Text version
Contract Opportunity Combined Synopsis/Solicitation Notice
PRODUCT SERVICE CODE
SUBJECT
CONTRACTING OFFICE'S
ZIP-CODE
SOLICITATION NUMBER
RESPONSE DATE/TIME/ZONE
ARCHIVE
DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
SET-ASIDE
NAICS CODE
CONTRACTING OFFICE
ADDRESS
POINT OF CONTACT
(POC Information Automatically Filled from User Profile Unless Entered)
DESCRIPTION
See Attachment
AGENCY'S URL
URL DESCRIPTION
AGENCY CONTACT'S EMAIL
ADDRESS
EMAIL DESCRIPTION
ADDRESS
POSTAL CODE
COUNTRY
ADDITIONAL INFORMATION
GENERAL INFORMATION
PLACE OF PERFORMANCE
* = Required Field Contract Opportunity Combined Synopsis/Solicitation Notice F103 Legionella Testing 21201 36C24521Q0068 11-20-2020
11:00AM
EASTERN TIME, NEW YORK, USA
N
SDVOSBC
561210 Department of Veterans Affairs
VAMC
10 N Greene St Baltimore MD 21201 Contracting Officer Robert "Tyler" Hallock robert.hallock@va.gov 410-642-2411 * 3222 Baltimore VA Medical Center 10 N. Greene St.
Baltimore
MD
21201 robert.hallock@va.gov Contracting Officer
STATEMENT OF WORK
This statement of work includes all necessary labor, materials, and equipment necessary to complete Legionella environmental testing at the following VA Maryland Healthcare System (VAMHCS) facilities:
· Baltimore VA Medical Center, 10 N. Green St, Baltimore, MD 21201
· Perry Point VA Medical Center, Perry Point, MD 21902
· Loch Raven VA Medical Center, 3901 The Alameda, Baltimore, MD 21218
The C&A requirements do not apply, and a Security Accreditation Package is not required.
Scope of Services:
The vendor will provide all labor, materials, and equipment necessary to complete Legionella environmental testing at the three (3) aforementioned VAMHCS facilities, and all buildings as required at each location. Legionella environmental testing will occur at a minimum of once per Federal fiscal year quarter, with additional testing to be conducted based on positive Legionella results. Service will include:
· Turnkey environmental sampling for Legionella, to include:
· All testing equipment and sample bottles. Sample bottles must be plastic with screw top, be sterile, and hold at least 250ml. Only 250ml is to be collected and tested.
· All labor necessary to draw samples.
· Routine quarterly sampling and testing:
· Minimum required samples for quarterly Legionella testing are ten (10) hot water samples and ten (10) cold water samples from each required building. Buildings shall be designated by facility staff. In buildings which have less than 10 outlets, all outlets will be sampled.
Estimated number of routine samples per quarter:
| Baltimore VA Medical Center: 35 samples |
| Perry Point VA Medical Center: 300 samples |
| Loch Raven VA Medical Center: 30 samples |
· Sampling locations shall include sinks, showers, tubs, ice machines, pools, and any other location designated by the facility. Pools will be tested twice annually, with associated locker room outlets to be tested on a rotating basis, quarterly.
· Vendor shall submit a sampling protocol for review. For example, that all samples will be first draw from the outlet.
Non-routine sampling and testing:
· Non-routine samples will be drawn and tested at the discretion of the facility, and to follow-up on positive Legionella results from quarterly testing. Number of additional samples and sampling locations shall be determined by the facility. Estimates number per quarter, to include all locations: 50 samples.
· Vendor shall submit a sampling protocol for review. For example, that all samples will be first draw from the outlet.
All packaging, handling, and shipping of samples to lab.
· Turnkey water testing of all outlets used to draw samples for Legionella testing. During testing, the following measurements will be recorded for each outlet:
· Temperature (in Fahrenheit), to be recorded after flushing outlet for approximately two to three (2-3) minutes.
· Oxidant residual, to be recorded from first draw sample. Must be free chlorine DPD test.
· pH, to be recorded from first draw sample. Must be taken suing pH meter and not test strips.
· ISO method Legionella culture and analysis through a laboratory certified by the Centers for Disease Control and Prevention (CDC) Environmental Legionella Isolation Techniques Evaluation (ELITE) program. Lab must be approved by the facility, cannot be changed without approval of the facility, and must be able to provide documentation of certification upon request. Negative Legionella results will be returned within 11-13 calendar days of sampling. Positive Legionella results will result in the immediate notification of designated VA staff via email and/or phone call. Legionella results to include:
· Total reporting of all L. pneumophila
· Complete serogroup reporting of L. pneumophila
· Total reporting of all non-pneumophila Legionella
· Detection limit of less than 1 CFU/ml.
· All data entry of water test results into an Excel spreadsheet, which will be updated and provided to VA staff following each water testing and results cycle. Spreadsheet template will be provided by the VA. At a minimum, data to be recorded includes: date and location of each sample, outlet type, temperature, pH, chlorine level, and results of Legionella lab testing. Temperature, pH, and oxidant levels that are out of normal range (range determined by the VA) will be highlighted.
Vendor water samplers must hold the Maryland Department of the Environment (MDE) Water Sampler Certification and successfully complete VA Legionella Water Sampler Training:
http://vaww.hefp.va.gov/resources/environmental-validation-training under the Environmental Validation section.
Vendor must provide, at the request of the facility, documentation that all instruments and equipment used during sampling are properly calibrated according to the manufacturer’s specifications.
All sampling data and documentation, delivered by vendor to the VA after each quarterly testing cycle and after each set of non-routine tests, shall be compatible to current software used by the VA.