANCH
A.T.S.
1E6
600A
EQUIPMENT
BRANCH
E N
600A
A.T.S.
1E7
800A
EQUIPMENT
BRANCH
TO
WIREWAY
BLDG. 15
300A 200A 200A 200A 400A
1000 AMP BUS, 65 KAIC
"1E7" 800 AMP, 208Y/120V, 3 PH, 4W, GENERAL
ELECTRIC SPECTRA SERIES, RM B13B
12345
TO
PANELS
PSBE
CSB
TO PANEL
E4A
TO PANEL
MCP-E
TO PANELS
P1 P2
TO 3RD
FLOOR 80kVA
UPS #1
(2) 500 KCMIL
(3
K
C M
IL
(3
K
C M
IL
G G
2500A
NO
2500A
NO
2500A
NO
1600A
NC
400A
NC
2000A
NC
1000A
NC
1500KW
GENSET
1500KW
GENSET
CONNECTION TO
LOAD BANK/TRAILER
GENSET
CONTROLLED
GENERATOR PARALLELING SWITCHGEAR
NEMA 1 5000A 480Y/277V 3PH, 4W, 100KAIC
RM B13 480Y/277V
3PH, 4W
RM B13 480Y/277V
3PH, 4W
TGEN #1
750KVA
480-208Y/120V,3P,4W
300KVA
480-208Y/120V,3P,4W
TO "ESWB"
#600
SPARE
TO BUILDINGS
15 & 16 ATS
TO ATS-16
TO ATS-SURGERY
(2
K
C M
IL
TO
SWITCHBOARD
"GDE"
Drawing Title
Approved: Project Director
Location
Building Number
Project Tit le
Checked DrawnDate
Project No.
Drawing Number
D w g . o f o n e -e ig h th i n c h o n e f o o t o n e
-q u a rt e r in c h o n e f o o t th re e
-e ig h th s i n c h o n e f o o t o n e
-h a lf i n c h o n e f o o t th re e
-q u a rt e rs i n c h o n e fo o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
FFE, Inc.
420 Springfield Pike Cincinnati OH, 45215 513-522-0956
Cincinnati, Ohio
Upgrade UPS and AC in Computer Room
06/09/17
NORMAL & EMERGENCY POWER
BRANCHES - 80kVA UPS - "1E7" /
ATS-"1E7" SINGLE LINE DIAGRAM
EP301
539-18-202
CL JK
NOT TO SCALE
EMERGENCY POWER BRANCH - 80kVA UPS - "IE7" / ATS-"IE7" SINGLE LINE DIAGRAM
EXISTING 80kVA UPS FEEDER
SHOWN FOR INFORMATION
ONLY
8 13 Revisions Date
0 ISSUED FOR CONSTRUCTION 06-09-2017
DRAWING NOTES:
1. PROVIDE (2)#12, 3/4"C TO TIE UPS OUTPUT SHUNT TRIP BREAKER INTO EXISTING SHUNT TRIP
CIRCUIT, FED FROM THE EMERGENCY POWER SHUTDOWN MANAGEMENT SYSTEM (EPSMS). REFER
TO PLAN FOR EPSMS LOCATION.
UPS - 3RD FLOOR 80kVA
UPS SHUNT TRIP
OUTPUT BREAKER
120V
20A TO 1E7
TO UPS BUS
"EDPEQ3" 400 AMP, 480Y/277V, 3 PH, 4W,
MECHANICAL 2, RM A23
SWBD
METERING
30A
SPD
50A 400A
G G
2500A
NO
2500A
NO
2500A
NO
1600A
NC
400A
NC
2000A
NC
1000A
NC
1500KW
GENSET
1500KW
GENSET
CONNECTION TO
LOAD BANK/TRAILER
GENSET
CONTROLLED
GENERATOR PARALLELING SWITCHGEAR
NEMA 1 5000A 480Y/277V 3PH, 4W, 100KAIC
RM B13 480Y/277V
3PH, 4W
RM B13 480Y/277V
3PH, 4W
TGEN #1
750KVA
480-208Y/120V,3P,4W
300KVA
480-208Y/120V,3P,4W
#600
TO "ESB"
SPARE
TO BUILDINGS
15 & 16 ATS
TO ATS-16
TO ATS-SURGERY
(2
K
C M
IL
250A 400A 600A 400A
3465 3 3
250A 200A
300A
200A
N E
ATS "ESWB-F-3"
400A EQUIPMENT
BRANCH, RM. C008
DISTRIBUTION SWITCHBOARD "ESWB" 1600 AMP, 480Y/277V, 3 PH, 4W,
GENERAL ELECTRIC SPECTRA SERIES, RM
EMERGENCY POWER
400A
"US-1X" 3000 AMP, 208Y/120V, 3 PH, 4W,
GENERAL ELECTRIC MICRO VERSA TRIP, RM A023
NORMAL POWER
SWBD
METERING
3 4 6 7
750KVA
12,470V-480Y/277V,3P,4W
1200A
TO MV "PS1"
SWITCHGEAR 8 9 10 11 12
TO
"MULTI-
STACK"
TO
"X-RAY"
T O
A
T S
E S
W B
-F
IM
A G
IN
G
TO
PANEL
"4P1"
TO
PANEL
"MCC-2"
800A
225A 600A 600A 600A 600A400A 400A600A
"US-1P" 2500 AMP, 480Y/277V, 3 PH, 4W,
GENERAL ELECTRIC MICRO VERSA TRIP, RM A23
NORMAL POWER
4 5 6 7
1000KVA
12,470V-480Y/277V,3P,4W
2500A
TO MV "PS1"
SWITCHGEAR 8 9 10 11 12
TO
PANEL
"MCP2"
TO
PANEL
"MCC-C"
TO
PANEL
"MCCB"
300A
400A 300A 800A 600A 600A600A 800A400A
K K K
TO
PANEL
"MCC-G"
TLPB
5KVA
480-208Y/120V,3P,4W
PANEL
"PP1"
PANEL
"LPB"
TO
300KVA
TEMP
PANEL
CH-1
TO
DISTRIB
PANEL
"DS-1P"
TO
PANEL
"MCC-D"
CH-2
TO
PANEL
"DS-1A"
2500A BUSWAY
TO
PANEL
"DS-1X"
TO
PANEL
"DPF"
(IMAGING)
TO
PANEL
"US-1P"
400A
N E
ATS-12
"ESWB-50 250A
TO
SUB
"US-1A"
TO
ELEVATORS
"E-15" & "E-16"
N E
ATS-11
600A EQP.
BRANCH
TO
"ESWB-40"
TO
SUB
"US-1A"
TO
"ESWB-20"
N E
ATS -10 400A
CRITICAL BRANCH
TO
DISTRIB
"DS-1A"
N E
ATS-9
200A LIFE
SAFETY. BRANCH
TO
SWBD
"ESWB-10"
TO
SUB
"US-1A"
N E
ATS-1
EQPUIP
BRANCH
TO
ATS-2 "MCC-F"
TO
SUB
"US-1C"
TO
SURGERY
SUITE, 3rd
FLOOR
N E
ATS -SURGERY 225A
CRITICAL BRANCH
TO
DISTRIB
"DS-1A"
"EDPLEQ3"
30KVA
480-208Y/120V,3P,4W
PANEL
"EDPLEQ3"
SPD
M
200A
30,089 SCA
13,275 SCA
SPARE
100kVA MODULAR STATIC UPS: UPS2 ON
LEVEL 3, RM. A3002-2
(1
S E
T O
F
(3
/0
/0 N
G
"C
TO
"GDE"
TO "GDE"
(1) SET OF:
(3) #600, (1) #600N, #1G, 3"C
PROVIDE NEW BREAKER IN EXISTING PANELBOARD
TO MATCH FULL AIC RATING OF PANELBOARD, FIELD
VERIFY PANELBOARD EDPEQ3 AIC RATING
"TR-UPS2"
125KVA
480-208Y/120V,3P,4W
PROVIDE FULL SYSTEM GROUNDING
FOR SEPARATELY DERIVED SYSTEM
PER NEC REQUIREMENTS. PROVIDE
#4 CONDUCTOR
600A
600V 200A 3P
NON-FUSED
DISCONNECT
100kVA
N E
INPUT
BREAKER
600A
SHUNT TRIP
OUTPUT
BREAKER
MODULAR
BATTERY BANK(S)
DISTRIBUTION
PANEL
"UPS2 PANEL 1"
600A MCB
PANELBOARD
"UPS2 PANEL 2"
225A MCB
FEED-THRU LUGS
(1) SET OF:
(3) #600, (1) #600N, #1G, 3"C
(1) SET OF:
(3) #3/0, (1) #3/0N, #4G, 2"C
4 4
UPS #1 (80kVA)
EXISTING - REF 1/EP301
UPS SHUNT TRIP
OUTPUT BREAKER
EXISTING
120V
20A, 1P
TO 1E7
TO UPS BUS
H N
EXISTING EPSMS
SHUNT TRIP CONTACT
UPS2 (100kVA)
NEW - REF 1/EP302
UPS SHUNT TRIP
OUTPUT BREAKER
TO EDPEQ3
TO UPS BUS
DIN MOUNT TERMINAL STRIP
IN JUNCTION BOX
(2)#12,3/4"C(2)#12,3/4"C
(2)#12,3/4"C(2)#12,3/4"C
Drawing Title
Approved: Project Director
Location
Building Number
Project Tit le
Checked DrawnDate
Project No.
Drawing Number
D w g . o f o n e -e ig h th i n c h o n e f o o t o n e
-q u a rt e r in c h o n e f o o t th re e
-e ig h th s i n c h o n e f o o t o n e
-h a lf i n c h o n e f o o t th re e
-q u a rt e rs i n c h o n e fo o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
FFE, Inc.
420 Springfield Pike Cincinnati OH, 45215 513-522-0956
Cincinnati, Ohio
Upgrade UPS and AC in Computer Room
06/09/17
POWER BRANCH - 100kVA UPS2, PANEL EDPEQ3 SINGLE LINE
DIAGRAM
EP302
539-18-202
RG JK
SCALE: N.T.S.
EMERGENCY POWER BRANCH - 80 kVA UPS SINGLE LINE - PANEL EPEDQ3
9 13 Revisions Date
0 ISSUED FOR CONSTRUCTION 06-09-2017
1 ADDENDUM 1 11-03-2017
SCALE: N.T.S.
WIRING DIAGRAM - EPSMS SHUNT TRIP
1. PROVIDE NEMA 1 JUNCTION BOX WITH DIN RAIL MOUNTED TERMINAL STRIP WITH 12
TERMINAL CONTACTS RATED FOR #12 WIRING AT STRUCTURE ABOVE UPS #1. PROVIDE ALL
CONDUIT AND WIRING ASSOCIATED WITH EXTENSION OF EMERGENCY POWER SHUTDOWN
MANAGEMENT SYSTEM (EPSMS) TO SHUTDOWN UPS2. CONNECT WIRING IN PARALLEL PER
WIRING DIAGRAM. EXTEND EXISTING CONDUIT.
2. RECONNECT SHUNT TRIP WIRING TO OUTPUT BREAKER WITHIN UPS #1.
3. CONNECT SHUNT TRIP WIRING TO OUTPUT BREAKER WITHIN UPS2.
4. EQUIPMENT SHALL BE FULLY RATED FOR A MINIMUM INTERRUPT RATING OF 14,000AIC.
DRAWING NOTES:
LENGTH AS REQUIRED
CONDUIT TRAPEZE MOUNTING DETAIL
NTS
CONDUIT CLAMP.
SIZE AS REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
REFER TO PLANS FOR
QUANTITY & SIZE OF
CONDUITS
GENERAL NOTES:
1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING
CHANNEL LONGER THAN 915mm (36") SHALL BE
INSTALLED WITH A CENTER SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED
METHOD PER SPECIFICATION 26 05 33, RACEWAY AND
BOXES FOR ELECTRICAL SYSTEMS. FIELD VERIFY
EXACT CONDITIONS.
3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER
TO SPECIFICATION SECTION 13 05 41, SEISMIC
RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL
COMPONENTS.
LOCKING SQUARE
WASHER &
LOCKNUT
9.52mm (3/8") MIN
GALVANIZED THREADED
ROD, TYP.
WASHER
LOCKNUT
INTEGRAL
GALVANIZED
LIPPED
STEEL
MOUNTING
CHANNEL
FLOOR SLAB PENETRATION DETAIL
NTS
CONDUIT, TYP MINERAL WOOL
(FIRMLY
PACKED)FIRESTOP SEALANT
PER SECTION 07 84 00,
FIRESTOPPING
JUNCTION BOX
(SIZE AS
REQUIRED)
CONDUIT FITTING
SPRING
NUT,
TYP
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL, TYP.FLOOR SLAB,
TYP.
STEEL
EXPANSION
ANCHOR, TYP
(3/8") MAX
RACK 1
RACK 1
RACK 2
RACK 2
RACK 3
RACK 4
RACK 5
RACK 5
RACK 6
RACK 6
RACK 7
RACK 7
RACK 7
RACK 7
RACK 8
RACK 9
RACK NUMBER VOLTAGE PANEL
RACK 9
RACK 9
RACK 9
RACK 10
RACK 10
RACK 11
RACK 11
RACK 12
RACK 12
RACK 12
RACK 14
RACK 15
RACK 16
RACK 16
RACK 16
RACK 16
RACK 17
RACK 19
RACK 19
RACK 19
RACK 19
RACK 20
RACK 20
RACK 20
RACK 21
RACK 21
RACK 22
RACK 22
RACK 23
RACK 23
208V
208V
208V
208V
208V
120V
208V
208V
120V
208V
120V
208V
120V
120V
120V
120V
120V
120V
120V
208V
208V
208V
208V
120V
120V
120V
120V
120V
208V
120V
208V
120V
120V
208V
208V
208V
120V
208V
208V
208V
120V
208V
120V
120V
120V
120V
EX. PANEL #1
EX. PANEL #1
EX. PANEL #1
EX. PANEL #2
EX. PANEL #1
EX. PANEL #1
EX. PANEL #1
EX. PANEL #2
EX. PANEL #1
EX. PANEL #2
EX. PANEL #1
EX. PANEL #1
EX. PANEL #2
E4A
EX. PANEL #1
EX. PANEL #2
EX. PANEL #1
EX. PANEL #2
EX. PANEL #1
EX. PANEL #2
EX. PANEL #1
EX. PANEL #2
EX. PANEL #1
EX. PANEL #2
EX. PANEL #1
EX. PANEL #2
EX. PANEL #2
EX. PANEL #1
EX. PANEL #1
RACK 24
RACK 25
RACK 25
RACK 25
120V
120V
120V
120V
RACK 25 120V
EX. PANEL #2
EX. PANEL #2
EX. PANEL #2
EX. PANEL #1
EX. PANEL #2
EX. PANEL #2
EX. PANEL #1
EX. PANEL #1
EX. PANEL #2
EX. PANEL #2
EX. PANEL #1
EX. PANEL #1
EX. PANEL #1
EX. PANEL #2
EX. PANEL #1
EX. PANEL #2
EX. PANEL #2
EX. PANEL #1
EX. PANEL #2
EX. PANEL #2
EX. PANEL #2
CIRCUIT
25, 27
26, 28
30, 32
33, 35
38, 40
37, 39
11, 13
25, 27
33, 35
34, 36
34, 36
34, 36
34, 36
6, 8
6, 8
1, 3
1, 3
39, 41
2, 4
2, 4
40, 42
29, 31
RECEPTACLE
NEMA L6-30
NEMA L6-30
NEMA L6-30
NEMA L6-30
NEMA L6-30
NEMA L5-20
NEMA L6-30
NEMA L6-30
NEMA L5-30
NEMA L6-30
NEMA L5-20
NEMA L6-30
NEMA L5-30
NEMA L5-20
NEMA L5-20
NEMA L5-30
NEMA L5-30
NEMA L5-30
NEMA L5-30
NEMA L6-30
NEMA L6-30
NEMA L6-30
NEMA L6-30
NEMA L5-20
NEMA L5-30
NEMA L5-30
NEMA L5-20
NEMA L5-20
NEMA L6-30
NEMA L5- 20
NEMA L6-30
NEMA L5-20
NEMA L5-20
NEMA L6-20
NEMA L6-20
NEMA L6-20
NEMA L5-30
NEMA L6-20
NEMA L6-20
NEMA L6-20
NEMA L5-20
NEMA L6-30
NEMA L5-30
NEMA L5-30
NEMA L5-30
NEMA L5-30
NEMA L5-20
NEMA L5-30
NEMA L5-30
NEMA L5-30
NEMA L5-30
CABLE SIZE
(2) #10 AWG / # 8 GND
(2) #12 AWG / #10 GND
CABLE TYPE
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
CABLE LENGTH
47' - 10"
47' - 2"
45' - 10"
44' - 11"
43' - 6"
36' - 4"
26' - 1"
26' - 4"
27' - 8"
28' - 11"
30' - 0"
30' - 0"
30' - 7"
30' - 7"
31' - 9"
40' - 0"
40' - 0"
40' - 0"
40' - 0"
37' - 4"
36' - 7"
35' - 3"
34' - 5"
33' - 3"
33' - 3"
33' - 3"
22' - 11"
20' - 0"
9' - 5"
9' - 5"
9' - 5"
9' - 5"
7' - 3"
9' - 10"
9' - 10"
9' - 10"
9' - 10"
12' - 0"
12' - 0"
12' - 0"
13' - 11"
13' - 11"
13' - 11"
15' - 10"
15' - 10"
17' - 10"
21' - 2"
23' - 5"
23' - 5"
23' - 5"
23' - 5"
RACK 21 208V EX. PANEL #2 29, 31 NEMA L6-30 MC
17' - 10"
EXISTING UPS1 PANELS 1 AND 2 CABLE SCHEDULE
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #12 AWG / #10 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #12 AWG / #10 GND
(2) #12 AWG / #10 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #12 AWG / #10 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #12 AWG / #10 GND
(2) #12 AWG / #10 GND
(2) #10 AWG / # 8 GND
(2) #12 AWG / #10 GND
(2) #10 AWG / # 8 GND
(2) #12 AWG / #10 GND
(2) #12 AWG / #10 GND
(2) #12 AWG / #10 GND
(2) #12 AWG / #10 GND
(2) #12 AWG / #10 GND
(2) #10 AWG / # 8 GND
(2) #12 AWG / #10 GND
(2) #12 AWG / #10 GND
(2) #12 AWG / #10 GND
(2) #12 AWG / #10 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #12 AWG / #10 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
(2) #10 AWG / # 8 GND
RACK 17 120V E4A 2 NEMA L5-20 MC 7' - 3"(2) #12 AWG / #10 GND
Drawing Title
Approved: Project Director
Location
Building Number
Project Tit le
Checked DrawnDate
Project No.
Drawing Number
D w g . o f o n e -e ig h th i n c h o n e f o o t o n e
-q u a rt e r in c h o n e f o o t th re e
-e ig h th s i n c h o n e f o o t o n e
-h a lf i n c h o n e f o o t th re e
-q u a rt e rs i n c h o n e fo o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
FFE, Inc.
420 Springfield Pike Cincinnati OH, 45215 513-522-0956
Cincinnati, Ohio
Upgrade UPS and AC in Computer Room
06/09/17
ELECTRICAL DETAILS
EP501
539-18-202
RG JK
Revisions Date
10 13
Location
Building Number
Project Tit le
Checked DrawnDate
Project No.
Drawing Number
D w g . o f o n e -e ig h th i n c h o n e f o o t o n e
-q u a rt e r in c h o n e f o o t th re e
-e ig h th s i n c h o n e f o o t o n e
-h a lf i n c h o n e f o o t th re e
-q u a rt e rs i n c h o n e fo o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
FFE, Inc.
420 Springfield Pike Cincinnati OH, 45215 513-522-0956
Cincinnati, Ohio
Upgrade UPS and AC in Computer Room
06/09/17
EXISTING UPS1 POWER PANEL
SCHEDULES
EP601
539-18-202
RG JK
Revisions Date
0 ISSUED FOR CONSTRUCTION 06-09-2017
Notes:
Total Est. Demand: 94 A
Total Conn.: 94 A
Total Est. Demand: 33798 VA
Total Conn. Load: 33798 VA
Computer Receptacle 33798 VA 100.00% 33798 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 122 A 115 A 59 A
Total Load: 13745 VA 12957 VA 7096 VA
41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42
39 1014... 3381... 40
Rack #5 30 A 2
1014... 3381...
2 100 A Rack #3
35 1014... 1014... 36
Rack #7 30 A 2
1014... 1014...
2 30 A Rack #10 & Rack #11
31 1014... 1014... 32
Rack #21 30 A 2
1014... 1014...
2 30 A Rack #2
27 1014... 1014... 28
Rack #1 30 A 2
1014... 1014...
2 30 A Rack #1
23 Console 20 A 1 450 VA 450 VA 1 20 A Rack # 12 24
21 Spare 20 A 1 0 VA 450 VA 1 20 A Test Bench 22
19 Rack 7, OPEN 20 A 1 450 VA 450 VA 1 20 A Rack #4 20
17 Rack #16 20 A 1 450 VA 0 VA 1 20 A Spare 18
15 Rack #21 20 A 1 676 VA 676 VA 1 30 A…