Startup Checklist package-start-up-sheet.pdf
PDF 84 KB Posted
- Attached to
- J045--Heating and Cooling | HVAC Repair on Non-BAS | Upper Chilled Water Coil Air Handler | Federal contract opportunity
- Solicitation number
- 36C24423Q0949
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24423Q0949 0003.pdf | ||
| 36C24423Q0949 0003_1.docx | DOCX document | |
| Philadelphia VAMC Directions to Bldg. 6.pdf | ||
| 36C24423Q0949 0002.pdf | ||
| 36C24423Q0949 0002_1.docx | DOCX document | |
| 36C24423Q0949 0001.pdf | ||
| 36C24423Q0949 0001_1.docx | DOCX document | |
| SCA WD 2015-4233 REV 26 DATED 05-10-2023.pdf | ||
| ATTACHMENT 1 AHU Nameplate.pdf | ||
| 36C24423Q0949.pdf | ||
| 36C24423Q0949_1.docx | DOCX document | |
| ATTACHMENT 2 Photos.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
START-UP & SERVICE DATA INSTRUCTION
AHU #1
START-UP CHECKLIST
Date:
Job Name:
Customer Name:
Address:
City: State: Zip:
Model Number: Serial Number:
Qualified Start-up Technician: Signature:
HVAC Contractor: Phone:
Address:
Contractor’s E-mail Address:
Electrical Contractor: Phone:
Distributor Name: Phone:
Design Supply Air CFM: Design Return Air CFM:
Design Outdoor Air CFM At Minimum Position:
Total External Static Pressure:
Supply Static Pressure:
Return Static Pressure:
Design Building Static Pressure:
Outside Air Dilution: Economizer Position Percentage: _ CFM:
REFERENCE
General Inspection Completed See Notes
New Chilled water coil inspected for shipping, storage, or rigging damage. Coil fins in good condition
New Chilled water coil installed with proper clearances
Chilled water coil checked for gross leaks
Terminal screws and Piping connections checked for tightness
Filters installed correctly and clean
Condensate drain trapped properly, refer to Installation Manual
All dampers and actuators exercised from BAS system (CM3)
New Chilled water control valves fully functional w/BAS
All field wiring (power and control) complete
Air Moving Inspection (If Required)
Completed See Notes
Alignment of drive components Correct rotation of motors, Return & Supply
Belt tension adjusted properly
Blower pulleys tight on shaft, bearing set screws tight, wheel tight to shaft
Pressure switch or transducer tubing installed properly
Operating Measurements - Air Flow (If Required)
Fan operates with proper rotation ID Fans Exh. Fans Cond. Fans
Pressure drop across dry Chilled water coil (At maximum design CFM) 1 IWC
External Static Pressure IWC
Return Static Pressure IWC
Supply Static Pressure IWC
Supply Air CFM Using Dry Coil Chart CFM
Final Adjusted Supply Air CFM2 CFM
Verify Proper Operation of Heating/Cooling Staging Controls (If Required)
Create a cooling demand at the Thermostat, BAS System (CM3) Verify that cooling is energized. Ensure new chilled water valve is modulating properly
Create a heating demand at the Thermostat, BAS System (CM3) Verify that heating stage is energized. Ensure new steam valve is modulating properly
Verify Proper Operation of the Variable Frequency Drive (If Required)
Verify that motor speed modulates with duct pressure change.
FINAL - INSPECTION
Verify that all operational control set points have been set to desired value. Verify proper sequence of operation with BAS (CM3) controls.
Thermal Insulation properly installed according to specification. All areas around new coils and fan motors clean and free of installation debris.
Verify that all access panels have been closed and secured
OBSERVED PRODUCT DIFFICIENCIES & CONCERNS: