36C24219B0029-004.pdf

PDF 10 MB Posted

Attached to
528A7-18-708 REPLACE OBSOLETE PANELBOARDS Federal contract opportunity
Solicitation number
36C24219B0029
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

36C24219B0029 S02-DRAWING Replace Obsolete Panel Boards Syracuse VA STAMPED.pdf

View the file

Other files for this federal contract opportunity

Other files attached to 528A7-18-708 REPLACE OBSOLETE PANELBOARDS, newest first.
File Type Posted
36C24219C0164-000.docx DOCX document
36C24219B0029-0002000.docx DOCX document
36C24219B0029-0002001.pdf PDF
36C24219B0029-0002002.jpg JPG image
36C24219B0029-0001000.docx DOCX document
36C24219B0029-002.pdf PDF
36C24219B0029-003.pdf PDF
36C24219B0029-001.docx DOCX document
36C24219B0029-000.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

100%

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Watson Engineering, P.C.

1112 State Rte. 434 Owego, NY 13827

(607) 223-4334

REPLACE OBSOLETE

PANEL BOARDS

SYRACUSE VAMC, SYRACUSE, NY

Project Director

03/08/2019 JWE JAHRevisions: Date:

528A7-18-708

T-101

COVER SHEET AND DRAWING INDEX

SHEET NO. DESCRIPTION

T-101 COVER SHEET & DRAWING INDEX

G-101 GENERAL NOTES

A-101

BASEMENT AND GROUND FLOOR KEY

PLANS

A-102 FIRST AND SECOND FLOOR KEY PLANS

A-103 THIRD AND FOURTH FLOOR KEY PLANS

A-104 FIFTH AND SIXTH FLOOR KEY PLANS

A-105 SEVENTH AND EIGHTH FLOOR KEY PLANS

E-101

BASEMENT PANELS (1 OF 6)

E-102

BASEMENT PANELS (2 OF 6)

E-103

BASEMENT PANELS (3 OF 6)

E-104

BASEMENT PANELS (4 OF 6)

E-105

BASEMENT PANELS (5 OF 6)

E-106

BASEMENT PANELS (6 OF 6)

E-107

GROUND FLOOR PANELS (1 OF 3)

E-108

GROUND FLOOR PANELS (2 OF 3)

E-109

GROUND FLOOR PANELS (3 OF 3)

E-110

FIRST FLOOR PANELS (1 OF 3)

E-111

FIRST FLOOR PANELS (2 OF 3)

E-112

FIRST FLOOR PANELS (3 OF 3)

E-113

SECOND FLOOR PANELS (1 OF 3)

E-114

SECOND FLOOR PANELS (2 OF 3)

E-115

SECOND FLOOR PANELS (3 OF 3)

E-116 THIRD FLOOR PANELS

E-117 FOURTH FLOOR PANELS

E-118 FIFTH FLOOR PANELS

E-119

SIXTH FLOOR PANELS (1 OF 2)

E-120

SIXTH FLOOR PANELS (2 OF 2)

E-121

SEVENTH FLOOR PANELS (1 OF 2)

E-122

SIXTH FLOOR PANELS (2 OF 2)

E-123 EIGHTH FLOOR PANELS

E-501 ELECTRICAL DETAILS

- VA ELECTRICAL DESIGN MANUAL

- STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE, NFPA 70E, 2018

- NATIONAL ELECTRICAL CODE, NFPA 70, 2017

AutoCAD SHX Text

DRAWING INDEX

AutoCAD SHX Text

REPLACE OBSOLETE PANEL BOARDS

AutoCAD SHX Text

DEPARTMENT OF VETERANS AFFAIRS PROJECT NO. 528A7-18-708 SYRACUSE, NY

AutoCAD SHX Text

SCALE: NONE

AutoCAD SHX Text

SITE PLAN

AutoCAD SHX Text

SCALE: NONE

AutoCAD SHX Text

SITE LOCATION

AutoCAD SHX Text

LIST OF APPLICABLE REFERENCES

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

100%

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Watson Engineering, P.C.

1112 State Rte. 434 Owego, NY 13827

(607) 223-4334

REPLACE OBSOLETE

PANEL BOARDS

SYRACUSE VAMC, SYRACUSE, NY

Project Director

03/08/2019 JWE JAHRevisions: Date:

528A7-18-708

G-101

GENERAL NOTES

DESIGN NARRATIVE

1. THE PROPOSED DESIGN DIRECTS THE RENOVATION OF APPROXIMATELY 41 ELECTRICAL PANELS LOCATED AT VARIOUS

PLACES THROUGHOUT THE SYRACUSE VA MEDICAL CENTER. EACH PANEL WILL BE REPLACED, RETROFITTED OR

DEMOLISHED AS SPECIFIED.

2. FOR PANELS TO BE REPLACED, THE CONTRACTOR SHALL DISCONNECT ALL EXISTING CONDUCTORS, AND THE EXISTING

PANEL COVER, BREAKERS, BUSES, AND BOX, SHALL BE REPLACED WITH THE APPROPRIATE CONTRACTOR SUPPLIED

REPLACEMENT PARTS. CONTRACTOR SHALL THEN RECONNECT CONDUCTORS AS EXISTING.

3. FOR PANELS TO BE RETROFITTED, THE CONTRACTOR SHALL DISCONNECT ALL EXISTING CONDUCTORS, AND THE

EXISTING PANEL COVER, BREAKERS, AND BUSES SHALL BE REMOVED. THE APPROPRIATE CONTRACTOR SUPPLIED

REPLACEMENT PARTS SHALL BE INSTALLED IN THE EXISTING BOX, AND THE CONDUCTORS SHALL BE RECONNECTED AS

EXISTING.

4. FOR PANELS TO BE DEMOLISHED, THE CONTRACTOR SHALL DISCONNECT ALL CONDUCTORS AND REROUTE TO THE

SPECIFIED PANEL. THE PANEL COVER, BUS, BREAKERS, AND BOX SHALL BE REMOVED AND RETURNED TO THE

SYRACUSE VA MEDICAL CENTER.

GENERAL NOTES:

1. THE GENERAL NOTES ON THIS SHEET APPLY TO ALL THE DRAWING DISCIPLINES.

2. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY ALL ASPECTS OF THE DESIGN, TO INCLUDE THE WORK OF

SUB-TRADES, PRIOR TO SUBMITTING A BID.

3. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE, ALTHOUGH NO ATTEMPT WAS MADE TO SHOW

EVERY OFFSET, FITTING, BEAM, PIPE SUPPORT, CLEARANCE, ETC. IT IS THE CONTRACTOR'S RESPONSIBILITY TO

SURVEY ALL WORK AREAS AND SUBMIT FINAL, DETAILED COORDINATED SHOP DRAWINGS FOR REVIEW BY THE

DESIGNER OF RECORD TO ENSURE THAT THE DESIGN INTENT WILL BE MET AND THAT ALL TRADES ARE PROPERLY

COORDINATED. CHANGES REQUIRED TO FIT EQUIPMENT, PIPING, AND DUCTWORK SHALL BE PROVIDED AT NO

ADDITIONAL COST TO THE OWNER. ANY MAJOR DISCREPANCIES SHALL BE CLARIFIED PRIOR TO SUBMITTAL OF BID.

4. BECAUSE OF THE SMALL SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL OFFSETS, TRANSITIONS, FITTINGS, CLEARANCES, POSSIBLES CLASHES, AND ACCESSORIES THAT MAY BE REQUIRED. COORDINATE ALL THE

WORK OF ALL THE TRADES TO INSURE ALL DUCTS, PIPES, CONDUITS, ETC. DO NOT CONFLICT AND CLEAR

STRUCTURAL AND ARCHITECTURAL MEMBERS. THE CONTRACTOR IS RESPONSIBLE FOR DEVELOPING COORDINATED

SHOP DRAWINGS FOR REVIEW PRIOR TO STARTING INSTALLATION.

5. IT IS RECOMMENDED THAT CONTRACTOR SHALL VISIT THE SITE AND BE FULLY COGNIZANT OF ALL CONDITIONS

PRIOR TO SUBMITTING BID. REPORT ANY DISCREPANCIES TO THE CONTRACTING OFFICER PRIOR TO SUBMITTAL OF

BID.

6. THE WORK INCLUDES ALL ITEMS OF THE SPECIFICATIONS THAT ARE EITHER WRITTEN ON THE DRAWINGS OR

SEPARATELY IN A SPECIFICATIONS BOOK.

7. WHERE THERE IS A CONFLICT ON THE PLANS, SPECIFICATIONS, NOTES, GENERAL NOTES, REFERENCES, PUBLICATIONS, CODES, ETC. WITH RESPECT TO CONSTRUCTION, MATERIALS, PRODUCTS, METHODS, WORKMANSHIP, PROCEDURE, EXECUTION, ETC. THE MOST STRINGENT SHALL BE UTILIZED OR INSTALLED. THE MOST STRINGENT

SHALL BE DEFINED AS THE SPECIFICATION OR REQUIREMENT THAT ALLOWS ALL SPECIFICATIONS OR REQUIREMENTS

THAT ARE IN CONFLICT TO BE SATISFIED. NO RELIEF OR EXTRA PAYMENT SHALL BE MADE TO THE CONTRACTOR

BECAUSE OF THIS INTERPRETATION.

8. CONTRACTOR SHALL NOT BEGIN FABRICATION, CUT ANY MEMBERS, OR BEGIN INSTALLATION UNTIL THE SUBMITTALS

AND COORDINATED SHOP DRAWINGS HAVE BEEN APPROVED. ANY WORK CONSTRUCTED OR INSTALLED PRIOR TO

THE APPROVAL OF SUBMITTALS AND COORDINATED SHOP DRAWINGS SHALL BE AT THE CONTRACTOR'S RISK AND

SHALL BE REMOVED AND REINSTALLED OR RECONSTRUCTED AT THE CONTRACTOR'S EXPENSE AT THE REQUEST OF

THE COR TO THE COMPLETE SATISFACTION OF THE COR.

9. ALL WORK SHALL BE DONE WITH COMPLETE COMPLIANCE WITH THE PUBLISHED EDITIONS OF THE APPLICABLE

CODES AND STANDARDS WHETHER STATUTORY OR NOT. ALL WORK SHALL BE INSTALLED TO COMPLY WITH THE

INTERNATIONAL BUILDING ELECTRICAL CODES, NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION, AND BASIC ELECTRICAL REGULATIONS. IF ANY PART OF THE INSTALLATION DOES

NOT MEET CODE, NOTIFY THE OWNER'S REPRESENTATIVE PRIOR TO BEGINNING THE INSTALLATION. IF ANY PART OF

THE PROJECT CANNOT BE INSTALLED TO CONFORM WITH THE PLANS AND/OR SPECIFICATIONS, NOTIFY THE COR

PRIOR TO BEGINNING THE INSTALLATION.

10. UNLESS STATED OTHERWISE, ALL EXISTING MATERIAL AND EQUIPMENT SHALL REMAIN THE PROPERTY OF THE

SYRACUSE VA MEDICAL CENTER.

11. THE CONTRACTOR SHALL DEVELOP AND PRESENT A CONSTRUCTION PLAN AND WORK SCHEDULE WITH ALL PHASING, STAGING, AND SEQUENCING OF WORK FOR APPROVAL PRIOR TO THE COMMENCEMENT AND BEGINNING

IMPLEMENTATION OF HIS WORK. THE CONTRACTOR SHALL DETERMINE PRIOR TO SUBMITTING HIS WORK SCHEDULE, THE SPECIFIC TIME AVAILABILITY OF ALL AREAS AND SPACES AND DETERMINE WHAT WORK MUST BE DONE DURING

"OFF HOURS".

12. WITH THE EXCEPTION OF SIGNIFICANT NOISE GENERATING ACTIVITIES SUCH AS CORE DRILLING, ETC., WORK

OUTSIDE OF THE OCCUPIED SPACES, SUCH AS ON THE ROOF, ETC., MAY BE PERFORMED DURING NORMAL WORKING

HOURS.

13. UNLESS SPECIFICALLY NOTED AS EXISTING, ALL ITEMS, EQUIPMENT, AND WORK SHOWN IS NEW AND SHALL BE

FURNISHED AND INSTALLED BY THE CONTRACTOR.

14. DURING THE EXECUTION OF THIS CONTRACT, THE SITE AND BUILDINGS WILL BE OCCUPIED AND IN USE. WORK DONE

UNDER THIS CONTRACT SHALL BE PERFORMED WITHOUT INCONVENIENCE TO THE OWNER INSOFAR AS POSSIBLE.

ALL WORK SHALL BE COORDINATED WITH THE COR AND IS SUBJECT TO THEIR CONTINUOUS APPROVAL.

15. THE CONTRACTOR IS COMPLETELY RESPONSIBLE FOR ALL CHARACTERISTICS OF THE EQUIPMENT THAT HE INTENDS

TO INSTALL AND MUST FOLLOW MANUFACTURER RECOMMENDATIONS FOR PROPER INSTALLATION. IF THERE ARE

ANY DIFFERENCES IN THE EQUIPMENT SHOWN ON THE DESIGN DRAWINGS AND THE EQUIPMENT TO BE INSTALLED, THE CONTRACTOR SHALL MAKE ALL CHANGES AND ADJUSTMENTS TO ACCOMMODATE THE PROPOSED EQUIPMENT

AT NO ADDITIONAL COST TO THE OWNER. THIS APPLIES TO ALL SUPPORT SERVICES AND FACILITIES NECESSARY TO

PROPERLY INSTALL THE EQUIPMENT TO FUNCTION ADEQUATELY AS PART OF THE SYSTEMS FOR WHICH THEY WERE

DESIGNED AND SELECTED. THESE CHARACTERISTICS INCLUDE SUCH THINGS AS WEIGHT, CLEARANCE, DIMENSIONS, ELECTRICAL, MECHANICAL, PLUMBING, AND UTILITY SERVICES, ETC. ACCOMMODATING SERVICES INCLUDE SUCH

THINGS AS DIMENSIONS, LOCATIONS, AND SIZES OF SUPPORTING MEMBERS, PIPE, CONNECTION SIZES, ELECTRICAL

SERVICE SIZE AND PROTECTION, ELECTRICAL CONNECTION LOCATION, UTILITY AND PLUMBING CONNECTION SIZES

AND LOCATIONS, ETC. ALL REQUIRED CHANGES TO THE CONTRACT DRAWINGS AND SPECIFICATIONS SHALL BE

DESIGNED AND STAMPED BY REGISTERED ENGINEERS IN THE APPROPRIATE DISCIPLINE EMPLOYED BY THE

CONTRACTOR AND SHALL BE INCLUDED AS PART OF THE EQUIPMENT SUBMITTALS. ALL CHANGES SHALL BE SUBJECT

TO THE APPROVAL OF THE PROJECT A/E AND THE OWNER'S REPRESENTATIVE.

16. BEFORE ANY DEMOLITION OR CONSTRUCTION WORK IS BEGUN, THE CONTRACTOR AND THE COR SHALL SURVEY THE

EXISTING BUILDING AREA TO BE MODIFIED AND/OR REPLACED TO ACCURATELY DOCUMENT EXISTING CONDITIONS.

THIS SURVEY WILL BE USED BY THE OWNER'S REPRESENTATIVE AT JOB COMPLETION TO DETERMINE WHICH

BUILDING/SITE COMPONENTS MUST BE REPLACED WITH NEW.

17. UNLESS STATED OTHERWISE, REQUEST APPROVAL FROM THE OWNER'S REPRESENTATIVE SEVEN DAYS IN ADVANCE

FOR THE SHUTDOWN OF ANY EXISTING SYSTEM.

18. UNLESS STATED OTHERWISE, FINAL ADVANCE NOTICE OF 48 HOURS SHALL BE GIVEN TO THE OWNER'S

REPRESENTATIVE PRIOR TO THE PROPOSED SHUTDOWN OF ANY SYSTEM.

19. PROVIDE ADEQUATE FIRE PROTECTION IN THE ENTIRE CONSTRUCTION AREA FOR THE DURATION OF THE

CONSTRUCTION PERIOD.

20. THE ENTIRE EXISTING FIRE PROTECTION SYSTEM SHALL BE RESTORED TO FULL OPERATION AT THE END OF EACH

WORKING DAY. ALL EXISTING FIRE ALARMS AND FIRE EXITS AND ANY OTHER ASPECT OF THE EXISTING FIRE ALARM

SYSTEM SHALL REMAIN IN FULL OPERATION. THE COST OF RESPONSE TO ANY FALSE ALARM AS CHARGED BY ANY

LOCAL FIRE DEPARTMENT SHALL BE PAID BY THE CONTRACTOR.

21. CONTRACTOR SHALL NOT PENETRATE OR CUT ANY STRUCTURAL MEMBERS NOT SPECIFICALLY SHOWN ON THE

DRAWINGS (E.G., JOISTS, BEAMS, ETC.). IF STRUCTURAL MEMBERS CONFLICT WITH ROUTING, CONTACT THE OWNER'S

REPRESENTATIVE FOR DIRECTION BEFORE PROCEEDING. EXERCISE CAUTION IN CUTTING CONCRETE FLOORS AND

WALLS TO AVOID EXISTING UTILITIES WHICH MAY BE LOCATED IN AND UNDER CONCRETE SURFACES.

22. THE CONTRACTOR SHALL PROVIDE NEW OPENINGS IN WALLS, FLOOR, AND ROOF, AND PATCH EXISTING OPENINGS IN

CONJUNCTION WITH THE DEMOLITION AND INSTALLATION OF THE NEW BUILDING COMPONENTS, INCLUDING

MECHANICAL, PLUMBING, ELECTRICAL, AND GENERAL CONTRACTOR'S ITEMS. ALL NECESSARY FRAMING, COUNTER-FLASHING, ETC. SHALL BE INCLUDED.

23. FOR ALL FLOOR, WALL, AND ROOF PENETRATION, VERIFY THE LOCATION OF THE EXISTING STRUCTURAL MEMBERS

PRIOR TO DRILLING AND CUTTING, RELOCATE OPENINGS AS REQUIRED AND OFFSET DUCTS, PIPES, CONDUIT, ETC.

24. ALL EXISTING DUCTWORK, PIPING, CONDUIT, AND MECHANICAL, PLUMBING, AND ELECTRICAL EQUIPMENT NOT TO BE

REUSED OR REMAIN IN SERVICE SHALL BE REMOVED FROM THE FACILITY. THE COR HAS THE OPTION TO RECLAIM

ANY DEMOLISHED MATERIALS OR EQUIPMENT, IN WHICH CASE IT SHALL BE DELIVERED TO THE LOCATION

DESIGNATED BY THE COR.

25. FOR EACH PHASE AND BEFORE INTERRUPTING EACH EXISTING UTILITY, DETERMINE, IN ADVANCE, IF ANY

DOWNSTREAM SERVICE BEYOND THE CONSTRUCTION AREA OF THE PHASE, WILL BE INTERRUPTED AND PROVIDE A

TEMPORARY SERVICE BYPASSING THE CONSTRUCTION AREA. DETERMINE ALL SUCH TEMPORARY SERVICES PRIOR

TO SUBMITTING BID. THERE WILL BE NO FUTURE CONSIDERATION TO THE CONTRACTOR FOR ANY TEMPORARY

SERVICES REQUIRED. PREPARE A DETAILED SHOP DRAWING SHOWING ALL OF THE EXISTING UTILITIES IN THEIR

RELOCATED LOCATION AND ALL THE NEW HVAC SYSTEMS.

26. EXISTING DUCTWORK, DOMESTIC COLD WATER PIPING, DOMESTIC HOT WATER PIPING, CHILLED AND HEATING HOT

WATER PIPING, WASTE, VENT, FIRE SPRINKLER LINES, FIRE ALARM EQUIPMENT, ELECTRICAL CONDUIT, TELEPHONE

CONDUIT, COMMUNICATION CONDUIT, PNEUMATIC TUBING, ETC., MAY HAVE TO BE RELOCATED TO FACILITATE THE

INSTALLATION OF THE NEW WORK. THE CONTRACTOR SHALL DETERMINE ALL EXISTING SERVICES THAT REQUIRE

RELOCATION PRIOR TO SUBMITTING HIS BID AND INCLUDE ALL COSTS IN THE BID. THERE WILL BE NO EXTRA

COMPENSATION TO THE CONTRACTOR FOR THIS WORK.

27. PATCH AND PAINT TO MATCH EXISTING, ALL SURFACES DAMAGED BY THE DEMOLITION AND ALL OPENINGS NOT TO BE

REUSED.

28. REPAIR DAMAGE TO CEILING, WALLS, ETC. TO THE SATISFACTION OF THE OWNER'S REPRESENTATIVE.

29. WHEN A DETAIL OR NOTE IS IDENTIFIED AS TYPICAL, THE CONTRACTOR IS TO APPLY THE DETAIL OR NOTE TO EVERY

SIMILAR CONDITION, WHETHER OR NOT THE REFERENCED DETAIL OR NOTE IS REPEATED OR REFERENCED.

30. WHERE NO CONSTRUCTION DETAIL IS INDICATED, SUCH WORK SHALL BE SIMILAR TO COMPARABLE WORK DETAILED

OR NOTED ELSEWHERE OR TO MATCH EXISTING CONDITIONS, SUBJECT TO THE APPROVAL OF THE OWNER'S

REPRESENTATIVE.

31. ALL HOLES, VOIDS, AND DAMAGED OR UNEVEN SURFACES WHICH ARE CAUSED BY THE CONTRACTOR'S WORK AND

WHICH REMAIN EXPOSED IN THE WALL, FLOOR, CEILING, OR OTHER SURFACES SHALL BE PATCHED, REPAIRED, AND

BROUGHT FLUSH WITH THE ADJACENT CONSTRUCTION. SUCH SURFACES, NOT CONCEALED BY THE NEW

CONSTRUCTION, SHALL MATCH IN EVERY RESPECT THE EXISTING NON-DAMAGED CONSTRUCTION. REMOVE EXISTING

UTILITIES BACK BEHIND EXISTING SURFACES AND CAP SO AS NOT TO INTERFERE WITH NEW PATCHES.

32. WHEREVER NEW WALL, FLOOR, OR CEILING FINISHES ARE INDICATED, THE CONTRACTOR SHALL BRING EXISTING

ELECTRICAL, MECHANICAL, PLUMBING, AND OTHER BUILDING COMPONENTS FLUSH WITH THE NEW FINISHED

SURFACES IF APPROPRIATE.

33. THE DEMOLITION SHALL INCLUDE ALL ASSOCIATED ANCHORAGES, HANGERS, SUPPORTS, BRACES, FASTENERS, MASTIC, MORTAR, LATH, AND RELATED ITEMS. THE EXISTING SUBSTRATE, INCLUDING CONCRETE, MASONRY, METAL

FRAMING AND FURRING SHALL BE REPAIRED WHERE DAMAGE BY THE CONTRACTOR'S WORK.

34. ANY ANTICIPATED HAZARDOUS MATERIALS (HAZMAT) IS INDICATED ON THE DRAWINGS, HOWEVER, IT IS IMPOSSIBLE

TO PREDICT WHERE EXACTLY ALL HAZMAT MAY BE ENCOUNTERED. IF HAZMAT IS ENCOUNTERED OR SUSPECTED AT

ANY POINT DURING CONSTRUCTION, CEASE ALL WORK IMMEDIATELY AND CONTACT THE OWNER'S REPRESENTATIVE

FOR GUIDANCE.

35. ALL ELECTRICAL PANEL REPLACEMENT PARTS SUCH AS COVERS, BREAKERS, BUSES, BOXES, ETC. SHALL BE SUPPLIED

BY THE CONTRACTOR UNLESS OTHERWISE NOTED.

36. ALL EQUIPMENT/MATERIALS REMOVED AND/OR DEMOLISHED DURING THIS PROJECT SHALL REMAIN THE PROPERTY OF

THE SYRACUSE VA MEDICAL CENTER UNLESS OTHERWISE NOTED.

37. CONTRACTOR SHALL REFER TO THE PARTIAL ONE-LINE DIAGRAMS AS WELL AS THE EXISTING AS-BUILT ONE-LINE

DIAGRAM TO IDENTIFY AND SHUT OFF THE APPROPRIATE POWER SOURCE PRIOR TO PERFORMING ANY WORK. FINAL

SCHEDULING AND PHASING OF WORK SHALL BE DEVELOPED BY CONTRACTOR AND COORDINATED WITH COR FOR

APPROVAL.

38. ALL PANELS AND BREAKERS SHALL BE UPGRADED TO 22 KAIC.

39. THE CONTRACTOR WILL BE RESPONSIBLE FOR FIELD VERIFYING MEASUREMENTS AT EACH PANEL LOCATION BEFORE

ORDERING EQUIPMENT.

40. MISCELLANEOUS AREAS OF SPRAY FOAM INSULATION SHALL BE REMOVED AS INDICATED ON DRAWINGS. PROPER

FIRE-STOPPING MATERIAL WILL BE USED.

41. ELECTRICAL SHUTDOWNS MUST OCCUR AFTER 6PM MONDAY THROUGH FRIDAY, WITH EXACT TIMING TO BE

DETERMINED BY COR.

42. CONTRACTOR IS RESPONSIBLE FOR CONTACTING AND COORDINATING WITH RED HAWK REGARDING ANY FIRE ALARM

MODIFICATIONS. FIRE HAWK CAN BE REACHED AT (315)458-1154.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

100%

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Watson Engineering, P.C.

1112 State Rte. 434 Owego, NY 13827

(607) 223-4334

REPLACE OBSOLETE

PANEL BOARDS

SYRACUSE VAMC, SYRACUSE, NY

Project Director

03/08/2019 JWE JAHRevisions: Date:

528A7-18-708

A-101

BASEMENT AND GROUND

FLOOR KEYPLANS

BASEMENT KEYPLAN F1

A1011/32"=1'-0"SCALE:

GROUND FLOOR KEYPLAN F6

A1011/32"=1'-0"SCALE:

SEE PARTIAL FLOOR PLAN

D2 ON SHEET E-102

(PANEL ELC-AC)

SEE PARTIAL FLOOR PLAN C2

ON SHEET E-103

(PANELS LC-E LEFT AND RIGHT)

SEE PARTIAL FLOOR PLAN C2 ON SHEET E-101

(PANELS ELC-G, AND ELC-B SECTION 1 AND 2)

SEE PARTIAL FLOOR

PLAN C2 ON SHEET E-104

(PANEL LB-1)

SEE PARTIAL FLOOR

PLAN C2 ON SHEET E-105

(PANEL LB-AC)

SEE PARTIAL FLOOR

PLAN C2 ON SHEET E-106

(ELC-C1)

SEE PARTIAL FLOOR

PLAN C2 ON SHEET E-107

(PANEL EGE-C)

SEE PARTIAL FLOOR

PLAN C2 ON SHEET E-108

(PANEL EGA-A1)

SEE PARTIAL FLOOR

PLAN C6 ON SHEET E-107

(PANEL GC-A)

SEE PARTIAL FLOOR

PLAN C5 ON SHEET E-108

(PANEL EGD-A)

SEE PARTIAL FLOOR

PLAN C2 ON SHEET E-109

(PANEL GD-DP, GDA

SECTION 1 AND 2)

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

100%

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Watson Engineering, P.C.

1112 State Rte. 434 Owego, NY 13827

(607) 223-4334

REPLACE OBSOLETE

PANEL BOARDS

SYRACUSE VAMC, SYRACUSE, NY

Project Director

03/08/2019 JWE JAHRevisions: Date:

528A7-18-708

A-102

FIRST AND SECOND FLOOR

KEYPLANS

FIRST FLOOR KEYPLAN F1

A1021/32"=1'-0"SCALE:

SECOND FLOOR KEYPLAN F6

A1021/32"=1'-0"SCALE:

SEE PARTIAL FLOOR

PLAN C6 ON SHEET E-110

(PANEL 1C-C)

SEE PARTIAL FLOOR PLAN

C2 ON SHEET E-111

(PANELS 1C-D, E1-CC, 1C-A)

SEE PARTIAL FLOOR

PLAN C2 ON SHEET E-112

(PANEL ELS1A-A)

SEE PARTIAL FLOOR

PLAN C2 ON SHEET E-113

(PANEL 2C-D)

SEE PARTIAL FLOOR

PLAN C5 ON SHEET E-113

(PANEL E2-CB)

SEE PARTIAL FLOOR

PLAN C2 ON SHEET E-114

(PANEL 2C-C)

SEE PARTIAL FLOOR

PLAN C2 ON SHEET E-115

(PANELS 2A-C AND 2A-A1)

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

100%

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Watson Engineering, P.C.

1112 State Rte. 434 Owego, NY 13827

(607) 223-4334

REPLACE OBSOLETE

PANEL BOARDS

SYRACUSE VAMC, SYRACUSE, NY

Project Director

03/08/2019 JWE JAHRevisions: Date:

528A7-18-708

A-103

THIRD AND FOURTH FLOOR

KEYPLANS

THIRD FLOOR KEYPLAN F1

A1031/32"=1'-0"SCALE:

FOURTH FLOOR KEYPLAN F6

A1031/32"=1'-0"SCALE:

SEE PARTIAL FLOOR

PLAN C2 ON SHEET E-116

(PANEL 3B-D)

SEE PARTIAL FLOOR

PLAN C5 ON SHEET E-116

(PANEL E3A-C)

SEE PARTIAL FLOOR

PLAN C2 ON SHEET E-117

(PANELS 4A-D AND 4A-A)

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

100%

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Watson Engineering, P.C.

1112 State Rte. 434 Owego, NY 13827

(607) 223-4334

REPLACE OBSOLETE

PANEL BOARDS

SYRACUSE VAMC, SYRACUSE, NY

Project Director

03/08/2019 JWE JAHRevisions: Date:

528A7-18-708

A-104

FIFTH AND SIXTH FLOOR

KEYPLANS

FIFTH FLOOR KEYPLAN F1

A1041/32"=1'-0"SCALE:

SIXTH FLOOR KEYPLAN F6

A1041/32"=1'-0"SCALE:

SEE PARTIAL FLOOR PLAN

C2 ON SHEET E-118

(PANELS 5B-A AND E5A-A)

SEE PARTIAL FLOOR PLAN

C2 ON SHEET E-120

(PANEL 6B-A)

SEE PARTIAL FLOOR PLAN C2

ON SHEET E-119

(PANELS 6A-A, E6A-A AND 6A-D)

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

100%

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Watson Engineering, P.C.

1112 State Rte. 434 Owego, NY 13827

(607) 223-4334

REPLACE OBSOLETE

PANEL BOARDS

SYRACUSE VAMC, SYRACUSE, NY

Project Director

03/08/2019 JWE JAHRevisions: Date:

528A7-18-708

A-105

SEVENTH AND EIGHTH

FLOOR KEYPLANS

SEVENTH FLOOR KEYPLAN F1

A1051/32"=1'-0"SCALE:

EIGHTH FLOOR KEYPLAN F6

A1051/32"=1'-0"SCALE:

SEE PARTIAL FLOOR PLAN

C2 ON SHEET E-121

(PANELS 7A-C, E7-AB, 7A-B)

SEE PARTIAL FLOOR PLAN

C2 ON SHEET E-122

(PANELS 7A-A, AND 7B-A)

SEE PARTIAL FLOOR PLAN

C2 ON SHEET E-123

(PANEL 8B-A)

ELC-G

ELC-B SECT 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

100%

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Watson Engineering, P.C.

1112 State Rte. 434 Owego, NY 13827

(607) 223-4334

REPLACE OBSOLETE

PANEL BOARDS

SYRACUSE VAMC, SYRACUSE, NY

Project Director

03/08/2019 JWE JAHRevisions: Date:

528A7-18-708

E-101

BASEMENT PANELS (1 OF 6)

BASEMENT ROOM CL 09 C2

E-1011/4"=1'-0"SCALE:

FLOOR ROOM PANEL

FRAME MAIN

DIMENSIONS (SEE NOTE 1)

EXISTING MAKE/MODEL # OF

SPACES

# OF

SPARES

# OF

EMPTY REPLACE RETROFIT FEED

LOCATIONRECESSED/

SURFACE V/PHASE RATING

(A)

MCB

RATING H W D FLANGE W RECESSED

DIMENSION

B CL09 ELC-G S 208/3 100 100 38" 20" 5 3/4" N/A N/A SQ D/CAT NO. 44-76874-7E 30

1-3Ø 1-2Ø 3-1Ø

0 X T

B CL09 ELC-B SECT 1 S 208/3 200 200 53" 20" 5 3/4" N/A N/A SQ D/CAT NO. 44-65937-15A 54 2-3Ø 7-1Ø 0 X T

B CL09 ELC-B SECT 2 S 208/3 200 MLO 44" 20" 5 3/4" N/A N/A SQ D/CAT NO. 44-65937-14D 54 1-3Ø 3-1Ø 12 X B

BRANCH PANEL: ELC-G

LOCATION: CL09

SUPPLY FROM: ELC-DPB

MOUNTING: SURFACE

ENCLOSURE: TYPE 1

VOLTS: 120/208

PHASE: 3

WIRES: 4

A.I.C. RATING: 22 KAIC

MAINS TYPE: MCB (TOP)

MAINS RATING: 100A

MCB RATING: 100A

PANEL

SECTION

NO.

BREAKER

RATING (A)

LOAD DESCRIPTION LOAD DESCRIPTION

BREAKER

RATING (A)

PANEL

SECTION

NO.

1 20 CL09 LIGHTS RECEPTACLE CL03 20 2

3 20 RECEP CL08A RECEPTACLE CL03 30 4

5 20 RECEP CL08A EXHAUST

FAN/DAMPER CL10A 30 6

7 20 RECEP CL08A

SPARE 80

9 20

LIGHTS, MECH

ROOM LOADING

DOCK, AAD

11 20 TRANE EMS PANEL 12

13 20

TEMP MONITOR

CL06 RECEP CL08A 20 14

15 20

JOHNSON CONTROL

FIRE PANEL RECEP CL08A 20 16

17 20 EXHAUST FAN CL09 RECEP CL08A 20 18

19 20 RECEP CL08

RECEP 2-POLE 30A 30

21 20 RECEP CL08 22

23 20 SPARE IN JBOX CL08

RECEP 2-POLE 20A 20

25 20 SPARE 26

27 20 SPARE

SPARE 30

29 20 SPARE 30

BRANCH PANEL: ELC-B

SECTION 1

LOCATION: CL09

SUPPLY FROM: EEQ-LCA1

MOUNTING: SURFACE

ENCLOSURE: TYPE 1

VOLTS: 120/208

PHASE: 3

WIRES: 4

A.I.C. RATING: 22 KAIC

MAINS TYPE: MCB

(TOP)

MAINS RATING: 200A

MCB RATING: 200A

PANEL

SECTION

NO.

BREAKER

RATING (A)

LOAD DESCRIPTION LOAD DESCRIPTION

BREAKER

RATING

(A)

PANEL

SECTION

NO.

1 20 AIR DRYER

DOCK LIFT #2 20

3 20 COFFEE POT BL08 4

5 20 REFRIGERATOR BL08 6

60 SPARE 3-POLE 60A

SPOTLIGHTS / HEATER ON

LOADING DOCK & CL10A 20

9 10

MIDDLE DOCK ELECTRIC DOOR

OPENER 20 12

13 20 GFCI RECEP W WALL DOCK WAREHOUSE RECEP. 20 14

15 20 LIGHTS BL10A

SPEED AIR - AIR COMPRESSOR 15

17 20 AUTO DOOR DOCK 18

80 DOCK LIFT #1

WALK IN FREEZER DOOR

HEATER BL06A 20 20

WALK IN FREEZER LIGHTS

BL06A 20 22

WALK IN FREEZER LIGHTS

BL06B 30 24

20 SPARE 3-POLE 20A

Lights CL06c 20 26

ROOF AIR HANDELER RECEP.

AND LIGHTS 20 28

29 FREEZER HEAT TAPE 20 30

31 20

RECEP COMPRESSOR ETO

STERILIZER SPARE 20 32

33 20

RECEP COMPRESSOR ETO

STERILIZER SPARE 20 34

35 20 SPARE SPARE 20 36

50 TRASH COMPACTOR BL12

SPARE 20 38

39 SPARE 20 40

41 SPARE 20 42

NOTE:

1. PANEL SHALL BE PROVIDED WITH THROUGH FEED LUGS ON BOTTOM TO FEED BLC-B SECTION 2.

BL06A

CL09

CL10

ELC-B SECT 2

PANEL SCHEDULES B6

E-101N/ASCALE:

PANEL DATA E5

E-101N/ASCALE:

100A/3P

ELC-G

CL09

100A/3P

ELC-DPA

1200A-120/208V,3Ø,4W+G

SECTION 2

CL02

200A/3P

EEQ-LCA1 CL02AGF

200A/3P

ELC-B

SECTION

ELC-B

SECTION

CL09

ELC-G AND ELC-B PARTIAL ONE-LINE DIAGRAMS E2

E-101N.T.S.SCALE:

BRANCH PANEL: ELC-B

SECTION 2

LOCATION: CL09

SUPPLY FROM: EEQ-LCA1

MOUNTING: SURFACE

ENCLOSURE: TYPE 1

VOLTS: 120/208

PHASE: 3

WIRES: 4

A.I.C. RATING: 22 KAIC

MAINS TYPE: MLO (BOTTOM

FEED)

MAINS RATING: 200A

MCB RATING: N/A

PANEL

SECTION NO.

BREAKER

RATING (A)

LOAD DESCRIPTION LOAD DESCRIPTION

BREAKER

RATING (A)

PANEL

SECTION NO.

1 20 TIME CLOCK - COMP #5 RECEP TOW MOTOR, BY

BL05 DOOR 20 2

3 20

RECEPT BL08, BL08A

LARGE FREEZER UNIT A 30

5 20

Fire Alarm Door Panel Holders 6

20 DOCK LIFT #3

9 LIGHTS BL05 20 10

11 BL08 A/C 28 & EF-28 20 12

13 20

WAREHOUSE BREAK

ROOM

COMPRESSOR RACK "B" 20

15 20

WAREHOUSE BREAK

ROOM 16

17 20

WAREHOUSE BREAK

ROOM 18

SMALL COOLER

COMPRESSOR

SMALL COOLER FAN 20 20

WALL EXHAUST FAN IN

CL09 20 22

FAN COIL UNIT IN CL16 20

COMPRESSOR RACK "A"

PANEL

FAN COIL UNIT IN CL16 20

29 30

30 SMALL FREEZER LARGE FREEZER UNIT B 30

33 34

35 36

80 SPARE

SPARE 20 38

39 SPARE 20 40

41 SPARE 20 42

43 SPACE SPACE 44

45 SPACE SPACE 46

47 SPACE SPACE 48

49 SPACE SPACE 50

51 SPACE SPACE 52

53 SPACE SPACE 54

NOTE:

1. SEE SHEET E501 DETAIL C2 FOR DIMENSION DESCRIPTION.

2. EXISTING EMPTY CONDUITS BELOW PANEL ELC-B SECTION 2 (RIGHT) SHALL BE DEMOLISHED TO FLOOR AND FILLED APPROPRIATELY.

ELC-G1

(FUTURE)

ELC-B1

(FUTURE)

80A/3P

80A/3P

CONTRACTOR IS RESPONSIBLE FOR REMOVAL OF ALL

INSULATING FOAM LOCATED ABOVE ELC-B PANELS,

AND INSTALLATION OF APPROPRIATE FIRESTOPPING

AROUND CONDUITS PER SPEC 078400.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

100%

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Watson Engineering, P.C.

1112 State Rte. 434 Owego, NY 13827

(607) 223-4334

REPLACE OBSOLETE

PANEL BOARDS

SYRACUSE VAMC, SYRACUSE, NY

Project Director

03/08/2019 JWE JAHRevisions: Date:

528A7-18-708

E-102

BASEMENT PANELS (2 OF 6)

BASEMENT ROOM LOWER NL30A D2

E-1023/8"=1'-0"SCALE:

FLOOR ROOM PANEL

FRAME MAIN

DIMENSIONS (SEE NOTE 2)

EXISTING MAKE/MODEL # OF

SPACES

# OF

SPARES

# OF

EMPTY REPLACE FEED

LOCATION NOTERECESSED/

SURFACE V/PHASE RATING

(A)

MCB/

MLO H W D FLANGE W RECESSED

DIMENSION

B NL30A ELC-AC S 208/3 300 300 38" 20" 5 3/4" N/A N/A SIEMENS ITE/TYPE CDP-7 SERIES 8A 42 8-1Ø 1-3Ø 12 X B 1

BRANCH PANEL: ELC-AC

LOCATION: NL30A

SUPPLY FROM: EEQ-GE-DP

MOUNTING: SURFACE

ENCLOSURE: TYPE 1

VOLTS: 120/208

PHASE: 3

WIRES: 4

A.I.C. RATING: 22 KAIC

MAINS TYPE: MCB (TOP)

MAINS RATING: 300A

MCB RATING: 300A

PANEL

SECTION NO.

BREAKER

RATING (A)

LOAD

DESCRIPTION

LOAD

DESCRIPTION

BREAKER

RATING

(A)

PANEL

SECTION NO.

1 20

UH-52, 70, 71

AND FC-31, 32,

SPARE 20 2

3 20 SPARE SPARE 20 4

5 20 SPARE SPARE 20 6

7 SPACE

HRP-32 15

9 SPACE 10

30 HWP-902

HCP-32 15

15 16

15 SPARE

EF-32 20

21 22

40 AC-32

25 SPACE 26

27 SPACE 28

29 20 SPARE SPACE 30

31 20 SPARE SPACE 32

33 20 SPARE SPACE 34

BUILDING 2

FEED

SPACE 36

37 SPACE 38

39 SPACE 40

41 SPACE SPACE 42

E L C

A

C

LOWER

NL30A

PANEL SCHEDULE F6

E-102N/ASCALE:

PANEL DATA F9

E-102N/ASCALE:

EEQ-GE-DP

600A-208/120V,3Ø,4W+G

100/3P

100/3P

100/3P

100/3P

150A/

3P

200A/

3P

E2-LA

BLDG 2

E2-1A

BLDG 2

E2-2A

BLDG 2

E2-3A

BLDG 2

200/3P

DP-1

BLDG 2

BUILDING

2 RISER

400AF

300AT

3P

ELC-AC PARTIAL ONE-LINE DIAGRAM F2

E-102N.T.S.SCALE:

NOTE:

1. PANEL ELC-AC SHALL BE RELOCATED TO UPPER MEZZANINE. FINAL LOCATION OF PANEL SHALL BE COORDINATED WITH COR. CONTRACTOR IS RESPONSIBLE FOR REROUTING EXISTING CONDUCTORS TO NEW PANEL LOCATION.

2. SEE SHEET E501 DETAIL C2 FOR DIMENSION DESCRIPTION.

ELC-AC

300A/3P

250A/3P

BASEMENT ROOM UPPER NL30A D8

E-1023/8"=1'-0"SCALE:

ELC-AC

UPPER

NL30A

DEMOLISH ALL EQUIPMENT INSIDE

PANEL. LEAVE BOX AS JUNCTION BOX

CORE DRILL THROUGH FLOOR ABOVE. RUN

EXISTING CIRCUITS TO NEW PANEL ABOVE.

DEMOLISH FIRE ALARM PULL STATION

AND CONDUIT TO JUNCTION BOX.

MOVE 8x8 FIRE ALARM JUNCTION BOX TO

OTHER SIDE OF WALL TO REPLACE 4x4 BOX.

DEMOLISH 4x4 FIRE ALARM BOX. REPLACE

WITH 8x8 BOX FROM OTHER SIDE OF WALL.

PROPOSED LOCATION FOR NEW PANEL. INTERCEPT BUILDING 2 RISER

AND FEED NEW ELC-AC PANEL. RECONNECT ALL EXISTING CIRCUITS

FROM BELOW. CORE DRILL WALL BELOW BOX AND RECONNECT

CONDUCTORS TO BUILDING 2 JUNCTION BOX.

J-BOX

300 KCMIL

300 KCMIL

J-BOX

PARTIAL RISER DIAGRAM E9

E-102N.T.S.SCALE:

SUB-BASEMENT

BASEMENT

FIRST FLOOR

NL30A

UPPER

NL30A

LOWER

EEQ-GE-DP

J-BOX

TO

BLDG 2

ELC-AC

SUB-BASEMENT

BASEMENT

FIRST FLOOR

NL30A

UPPER

NL30A

LOWER

EEQ-GE-DP

J-BOX

TO

BLDG 2

J-BOX

TO

LOADS

TO

LOADS

ELC-AC

EXISTING PROPOSED

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

100%

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Watson Engineering, P.C.

1112 State Rte. 434 Owego, NY 13827

(607) 223-4334

REPLACE OBSOLETE

PANEL BOARDS

SYRACUSE VAMC, SYRACUSE, NY

Project Director

03/08/2019 JWE JAHRevisions: Date:

528A7-18-708

E-103

BASEMENT PANELS (3 OF 6)

BASEMENT ROOM CL 24 DEMO PLAN C2

E-1031/4"=1'-0"SCALE:

FLOOR ROOM PANEL

FRAME MAIN

DIMENSIONS (SEE NOTE 1)

EXISTING MAKE/MODEL # OF

SPACES

# OF

SPARES

# OF

EMPTY REPLACE FEED

LOCATIONRECESSED/

SURFACE V/PHASE RATING

(A)

MCB/

MLO H W D FLANGE W RECESSED

DIMENSION

B CL24 LC-E SECTION 2 S 208/3

400 MLO 35" 20" 5 3/4" N/A N/A SQ D/CAT NO. 44-76874-7C 54 9-1Ø

1-2Ø 2 X B

B CL24 LC-E SECTION 1 S 208/3 400 400 35" 20" 5 3/4" N/A N/A SQ D/CAT NO. 44-76874-7B 54 1-1Ø 1-3Ø 0 X T

BRANCH PANEL: LC-E SECT. 2

LOCATION: CL24

SUPPLY FROM: LC-DPF

MOUNTING: SURFACE

ENCLOSURE: TYPE 1

VOLTS: 120/208

PHASE: 3

WIRES: 4

A.I.C. RATING: 22 KAIC

MAINS TYPE: MLO

(BOTTOM)

MAINS RATING: 400A

MCB RATING: N/A

PANEL

SECTION NO.

BREAKER

RATING (A)

LOAD

DESCRIPTION

LOAD

DESCRIPTION

BREAKER

RATING (A)

PANEL

SECTION NO.

1 20 CL27 LIGHTS

RECPT WEST

WALL

AUDITORIUM

CG43

20 2

3 20

CORR RECP

OUTSIDE CL28,

LIGHTS CL30A &

JC CONTRL

CL27 UNIT

HEATER 20 4

5 20

RECPS

WORKBENCH IN

PAINT SHOP

M006

CL27 EXH FAN,

CL24 GRINDER, 7

RECPTS E. WALL

CL24

20 6

7 20

LIGHTS PAINT

SHOP M006

CL27 RECPT

EAST WALL 20 8

9 20 CL29 HEATER

CL27

THREADING

MACHINE

20 10

11 20 CL29 LIGHTS

RECPT GFCI

MEN'S BATHRM

CL26

20 12

13 20

RECPT SOUTH

WALL & OFFICE

CL27

PIPE THREADING

MACHINE 20 14

3P-40A CL24

3-PHASE

WELDER

3P-15A HRP-37 15

17 18

19 20

3P-20A RECEP

208V CL27

3P-70A PANEL

1CC-COUMADIN

CLINIC BY C129

23 24

25 26

27 20 1P-20A SPARE 3P-70A PANEL

2CD - 3-PHASE

208V

(AUDITORIUM

ROOF)

29 21 1P-20A SPARE 30

31 22 1P-20A SPARE 32

3P-100A PANEL

LCE-1 CL25

(LOWER BIOMED

SHOP)

2P-50A CL27

SPARE 50

35 36

37 3P-100A PANEL

GCD -

AUDITORIUM

15 3P-15A HCP-37

41 42

43 SPARE 20 44

3P-150A PANEL

2CE STAGE

HATCH

SPARE 20 46

47 SPARE 20 48

49 SPARE 20 50

51 SPACE SPARE 20 52

53 SPACE SPARE 20 54

BRANCH PANEL: LC-E SECT. 1

LOCATION: CL24

SUPPLY FROM: LC-DPF

MOUNTING: SURFACE

ENCLOSURE: TYPE 1

VOLTS: 120/208

PHASE: 3

WIRES: 4

A.I.C. RATING: 22 KAIC

MAINS TYPE: MCB (TOP)

MAINS RATING: 400A

MCB RATING: 400A

PANEL

SECTION NO.

BREAKER

RATING (A)

LOAD

DESCRIPTION

LOAD

DESCRIPTION

BREAKER

RATING (A)

PANEL

SECTION NO.

1 20

MEN'S

BATHROOM

LIGHTS CL26

EXHAUST FAN

CL23 20 2

3 20

UNIT HEATER

CL23

RECPT CL23 &

UNIT HEATER 20 4

5 20

RECP CL24

NORTH WALL

(2), EAST

WALL (1)

OUTSIDE

LIGHTS,

LIGHTS CL23

20 6

7 20

UNIT HEATER

CL23, RECP

CL24 EAST

WALL

OUTSIDE

LIGHTS, CL24 S

WALL RECPT

20 8

9 20

COMPUTER

RECEPTACLE

CL24

LIGHTS CL24 20 10

11 20

WATER

FOUNTAIN &

LIGHTS FOR

BILLBOARD IN

HALL

RECEPT

NORTH WALL

CL24

20 12

13 20

HANGING

RECEPTACLE

CL24

2P-50A

RECEPT 208V

RANGE IN

AUDITORIUM

15 20

RECEPTACLE

BAND SAW

CL24

17 20

UNIT HEATER -

PAINT SHOP 2P-20A 208V

CL24 DRILL

PRESS

3P-30A

RECEPT 208V

CANTEEN AIR

CONDITIONER

21 2P-20A 208V

CL24 LATHE 20

23 24

25 20 1P-20A SPARE

3P-20A 208V

RECEPT AIR

COMPRESSOR

CL25

2P-20A 208V

RECEPT

MILLING

MACHINE

CL24

29 30

3P-30A SPARE

30 AMP

3P-20A

RECEPT 208V

HYDRAULIC

LIFT

33 34

35 36

40 3P-40A AC37 3P-60A EF37 60

39 40

41 42

NOTES:

1. PANEL SHALL BE PROVIDED WITH THROUGH FEED LUGS ON BOTTOM TO FEED LC-E

SECTION 2

LC-E SECTION 2

CL24

LC-E SECTION 1

PANEL SCHEDULES C6

E-103N/ASCALE:

PANEL DATA E6

E-103N/ASCALE:

100A/3P

100A/3P100A/3P 70A/3P60A/3P

400A/3P

LC-E

GC-D

CL25

STAGE

LC-DPF

2000A-208V, 3ɸ,4W

400A/3P

40A/3P

LC-E1

CL25

70A/3P

2C-D

STAGE

HATCH

1C-C

C128-

CORRIDOR

70A/3P 70A/3P

LC-E PARTIAL ONE-LINE DIAGRAM E2

E-103N.T.S.SCALE:

NOTE:

1. SEE SHEET E501 DETAIL C2 FOR DIMENSION DESCRIPTION.

150A/3P

2C-E

STAGE

HATCH

150A/3P

PROPOSED BASEMENT ROOM CL 24 C6

E-1031/4"=1'-0"SCALE:

LC-E

SECT. 2

CL24

LC-E

SECT. 1

DEMOLISH EXISTING

JUNCTION BOXES

DEMOLISH EXISTING PANELS

EXISTING

WIRE DUCT,

TO REMAIN

PLACE NEW PANELS AT

LOCATION OF DEMOLISHED

JUNCTION BOXES.

EXTEND EXISTING

WIREWAY TO CAPTURE ALL

EXISTING WIRE CONDUITS

EXTEND WIREWAY TO

CONNECT TO NEW LC-E

LEFT PANEL

CONTRACTOR SHALL FIELD

VERIFY EXISTING WIREWAY IS

SUFFICIENTLY SIZED TO HOLD

ALL CONDUCTORS. UPSIZE TO

LARGER WIREWAY IF REQUIRED.

AutoCAD SHX Text

EF-37

AutoCAD SHX Text

AC-37

AutoCAD SHX Text

CL24

CL02CL02

L B

D

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

100%

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Watson Engineering, P.C.

1112 State Rte. 434 Owego, NY 13827

(607) 223-4334

REPLACE OBSOLETE

PANEL BOARDS

SYRACUSE VAMC, SYRACUSE, NY

Project Director

03/08/2019 JWE JAHRevisions: Date:

528A7-18-708

E-104

BASEMENT PANELS (4 OF 6)

BASEMENT ROOM BL 20 C2

E-1041/4"=1'-0"SCALE:

FLOOR ROOM PANEL

FRAME MAIN

DIMENSIONS (SEE NOTE 1)

EXISTING MAKE/MODEL # OF

SPACES

# OF

SPARES

# OF

EMPTY REPLACE FEED

LOCATIONRECESSED/

SURFACE V/PHASE RATING

(A)

MCB/

MLO H W D FLANGE W RECESSED

DIMENSION

B BL20 LB-D S 208/3 100 100 35" 20" 5 3/4" N/A N/A WESTINGHOUSE/TYPE EB-20-CDP 42 5-1Ø 24 X T

BRANCH PANEL: LB-D

LOCATION: BL20

SUPPLY FROM: MCC-1

MOUNTING: SURFACE

ENCLOSURE: TYPE 1

VOLTS: 120/208

PHASE: 3

WIRES: 4

A.I.C. RATING: 22 KAIC

MAINS TYPE: MCB

MAINS RATING: 100A

MCB RATING: 100A

PANEL

SECTION NO.

BREAKER

RATING (A)

LOAD

DESCRIPTION

LOAD

DESCRIPTION

BREAKER

RATING (A)

PANEL

SECTION NO.

1 20 LIGHTS BL20 AHU-48

CONTROLS 20 2

3 20

GFCI RECP. ON

AIR HANDLER

BL20

SUMP PUMP

CONTROL

BL20/JOHNSON

CONTROLS

20 4

5 20

RECEP AND

SPARE IN JB

UNIT HEATER

AND EXHAUST

FAN BL20

20 6

7 20 SPARE

MORGUE

DOOR DOCK

LIFT

9 20

TEMP

MORGUE 10

11 20 SPARE 12

13 20 SPARE

3P-60A

DISCONNECT

MOUNTED ON

OUTSIDE WALL

(OLD TRASH

COMPACTOR

CIRCUIT)

15 20 SPARE 16

17 20 SPARE 18

19 SPACE SPACE 20

21 SPACE SPACE 22

23 SPACE SPACE 24

25 SPACE SPACE 26

27 SPACE SPACE 28

29 SPACE SPACE 30

31 SPACE SPACE 32

33 SPACE SPACE 34

35 SPACE SPACE 36

37 SPACE SPACE 38

39 SPACE SPACE 40

41 SPACE SPACE 42

BL20

BL19B

PANEL SCHEDULES B6

E-104N/ASCALE:

PANEL DATA E6

E-104N/ASCALE:

LC-DPD CL02

2000A-208V, 3ɸ, 4W

MCC-1

(MORGUE

BL20)

BB-A

B01A

LB-D

BL20

LB-D PARTIAL ONE-LINE DIAGRAM E2

E-104N.T.S.SCALE:

NOTE:

1. SEE SHEET E501 DETAIL C2 FOR DIMENSION DESCRIPTION.

AutoCAD SHX Text

CL02

AutoCAD SHX Text

AutoCAD SHX Text 300A/3P

AC-30

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

100%

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Watson Engineering, P.C.

1112 State Rte. 434 Owego, NY 13827

(607) 223-4334

REPLACE OBSOLETE

PANEL BOARDS

SYRACUSE VAMC, SYRACUSE, NY

Project Director

03/08/2019 JWE JAHRevisions: Date:

528A7-18-708

E-105

BASEMENT PANELS (5 OF 6)

BASEMENT ROOM BL 05 C2

E-1051/4"=1'-0"SCALE:

FLOOR ROOM PANEL

FRAME MAIN

DIMENSIONS (SEE NOTE 1)

EXISTING MAKE/MODEL # OF

SPACES

# OF

SPARES

# OF

EMPTY REPLACE FEED

LOCATIONRECESSED/

SURFACE V/PHASE RATING

(A)

MCB/

MLO H W D FLANGE W RECESSED

DIMENSION

B BL05 LB-AC S 208/3 225 225 38" 20" 5 3/4" N/A N/A SIEMENS ITE/TYPE CDP-7 SERIES 8A 42 3-1Ø 7 X T

BRANCH PANEL: LB-AC

LOCATION: BL05

SUPPLY FROM: LC-DPD

MOUNTING: SURFACE

ENCLOSURE: TYPE 1

VOLTS: 120/208

PHASE: 3

WIRES: 4

A.I.C. RATING: 22 KAIC

MAINS TYPE: MCB

MAINS RATING: 225A

MCB RATING: 225A

PANEL

SECTION NO.

BREAKER

RATING (A)

LOAD

DESCRIPTION

LOAD

DESCRIPTION

BREAKER

RATING (A)

PANEL

SECTION NO.

1 20

RECEPTACLE

TO RIGHT OF

PANEL

TEKMAR (ICE

MELT) 20 2

3 20

UNIT HEATER

FRONT LOBBY JC DSC A33 20 4

15 EF12 HRP-33 15

7 8

9 10

15 HCP-07 HCP-33 15

13 14

15 16

CL-16

MOTORS:

AC31, EF31,

HCP31, HRP31

PUMP 8 20

19 20

21 22

60 AC-33 EF-33 50

25 26

27 28

29 20

RECEPTACLE

ED BASEMENT

GFCI

RECEPTACLE

FOR GYCOL

TANK

20 30

31 20

RECEPTCLE

FOR SHRINK

WRAPPER

SPARE 20 32

33 20

RECEPTACLE

ED BASEMENT SPARE 20 34

35 SPACE SPARE 20 36

37 SPACE SPACE 38

39 SPACE SPACE 40

41 SPACE SPACE 42

LB-AC

BL05

CL02B

BL05A

BL05B

BL05C

PANEL SCHEDULES B7

E-105N/ASCALE:

PANEL DATA E6

E-105N/ASCALE:

LB-AC

BL05

LC-DPD CL02

2000A-208V, 3ɸ, 4W

LB-AC PARTIAL ONE-LINE DIAGRAM E2

E-105N.T.S.SCALE:

NOTE:

1. SEE SHEET E501 DETAIL C2 FOR DIMENSION DESCRIPTION.

AutoCAD SHX Text

AC33

AutoCAD SHX Text 225A/3P

AutoCAD SHX Text

CL02

AutoCAD SHX Text

AC31

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

100%

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Watson Engineering, P.C.

1112 State Rte. 434 Owego, NY 13827

(607) 223-4334

REPLACE OBSOLETE

PANEL BOARDS

SYRACUSE VAMC, SYRACUSE, NY

Project Director

03/08/2019 JWE JAHRevisions: Date:

528A7-18-708

E-106

BASEMENT PANELS (6 OF 6)

BASEMENT ROOM BL 20 C2

E-1061/4"=1'-0"SCALE:

FLOOR ROOM PANEL

FRAME MAIN

DIMENSIONS (SEE NOTE 1)

EXISTING MAKE/MODEL # OF

SPACES

# OF

SPARES

# OF

EMPTY REPLACE FEED

LOCATIONRECESSED/

SURFACE V/PHASE RATING

(A)

MCB/

MLO H W D FLANGE W RECESSED

DIMENSION

B Syr Steam ELC-C1 S 208/3 150 150 32" 20" 5 3/4" N/A N/A SIEMENS ITE/TYPE CDP-7 SERIES 8A 42 5-1Ø 16 X T

BRANCH PANEL: ELC-C1

LOCATION: BL21

SUPPLY FROM: ELC-DPA

MOUNTING: SURFACE

ENCLOSURE: TYPE 1

VOLTS: 120/208

PHASE: 3

WIRES: 4

A.I.C. RATING: 22 KAIC

MAINS TYPE: MCB

MAINS RATING: 150A

MCB RATING: 150A

PANEL

SECTION NO.

BREAKER

RATING (A)

LOAD

DESCRIPTION

LOAD

DESCRIPTION

BREAKER

RATING (A)

PANEL

SECTION NO.

1 20

JOHNSON

CONTROL

LIGHT ABOVE

PANEL 20 2

15 EXHAUST FAN CONDENSATE

PUMP CP-09B 20

5 6

7 8

CONDENSATE

PUMP CP-09A DSP-01B 40

11 12

13 14

40 DSP-01A

SUPPLY

EXHAUST FAN 20 16

17 SPARE 20 18

19 SPARE 20 20

20 PUMP 7

SPARE 20 22

23 SPARE 20 24

25 SPARE 20 26

27 SPACE SPACE 28

29 SPACE SPACE 30

31 SPACE SPACE 32

33 SPACE SPACE 34

35 SPACE SPACE 36

37 SPACE SPACE 38

39 SPACE SPACE 40

41 SPACE SPACE 42

E L C

C

BL21

PANEL SCHEDULES B6

E-106N/ASCALE:

PANEL DATA E6

E-106N/ASCALE:

ELC-DPA

150A/3P

1200A-120/208V,3Ø,4W+G

ELC-C1

BL21

STEAM

RM.

SECTION 2

CL02

150A/3P

ELC-C1 PARTIAL ONE-LINE DIAGRAM E2

E-106N.T.S.SCALE:

NOTE:

1. SEE SHEET E501 DETAIL C2 FOR DIMENSION DESCRIPTION.

EGE-C

G C

A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

100%

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Watson Engineering, P.C.

1112 State Rte. 434 Owego, NY 13827

(607) 223-4334

REPLACE OBSOLETE

PANEL BOARDS

SYRACUSE VAMC, SYRACUSE, NY

Project Director

03/08/2019 JWE JAHRevisions: Date:

528A7-18-708

E-107

GROUND FLOOR PANELS (1 OF 3)

GROUND FLOOR ROOM NG 15 C2

E-1071/4"=1'-0"SCALE:

GROUND FLOOR ROOM CG 29 C6

E-1071/2"=1'-0"SCALE:

FLOOR ROOM PANEL

FRAME MAIN

DIMENSIONS (SEE NOTE 1)

EXISTING MAKE/MODEL # OF

SPACES

# OF

SPARES

# OF

EMPTY RETROFIT FEED

LOCATIONRECESSED/

SURFACE V/PHASE RATING

(A)

MCB/

MLO H W D FLANGE W RECESSED

DIMENSION

G ECC-NG15 EGE-C R 208/3 100 100 31" 20" 5 3/4" 1" 1/4" SIEMENS ITE/TYPE CDP-7 SERIES 8A 30 8-1Ø 0 X B

G CG29 GC-A S 208/3 100 100 38" 20" 5 3/4" N/A N/A SQ D/CAT NO. 44-65937-13L 42 1-1Ø 0 X B

BRANCH PANEL: EGE-C

LOCATION: ECC-NG15

SUPPLY FROM: EGE-DPB

MOUNTING: SURFACE

ENCLOSURE: TYPE 1

VOLTS: 120/208

PHASE: 3

WIRES: 4

A.I.C. RATING: 22 KAIC

MAINS TYPE: MCB

MAINS RATING: 100A

MCB RATING: 100A

PANEL

SECTION NO.

BREAKER

RATING (A)

LOAD

DESCRIPTION

LOAD

DESCRIPTION

BREAKER

RATING (A)

PANEL

SECTION NO.

1 15

ECC ROOM

LIGHTS

JOHNSON

CONTROLS 20 2

3 20

CORRIDOR

LIGHTS,

BATHROOM

AND STORAGE

LIGHTS

LIGHTING 20 4

5 20

RECEPTACLES

ECC ROOM

AND GFI IN

BATHROOM

HOT WATER TANK

7 20

GENERATOR

FUEL TANK

ALARM

SYSTEM

HOT WATER TANK 8

9 20

CONTROL

POWER

HWH-904

WTP-001

ECC DELL

COMPUTER 20 10

11 20

FIRE ALARM

BOOSTER

PANEL *

METASYS UPS 20 12

13 20

FIRE ALARM

PANEL 1 *

POWER

MONITORING EGX 20 14

15 20

FIRE ALARM

PANEL 29 EF-35 20 16

17 20

TANK ALARM

RELAYS EMERGENCY LIGHT 20 18

19 20

RECEPTACLES

ECC ROOM

EXIT LIGHTS/NIGHT

LIGHTS CHILLER

PLANT

20 20

21 20

RECEPTACLES

ECC ROOM SPARE 20 22

23 20

RECEPTACLES

ECC ROOM SPARE 20 24

25 20 SPARE SPARE 20 26

27 20 SPARE SPARE 20 28

29 20 SPARE SPARE 20 30

BRANCH PANEL: GC-A

LOCATION: CG29

SUPPLY FROM: LC-DPF

MOUNTING: SURFACE

ENCLOSURE: TYPE 1

VOLTS: 120/208

PHASE: 3

WIRES: 4

A.I.C. RATING: 22 KAIC

MAINS TYPE: MCB

MAINS RATING: 100A

MCB RATING: 100A

PANEL

SECTION NO.

BREAKER

RATING (A)

LOAD

DESCRIPTION

LOAD

DESCRIPTION

BREAKER

RATING (A)

PANEL

SECTION NO.

1 20

J-BOX ABOVE

DOOR CG33

RECEPTACLES

CG29 20 2

3 20

LIGHTS CG33,

CG35, CG37

LIGHTS

CORRIDOR 20 4

5 20

J-BOX ABOVE

DOOR CG33 LIGHTS CG29 20 6

7 20

RECEPTACLES

CG40, LIGHTS

CG40, 42, 38A

LIGHTS CG27 20 8

9 20

RECEPTACLE

CG36

RECEPTACLES

NG45 N. AND

W. WALLS

20 10

11 20

LIGHTS CG: 30,

32, 36, 38, 43

LIGHTS CG: 21,

23, 25A 20 12

13 20

RECEPTACLES

CG37

RECEPTACLES

CG CG 40, CG42 20 14

15 20

RECEPTACLES

CG37

RECEPTACLES

CORRIDOR 20 16

17 20

RECEPTACLES

CG28 LIGHTING 20 18

19 20

RECEPTACLES

CG 41 LIGHTING 20 20

21 20

RECEPTACLES

CG 28 LIGHTING 20 22

23 20 SPARE J-BOX ABOVE

CG43 20 24

25 20

CXANTEEN

DOORS LIGHTING 20 26

27 20

J-BOX ABOVE

DOOR CG36 LIGHTING 20 28

29 20

DOOR TO

SMOKING

PATIO

RECEPTACLES

NG45 S. AND E.

WALLS

20 30

31 15 LIGHTS CG26

RECEPTACLE

CG42 NORTH

WALL/RIGHT

SIDE

20 32

33 20 LIGHTS CG26

RECEPTACLE

CG42 NORTH

WALL/LEFT SIDE

20 34

35 20

RECEPTACLE ON

COLUMN CG26

RECEPTACLE ON

COLUMN CG42 20 36

37 20

LIGHTS

CORRIDOR

NEAR SMOKING

PATIO

RECEPTACLES

CG35 20 38

39 20 LIGHTING NG45 RECEPTACLES

CG35 20 40

41 20

RECEPTACLE

CORRIDOR

NEAR PATIO

DOOR

RECEPTACLES

CG33 20 42

NG15

NG15C NG15B NG15A

CG29

CORRIDOR

CORRIDOR

PANEL SCHEDULES C8

E-107N/ASCALE:

PANEL DATA E6

E-107N/ASCALE:

125A/3P

ESC-B2

BUILDING 2

BSMT

CORR.

ELSA-A

CL03

ELSGE-A

CM01

EGCBEGE-C

ECC-NG15

225A/3P

60A/3P

100A/3P 40A/3P

EGE-C PARTIAL ONE-LINE DIAGRAM F2

E-107N.T.S.SCALE:

200A/3P

LC-DPF

2000A-208V, 3ɸ, 4W

100A/3P

100A/3P

175A/3P

LC-A CL40

GC-A

GG29

1C-A

C111

GC-A PARTIAL ONE-LINE DIAGRAM F2

E-107N.T.S.SCALE:

NOTE:

1. SEE SHEET E501 DETAIL C2 FOR DIMENSION DESCRIPTION.

#2 AWG

NOTE:

* PROVIDE LOCKOFF DEVICE

AutoCAD SHX Text

CL02CL02

CL40

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

100%

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Watson Engineering, P.C.

1112 State Rte. 434 Owego, NY 13827

(607) 223-4334

REPLACE OBSOLETE

PANEL BOARDS

SYRACUSE VAMC, SYRACUSE, NY

Project Director

03/08/2019 JWE JAHRevisions: Date:

528A7-18-708

E-108

GROUND FLOOR PANELS (2 OF 3)

GROUND FLOOR ROOM CG26A C5

E-1081/4"=1'-0"SCALE:

GROUND FLOOR ROOM AG 03 C2

E-1081/2"=1'-0"SCALE:

FLOOR ROOM PANEL

FRAME MAIN

DIMENSIONS (SEE NOTE 1)

EXISTING MAKE/MODEL # OF

SPACES

# OF

SPARES

# OF

EMPTY RETROFIT FEED

LOCATIONRECESSED/

SURFACE V/PHASE RATING

(A)

MCB/

MLO H W D FLANGE W RECESSED

DIMENSION

G AG03 EGA-A1 S 208/3 100 70 29" 20" 5 3/4" N/A N/A SQ D/CAT NO. NQOB-304-1 SERIES 2 30 13-1Ø 4 X T

G CG26A EGD-A S 208/3 50 50 22" 20" 5 3/4" N/A N/A SQ D/CAT NO. 44-76874-9H 30 6-1Ø 1-2Ø 7 X B

BRANCH PANEL: EGA-A1

LOCATION: AG03

SUPPLY FROM: ELC-DPC

MOUNTING: SURFACE

ENCLOSURE: TYPE 1

VOLTS: 120/208

PHASE: 3

WIRES: 4

A.I.C. RATING: 22 KAIC

MAINS TYPE: MCB

MAINS RATING: 100A

MCB RATING: 70A

PANEL

SECTION NO.

BREAKER

RATING (A)

LOAD

DESCRIPTION

LOAD

DESCRIPTION

BREAKER

RATING (A)

PANEL

SECTION NO.

1 20

LIGHTS

COMP/PEN

EXAM ROOMS

AG13A,C,D,E,F,

G,H,I,J

SPARE 20 2

3 20

RECEP ABOVE

COUNTER

CORRIDOR

AG13K

SPARE 20 4

5 20

RECEP ABOVE

COUNTER

CORRIDOR

AG13K

SPARE 20 6

7 20

RECEP

RECEPTION

CG18A

SPARE 20 8

9 20 SPARE SPARE 20 10

11 20 SPARE SPARE 20 12

PANEL EGAC

RM AG16

SPARE 20 14

15 SPARE 20 16

17 SPARE 20 18

19 20

EXIT LIGHTS

CORRIDOR

AG13K,

WAITING CG18

SPACE 20

21 20 SPARE SPACE 22

23 20 SPARE SPACE 24

25 20 RECEP AL03

DATA CLOSET

RECEPTACLES

AG01

20 26

27 20

SPARE J-BOX

AL03

FAN COIL DATA

CLOSET AG01 20 28

29 20

SECURITY

PANEL POWER

SUPPLY

SPACE 30

BRANCH PANEL: EGD-A

LOCATION: CG26A

SUPPLY FROM: ELC-E

MOUNTING: SURFACE

ENCLOSURE: TYPE 1

VOLTS: 120/208

PHASE: 3

WIRES: 4

A.I.C. RATING: 22 KAIC

MAINS TYPE: MCB

MAINS RATING: 50A

MCB RATING: 50A

PANEL

SECTION NO.

BREAKER

RATING (A)

LOAD

DESCRIPTION

LOAD

DESCRIPTION

BREAKER

RATING (A)

PANEL

SECTION NO.

1 20

GROUND

FLOOR MAIN

CORRIDOR

LIGHTS

GROUND

FLOOR D-WING

CORRIDOR

LIGHTS

20 2

3 20

GRD FL CORR

LIGHTS, CG22

& CG26 LTS,

SEC. CAMERAS

GROUND

FLOOR D-WING

CORRIDOR

LIGHT

20 4

5 20

SPARE

CURCUIT TO

PULLBOX CG20

LIGHTS 20 6

7 20

BURGLAR

ALARM BACK

DOOR

CANTEEN CG26

CARD READER

MICRO

CONTROLLER

CG20

20 8

9 20

RECEPTACLE

CG26 EAST

WALL CANTEEN

RETAIL STORE

LIGHTS AND

RECEPTACLE

CG26

20 10

11 SPACE SPACE 12

13 SPACE SPACE 14

15 SPACE

EMERGENCY

EXIT LIGHT

BACK OF

CANTEEN

STORE

20 16

17 SPACE SPACE 18

19 20

RECEPTACLES

GAS METER

ROOM

SPARE 20 20

2-POLE 20 AMP

SPARE

SPARE 20 22

23 SPARE 20 24

50A MCB

SPARE 20 26

27 SPARE 20 28

29 SPARE 20 30

E G

A A

E G

D A

CG75

CG76

CG26A

CG26B

AG03

CORRIDOR

PANEL SCHEDULES B8

E-108N/ASCALE:

PANEL DATA E6

E-108N/ASCALE:

ELC-DPC

1600A-120/208V,3Ø,4W+G

EGA-C

AG16

AG03

E1A-A

A103

EGA-A1 PARTIAL ONE-LINE DIAGRAM E1

E-108N.T.S.SCALE:

ELC-E CL02

EGDA

CG26

EGDA PARTIAL ONE-LINE DIAGRAM E3

E-108N.T.S.SCALE:

EGA-A1

NOTE:

1. SEE SHEET E501 DETAIL C2 FOR DIMENSION DESCRIPTION.

AutoCAD SHX Text 300A/3P

AutoCAD SHX Text 50A/3P

AutoCAD SHX Text 70A/3P

AutoCAD SHX Text

AutoCAD SHX Text

CL02

AutoCAD SHX Text 100A/3P

AutoCAD SHX Text 150A/3P

AutoCAD SHX Text 50A/3P

AutoCAD SHX Text

CL02

50A/3P

GD-DP

GD-A

SECT. 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

100%

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Watson Engineering, P.C.

1112 State Rte. 434 Owego, NY 13827

(607) 223-4334

REPLACE OBSOLETE

PANEL BOARDS

SYRACUSE VAMC, SYRACUSE, NY

Project Director

03/08/2019 JWE JAHRevisions: Date:

528A7-18-708

E-109

GROUND FLOOR PANELS (3 OF 3)

AND FIRST FLOOR PANELS (1 OF 3)

GROUND FLOOR ROOM DG11 DEMO PLAN C2

E-1091/2"=1'-0"SCALE:

FLOOR ROOM PANEL

FRAME MAIN

DIMENSIONS (SEE NOTE 3)

EXISTING MAKE/MODEL # OF

SPACES

# OF

SPARES

# OF

EMPTY REPLACE RELABEL FEED

LOCATION NOTERECESSED/

SURFACE V/PHASE RATING

(A)

MCB/

MLO H W D FLANGE W RECESSED

DIMENSION

G DG11 GD-DP S 208/3 800 MLO 85" 38" 10 3/8" N/A N/A GE SPECTRA SERIES 12-3Ø 2-3Ø 0 X B 1

G DG11 GD-A S 208/3

350 350 70" 20" 4 3/4" N/A N/A SQ D/CAT NO. 12282504511140001 SER. E1 42 14-1Ø 2 X (GDA)

T 2

BRANCH PANEL: GD-DP

LOCATION: DG11

SUPPLY FROM: MSWGR

MOUNTING: SURFACE

ENCLOSURE: TYPE 1

VOLTS: 208

PHASE: 3

WIRES: 4

A.I.C. RATING: 22 KAIC

MAINS TYPE: MLO

MAINS RATING: 800A

MCB RATING: N/A

PANEL

SECTION NO.

BREAKER

RATING (A)

LOAD

DESCRIPTION

LOAD

DESCRIPTION

BREAKER

RATING (A)

PANEL

SECTION NO.

3P-400A

PANEL 3D-A

(D306)

3P-400A

PANEL 4D-A

(D410)

3 4

5 6

3P-400A

PANEL 2D-A

(D210)

3P-350A

PANEL GD-A

(DG11)

9 10

11 12

3P-250A

SPARE

3P-300A

PANEL 4D-AC 300

15 16

17 18

3P-225A

SPARE

3P-225A

PANEL 1C-NME 225

21 22

23 24

3P-200A

PANEL GD-B

(DG24)

3P-200A

ELEVATOR 200

27 28

29 30

3P-100A

PANEL GDA-2

3P-100A

PANEL 1D-A

(D110)

33 34

35 36

NOTES:

1. THIS PANEL AND ASSOCIATED BREAKERS SHALL BE SUPPLIED BY THE VA.

DG09

DG11

CORRIDOR

PANEL SCHEDULES B8

E-109N/ASCALE:

PANEL DATA E6

E-109N/ASCALE:

MAIN SWITCHGEAR "MSWGR"

3200A-120/208V 3ɸ, 4W CL02

SECTION 10

GD-DP DG11

1D-A

D110

4D-AC

D417

GD-B

DG24

GD-A

(NEW)

3D-A

D306

3D-A2

D313

3D-A3 3D-A4 3D-A5

D326

3D-A1

D314

3D-A7

D304

2D-A

D210

2D-A2

D217A

2D-A3

D213

2D-A4

D210

2D-A5

D222

2D-A1

D217

2D-A6

1C-NME

MAIN

ENTRY

CLOSET

1C-G

POLICE

ENTRY

CORRIDOR

4D-A

D410

4D-A1

D415

4D-A2

D402

GDA-2

DG11

GDA-1

DG18

GD-DP AND GD-A (NEW) PARTIAL ONE-LINE DIAGRAM E3

E-109N.T.S.SCALE:

NOTES:

1. PANEL GD-DP SHALL BE REPLACED WITH VA OWNED GE SPECTRA SERIES PANELBOARD. CONTRACTOR IS RESPONSIBLE FOR REMOVAL OF EXISTING PANEL AND INSTALLATION OF NEW, VA SUPPLIED PANELBOARD.

2. PANEL GD-A SECTION 1 SHALL BE DEMOLISHED, AND ALL EXISTING CONDUCTORS SHALL BE RECONNECTED TO PANEL GD-A SECTION 2. GD-A SECTION 2 SHALL BE RELABELED GDA CONTRACTOR IS RESPONSIBLE FOR REROUTING EXISTING CONDUCTORS AND INTEGRATING EXISTING

CIRCUITS INTO GDA.

PROPOSED GROUND FLOOR ROOM DG11 C2

E-1091/2"=1'-0"SCALE:

DG09

DG11

CORRIDOR

G D

A

S E

C T

G D

A

GD-DP

G D

A

G D

A

PANEL DEMOLITION PHASING PLAN:

1. INSTALL NEW PROPERLY SIZED FEED FOR FEED GDA-2 (100A) FROM GD-DP.

2. DISCONNECT GD-A SECTION 1, COORDINATE ANY ASSOCIATED OUTAGES WITH C.O.R. DEMOLISH GD-A SECTION 1.

3. GDA SECTION 2 SHALL BE DISCONNECTED. RE-ROUTE ALL EXISTING CIRCUITS FROM GD-A SECTION 1 TO GD-A SECTION 2. GD-A SECTION 2 SHALL NOW BE

TERMED GD-A. COORDINATE ANY ASSOCAITED OUTAGES WITH C.O.R.

4. INSTALL NEW 500 KCMIL FEED FOR GD-A (350A) FROM GDDP.

5. COORDINATE OUTAGE WITH COR, AND REPLACE GD-DP. NEW PANEL LOCATION SHALL BE SHIFTED TO THE RIGHT, SUCH THAT IT IS NOT BLOCKED BY

GD-A.

BRANCH PANEL: GD-A

LOCATION: DG11

SUPPLY FROM: GDDP

MOUNTING: SURFACE

ENCLOSURE: TYPE 1

VOLTS: 120/208

PHASE: 3

WIRES: 4

A.I.C. RATING: 22 KAIC

MAINS TYPE: MCB

MAINS RATING: 350A

MCB RATING: 350A

PANEL

SECTION NO.

BREAKER

RATING (A)

LOAD

DESCRIPTION

LOAD

DESCRIPTION

BREAKER

RATING (A)

PANEL

SECTION NO.

1 20

FIRE DAMPER F/S

-06G

RECP. FRESH LOCK

DG14 20 2

3 20 SPARE SPARE 20 4

5 20

LIGHTS

BASEMENT

SOUTH

SPARE 20 6

7 20

LIGHTS

BASEMENT

NORTH

RECP. BASEMENT 20 8

9 SPACE SPARE 20 10

11 SPACE SPARE 20 12

13 20

SPARE WIRE IN

WIRE WAY BELOW

PANEL

LIGHTS & RECP.

ELEVATOR SHAFT 20 14

15 20

SPARE WIRE IN

WIRE WAY BELOW

PANEL

SPARE 20 16

17 20

SPARE WIRE IN

WIRE WAY BELOW

PANEL

RECP. DG5, DG7

20 18

19 20 RECP. CG26B SPARE 20 20

21 20

SPARE WIRE IN

WIRE WAY BELOW

PANEL

UNIT HEATER

DG24 20 22

23 20

SPARE WIRE IN

WIRE WAY BELOW

PANEL

SPARE 20 24

25 20

RECP. DG19, DG20 SPARE 20 26

27 20 SPARE RECP. DG24,

FLOOR RECP. 20 28

29 20

RECP. DG3, DG5 SPARE 20 30

31 20

RECP. DG3,

FAN DG26 - FAN

REMOVED WIRES

FOR STATER IN

2-GANG BOX BY

SIGN

20 32

33 20 SPARE SPARE 20 34

35 20 LIGHTS DG9 RECP. CORRIDOR

EAST 20 36

37 20

RECP. CORRIDOR

SOUTH

GDA-1 3- POLE 100

A RM. DG18 100

39 20 SPARE 40

41 20 RECP. WEST WALL 42

NOTES:

1. MOVE UNIT HEATER DG24 FEED FROM CIRCUIT 22 TO CIRCUIT 20.

2. MOVE 30A BREAKER AND CAGE WASHER FEED FROM GDA SECTION 1 CIRCUIT 13,15,17, TO

CIRCUIT 22,24,26.

3. REMOVE CONDUCTORS FROM CIRCUIT 13,15,17. MOVE 50A BREAKER AND FEEDS FROM GDA

SECTION 1 37,39,41 TO 13,15,17.

AutoCAD SHX Text 400A/3P

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

DG11

AutoCAD SHX Text 400A/3P

AutoCAD SHX Text 400A/3P

AutoCAD SHX Text 100A/3P

AutoCAD SHX Text 150A/3P

AutoCAD SHX Text 225A/3P

AutoCAD SHX Text 300A/3P

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text 200A/3P

AutoCAD SHX Text 200A/3P

AutoCAD SHX Text 350A/3P

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

ELEVATOR

AutoCAD SHX Text 70A/3P

AutoCAD SHX Text 70A/3P

AutoCAD SHX Text 70A/3P

AutoCAD SHX Text 90A/3P

AutoCAD SHX Text 90A/3P

AutoCAD SHX Text 70A/3P

AutoCAD SHX Text 100A/3P

AutoCAD SHX Text 110A/3P

AutoCAD SHX Text 100A/3P

AutoCAD SHX Text 300A/3P

AutoCAD SHX Text 200A/3P

AutoCAD SHX Text 350A/3P

AutoCAD SHX Text 400A/3P

AutoCAD SHX Text 225A/3P

AutoCAD SHX Text 10A

AutoCAD…