528A5-17-549 RENOVATE B36 1st FLOOR Federal contract opportunity
Solicitation number
36C24219B0043
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

36C24219B0043 S02 -Renovate B36A DRAWINGS.pdf

View the file

Other files for this federal contract opportunity

Other files attached to 528A5-17-549 RENOVATE B36 1st FLOOR, newest first.
File Type Posted
36C24219B0043-0004001.pdf PDF
36C24219B0043-0004000.docx DOCX document
36C24219B0043-0004000.docx DOCX document
36C24219B0043-0004001.pdf PDF
36C24219B0043-0003000.docx DOCX document
36C24219B0043-0003000.docx DOCX document
36C24219B0043-0002000.docx DOCX document
36C24219B0043-0002001.pdf PDF
36C24219B0043-0002000.docx DOCX document
36C24219B0043-0002001.pdf PDF
36C24219B0043-0001001.pdf PDF
36C24219B0043-0001000.docx DOCX document
36C24219B0043-0001001.pdf PDF
36C24219B0043-0001000.docx DOCX document
36C24219B0043-001.docx DOCX document
36C24219B0043-002.pdf PDF
36C24219B0043-005.pdf PDF
36C24219B0043-004.pdf PDF
36C24219B0043-003.pdf PDF
36C24219B0043-005.pdf PDF
36C24219B0043-002.pdf PDF
36C24219B0043-003.pdf PDF
36C24219B0043-001.docx DOCX document
36C24219B0043-000.docx DOCX document
36C24219B0043-000.docx DOCX document
Show all 25

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

System No. C-AJ-5096

SECTION A-A

A

A

5B 1

5A

5B

C

CL

ASS IF IED

Classified by Underwriters Laboratories, Inc.

to UL 1479 and CAN/ULC-S115

US

ANSI/UL1479 (ASTM E814) CAN/ULC S115

F Rating — 2 Hr F Rating — 2 Hr

T Rating — 0 Hr FT Rating — 0 Hr

L Rating At Ambient — 4 CFM/sq ft FH Rating — 2 Hr

L Rating At 400 F — Less Than 1 CFM/sq ft FTH Rating — 0 Hr

L Rating At Ambient — 4 CFM/sq ft

L Rating At 400 F — Less Than 1 CFM/sq ft

Db Wb

CFM IN WG MBH °F °F GPM °F FT IN BTUH °F GPM °F FT MERV RATING HP W

36-FCU-1 OPEN OFFICE 103 VESTIBULE 102, OFFICE

101, OFFICE 103 HORIZONTAL 850 0.25 21.3 80 67 4.3 45 3.45 3/4 21.3 60 2.1 180 3.94 8 0.130 39 1 115 1080 LOW/MED/HIGH 1

36-FCU-2 OPEN OFFICE 104 OPEN OFFICE 104 HORIZONTAL 570 0.25 12.7 80 67 2.5 45 3.45 3/4 12.7 60 1.3 180 3.94 8 0.130 39 1 115 1080 LOW/MED/HIGH 1

36-FCU-3 BREAK ROOM 105 BREAK ROOM 105 HORIZONTAL 570 0.25 12.7 80 67 2.5 45 3.45 3/4 12.7 60 1.3 180 3.94 8 0.130 39 1 115 1080 LOW/MED/HIGH 1

36-FCU-4 WOMEN'S 115 WOMEN'S 115

MEN'S 118 HORIZONTAL 300 0.25 8.3 80 67 1.7 45 3.45 3/4 8.3 60 0.8 180 3.94 8 0.130 39 1 115 1080 LOW/MED/HIGH 1

36-FCU-5 CORRIDOR 114 CORR 114 & 133,

VESTIBULE 117 HORIZONTAL 740 0.25 3.0 80 67 0.6 45 3.45 3/4 3.0 60 0.3 180 3.94 8 0.130 39 1 115 1080 LOW/MED/HIGH 1

36-FCU-6 OPEN OFFICE 123 OPEN OFFICE 123 HORIZONTAL 975 0.25 46.5 80 67 9.3 45 3.45 3/4 46.5 60 4.7 180 3.94 8 0.130 39 1 115 1080 LOW/MED/HIGH 1

36-FCU-7 CONFERENCE 122 CONFERENCE 122 HORIZONTAL 650 0.25 19.8 80 67 4 45 3.45 3/4 19.8 60 2 180 3.94 8 0.130 39 1 115 1080 LOW/MED/HIGH 1

36-FCU-8 OPEN OFFICE 123 OPEN OFFICE 123 HORIZONTAL 975 0.25 46.5 80 67 9.3 45 3.45 3/4 46.5 60 4.7 180 3.94 8 0.130 39 1 115 1080 LOW/MED/HIGH 1

36-FCU-9 OFFICE 127 OFFICES 127 & 128 HORIZONTAL 360 0.25 8.5 80 67 1.7 45 3.45 3/4 8.5 60 0.9 180 3.94 8 0.130 39 1 115 1080 LOW/MED/HIGH 1

36-FCU-10 OFFICE 129 OFFICES 129, 130, 131 HORIZONTAL 530 0.25 12.6 80 67 2.5 45 3.45 3/4 12.6 60 1.3 180 3.94 8 0.130 39 1 115 1080 LOW/MED/HIGH 1

36-FCU-11 COMMUNICATIONS COMMUNICATIONS HORIZONTAL 250 0.25 5.6 80 67 1.1 45 3.45 3/4 5.6 60 0.6 180 3.94 8 0.130 39 1 115 1080 LOW/MED/HIGH 1

NOTES:

TOTAL

CAPACITY POWER

PHASE

FLOWAREA OR ROOMS

SERVED

EWT

FILTEREAT

VOLT

HEATING REQUIREMENTS

RPM

FLOWEAT Db SPEED

CONTROL

WPDMARK LOCATION

COOLING REQUIREMENTS

RUNOUT

SIZE

TOTAL

CAPACITY

FAN MOTOR

NOTES

EWT

EXTERNAL

APD WPDTYPE

TWO-PIPE FAN COIL UNIT SCHEDULE [PRE-PURCHASED]

FAN

AIR FLOW

CONDENSER

NOMINAL

TONS GPM °F °F FT °F HP

36-ACCH-1 BLDG 36 BLDG 36 SCROLL 30 2 0.93 15.6 67.1 54 44 15 0.0001 95 2 3 460 3 1.2 3 460 1,2

VOLT

CONDENSER FAN MOTORS

ELECTRICAL

NOTES

AIR COOLED CHILLER SCHEDULE [PRE-PURCHASED]

MARK

AREA

AND/OR BLDG

SERVED

FOULING

FACTOR

COMPRESSOR MOTOR

TYPE EWT LWT MAX

WPD

CAPACITY MAX

kW/TON

FLOWLOCATION

EVAPORATOR

PHASE PHASE

AMBIENT OA

TEMP

NOTES:

# OF

COMP VOLT # FANS# COMP

MAX IPLV

(kW/TON)

PANEL

FRAME SIZE

NECK

SIZE

MIN MAX

CFM CFM

SUPPLY DIFFUSER 0 100 0.100 CEILING 24x24 6 25 NONE WHITE TITUS/TDC 1,2,3,4,5,6,7,8

SUPPLY DIFFUSER 101 200 0.100 CEILING 24x24 8 25 NONE WHITE TITUS/TDC 1,2,3,4,5,6,7,8

SUPPLY DIFFUSER 201 325 0.100 CEILING 24x24 10 25 NONE WHITE TITUS/TDC 1,2,3,4,5,6,7,8

RETURN GRILLE FIXED LOUVER

35 DEG. DEFLECTION 3/4 BLADE 0 100 0.100 CEILING 24x24 6x6 25 NONE WHITE TITUS/350 4,6

RETURN GRILLE FIXED LOUVER

35 DEG. DEFLECTION 3/4 BLADE 101 275 0.100 CEILING 24x24 10x10 25 NONE WHITE TITUS/350 4,6

RETURN GRILLE FIXED LOUVER

35 DEG. DEFLECTION 3/4 BLADE 276 400 0.100 CEILING 24x24 12x12 25 NONE WHITE TITUS/350 4,6

EXHAUST GRILLE FIXED LOUVER

35 DEG. DEFLECTION 3/4 BLADE 101 275 0.100 CEILING 12x12 10x10 25 NONE WHITE TITUS/350 4,6

EXHAUST GRILLE FIXED LOUVER

35 DEG. DEFLECTION 3/4 BLADE 0 100 0.100 CEILING 12X12 6x6 25 NONE WHITE TITUS/350 4,6

NOTES:

AIR FLOW

IN

ADE-1

TYPE

MAX

APD BASIS OF DESIGN

OR APPROVED EQUALNC FINISHMARK

ADS-1

ADR-1

AIR DEVICE SCHEDULE

NOTESDAMPERMOUNTING

IN x IN

BHP HP

36-EF-1 MEN'S TOILET 118 BLDG 36

RMS 115, 116, 118 EXHAUST 800 0.5 INLINE DIRECT 1031 0.311 1/2 1 120 1500 FSC GEMINI GN-862 1

NOTES:

EXHAUST FAN SCHEDULE

AREA AND/OR

BLDG SERVED

SYSTEM

AND/OR

SERVICE VOLT

FAN

MAX

RPM

DRIVE

MARK

RPM

NOMINAL

POWER

LOCATION

TYPE

FAN

AIR

FLOW

(CFM)

TSP

(IN)

BASIS OF

DESIGN OR

APPROVED

EQUAL

MOTOR ELECTRICAL

NOTESSPEED

CONTROLPHASE

FLOW HEAD NPSH AVAILABLE TEMPERATURE NOMINAL

POWER

GPM FT FT °F HP

36-P 1A HHW SKID BUILDING 36 HEATING WATER/

SYSTEM IN-LINE WATER 30 30 6.17 180 50.9 1 3 460 1750 VFD BELL & GOSSETT E-80 SERIES

OR EQUAL -

36-P 1B HHW SKID BUILDING 36 HEATING WATER/

SYSTEM IN-LINE WATER 30 30 6.17 180 50.9 1 3 460 1750 VFD BELL & GOSSETT E-80 SERIES

OR EQUAL -

PHASE VOLT MAX

RPM

BASIS OF DESIGN

OR APPROVED EQUAL NOTESSPEED

CONTROL

SYSTEM

AND/OR

SERVICE

TYPE

PUMP SCHEDULE

MARK LOCATION

AREA

AND/OR

BLDG SERVED

CIRCULATING FLUID

MIN %

EFF

ELECTRICAL MOTOR

FLUID

SIZE IN FLOW WPD

IN GPM FT

36-AS 1 SUBASMENT HEATING AND

CHILLED WATER

FULL FLOW

TANGENTIAL 3 70 0.24 BELL & GOSSET RL-3F OR EQUAL -

AIR SEPARATOR SCHEDULE

AIR SEPARATOR

BASIS OF DESIGN

OR APPROVED EQUALMARK LOCATION SYSTEM AND/OR

SERVICE NOTESTYPE

MIN MAX

GAL °F °F PSIG PSIG GAL IN IN

36-ET 1 HHW SKID HEATING WATER HORIZONTAL

DIAPHRAGM 265 140 180 30 70 20 1 3/4 BELL & GOSSETT D-40 OR EQUAL -

BASIS OF DESIGN

OR APPROVED EQUAL

PIPE SIZE

TO TANK

COLD WATER

FILL SIZE

SYSTEM

TEMPERATURE INITIAL

PRESSURE

IN TANK

MAX

OPERATING

PRESSURE

EXPANSION TANK SCHEDULE

APPROX

SYSTEM

VOLUME

MIN

VOLUME

TANKTYPE NOTESMARK LOCATION

SYSTEM

AND/OR

SERVICE

FLOW EWT LWT WPD ENT

CONTROL VALVE

ENT

HEAT EXCHANGER CAPACITY

GPM °F °F FT PSIG PSIG LBS/HR LBS/HR

36-HX-1 HHW SKID BUILDING 36 HEATING WATER SHELL & TUBE 30 160 180 9 25 5 303 - 310 BELL & GOSSET -

SYSTEM

AND/OR

SERVICE

STEAM PRESSURE

TYPE BASIS OF DESIGN

OR APPROVED EQUAL

STEAM TO WATER HEAT EXCHANGER SCHEDULE

MARK LOCATION AREA AND/OR

BLDG SERVED

TRAP

TRAP #

WATER CONDITIONS

NOTES

CONTROL

VALVE