36C24820Q0820-001.docx
DOCX document Posted
- Attached to
- J041--Chiller 1 and 3 VSD Replacement Federal contract opportunity
- Solicitation number
- 36C24820Q0820
About this file
This combined synopsis and solicitation requests quotes for variable speed drive replacements on two York chillers at the Miami VA Medical Center. The Department of Veterans Affairs seeks to award a firm-fixed price contract to a service-disabled veteran-owned small business to fully replace the existing 1100HP VSDs, which are past their useful life. Quotes are due by May 22nd and must include authorization to provide OEM parts from Johnson Controls. The selected contractor will remove and replace the VSD assemblies per the specifications, integrate them into the control system, provide a generator and fuel for backup power, and verify operation. Work is to take place on weekends from 7am to 4:30pm.
36C24820Q0820 work documentation.docx
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24820Q0820 0001.docx | DOCX document | |
| 36C24820Q0820-000.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Work Documentation (Overview) The Miami VA Healthcare System, Engineering Service, requires replacement of (2) York variable speed drives (VSD) for water cooled chillers.
Work hours shall be Saturday and Sunday 7 AM to 430 PM, unless otherwise authorized.
Only one chiller can be down for service at any one time, unless specifically permitted by the COR due to favorable weather conditions.
Contractor should have experience working in hospital setting on chillers with TWO references for previous projects.
The Miami VA Healthcare System requires contractor to perform the following tasks:
4.1.1 Contractor shall fully replace existing VSD 1100 HP Frequency Drive, York Model # 371-06863702 VSD 1055k-46 variable speed drives which are past useful life.
4.1.2 VSD 1100 HP PART NO (371-06863702) is considered the new component for chillers and can only be priced through and sold through Johnson controls engineered sales.
4.1.3 New VSD must integrate and be controlled by Tridium Niagra system. Existing Chiller #2 VSD shall also be integrated to Tridium Niagra system (currently on Siemens Insight system) as part of this project.
4.1.4 Contractor shall provide generator with fuel for entire duration of project to supply the Trane portable 500-ton chiller while any chiller is offline for this project.
4.1.5. Remove the existing VSD assembly including the housing and replace with a New VSD must be compatible with Johnson Control York chillers (Model # 371-06863702, or equal)
4.1.6. Reconnect the new VSD in accordance with York/Johnson Control specifications.
| 4.1.7. | Vendor will program/connect the newly installed VSD for Chiller #1 and #3. Vendor will verify operation with the existing control system operation. |
| 4.1.8. | Perform unit checkout and demonstration after installation, as in-service checkout of VSD assembles. |
| 4.1.9. | All equipment installation and parts should be of high quality, rust resistance paint and meet, at a minimum, like kind replacement for fit, form and function, as applicable to existing like-kind replacement VSD’s, engineering specifications, including any currently installed add-on optional components. Workmanship and configuration will be done in a method that ensures high reliability per manufacturer’s recommendations. |
| 4.2.0. | All work performed shall be fully documented by the Contractor. All work performed shall be in compliance with any manufacturer’s recommendations and applicable NEMA, NEC, ANSI, and VA standards. |
File details come from the government source that posted it. Updated .