36C24819Q0848-001.docx

DOCX document 25 KB Posted

Attached to
Supply: Mobile Generator Federal contract opportunity
Solicitation number
36C24819Q0848
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8

About this file

36C24819Q0848 36C24819Q0848-Attachment 1.docx

View the file

Other files for this federal contract opportunity

Other files attached to Supply: Mobile Generator, newest first.
File Type Posted
-17077.docx DOCX document
36C24819Q0848-004.pdf PDF
36C24819Q0848-005.pdf PDF
36C24819Q0848-003.docx DOCX document
36C24819Q0848-002.docx DOCX document
36C24819Q0848-000.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment #1 RFQ 36C24819Q0848 Salient Characteristics/Pricing Schedule

* Brand Name or Equal* (CUMMINS-ALLISON CORP.)

CUMMINS-ALLISON CORP Standby Mobile Generator Genset: 50/60Hz-275kW, 325 KVA prime, 286 kW.

Equal Item must meet these Salient Characteristics. Explanation of how Equal Item(s) meet each Salient Characteristic and must be included with quote.

Salient Characteristics for Mobile Generator Bay Pines VAHCS (516)

Item Specifications

· Generator shall have a voltage selector switch. Voltage selector switch should provide 120/240V Single Phase, 120/208V Three Phase, and 277/480V Three Phase.

· Shall be trailer mounted with pintle hook tow capabilities and at a minimum double axil.

· 50/60Hz 325 KVA prime, 286 kW standby at 277/480 volts, three phase.

· Shall have subbase fuel tank, fuel capacity of 225-250 gal., runtime of over 24 hours with full load, and diesel engine.

· Shall have battery rack and cables, starting battery, lead acid battery charger.

· Generator shall have a control panel that enables user to monitor operations using a set of displays, (Meters/Gauges) that indicate the measure of various parameters like voltage, current and frequency.

· Shall have spare tire and wheel, tire mount on trailer, grease zerk axle hubs, or compatible, suspension system, hydraulic surge brakes. safety chains with spring clips, adjustable front stabilizer jack, 2 rear stabilizer jacks, tubeless tires and wheels,

· Shall have Lighting and Reflector package.

· Seller shall provide initial startup and check out of the system.

· Shall come with a minimum of five 50ft lengths of 4/0 Camlock cables.

· Shall have sound level of 74 dB(A) log average @ 7 m (23 ft.) or better with full load.

· Shall have sound attenuated, Steel and Internally mounted critical silencer

· Shall 125% environmental containment basin for oil and coolant and 110% secondary containment tank for fuel

· Shall be certified by the EPA to conform to Tier 4 Final nonroad emissions standards

· Max weight desired is 15000 Lbs.

Warranties

· Shall have a minimum 3-year, 3000 hr. limited warranty covering all generator systems and components and one-year limited warranty covers the trailer.

PRICE/COST SCHEDULE

ITEM INFORMATION

ITEM NUMBER
DESCRIPTION OF SUPPLIES/SERVICES
QUANTITY
UNIT
UNIT PRICE
AMOUNT
1.00
EA
__________________
__________________

Standby Mobile Generator Genset: 50/60Hz-275kW, 325 KVA prime, 286 kW.

GRAND TOTAL
__________________

B.3 DELIVERY SCHEDULE

ITEM NUMBER
QUANTITY
DELIVERY DATE
0001
SHIP TO:
Bay Pines VA Medical Center

10,000 Bay Pines Blvd Bldg. 13 Bay Pines, FL 33477

USA

1.00
30 Days ARO

File details come from the government source that posted it.