36C24219B0046-0001001.pdf

PDF 354 KB Posted

Attached to
Repair Failing Doors Federal contract opportunity
Solicitation number
36C24219B0046
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

36C24219B0046 0001 Replace Failing Fire doors - RFI Responses Revised.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Repair Failing Doors, newest first.
File Type Posted
36C24219B0046-0002000.docx DOCX document
36C24219B0046-0001002.pdf PDF
36C24219B0046-0001003.pdf PDF
36C24219B0046-0001000.docx DOCX document
36C24219B0046-002.pdf PDF
36C24219B0046-004.pdf PDF
36C24219B0046-003.pdf PDF
36C24219B0046-001.docx DOCX document
36C24219B0046-000.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Requests for Information

Project Name: Replace Multiple Failing Fire doors Project No: 528A7-18-712

Project Location: Syracuse VAMC

RFI#1 Is the attached Von Duprin 99-F Rim Exit Device with Safety Glow feature acceptable for this project? I am having trouble locating a model of exit device that meets all the requirements listed on the hardware schedule. Or can you provide a Manufacturer and Model that does meet the requirements or is a basis of design?

Answer:

Push bar must include the word “Exit” in its finish using photoluminescence technology. Provide product as specified in the bid documents.

RFI#2: Hardware sets call out a threshold with Thermo-Seals. I do not see where thresholds are needed nor wanted at all on interior stairway doors. Please check with them to be sure.

Answer:

Thresholds are not required and have been removed from the bid documents. Replace specification section 08 71 00 in its entirety with revised specification section 08 71 00 dated 8/29/19 to reflect deletion of thresholds.

RFI#3) Continuous hinges are specified for all replacement doors. However, the installation of a continuous hinge is not compatible with existing solid grout filled frames. Can replacement of existing Butt Hinges be specified in lieu of Continuous Hinges.

Answer:

Provide continuous hinges as specified in the bid documents. Replace specification section 08 71 00 in its entirety with revised specification section 08 71 00 dated 8/29/19 to reflect deletion of butt hinges.

All existing hinge pockets in the existing frames are to be filled with steel frame filler plates prior to installation of the new continuous hinges. As the existing frames are grouted, predrilling into the steel frame and grout will be required for proper installation of the continuous hinges.