36C24919B0001_0002.docx

DOCX document 15 KB Posted

Attached to
Project 603-16-701 Replace TIPP Units Federal contract opportunity
Solicitation number
36C24919B0001
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9

About this file

36C24919B0001 0002 36C24919B0001 0002.docx

View the file

Other files for this federal contract opportunity

Other files attached to Project 603-16-701 Replace TIPP Units, newest first.
File Type Posted
36C24919C0079-000.docx DOCX document
36C24919B0001-0004000.docx DOCX document
36C24919B0001-0003000.docx DOCX document
36C24919B0001_0001.docx DOCX document
Specs_All_Signed_603-16-701_Replace_TIP_Units_R1_Bid.pdf PDF
00_01_15-_List_of_Drawing_Sheets_V2.pdf PDF
36C24919B0001_1.docx DOCX document
01_00_00-_General_Requirements_R5.pdf PDF
Drawings_-__All_Signed_603-16-701_Replace_TIP_Units.pdf PDF
36C24919B0001.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FedBizOpps Modification to a Previous Notice

CLASSIFICATION CODE

SUBJECT

CONTRACTING OFFICE'S

ZIP-CODE

SOLICITATION NUMBER

BASE NOTICE TYPE

RESPONSE DATE (MM-DD-YYYY)

ARCHIVE

DAYS AFTER THE RESPONSE DATE

RECOVERY ACT FUNDS

SET-ASIDE

NAICS CODE

CONTRACTING OFFICE

ADDRESS

POINT OF CONTACT

(POC Information Automatically Filled from User Profile Unless Entered)

DESCRIPTION

See Attachment

AGENCY'S URL

URL DESCRIPTION

AGENCY CONTACT'S EMAIL

ADDRESS

EMAIL DESCRIPTION

ADDRESS

POSTAL CODE

COUNTRY

ADDITIONAL INFORMATION

GENERAL INFORMATION

PLACE OF PERFORMANCE

* = Required Field FedBizOpps Modification to a Previous Notice Rev. March 2010 Z Project 603-16-701 Replace TIPP Units 37129 36C24919B0001

PRESOL

01-30-2019 N 236220 Department of Veterans Affairs Network Contracting Office 9 1639 Medical Center Parkway Suite 400 Murfreesboro TN 37129 Scheronica Cochran Contract Specialist Department of Veterans Affairs Robley Rex VA Medical Center 800 Zorn Avenue Louisville, KY 40206 scheronica.cochran@va.gov Answers to the questions that were submitted:

1. Do we need to connect VRF to an Energy Management System? If so, what is the Energy Management System and who maintains the Energy Management System?

Yes, per the specs, the VRF and its individual units are to be connected to the energy management system which is Johnson Controls Metasys Controls system. See specs 23 09 23 (Direct-Digital Control System for HVAC) and 23 81 43 ( Air Source Unitary Heat Pumps). This work shall include all work, materials, etc. such that all points available from the BacNet cards can be pulled to the Metasys server and then creating graphics to display this data. Metasys administrator contact info: Jon Bloom, jon.bloom@va.gov. Phone: 502-287-5509.

2. Is there a minimum efficiency requirement for the VRF?

Yes, per the specs, the VRF is to have a minimum EER of 11.1 for cooling and 12.1 for heating; a minimum IEER of 16.1 for cooling and 16.6 for heating; and a minimum SCHE of 21.4 for simultaneous cooling and heating. See page 3 in spec 23 81 43.

3. Will the contractor have access to multiple escorts simultaneously?

One escort will be provided and an additional escort on a limited basis for a total of no more than 2 escorts at any time. Also take note of Specification Section 01 00 00, 1.5 Construction Security Requirements…”The General Contractors’ employees working on this project shall hold a National Background Investigation Bureau (NBIB) https://nbib.opm.gov Tier 1 VA badge.” This is also known as a NACI investigation.

4. What type of air handler is required for the VRF in each IT closet? Ceiling Cassette, Wall Mount or Floor Mount?

Air handler shall be Wall mounted type for all locations.