S05 RFIs-36C24220B0060 - Response.pdf
PDF 4 MB Posted
- Attached to
- Y1DA--561-18-125 Replace Both 900-Ton Chillers Federal contract opportunity
- Solicitation number
- 36C24220B0060
About this file
This document contains a solicitation for a federal construction contract opportunity to replace two 900-ton chillers at the VA East Orange Campus in New Jersey. The scope of work includes demolishing existing structures, replacing two 900-ton chillers, one 400-ton chiller, one 900-ton cooling tower, miscellaneous piping modifications, integrating new chillers into the building management system, replacing two centrifugal pumps, and other items. The cost estimate range is $2,000,000 to $5,000,000. Responses are due on or around October 15, 2020 via hard copy submittal to the address in the solicitation, which will be posted on SAM.gov. This is a Service-Disabled Veteran Owned Small Business set-aside requiring registration on SAM.gov and VIP.vetbiz.gov as a verified SDVOSB. The NAICS code is 236220 with a $36.5 million size standard.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24220B0060 0002.docx | DOCX document | |
| 36C24220B0060 0001.docx | DOCX document | |
| S02 Wage Determination.pdf | ||
| S02 Replace Both 900 Ton Chillers - Drawings - Issued for Bid.pdf | ||
| 36C24220B0060_1.docx | DOCX document | |
| S02 Replace Both 9000 Ton Chillers - Specifications - Issued for Bid.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
36C24220B0060 561-18-125 Replace Both 900 Chillers
RFIs
November 13, 2020
1. Section 02 83 33.13 part 1 - general 1.1 Summary A Section Includes: Removing and disposal of lead based paint at interior and exterior locations indicated in existing conditions report.
please provide existing conditions report indicated above, specification refers to report that has not been provided by VA.
Response: See attached Regulated Materials Survey Report dated 2020-06-23.
2. On Drawing EP101 at the Cooling Tower and in Sheet Keynote #6 we are directed to provide (4)
Vapor tight Exterior LED Light fixtures on the cooling tower but no spec for a manufacturer or catalog number is provided; please provide the same.
Response: VA does not allow specific manufacturer or model numbers to be included on engineered drawings. Contractor shall take the fixture information provided in keynote 6 and submit a light fixture that conforms to keynote 6 for review by the engineer.
3. On Drawing E601in the existing 480V MCC we are directed to remove and dispose of (2) 25HP and (1) 50HP Starters and replace them with new Starters; does the Owner presently have a particular vendor or supplier who maintains this MCC who we could contact for information and pricing?
Response: Scott testing Inc. maintains the MCC. The drawings call for removal of (3) starters and reinstallation of (1) starter and (2) circuit breakers. The 50-HP starter to be demolished is located in a newer Cutler-Hammer Freedom Series 2100 section of the MCC. The (2) 25-HP starters to be demolished are located in the original Federal Pacific section of the MCC.
4. On Drawing E601in the existing 4160V Substation we are directed to remove and dispose of (2)
200 Amp Fused Switches and replace them with new Switches; does the Owner presently have a particular vendor or supplier who maintains this Substation who we could contact for information and pricing?
Response: Scott testing Inc. maintains the MCC.. The (2) fused switches to be demolished are located in the original Federal Pacific section of the 4160-volt MCC.
5. Pump schedule indicates pumps as being a vertical split case pump. Detail on Dwg M-501 shows a horizontal split case pump. Please provide detail for vertical split case pump.
Response: See attached sketch SKM-01 – Vertical Split Case Pump Detail.
6. Who is the in house ATC contractor? Please provide contact.
Response: Delta Connects, INC. Robert Hermano, 609-860-6600. This information is also on drawing M-801, under controls general notes.
7. Is there a sequence schedule for chiller, cooling tower, & pump removals / installation of new?
Response: There is no mandated construction sequence for the removal and installation of the new and existing equipment. Scheduling of replacements to be coordinated with VA after award.
8. Please confirm that the new chillers are to have variable frequency drives. The schedule indicates a VFD/variable speed operation however the spec refers to a standard starter.
Response: New chillers shall have VFDs per Bulletin #1 drawings.
9. Drawing E-601(Electrical Motor Control details & schedule: Please provide name plate details of the existing Federal pacific 4160V substation & 480V MCC-DN.
Response: See question #2 for information on the newer section of 480-volt MCC-DN. The remainder of the substation is an original vintage Federal Pacific lineup. The 480-volt section if a type RA-3. Additional model numbers are not available or can be provided by the VA if required.
10. Drawing GI002 sheet keynote nos. 2 and 3 states to provide plastic barrier to deck above… --
Please inform what is the deck height and provide construction details of the plastic barrier.
Response: Reefer to specification 01 35 26, section 1.12.
11. Are manometers required for the ICRA work, if yes how many units?
Response: Reefer to specification 01 35 26, section 1.12.
12. Drawing ABT-1 the abatement keynote no.1 is shown at one location only. Please confirm removal and disposal of pipe floor penetration packing is at one location only.
Response: As indicated in the attached Regulated Materials Survey Report dated 2020-06-23, there is only (1) penetration containing ACM.
13. Spec section 01 91 00 and 23 08 00 is for general commissioning and commissioning of HVAC system respectively. Please clarify if all this commissioning work is VA responsibility and confirm that contractor does not have to hire any third-party agent for this work.
Response: The VA, at its discretion, may contract with a third-party Cx agent for this project.
The contractor will be responsible to provide all required Cx support, including pre-functional checks, contractor tests, systems functional performance testing, training, etc. as outlined in
Specifications 01 -91 00, 23 08 00, and 26 08 00.
14. Spec section 02 83 33.13, Para 1.1.A1 states removing and disposal of lead-based paint at interior and exterior locations indicated in existing conditions report. – There is no report in the bid documents and no work shown on drawings and specs, please identify on the scaled drawings locations/areas of these lead-based paint or provide quantities, also Para 2 states to use chemical stripper, can this chemical stripper used for both the interior and exterior locations?
Response: Please see attached Regulated Materials Survey Report dated 2020-06-23 for potential locations of lead-based paint.
15. Drawing S-002 Finishes – Flooring note no.1 C states shot blast floor or mechanically abrade floor area… --- is the existing floor paint lead-based paint?
Response: Please see attached Regulated Materials Survey Report dated 2020-06-23. Based on this report the concrete floor paint may contain lead.
16. Spec section 05 12 00 page 3, para 1.4 states AISC certified fabricator and erector is required. Is this correct and mandatory requirement?
Response: An AISC certified fabricator and erector is required.
17. Drawing S-002 Finishes – Flooring note no.2 states ‘Contractor to cover floor with epoxy paint with scattered media’ --- Please provide basis of design or manufacturer’s name and correct name of the paint system.
Response: VA does not allow specific manufacturer or model numbers to be included on engineering drawings.
18. Will VA have their own industrial hygienist for air monitoring for the work of asbestos abatement and lead-based paint removal and disposal? Please clarify in detail.
Response: Contractor shall provide the services of a CIH during all abatement activities per 02 83
33, Section 1.3.D.
19. Spec section 01 45 00 para 3.4 states to have a CQC system manager as one of the personnel requirements. Please clarify if this CQC system manager will be a full-time personnel and whether contractor’s site supervisor can simultaneously perform the duties of this CQC system manager? Also please clarify if there is any other full time personnel required to be hired by contractor for this quality control work, there is an extensive spec section with requirements so please clarify in detail.
Response: The contractor’s supervisor may simultaneously perform the duties of the CQC
System Manager. No other full-time personnel are required for this quality work.
20. Please provide whom is BMS vendor.
Response: Delta Connects, INC. Robert Hermano, 609-860-6600. This information is also on drawing M-801, under controls general notes.
p
REGULATED BUILDING MATERIALS
SURVEY REPORT
East Orange VA Medical Center Chiller Plant
A/E Design Services to Replace Both 900-Ton Chillers VA Project No. 561-18-125 385 Tremont Ave.
East Orange, NJ
June 23, 2020 Mabbett Project No. R2019057.001.001
Prepared for:
Miller-Remick, LLC.
1010 Kings Highway South Cherry Hill, NJ 08034
Mabbett & Associates, Inc.
105 Central Street, Suite 4100 Stoneham, MA 02180-1260 T. 781-275-6050 Massachusetts | Virginia | Rhode Island | New Jersey
© 2020, Mabbett & Associates, Inc.
www.mabbett.com
REGULATED BUILDING MATERIALS SURVEY REPORT
VAMC A/E Design Services to Replace Chillers | East Orange, N.J.
© 2020, Mabbett & Associates, Inc. Page i June 22, 2020 Project No. R2019057.001.001 S:\ADMINA\2019057 Miller-Remick\001\001\Miller-Remick East Orange VAMC Replace Chillers RBM Report V1 - Final.doc
ACKNOWLEDGEMENT
This Regulated Building Materials Survey Report has been prepared by Mabbett & Associates, Inc. (Mabbett®) for the A/E Design Services to Replace Both 900-ton Chillers at the East Orange Veterans Affairs Medical Center located in East Orange, New Jersey, VA Project No. 561-18-125. The information presented herein is based on the facts and information conveyed to or received by Mabbett during the preparation of this report. If any of the information provided to Mabbett that was used in preparing this report is incorrect, incomplete, or subject to change, Mabbett would wish to alter its opinion(s) accordingly. In addition, the professional opinions and information contained in this report are based solely on the requirements of the applicable regulations and technical data as known to Mabbett as of the date of this report and considered applicable to this report.
The attached Regulated Building Materials Survey Report was prepared by the following Mabbett personnel:
Brendan M. Clune Environmental, Health & Safety Specialist
This report has been reviewed and approved by:
Michael F. Delaney Director, Building Sciences Group
© 2020, Mabbett & Associates, Inc. Page ii June 22, 2020 Project No. R2019057.001.001 S:\ADMINA\2019057 Miller-Remick\001\001\Miller-Remick East Orange VAMC Replace Chillers RBM Report V1 - Final.doc
TABLE OF CONTENTS
SECTION PAGE
1.0 INTRODUCTION
2.0 ASBESTOS SURVEY
2.1 Sampling Methodology
2.2 Analytical Methodology
2.3 Summary of Asbestos Containing Materials Findings
3.0 LEAD CONTAINING PAINT SURVEY
4.0 CONCLUSIONS AND RECOMMENDATIONS
4.1 Asbestos
4.2 Lead Containing Paint
5.0 LIMITATIONS
TABLES
Table 1 – Summary of ACM (in text) Table 2 – Summary of Lead Paint Chip Analytical Results (in text)
FIGURES
HA-101 Asbestos and Lead Sampling Location Plan
APPENDICES
Appendix A – Summary of ACM Building Survey Results, Including Negative Results Appendix B – PLM Laboratory Report and Chain of Custody Appendix C – Lead Paint Chip Laboratory Report and Chain of Custody
© 2020, Mabbett & Associates, Inc. Page 1 June 22, 2020 Project No. R2019057.001.001 S:\ADMINA\2019057 Miller-Remick\001\001\Miller-Remick East Orange VAMC Replace Chillers RBM Report V1 - Final.doc
1.0 INTRODUCTION
Mabbett and Associates, Inc. (Mabbett®) performed a survey for regulated building materials (RBM) as part of the A/E Design to Replace Both 900-ton Chillers at the East Orange Veterans Affairs Medical Center (VAMC) located in East Orange, New Jersey, VA Project No. 561-18-125. Site survey work was performed on April 30, 2020 by appropriately credentialed regulated building materials inspectors, and consisted of the following activities:
A review of the existing 50% A/E Construction Documents;
An Asbestos Containing Material (ACM) survey of suspect materials (Analysis by Polarized Light Microscopy
[PLM]; and Limited Lead Containing Paint (LCP) sampling (Analysis by atomic absorption [AA]).
The survey was limited to the two 900-ton chillers and associated equipment located on the ground floor of the building and areas anticipated to be disturbed and identified on the 50% construction set drawing, dated March 31, 2020 which was provided to Mabbett prior to the survey. Areas and materials outside of this scope of work were not surveyed by Mabbett.
2.0 ASBESTOS SURVEY
A visual screening inspection was conducted by EPA trained and accredited asbestos inspectors to identify locations of suspect ACM and conceptualize the sampling program. Only areas that were accessible during the field work phase were inspected, with reasonable efforts made during the initial field survey work to access areas as necessary to complete the asbestos survey and sampling program.
Prior to the execution of this survey, provided Chiller Plant plans were examined and VA engineering personnel interviewed to discern the age and condition of existing materials, as well as the renovation history of the areas being surveyed.
2.1 Sampling Methodology
Site inspection work was performed on April 30, 2020, by EPA trained and accredited asbestos inspector Mr. Kevin Donovan. Bulk asbestos samples were collected using EPA National Emissions Standards for Hazardous Air Pollutants (NESHAP), 40 CFR Part 763, and Asbestos Hazard Emergency Response Act (AHERA) protocols. The inspection was limited to areas that may be impacted by the proposed renovation project. Bulk suspect ACM sampling was generally conducted according to the following sampling protocol:
Friable surfacing material:
At least three bulk samples shall be collected from each homogeneous area that is 1,000 ft2 or less.
At least five bulk samples shall be collected from each homogeneous area that is greater than 1,000 ft2 but less than or equal to 5,000 ft2.
At least seven bulk samples shall be collected from each homogeneous area that is greater than
5,000 ft2.
Thermal system insulation:
At least three bulk samples shall be collected from each homogeneous area of thermal system insulation.
At least one bulk sample shall be collected from each homogeneous area of patched area of thermal system insulation.
Sufficient samples shall be collected from elbows and fittings to determine if they contain ACM.
Bulk samples shall not be collected from any homogeneous area where the state licensed asbestos inspector determined that the thermal system insulation is fiberglass, foam glass, rubber, or other non-ACM.
© 2020, Mabbett & Associates, Inc. Page 2 June 22, 2020 Project No. R2019057.001.001 S:\ADMINA\2019057 Miller-Remick\001\001\Miller-Remick East Orange VAMC Replace Chillers RBM Report V1 - Final.doc
Miscellaneous material:
At least two bulk sample shall be collected from each homogeneous area that is less than 100 ft2.
At least three bulk samples shall be collected from each homogeneous area that is greater than 100 ft2.
Areas that were inaccessible, or where the survey was limited to visual observation only, are identified below:
Within walls Within fire doors Enclosed pipe/duct chases Inside mechanical equipment/ductwork Above fixed drywall or plaster ceilings Electrical equipment
2.2 Analytical Methodology
The collected bulk samples were submitted under chain of custody (COC) procedures to AmeriSci of Midlothian, VA for polarized light microscopy (PLM) analysis of bulk materials using EPA Methods 600/R-93/116. AmeriSci is accredited by the American Industrial Hygiene Association (AIHA) and participates in the National Voluntary Laboratory Accreditation Program (NVLAP) and is licensed by the New Jersey Department of Environmental Protection (NJDEP) (Certification No. VA012) for asbestos analysis.
All bulk sample results from this inspection are summarized in Appendix A, Summary of ACM Building Survey Results.
The EPA, Occupational Safety and Health Administration (OSHA), and the NJDEP defines any material that contains greater than one percent (>1%) asbestos as being an ACM. As such, the analytical laboratory identified bulk samples as positive for asbestos that met the regulatory criteria of greater than one percent (>1%) asbestos. Laboratory reports and COC documentation are provided in Appendix B of this report.
2.3 Summary of Asbestos Containing Materials Findings
Mabbett identified ten (10) areas of homogenous materials and collected thirty (30) representative bulk ACM samples. Asbestos sampling locations and results are identified on Figure HA-101. The laboratory reported analytical data indicated that one (1) homogenous material had greater than 1% asbestos and was identified as ACM.
Estimated quantities of materials identified as ACM are presented in Table 1 below:
TABLE 1
Summary of ACM
A/E Design Services to Replace Both 900-Ton Chillers East Orange Veterans Affairs Medical Center
Location Description of Material Percent and
Type of Asbestos
Estimated Quantity
Amount Units
Mechanical Room B-128, Floor Penetration Between 900-ton and 1,200-ton Chillers Pipe Penetration Packing 7% Chrysotile 1 Each
© 2020, Mabbett & Associates, Inc. Page 3 June 22, 2020 Project No. R2019057.001.001 S:\ADMINA\2019057 Miller-Remick\001\001\Miller-Remick East Orange VAMC Replace Chillers RBM Report V1 - Final.doc
3.0 LEAD CONTAINING PAINT SURVEY
The limited LCP survey included the collection of paint chips from painted surfaces and systems in the areas surveyed that may be impacted by the planned renovation. Seven (7) samples of different homogenous areas of paint were collected during this survey. Paint chip samples were submitted under standard COC procedures to Environmental Hazards Services, LLC (EHS), via AmeriSci. Analysis was conducted using EPA Method SW846 7000B:
Flame Atomic Absorption Spectrophotometry.
The results of the limited LCP sampling are summarized in Table 2, with laboratory reports provided in Appendix C.
TABLE 2
Summary of Lead Paint Chip Analytical Results
A/E Design Services to Replace Both 900-ton Chillers East Orange Veterans Affairs Medical Center
Sample # Location Substrate and
Component Color Result % Pb by Wt.)
Pb-01 Chiller 1 Metal Pipe White 0.056 Pb-02 Between Chillers Concrete Column White 0.0048 Pb-03 Ramp Metal Railing Blue <0.012 Pb-04 Top of Ramp Concrete Floor Gray <0.0049 Pb-05 Chiller Room Entry Metal Door Frame Brown 0.044 Pb-06 Cooling Tower Metal Beam White <0.0036 Pb-07 Chiller 2 Concrete Pad Yellow <0.0046
The Occupational Safety & Health Administration (OSHA) does not recognize a “safe” level of lead in paint.
Depending on the method of removal used, even trace amounts of lead in paint may result in airborne concentrations of lead during removal. An employer or contractor who disturbs or removes lead paint must comply with OSHA Standard 29 CFR 1926.62, “Lead Exposure in Construction; Interim Final Rule.”
4.0 CONCLUSIONS AND RECOMMENDATIONS
4.1 Asbestos
Identified ACM must be abated and properly disposed of prior to disturbance by state licensed and properly trained contractors. All abatement must be performed in accordance with federal, state and local requirements. Any suspect materials encountered during demolition or renovation activities that were not identified in this report as being non- ACM, should be assumed to be ACM unless sample results prove otherwise. Suspect ACM that may be present within operating equipment, walls, above inaccessible hard ceilings, or in other inaccessible locations, should be assumed to contain asbestos if discovered during any demolition or renovation process or until otherwise verified.
4.2 Lead Containing Paint
The purpose of the limited LCP survey was to identify similar areas of LCP. During the on-site survey, representative samples of similar areas of interior and exterior building coatings were collected and analyzed for lead content. The regulations addressing LCP in non-residential buildings are focused on occupational exposures involved with paint-disturbing activities and related waste-disposal activities.
Occupational exposure to lead during construction is regulated by OSHA regulation 29 CFR 1926.62 “Lead in Construction,” as well as other applicable state and local regulations. These regulations involve air monitoring to determine worker exposure levels when disturbing paint containing measurable levels of lead. This LCP survey
© 2020, Mabbett & Associates, Inc. Page 4 June 22, 2020 Project No. R2019057.001.001 S:\ADMINA\2019057 Miller-Remick\001\001\Miller-Remick East Orange VAMC Replace Chillers RBM Report V1 - Final.doc cannot determine a safe level of lead for the purpose of paint-disturbing activities. However, this report is intended to provide guidance as to the location of LCP so it can be controlled, abated or disposed of properly during this project’s construction related activities. Information gathered during this LCP survey should be used to determine where worker exposures to airborne lead may occur. Additionally, this information should also be used to assess the potential for exposure to workers, and for determining appropriate controls necessary to limit his or her health risks during this project.
A concentration of lead greater than or equal to 0.5 percent by weight or 1.0 mg/cm2 exceeds EPA and HUD residential standards and is considered an indicator of risk. Representative samples of LCP waste to be generated during building renovation, or following demolition but prior to disposal, should be collected and analyzed using toxicity characteristic leaching procedure (TCLP) in accordance with 40 CFR Part 261. Management and disposal of lead containing waste must be done in accordance with all applicable local, state, and federal regulations.
OSHA regulations may require certain procedures for any paint that contains lead, even if it is below these levels. All LCP identified, regardless of the lead content, should either be sampled and analyzed by TCLP and then handled/disposed of accordingly, or segregated from other large-scale debris and then managed as hazardous waste in accordance with federal, state and local hazardous waste disposal regulations.
5.0 LIMITATIONS
This survey report is the result of a diligent and thorough inspection for regulated building materials of the designated areas and materials that may be impacted by the renovation project. Inaccessible areas were not included in this survey. Although a comprehensive inspection of these areas was performed, Mabbett does not claim to have identified all hazardous materials that could be present in the facility (for example, materials potentially located within the inaccessible areas). Mabbett has conducted this assessment with reasonable care and has performed this project in accordance with generally accepted industry standards. There can be no assurances, and Mabbett makes no assurances, that the information, research, and technology used to prepare this report may not change in the future, thus affecting the results reported herein.
© 2020, Mabbett & Associates, Inc. FIGURES June 22, 2020 Project No. R2019057.001.001 Miller-Remick East Orange VAMC Replace Chillers RBM Report V1 - Final.doc
FIGURES
MECHANICAL
ROOM
B-128
STAIR 6
B-S6
LINEN
ROOM
B-134D
MECHANICAL
ROOM
B-128
OFFICE
B-134
TOILET
B-134B
CLOSET
B-134A
STAIR 5
B-S5
SHAFT 8
ELEC. CLO.
B-E-105
CLOSET
B-135
CORRIDOR
B-137C
CORRIDOR
B-133
WALK-IN
COOLER
B-128A
WALK-IN
COOLER
B-128B
MECHANICAL
ROOM
B-128D
REFRIG
B-119
REFRIG
B-118
REFRIG
B-120
CORR.
B-117
CORR.
B-113
STORAGE
FOOD
SERVICE
B-115
SUPERVISOR
FOOD
SERVICE
B-116
ASBESTOS AND LEAD (Pb)
SURVEY PLAN
ROOF PLAN
HA-101
DJAMFD
NO. DESCRIPTION DATE
o n e e i g h t h i n c o e f o t
B
A
C
D
E
F t h r e e i n c h e s o t o n e a d a l f i n c h e s o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned
Small Business
A
S r v i c e
D i s a b l
V t e r a
O w n
S m a l l
B u s i n e s s
SDVOSB
CVE
MR PROJECT NO: 0499-0120
B
A
C
D
E
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
100% SCHEMATIC DESIGN
NOT FOR CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseENGINEER OF RECORDCONSULTANT EAST ORANGE VAMC
REPLACE BOTH 900-TON
CHILLERS
VA EAST ORANGE CAMPUS
561-18-125
Project Director
2020-06-12
PLAN
NORTH
ACTUAL
NORTH
Scientists I Engineers I Program Managers
Mabbett & Associates, Inc.
105 Central Street Stoneham, MA 02180
T. 781-275-6050 www.mabbett.com
Mabbett
R
05A*
05A**
05A
05A
Pb-01
01APb-06
01C
01B
02A, 02B, 02C
03A*, 03B**, 03C**
Pb-01
09A
10A
06B, 06C
06A
10B, 10C
09B, 09C
Pb-05
Pb-02
08A, 08B, 08C
Pb-04
04A, 04B, 04C
07C
Pb-07Pb-03
07A
05B, 05C
05A
07B
AutoCAD SHX Text
KITCHEN
AutoCAD SHX Text I.V.
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text B-136
AutoCAD SHX Text
PROCESS
AutoCAD SHX Text
STORES
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text B-137A
AutoCAD SHX Text
WALKIN
AutoCAD SHX Text
REFRIG
AutoCAD SHX Text B-128C
AutoCAD SHX Text B-110
AutoCAD SHX Text
CLOSET
AutoCAD SHX Text B-401
AutoCAD SHX Text
B-ELEV13
AutoCAD SHX Text
ELEVATOR
AutoCAD SHX Text
IRM
AutoCAD SHX Text
DIETETICS
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text B-111
AutoCAD SHX Text
CHIEF
AutoCAD SHX Text
GENERAL
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text B-114
AutoCAD SHX Text
SUPERVISOR
AutoCAD SHX Text
DIET.
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text B-112
AutoCAD SHX Text
(E) COOLING TOWERCOOLING TOWER
AutoCAD SHX Text
DEDUCT-ALTERNATE CHILLER PUMPS
AutoCAD SHX Text
900-TON COOLING TOWER ON NEW DUNNAGE
AutoCAD SHX Text
(E) COOLING TOWERCOOLING TOWER
AutoCAD SHX Text
1-CT-3
AutoCAD SHX Text
CT-2
AutoCAD SHX Text
1-CT-1
AutoCAD SHX Text (E)
AutoCAD SHX Text (E)
AutoCAD SHX Text
(E) CONCRETE PIER (TYP)
AutoCAD SHX Text
FENCE
AutoCAD SHX Text
RETAINING WALL
AutoCAD SHX Text
(E) 1,200-TON CHILLER1,200-TON CHILLER
AutoCAD SHX Text
(E) MOTOR CONTROL CENTERMOTOR CONTROL CENTER
AutoCAD SHX Text
ON NEW CONCRETE PAD
AutoCAD SHX Text
1-CH-1
AutoCAD SHX Text
1-CH-2
AutoCAD SHX Text
1-CHP-4
AutoCAD SHX Text (N)
AutoCAD SHX Text
1-CHP-5
AutoCAD SHX Text (E)
AutoCAD SHX Text
1-CHP-6
AutoCAD SHX Text (N)
AutoCAD SHX Text
1-CHP-7
AutoCAD SHX Text (E)
AutoCAD SHX Text
1-CHP-8
AutoCAD SHX Text (E)
AutoCAD SHX Text
1-CHP-9
AutoCAD SHX Text (E)
AutoCAD SHX Text
(E) CHILLED CHILLED WATER BUILDING PUMPS
AutoCAD SHX Text
(E) BAS USER INTERFACE
AutoCAD SHX Text
(E) MCC
AutoCAD SHX Text
(E) CWP
AutoCAD SHX Text
(E) CWP
AutoCAD SHX Text
(E) VFD
AutoCAD SHX Text
(E) SSR
AutoCAD SHX Text
ON NEW CONCRETE PAD
AutoCAD SHX Text
TUBE PULL
AutoCAD SHX Text
TUBE PULL
AutoCAD SHX Text
CLEARANCE SPACE
AutoCAD SHX Text
MECHANICAL EQUIPMENT ROOM B-128
AutoCAD SHX Text
UTILITY SHOP B-119C
AutoCAD SHX Text
CLEARANCE SPACE
AutoCAD SHX Text
TUBE PULL
AutoCAD SHX Text
1-SSF-2
AutoCAD SHX Text
1-WCC-1
AutoCAD SHX Text
ON NEW CONCRETE PAD
AutoCAD SHX Text
1-CH-4
AutoCAD SHX Text
(E) CHP
AutoCAD SHX Text
CLEARANCE SPACE
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text
ASBESTOS AND LEAD SURVEY PLAN - ROOF PLAN
AutoCAD SHX Text 3/16" = 1'-0"
AutoCAD SHX Text
STOP POSITIVE SAMPLE FOR ASBESTOS
AutoCAD SHX Text
NO ASBESTOS DETECTED (NAD)
AutoCAD SHX Text
SAMPLE POSITIVE FOR ASBESTOS
AutoCAD SHX Text
APPROXIMATE SAMPLE LOCATION
AutoCAD SHX Text
GENERAL SHEET NOTES:
AutoCAD SHX Text LEAD (Pb) SAMPLING LOCATION
© 2020, Mabbett & Associates, Inc. APPENDIX A June 22, 2020 Project No. R2019057.001.001 Miller-Remick East Orange VAMC Replace Chillers RBM Report V1 - Final.doc
APPENDIX A
Summary of ACM Building Survey Results, Including Negative Results
© 2020, Mabbett & Associates, Inc. Appendix A Page 1 of 1 June 22, 2020 Project No. R2019057.001.001 Miller-Remick East Orange VAMC Replace Chillers RBM Report V1 - Final.doc
APPENDIX A
Summary of ACM Sampling Results A/E Design Services to Replace Both 900-ton Chillers
East Orange Veterans Affairs Medical Center
Sample No. Sample Location Description of Material
Percent and Type of
Asbestos 01A Ext. Cooling Tower - NW Corner Cooling Tower Caulk NAD 01B Ext. Cooling Tower - NE Corner Cooling Tower Caulk NAD 01C Ext. Cooling Tower - South Corner Cooling Tower Caulk NAD 02A 200 Ton Chiller, Wall Penetration Wall Patching at Pipe Penetration NAD 02B 200 Ton Chiller, Wall Penetration Wall Patching at Pipe Penetration NAD 02C 200 Ton Chiller, Wall Penetration Wall Patching at Pipe Penetration NAD 03A 200 Ton Chiller, Floor Penetration Pipe Penetration Packing 7% Chrysotile 03B 200 Ton Chiller, Floor Penetration Pipe Penetration Packing NA/PS 03C 200 Ton Chiller, Floor Penetration Pipe Penetration Packing NA/PS 04A Chiller Room by Switch Gear Red Fire Stop NAD 04B Chiller Room by Switch Gear Red Fire Stop NAD 04C Chiller Room by Switch Gear Red Fire Stop NAD 05A Chiller Room, Interior Double Doors White Door Frame Caulk NAD 05B Chiller Room, Interior Double Doors White Door Frame Caulk NAD 05C Chiller Room, Interior Double Doors White Door Frame Caulk NAD 06A Chiller Room Entry Brown Door Frame Caulk NAD 06B Chiller Room Entry Brown Door Frame Caulk NAD 06C Chiller Room Entry Brown Door Frame Caulk NAD 07A Chiller Room White Fiberglass End Sealant NAD 07B Chiller Room White Fiberglass End Sealant NAD 07C Chiller Room White Fiberglass End Sealant NAD 08A Chiller Room, Chilled Water Supply Fitting Insulation on Fiberglass Pipe NAD 08B Chiller Room, Chilled Water Supply Fitting Insulation on Fiberglass Pipe NAD 08C Chiller Room, Chilled Water Supply Fitting Insulation on Fiberglass Pipe NAD 09A Exterior, Rear of Building Brick Mortar NAD 09B Exterior, Rear of Building Brick Mortar NAD 09C Exterior, Rear of Building Brick Mortar NAD 10A Exterior, Rear of Building Gray Expansion Joint Caulk NAD 10B Exterior, Rear of Building Gray Expansion Joint Caulk NAD 10C Exterior, Rear of Building Gray Expansion Joint Caulk NAD Notes: NAD = No Asbestos Detected
NA/PS = Not Analyzed, Positive Stop
© 2020, Mabbett & Associates, Inc. APPENDIX B June 22, 2020 Project No. R2019057.001.001 Miller-Remick East Orange VAMC Replace Chillers RBM Report V1 - Final.doc
APPENDIX B
PLM Laboratory Report and Chain of Custody
AmeriSci Richmond
13635 GENITO ROAD
MIDLOTHIAN, VA 23112
TEL: (804) 763-1200 • FAX: (804) 763-1800
May 5, 2020
Dear Michael Delaney:
Mabbett & Associates, Inc.
Attn: Michael Delaney 105 Central Street Suite 4100 Stoneham, MA 02180
RE: Mabbett & Associates, Inc.
Job Number 120051035 P.O. #R2019057.001 R2019057.001; East Orange VAMC; East Orange, NJ
Enclosed are the results for PLM asbestos analysis of the following Mabbett & Associates, Inc. samples received at AmeriSci on Monday, May 4, 2020, for a 24 hour turnaround:
01A, 01B, 01C, 02A, 02B, 02C, 03A, 03B, 03C, 04A, 04B, 04C, 05A, 05B, 05C, 06A, 06B, 06C, 07A, 07B, 07C, 08A, 08B, 08C, 09A, 09B, 09C, 10A, 10B, 10C
The 30 samples contained in zip lock bag were shipped to AmeriSci via UPS1Z5AR1431500259080. These samples were prepared and analyzed according to EPA PLM Method (EPA 600/R-93/116 Section 2.2). The required analytical information, analysis results, analyst signature and laboratory identification are contained in the PLM Bulk Asbestos Report. If TEM analysis was requested for selected samples the gravimetric reduction data (by Sec 2.3) and TEM Asbestos % (by Sec 2.5) are included in Table 1 along with a summary of Asbestos % by PLM for all samples analyzed.
This report relates ONLY to the sample analysis expressed as % asbestos. AmeriSci assumes no responsibility for customer supplied data such as “sample type”, "location", or “area sampled”. This report must not be used to claim product endorsement by AmeriSci, NVLAP or any agency of the U. S. Government. The National Institute of Standards and Technology accreditation requirements mandate that this report must not be reproduced, except in full, without the written approval of the laboratory. This report may contain specific data not covered by NVLAP or ELAP accreditations, if so identified in relevant footnotes.
Sincerely, Authorized Signatory
AmeriSci appreciates this opportunity to serve your organization. Please contact us for any further assistance or with any questions.
Boston - Los Angeles - New York - Richmond
13635 GENITO ROAD
MIDLOTHIAN, VIRGINIA 23112
TEL: (804) 763-1200 • FAX: (804) 763-1800
05/04/20 AmeriSci Job # 120051035 05/04/20
1 6 R2019057.001; East Orange VAMC; East Orange, NJ
PLM Bulk Asbestos Report Date Received Date Examined
RE:
ofPage
P.O. # Mabbett & Associates, Inc.
105 Central Street Suite 4100 Stoneham, MA 02180
Attn: Michael Delaney
Asbestos Present Total % AsbestosClient No. / HGA Lab No.
Location:
Analyst Description:
Asbestos Types:
Other Material:
No01A 120051035-01 NAD Exterior Cooling Tower - NW Corner; Cooling Tower Caulk1
Black, Homogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No01B 120051035-02 NAD Exterior Cooling Tower - NE Corner; Cooling Tower Caulk1
Black, Homogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No01C 120051035-03 NAD Exterior Cooling Tower - South Corner; Cooling Tower Caulk1
Black, Homogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No02A 120051035-04 NAD 200 Ton Chiller Wall Penetration; Wall Patching @ Pipe2
Gray, Homogeneous, Non-Fibrous, Cementitious, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No02B 120051035-05 NAD 200 Ton Chiller Wall Penetration; Wall Patching @ Pipe2
Gray, Homogeneous, Non-Fibrous, Cementitious, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
See Reporting notes on last page
AmeriSci Job #: 120051035 Page 2 of 6
R2019057.001; East Orange VAMC; East Orange, NJ
PLM Bulk Asbestos Report Client Name: Mabbett & Associates, Inc.
Asbestos Present Total % AsbestosClient No. / HGA Lab No.
Location:
Analyst Description:
Asbestos Types:
Other Material:
No02C 120051035-06 NAD 200 Ton Chiller Wall Penetration; Wall Patching @ Pipe2
Gray, Homogeneous, Non-Fibrous, Cementitious, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
Yes03A 120051035-07 7 % 200 Ton Chiller Floor Penetration; Pipe Penetration Packing3
Brown/Off-White, Homogeneous, Non-Fibrous, Bulk Material Chrysotile 7.0 % Non-fibrous 93 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
03B 120051035-08 NA/PS
200 Ton Chiller Floor Penetration; Pipe Penetration Packing3
Bulk Material
Location:
Analyst Description:
Asbestos Types:
Other Material:
03C 120051035-09 NA/PS
200 Ton Chiller Floor Penetration; Pipe Penetration Packing3
Bulk Material
Location:
Analyst Description:
Asbestos Types:
Other Material:
No04A 120051035-10 NAD Chiller Room By Switch Gear; Red Fire Stop4
Red, Homogeneous, Fibrous, Bulk Material
Fibrous glass 10 %, Non-fibrous 90 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No04B 120051035-11 NAD Chiller Room By Switch Gear; Red Fire Stop4
Red, Homogeneous, Fibrous, Bulk Material
Fibrous glass 10 %, Non-fibrous 90 %
(by CVES) by Gordon T. Saleeby
AmeriSci Job #: 120051035 Page 3 of 6
PLM Bulk Asbestos Report Client Name: Mabbett & Associates, Inc.
Asbestos Present Total % AsbestosClient No. / HGA Lab No.
Location:
Analyst Description:
Asbestos Types:
Other Material:
No04C 120051035-12 NAD Chiller Room By Switch Gear; Red Fire Stop4
Red, Homogeneous, Fibrous, Bulk Material
Fibrous glass 10 %, Non-fibrous 90 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No05A 120051035-13 NAD Chiller Room - Interior Double Doors; White Door Frame Caulk5
Off-White/Lt.Gray, Homogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No05B 120051035-14 NAD Chiller Room - Interior Double Doors; White Door Frame Caulk5
Off-White/Lt.Gray, Homogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No05C 120051035-15 NAD Chiller Room - Interior Double Doors; White Door Frame Caulk5
Off-White/Lt.Gray, Homogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No06A 120051035-16 NAD Chiller Room - Entry; Brown Door Frame Caulk6
Brown, Heterogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No06B 120051035-17 NAD Chiller Room - Entry; Brown Door Frame Caulk6
Brown, Heterogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby
AmeriSci Job #: 120051035 Page 4 of 6
PLM Bulk Asbestos Report Client Name: Mabbett & Associates, Inc.
Asbestos Present Total % AsbestosClient No. / HGA Lab No.
Location:
Analyst Description:
Asbestos Types:
Other Material:
No06C 120051035-18 NAD Chiller Room - Entry; Brown Door Frame Caulk6
Brown, Heterogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No07A 120051035-19 NAD Chiller Room; White Fiberglass End Sealant7
White, Heterogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No07B 120051035-20 NAD Chiller Room; White Fiberglass End Sealant7
White, Homogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No07C 120051035-21 NAD Chiller Room; White Fiberglass End Sealant7
White, Heterogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No08A 120051035-22 NAD Chiller Room - Chilled Water Supply; Fitting Insulation On F/G Pipe8
White/Lt. Gray, Heterogeneous, Fibrous, Bulk Material
Cellulose 10 %, Fibrous glass 30 %, Non-fibrous 60 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No08B 120051035-23 NAD Chiller Room - Chilled Water Supply; Fitting Insulation On F/G Pipe8
White/Lt. Gray, Heterogeneous, Fibrous, Bulk Material
Cellulose 10 %, Fibrous glass 30 %, Non-fibrous 60 %
(by CVES) by Gordon T. Saleeby
AmeriSci Job #: 120051035 Page 5 of 6
PLM Bulk Asbestos Report Client Name: Mabbett & Associates, Inc.
Asbestos Present Total % AsbestosClient No. / HGA Lab No.
Location:
Analyst Description:
Asbestos Types:
Other Material:
No08C 120051035-24 NAD Chiller Room - Chilled Water Supply; Fitting Insulation On F/G Pipe8
White/Lt. Gray, Heterogeneous, Fibrous, Bulk Material
Cellulose 10 %, Fibrous glass 30 %, Non-fibrous 60 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No09A 120051035-25 NAD Exterior - Rear Of Building; Brick Mortar9
Lt. Gray, Homogeneous, Non-Fibrous, Cementitious, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No09B 120051035-26 NAD Exterior - Rear Of Building; Brick Mortar9
Lt. Gray, Homogeneous, Non-Fibrous, Cementitious, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No09C 120051035-27 NAD Exterior - Rear Of Building; Brick Mortar9
Lt. Gray, Homogeneous, Non-Fibrous, Cementitious, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No10A 120051035-28 NAD Exterior - Rear Of Building; Gray Expansion Joint Caulk10
Lt. Tan, Homogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Location:
Analyst Description:
Asbestos Types:
Other Material:
No10B 120051035-29 NAD Exterior - Rear Of Building; Gray Expansion Joint Caulk10
Lt. Tan, Homogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby
AmeriSci Job #: 120051035 Page 6 of 6
PLM Bulk Asbestos Report Client Name: Mabbett & Associates, Inc.
Asbestos Present Total % AsbestosClient No. / HGA Lab No.
Location:
Analyst Description:
Asbestos Types:
Other Material:
No10C 120051035-30 NAD Exterior - Rear Of Building; Gray Expansion Joint Caulk10
Lt. Tan, Homogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100 %
(by CVES) by Gordon T. Saleeby on 05/04/20
Reporting Notes:
Analyzed by: Gordon T. Saleeby________________________________ Date: 5/4/2020 Reviewed by:________________________________
*NAD = no asbestos detected, Detection Limit <1%, Reporting Limits: CVES = 1%, 400 Pt Ct = 0.25%, 1000 Pt Ct = 0.1%; "Present" or NVA = "No Visible Asbestos" are observations made during a qualitative analysis; NA = not analyzed; NA/PS = not analyzed / positive stop; PLM Bulk Asbestos Analysis by EPA 600/R-93/116 per 40 CFR 763 (NVLAP Lab Code 101904-0) and ELAP PLM Analysis Protocol 198.1 for New York friable samples which includes quantitation of any vermiculite observed (198.6 for NOB samples) or EPA 400 pt ct by EPA 600/M4-82-020 (NYSDOH ELAP Lab # 10984); CA ELAP Lab # 2508; Note: PLM is not consistently reliable in detecting asbestos in floor coverings and similar NOB materials. NAD or Trace results by PLM are inconclusive, TEM is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos-containing in New York State (also see EPA Advisory for floor tile, FR 59, 146, 38970, 8/1/94). NIST Accreditation requirements mandate that this report must not be reproduced except in full without the approval of the laboratory. This PLM report relates ONLY to the items tested.
© 2020, Mabbett & Associates, Inc. APPENDIX C June 22, 2020 Project No. R2019057.001.001 Miller-Remick East Orange VAMC Replace Chillers RBM Report V1 - Final.doc
APPENDIX C
Lead Paint Chip Laboratory Report and Chain of Custody
Analysis Report
Client:
Project/Test Address:
Ameri-Sci
7469 Whitepine Rd
Telephone: 800.347.4010 Richmond, VA 23237
Environmental Hazards Services, L.L.C.
120-05-1040; R2019057.001; East Orange VAMC; Chiller Replacement
Client Number:
48-3042
Fax Number:
804-763-1800Laboratory Results
Analyzed Date:
Client Sample Number
Lab Sample Number
Pb (ug/g) ppm
Lead Paint Chip
05/05/2020
05/04/2020
20-05-00281
Reported Date:
Received Date:
Report Number:
13635 Genito Road Midlothian, VA 23112-400
Narrative
ID
05/05/2020
Collection Location % Pb by Wt.
04/30/2020Collection Date:
PB-01 WHITE
METAL PI
20-05-00281-001 CHILLER 1 560 0.056
PB-02 WHITE
CONCRETE
20-05-00281-002 BETWEEN CHILLERS 48 0.0048
PB-03 BLUE
METAL RAI
20-05-00281-003 L03RAMP <120 <0.012
PB-04 GRAY
CONCRETE
20-05-00281-004 TOP OF RAMP <49 <0.0049
PB-05 BROWN
METAL DO
20-05-00281-005 CHILLER ROOM ENTRY 440 0.044
PB-06 WHITE
METAL BE
20-05-00281-006 COOLING TOWER <36 <0.0036
PB-07
YELLOW
CONCRET
20-05-00281-007 CHILLER 2 <46 <0.0046
Page 2of1
Report Number:
Environmental Hazards Services, L.L.C
Project/Test Address:
Client Number: 20-05-00281
120-05-1040; R2019057.001; East Orange VAMC;
Chiller Replacement
48-3042
Collection LocationClient Sample Number
Lab Sample Number
% Pb by Wt.
Narrative
ID
Pb (ug/g) ppm
Missy Kanode QA/QC Clerk
Analysis Method: EPA SW846 7000B
The HUD lead guidelines for lead paint chips are 0.50% by Weight, 5000 ppm, or 1.0 mg/cm². The Reporting Limit (RL) for samples prepared by ASTM E-1979-17 is 10.0 ug Total Pb. The RL for samples prepared by EPA SW846 3050B is 25.0 ug Total Pb. Paint chip area and results are calculated based on area measurements determined by the client. All internal quality control requirements associated with this batch were met, unless otherwise noted.
LEGEND Pb= lead ug = microgram ppm = parts per million ug/g = micrograms per gram Wt. = weight
Reviewed By Authorized Signatory:
L03: Sample submitted was less than the recommended amount. A minimum of 0.1 grams should be submitted.
Sample Narratives:
Preparation Method: ASTM E-1979-17
The condition of the samples analyzed was acceptable upon receipt per laboratory protocol unless otherwise noted on this report. Results represent the analysis of samples submitted by the client. Sample location, description, area, etc., was provided by the client. Results reported above in mg/cm3 are calculated based on area supplied by client. This report shall not be reproduced except in full, without the written consent of the Environmental Hazards Service, L.L.C.
ELLAP Accredtitation through AIHA-LAP, LLC (100420), NY ELAP #11714.
Page 2of2
NO. DESCRIPTION DATE
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0120
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
ISSUED FOR BID
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT EAST ORANGE VAMC
REPLACEMENT BOTH 900-TON
CHILLERS
VA EAST ORANGE CAMPUS
561-18-125
Project Director
2020-08-19
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
ELECTRICAL
MOTOR CONTROL CENTER DETAILS
& SCHEDULES
E-601
MJRMJR
B-128
STAIR 6
B-S6
UTILITY
SHOP
B-119C
LINEN
ROOM
B-134D
MECHANICAL
ROOM
B-128
OFFICE
B-134
TOILET
B-134B
CLOSET
B-134A
STAIR 5
B-S5
SHAFT 8
ELEC. CLO.
B-E-105
CLOSET
B-135
CORRIDOR
B-137C
CORRIDOR
B-133
WALK-IN
COOLER
B-128A
WALK-IN
COOLER
B-128B
MECHANICAL
ROOM
B-128D
REFRIG
B-119
REFRIG
B-118
REFRIG
B-120
CORR.
B-117
CORR.
B-113
STORAGE
FOOD
SERVICE
B-115
SUPERVISOR
FOOD
SERVICE
B-116
ELECTRICAL
DEMOLITION PLAN
ED101
MJRMJR
PLAN
NORTH
ACTUAL
NORTH
KEYPLAN
NO. DESCRIPTION DATE
PLAN
NORTH
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0120
KEYPLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
ISSUED FOR BID
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT EAST ORANGE VAMC
REPLACEMENT BOTH 900-TON
CHILLERS
VA EAST ORANGE CAMPUS
561-18-125
Project Director
2020-08-19
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
B-128
STAIR 6
B-S6
UTILITY
SHOP
B-119C
LINEN
ROOM
B-134D
MECHANICAL
ROOM
B-128
OFFICE
B-134
TOILET
B-134B
CLOSET
B-134A
STAIR 5
B-S5
SHAFT 8
ELEC. CLO.
B-E-105
CLOSET
B-135
CORRIDOR
B-137C
CORRIDOR
B-133
WALK-IN
COOLER
B-128A
WALK-IN
COOLER
B-128B
MECHANICAL
ROOM
B-128D
REFRIG
B-119
REFRIG
B-118
REFRIG
B-120
CORR.
B-117
CORR.
B-113
STORAGE
FOOD
SERVICE
B-115
SUPERVISOR
FOOD
SERVICE
B-116
ELECTRICAL
POWER PLAN
EP101
MJRMJR
PLAN
NORTH
ACTUAL
NORTH
KEYPLAN
NO. DESCRIPTION DATE
PLAN
NORTH
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0120
KEYPLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
ISSUED FOR BID
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT EAST ORANGE VAMC
REPLACEMENT BOTH 900-TON
CHILLERS
VA EAST ORANGE CAMPUS
561-18-125
Project Director
2020-08-19
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F