36C24219B0029-004.pdf
PDF 10 MB Posted
- Attached to
- 528A7-18-708 REPLACE OBSOLETE PANELBOARDS Federal contract opportunity
- Solicitation number
- 36C24219B0029
About this file
36C24219B0029 S02-DRAWING Replace Obsolete Panel Boards Syracuse VA STAMPED.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24219C0164-000.docx | DOCX document | |
| 36C24219B0029-0002000.docx | DOCX document | |
| 36C24219B0029-0002001.pdf | ||
| 36C24219B0029-0002002.jpg | JPG image | |
| 36C24219B0029-0001000.docx | DOCX document | |
| 36C24219B0029-002.pdf | ||
| 36C24219B0029-003.pdf | ||
| 36C24219B0029-001.docx | DOCX document | |
| 36C24219B0029-000.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100%
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827
(607) 223-4334
REPLACE OBSOLETE
PANEL BOARDS
SYRACUSE VAMC, SYRACUSE, NY
Project Director
03/08/2019 JWE JAHRevisions: Date:
528A7-18-708
T-101
COVER SHEET AND DRAWING INDEX
SHEET NO. DESCRIPTION
T-101 COVER SHEET & DRAWING INDEX
G-101 GENERAL NOTES
A-101
BASEMENT AND GROUND FLOOR KEY
PLANS
A-102 FIRST AND SECOND FLOOR KEY PLANS
A-103 THIRD AND FOURTH FLOOR KEY PLANS
A-104 FIFTH AND SIXTH FLOOR KEY PLANS
A-105 SEVENTH AND EIGHTH FLOOR KEY PLANS
E-101
BASEMENT PANELS (1 OF 6)
E-102
BASEMENT PANELS (2 OF 6)
E-103
BASEMENT PANELS (3 OF 6)
E-104
BASEMENT PANELS (4 OF 6)
E-105
BASEMENT PANELS (5 OF 6)
E-106
BASEMENT PANELS (6 OF 6)
E-107
GROUND FLOOR PANELS (1 OF 3)
E-108
GROUND FLOOR PANELS (2 OF 3)
E-109
GROUND FLOOR PANELS (3 OF 3)
E-110
FIRST FLOOR PANELS (1 OF 3)
E-111
FIRST FLOOR PANELS (2 OF 3)
E-112
FIRST FLOOR PANELS (3 OF 3)
E-113
SECOND FLOOR PANELS (1 OF 3)
E-114
SECOND FLOOR PANELS (2 OF 3)
E-115
SECOND FLOOR PANELS (3 OF 3)
E-116 THIRD FLOOR PANELS
E-117 FOURTH FLOOR PANELS
E-118 FIFTH FLOOR PANELS
E-119
SIXTH FLOOR PANELS (1 OF 2)
E-120
SIXTH FLOOR PANELS (2 OF 2)
E-121
SEVENTH FLOOR PANELS (1 OF 2)
E-122
SIXTH FLOOR PANELS (2 OF 2)
E-123 EIGHTH FLOOR PANELS
E-501 ELECTRICAL DETAILS
- VA ELECTRICAL DESIGN MANUAL
- STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE, NFPA 70E, 2018
- NATIONAL ELECTRICAL CODE, NFPA 70, 2017
AutoCAD SHX Text
DRAWING INDEX
AutoCAD SHX Text
REPLACE OBSOLETE PANEL BOARDS
AutoCAD SHX Text
DEPARTMENT OF VETERANS AFFAIRS PROJECT NO. 528A7-18-708 SYRACUSE, NY
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
SITE PLAN
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
SITE LOCATION
AutoCAD SHX Text
LIST OF APPLICABLE REFERENCES
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100%
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827
(607) 223-4334
REPLACE OBSOLETE
PANEL BOARDS
SYRACUSE VAMC, SYRACUSE, NY
Project Director
03/08/2019 JWE JAHRevisions: Date:
528A7-18-708
G-101
GENERAL NOTES
DESIGN NARRATIVE
1. THE PROPOSED DESIGN DIRECTS THE RENOVATION OF APPROXIMATELY 41 ELECTRICAL PANELS LOCATED AT VARIOUS
PLACES THROUGHOUT THE SYRACUSE VA MEDICAL CENTER. EACH PANEL WILL BE REPLACED, RETROFITTED OR
DEMOLISHED AS SPECIFIED.
2. FOR PANELS TO BE REPLACED, THE CONTRACTOR SHALL DISCONNECT ALL EXISTING CONDUCTORS, AND THE EXISTING
PANEL COVER, BREAKERS, BUSES, AND BOX, SHALL BE REPLACED WITH THE APPROPRIATE CONTRACTOR SUPPLIED
REPLACEMENT PARTS. CONTRACTOR SHALL THEN RECONNECT CONDUCTORS AS EXISTING.
3. FOR PANELS TO BE RETROFITTED, THE CONTRACTOR SHALL DISCONNECT ALL EXISTING CONDUCTORS, AND THE
EXISTING PANEL COVER, BREAKERS, AND BUSES SHALL BE REMOVED. THE APPROPRIATE CONTRACTOR SUPPLIED
REPLACEMENT PARTS SHALL BE INSTALLED IN THE EXISTING BOX, AND THE CONDUCTORS SHALL BE RECONNECTED AS
EXISTING.
4. FOR PANELS TO BE DEMOLISHED, THE CONTRACTOR SHALL DISCONNECT ALL CONDUCTORS AND REROUTE TO THE
SPECIFIED PANEL. THE PANEL COVER, BUS, BREAKERS, AND BOX SHALL BE REMOVED AND RETURNED TO THE
SYRACUSE VA MEDICAL CENTER.
GENERAL NOTES:
1. THE GENERAL NOTES ON THIS SHEET APPLY TO ALL THE DRAWING DISCIPLINES.
2. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY ALL ASPECTS OF THE DESIGN, TO INCLUDE THE WORK OF
SUB-TRADES, PRIOR TO SUBMITTING A BID.
3. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE, ALTHOUGH NO ATTEMPT WAS MADE TO SHOW
EVERY OFFSET, FITTING, BEAM, PIPE SUPPORT, CLEARANCE, ETC. IT IS THE CONTRACTOR'S RESPONSIBILITY TO
SURVEY ALL WORK AREAS AND SUBMIT FINAL, DETAILED COORDINATED SHOP DRAWINGS FOR REVIEW BY THE
DESIGNER OF RECORD TO ENSURE THAT THE DESIGN INTENT WILL BE MET AND THAT ALL TRADES ARE PROPERLY
COORDINATED. CHANGES REQUIRED TO FIT EQUIPMENT, PIPING, AND DUCTWORK SHALL BE PROVIDED AT NO
ADDITIONAL COST TO THE OWNER. ANY MAJOR DISCREPANCIES SHALL BE CLARIFIED PRIOR TO SUBMITTAL OF BID.
4. BECAUSE OF THE SMALL SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL OFFSETS, TRANSITIONS, FITTINGS, CLEARANCES, POSSIBLES CLASHES, AND ACCESSORIES THAT MAY BE REQUIRED. COORDINATE ALL THE
WORK OF ALL THE TRADES TO INSURE ALL DUCTS, PIPES, CONDUITS, ETC. DO NOT CONFLICT AND CLEAR
STRUCTURAL AND ARCHITECTURAL MEMBERS. THE CONTRACTOR IS RESPONSIBLE FOR DEVELOPING COORDINATED
SHOP DRAWINGS FOR REVIEW PRIOR TO STARTING INSTALLATION.
5. IT IS RECOMMENDED THAT CONTRACTOR SHALL VISIT THE SITE AND BE FULLY COGNIZANT OF ALL CONDITIONS
PRIOR TO SUBMITTING BID. REPORT ANY DISCREPANCIES TO THE CONTRACTING OFFICER PRIOR TO SUBMITTAL OF
BID.
6. THE WORK INCLUDES ALL ITEMS OF THE SPECIFICATIONS THAT ARE EITHER WRITTEN ON THE DRAWINGS OR
SEPARATELY IN A SPECIFICATIONS BOOK.
7. WHERE THERE IS A CONFLICT ON THE PLANS, SPECIFICATIONS, NOTES, GENERAL NOTES, REFERENCES, PUBLICATIONS, CODES, ETC. WITH RESPECT TO CONSTRUCTION, MATERIALS, PRODUCTS, METHODS, WORKMANSHIP, PROCEDURE, EXECUTION, ETC. THE MOST STRINGENT SHALL BE UTILIZED OR INSTALLED. THE MOST STRINGENT
SHALL BE DEFINED AS THE SPECIFICATION OR REQUIREMENT THAT ALLOWS ALL SPECIFICATIONS OR REQUIREMENTS
THAT ARE IN CONFLICT TO BE SATISFIED. NO RELIEF OR EXTRA PAYMENT SHALL BE MADE TO THE CONTRACTOR
BECAUSE OF THIS INTERPRETATION.
8. CONTRACTOR SHALL NOT BEGIN FABRICATION, CUT ANY MEMBERS, OR BEGIN INSTALLATION UNTIL THE SUBMITTALS
AND COORDINATED SHOP DRAWINGS HAVE BEEN APPROVED. ANY WORK CONSTRUCTED OR INSTALLED PRIOR TO
THE APPROVAL OF SUBMITTALS AND COORDINATED SHOP DRAWINGS SHALL BE AT THE CONTRACTOR'S RISK AND
SHALL BE REMOVED AND REINSTALLED OR RECONSTRUCTED AT THE CONTRACTOR'S EXPENSE AT THE REQUEST OF
THE COR TO THE COMPLETE SATISFACTION OF THE COR.
9. ALL WORK SHALL BE DONE WITH COMPLETE COMPLIANCE WITH THE PUBLISHED EDITIONS OF THE APPLICABLE
CODES AND STANDARDS WHETHER STATUTORY OR NOT. ALL WORK SHALL BE INSTALLED TO COMPLY WITH THE
INTERNATIONAL BUILDING ELECTRICAL CODES, NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION, AND BASIC ELECTRICAL REGULATIONS. IF ANY PART OF THE INSTALLATION DOES
NOT MEET CODE, NOTIFY THE OWNER'S REPRESENTATIVE PRIOR TO BEGINNING THE INSTALLATION. IF ANY PART OF
THE PROJECT CANNOT BE INSTALLED TO CONFORM WITH THE PLANS AND/OR SPECIFICATIONS, NOTIFY THE COR
PRIOR TO BEGINNING THE INSTALLATION.
10. UNLESS STATED OTHERWISE, ALL EXISTING MATERIAL AND EQUIPMENT SHALL REMAIN THE PROPERTY OF THE
SYRACUSE VA MEDICAL CENTER.
11. THE CONTRACTOR SHALL DEVELOP AND PRESENT A CONSTRUCTION PLAN AND WORK SCHEDULE WITH ALL PHASING, STAGING, AND SEQUENCING OF WORK FOR APPROVAL PRIOR TO THE COMMENCEMENT AND BEGINNING
IMPLEMENTATION OF HIS WORK. THE CONTRACTOR SHALL DETERMINE PRIOR TO SUBMITTING HIS WORK SCHEDULE, THE SPECIFIC TIME AVAILABILITY OF ALL AREAS AND SPACES AND DETERMINE WHAT WORK MUST BE DONE DURING
"OFF HOURS".
12. WITH THE EXCEPTION OF SIGNIFICANT NOISE GENERATING ACTIVITIES SUCH AS CORE DRILLING, ETC., WORK
OUTSIDE OF THE OCCUPIED SPACES, SUCH AS ON THE ROOF, ETC., MAY BE PERFORMED DURING NORMAL WORKING
HOURS.
13. UNLESS SPECIFICALLY NOTED AS EXISTING, ALL ITEMS, EQUIPMENT, AND WORK SHOWN IS NEW AND SHALL BE
FURNISHED AND INSTALLED BY THE CONTRACTOR.
14. DURING THE EXECUTION OF THIS CONTRACT, THE SITE AND BUILDINGS WILL BE OCCUPIED AND IN USE. WORK DONE
UNDER THIS CONTRACT SHALL BE PERFORMED WITHOUT INCONVENIENCE TO THE OWNER INSOFAR AS POSSIBLE.
ALL WORK SHALL BE COORDINATED WITH THE COR AND IS SUBJECT TO THEIR CONTINUOUS APPROVAL.
15. THE CONTRACTOR IS COMPLETELY RESPONSIBLE FOR ALL CHARACTERISTICS OF THE EQUIPMENT THAT HE INTENDS
TO INSTALL AND MUST FOLLOW MANUFACTURER RECOMMENDATIONS FOR PROPER INSTALLATION. IF THERE ARE
ANY DIFFERENCES IN THE EQUIPMENT SHOWN ON THE DESIGN DRAWINGS AND THE EQUIPMENT TO BE INSTALLED, THE CONTRACTOR SHALL MAKE ALL CHANGES AND ADJUSTMENTS TO ACCOMMODATE THE PROPOSED EQUIPMENT
AT NO ADDITIONAL COST TO THE OWNER. THIS APPLIES TO ALL SUPPORT SERVICES AND FACILITIES NECESSARY TO
PROPERLY INSTALL THE EQUIPMENT TO FUNCTION ADEQUATELY AS PART OF THE SYSTEMS FOR WHICH THEY WERE
DESIGNED AND SELECTED. THESE CHARACTERISTICS INCLUDE SUCH THINGS AS WEIGHT, CLEARANCE, DIMENSIONS, ELECTRICAL, MECHANICAL, PLUMBING, AND UTILITY SERVICES, ETC. ACCOMMODATING SERVICES INCLUDE SUCH
THINGS AS DIMENSIONS, LOCATIONS, AND SIZES OF SUPPORTING MEMBERS, PIPE, CONNECTION SIZES, ELECTRICAL
SERVICE SIZE AND PROTECTION, ELECTRICAL CONNECTION LOCATION, UTILITY AND PLUMBING CONNECTION SIZES
AND LOCATIONS, ETC. ALL REQUIRED CHANGES TO THE CONTRACT DRAWINGS AND SPECIFICATIONS SHALL BE
DESIGNED AND STAMPED BY REGISTERED ENGINEERS IN THE APPROPRIATE DISCIPLINE EMPLOYED BY THE
CONTRACTOR AND SHALL BE INCLUDED AS PART OF THE EQUIPMENT SUBMITTALS. ALL CHANGES SHALL BE SUBJECT
TO THE APPROVAL OF THE PROJECT A/E AND THE OWNER'S REPRESENTATIVE.
16. BEFORE ANY DEMOLITION OR CONSTRUCTION WORK IS BEGUN, THE CONTRACTOR AND THE COR SHALL SURVEY THE
EXISTING BUILDING AREA TO BE MODIFIED AND/OR REPLACED TO ACCURATELY DOCUMENT EXISTING CONDITIONS.
THIS SURVEY WILL BE USED BY THE OWNER'S REPRESENTATIVE AT JOB COMPLETION TO DETERMINE WHICH
BUILDING/SITE COMPONENTS MUST BE REPLACED WITH NEW.
17. UNLESS STATED OTHERWISE, REQUEST APPROVAL FROM THE OWNER'S REPRESENTATIVE SEVEN DAYS IN ADVANCE
FOR THE SHUTDOWN OF ANY EXISTING SYSTEM.
18. UNLESS STATED OTHERWISE, FINAL ADVANCE NOTICE OF 48 HOURS SHALL BE GIVEN TO THE OWNER'S
REPRESENTATIVE PRIOR TO THE PROPOSED SHUTDOWN OF ANY SYSTEM.
19. PROVIDE ADEQUATE FIRE PROTECTION IN THE ENTIRE CONSTRUCTION AREA FOR THE DURATION OF THE
CONSTRUCTION PERIOD.
20. THE ENTIRE EXISTING FIRE PROTECTION SYSTEM SHALL BE RESTORED TO FULL OPERATION AT THE END OF EACH
WORKING DAY. ALL EXISTING FIRE ALARMS AND FIRE EXITS AND ANY OTHER ASPECT OF THE EXISTING FIRE ALARM
SYSTEM SHALL REMAIN IN FULL OPERATION. THE COST OF RESPONSE TO ANY FALSE ALARM AS CHARGED BY ANY
LOCAL FIRE DEPARTMENT SHALL BE PAID BY THE CONTRACTOR.
21. CONTRACTOR SHALL NOT PENETRATE OR CUT ANY STRUCTURAL MEMBERS NOT SPECIFICALLY SHOWN ON THE
DRAWINGS (E.G., JOISTS, BEAMS, ETC.). IF STRUCTURAL MEMBERS CONFLICT WITH ROUTING, CONTACT THE OWNER'S
REPRESENTATIVE FOR DIRECTION BEFORE PROCEEDING. EXERCISE CAUTION IN CUTTING CONCRETE FLOORS AND
WALLS TO AVOID EXISTING UTILITIES WHICH MAY BE LOCATED IN AND UNDER CONCRETE SURFACES.
22. THE CONTRACTOR SHALL PROVIDE NEW OPENINGS IN WALLS, FLOOR, AND ROOF, AND PATCH EXISTING OPENINGS IN
CONJUNCTION WITH THE DEMOLITION AND INSTALLATION OF THE NEW BUILDING COMPONENTS, INCLUDING
MECHANICAL, PLUMBING, ELECTRICAL, AND GENERAL CONTRACTOR'S ITEMS. ALL NECESSARY FRAMING, COUNTER-FLASHING, ETC. SHALL BE INCLUDED.
23. FOR ALL FLOOR, WALL, AND ROOF PENETRATION, VERIFY THE LOCATION OF THE EXISTING STRUCTURAL MEMBERS
PRIOR TO DRILLING AND CUTTING, RELOCATE OPENINGS AS REQUIRED AND OFFSET DUCTS, PIPES, CONDUIT, ETC.
24. ALL EXISTING DUCTWORK, PIPING, CONDUIT, AND MECHANICAL, PLUMBING, AND ELECTRICAL EQUIPMENT NOT TO BE
REUSED OR REMAIN IN SERVICE SHALL BE REMOVED FROM THE FACILITY. THE COR HAS THE OPTION TO RECLAIM
ANY DEMOLISHED MATERIALS OR EQUIPMENT, IN WHICH CASE IT SHALL BE DELIVERED TO THE LOCATION
DESIGNATED BY THE COR.
25. FOR EACH PHASE AND BEFORE INTERRUPTING EACH EXISTING UTILITY, DETERMINE, IN ADVANCE, IF ANY
DOWNSTREAM SERVICE BEYOND THE CONSTRUCTION AREA OF THE PHASE, WILL BE INTERRUPTED AND PROVIDE A
TEMPORARY SERVICE BYPASSING THE CONSTRUCTION AREA. DETERMINE ALL SUCH TEMPORARY SERVICES PRIOR
TO SUBMITTING BID. THERE WILL BE NO FUTURE CONSIDERATION TO THE CONTRACTOR FOR ANY TEMPORARY
SERVICES REQUIRED. PREPARE A DETAILED SHOP DRAWING SHOWING ALL OF THE EXISTING UTILITIES IN THEIR
RELOCATED LOCATION AND ALL THE NEW HVAC SYSTEMS.
26. EXISTING DUCTWORK, DOMESTIC COLD WATER PIPING, DOMESTIC HOT WATER PIPING, CHILLED AND HEATING HOT
WATER PIPING, WASTE, VENT, FIRE SPRINKLER LINES, FIRE ALARM EQUIPMENT, ELECTRICAL CONDUIT, TELEPHONE
CONDUIT, COMMUNICATION CONDUIT, PNEUMATIC TUBING, ETC., MAY HAVE TO BE RELOCATED TO FACILITATE THE
INSTALLATION OF THE NEW WORK. THE CONTRACTOR SHALL DETERMINE ALL EXISTING SERVICES THAT REQUIRE
RELOCATION PRIOR TO SUBMITTING HIS BID AND INCLUDE ALL COSTS IN THE BID. THERE WILL BE NO EXTRA
COMPENSATION TO THE CONTRACTOR FOR THIS WORK.
27. PATCH AND PAINT TO MATCH EXISTING, ALL SURFACES DAMAGED BY THE DEMOLITION AND ALL OPENINGS NOT TO BE
REUSED.
28. REPAIR DAMAGE TO CEILING, WALLS, ETC. TO THE SATISFACTION OF THE OWNER'S REPRESENTATIVE.
29. WHEN A DETAIL OR NOTE IS IDENTIFIED AS TYPICAL, THE CONTRACTOR IS TO APPLY THE DETAIL OR NOTE TO EVERY
SIMILAR CONDITION, WHETHER OR NOT THE REFERENCED DETAIL OR NOTE IS REPEATED OR REFERENCED.
30. WHERE NO CONSTRUCTION DETAIL IS INDICATED, SUCH WORK SHALL BE SIMILAR TO COMPARABLE WORK DETAILED
OR NOTED ELSEWHERE OR TO MATCH EXISTING CONDITIONS, SUBJECT TO THE APPROVAL OF THE OWNER'S
REPRESENTATIVE.
31. ALL HOLES, VOIDS, AND DAMAGED OR UNEVEN SURFACES WHICH ARE CAUSED BY THE CONTRACTOR'S WORK AND
WHICH REMAIN EXPOSED IN THE WALL, FLOOR, CEILING, OR OTHER SURFACES SHALL BE PATCHED, REPAIRED, AND
BROUGHT FLUSH WITH THE ADJACENT CONSTRUCTION. SUCH SURFACES, NOT CONCEALED BY THE NEW
CONSTRUCTION, SHALL MATCH IN EVERY RESPECT THE EXISTING NON-DAMAGED CONSTRUCTION. REMOVE EXISTING
UTILITIES BACK BEHIND EXISTING SURFACES AND CAP SO AS NOT TO INTERFERE WITH NEW PATCHES.
32. WHEREVER NEW WALL, FLOOR, OR CEILING FINISHES ARE INDICATED, THE CONTRACTOR SHALL BRING EXISTING
ELECTRICAL, MECHANICAL, PLUMBING, AND OTHER BUILDING COMPONENTS FLUSH WITH THE NEW FINISHED
SURFACES IF APPROPRIATE.
33. THE DEMOLITION SHALL INCLUDE ALL ASSOCIATED ANCHORAGES, HANGERS, SUPPORTS, BRACES, FASTENERS, MASTIC, MORTAR, LATH, AND RELATED ITEMS. THE EXISTING SUBSTRATE, INCLUDING CONCRETE, MASONRY, METAL
FRAMING AND FURRING SHALL BE REPAIRED WHERE DAMAGE BY THE CONTRACTOR'S WORK.
34. ANY ANTICIPATED HAZARDOUS MATERIALS (HAZMAT) IS INDICATED ON THE DRAWINGS, HOWEVER, IT IS IMPOSSIBLE
TO PREDICT WHERE EXACTLY ALL HAZMAT MAY BE ENCOUNTERED. IF HAZMAT IS ENCOUNTERED OR SUSPECTED AT
ANY POINT DURING CONSTRUCTION, CEASE ALL WORK IMMEDIATELY AND CONTACT THE OWNER'S REPRESENTATIVE
FOR GUIDANCE.
35. ALL ELECTRICAL PANEL REPLACEMENT PARTS SUCH AS COVERS, BREAKERS, BUSES, BOXES, ETC. SHALL BE SUPPLIED
BY THE CONTRACTOR UNLESS OTHERWISE NOTED.
36. ALL EQUIPMENT/MATERIALS REMOVED AND/OR DEMOLISHED DURING THIS PROJECT SHALL REMAIN THE PROPERTY OF
THE SYRACUSE VA MEDICAL CENTER UNLESS OTHERWISE NOTED.
37. CONTRACTOR SHALL REFER TO THE PARTIAL ONE-LINE DIAGRAMS AS WELL AS THE EXISTING AS-BUILT ONE-LINE
DIAGRAM TO IDENTIFY AND SHUT OFF THE APPROPRIATE POWER SOURCE PRIOR TO PERFORMING ANY WORK. FINAL
SCHEDULING AND PHASING OF WORK SHALL BE DEVELOPED BY CONTRACTOR AND COORDINATED WITH COR FOR
APPROVAL.
38. ALL PANELS AND BREAKERS SHALL BE UPGRADED TO 22 KAIC.
39. THE CONTRACTOR WILL BE RESPONSIBLE FOR FIELD VERIFYING MEASUREMENTS AT EACH PANEL LOCATION BEFORE
ORDERING EQUIPMENT.
40. MISCELLANEOUS AREAS OF SPRAY FOAM INSULATION SHALL BE REMOVED AS INDICATED ON DRAWINGS. PROPER
FIRE-STOPPING MATERIAL WILL BE USED.
41. ELECTRICAL SHUTDOWNS MUST OCCUR AFTER 6PM MONDAY THROUGH FRIDAY, WITH EXACT TIMING TO BE
DETERMINED BY COR.
42. CONTRACTOR IS RESPONSIBLE FOR CONTACTING AND COORDINATING WITH RED HAWK REGARDING ANY FIRE ALARM
MODIFICATIONS. FIRE HAWK CAN BE REACHED AT (315)458-1154.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100%
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827
(607) 223-4334
REPLACE OBSOLETE
PANEL BOARDS
SYRACUSE VAMC, SYRACUSE, NY
Project Director
03/08/2019 JWE JAHRevisions: Date:
528A7-18-708
A-101
BASEMENT AND GROUND
FLOOR KEYPLANS
BASEMENT KEYPLAN F1
A1011/32"=1'-0"SCALE:
GROUND FLOOR KEYPLAN F6
A1011/32"=1'-0"SCALE:
SEE PARTIAL FLOOR PLAN
D2 ON SHEET E-102
(PANEL ELC-AC)
SEE PARTIAL FLOOR PLAN C2
ON SHEET E-103
(PANELS LC-E LEFT AND RIGHT)
SEE PARTIAL FLOOR PLAN C2 ON SHEET E-101
(PANELS ELC-G, AND ELC-B SECTION 1 AND 2)
SEE PARTIAL FLOOR
PLAN C2 ON SHEET E-104
(PANEL LB-1)
SEE PARTIAL FLOOR
PLAN C2 ON SHEET E-105
(PANEL LB-AC)
SEE PARTIAL FLOOR
PLAN C2 ON SHEET E-106
(ELC-C1)
SEE PARTIAL FLOOR
PLAN C2 ON SHEET E-107
(PANEL EGE-C)
SEE PARTIAL FLOOR
PLAN C2 ON SHEET E-108
(PANEL EGA-A1)
SEE PARTIAL FLOOR
PLAN C6 ON SHEET E-107
(PANEL GC-A)
SEE PARTIAL FLOOR
PLAN C5 ON SHEET E-108
(PANEL EGD-A)
SEE PARTIAL FLOOR
PLAN C2 ON SHEET E-109
(PANEL GD-DP, GDA
SECTION 1 AND 2)
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100%
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827
(607) 223-4334
REPLACE OBSOLETE
PANEL BOARDS
SYRACUSE VAMC, SYRACUSE, NY
Project Director
03/08/2019 JWE JAHRevisions: Date:
528A7-18-708
A-102
FIRST AND SECOND FLOOR
KEYPLANS
FIRST FLOOR KEYPLAN F1
A1021/32"=1'-0"SCALE:
SECOND FLOOR KEYPLAN F6
A1021/32"=1'-0"SCALE:
SEE PARTIAL FLOOR
PLAN C6 ON SHEET E-110
(PANEL 1C-C)
SEE PARTIAL FLOOR PLAN
C2 ON SHEET E-111
(PANELS 1C-D, E1-CC, 1C-A)
SEE PARTIAL FLOOR
PLAN C2 ON SHEET E-112
(PANEL ELS1A-A)
SEE PARTIAL FLOOR
PLAN C2 ON SHEET E-113
(PANEL 2C-D)
SEE PARTIAL FLOOR
PLAN C5 ON SHEET E-113
(PANEL E2-CB)
SEE PARTIAL FLOOR
PLAN C2 ON SHEET E-114
(PANEL 2C-C)
SEE PARTIAL FLOOR
PLAN C2 ON SHEET E-115
(PANELS 2A-C AND 2A-A1)
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100%
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827
(607) 223-4334
REPLACE OBSOLETE
PANEL BOARDS
SYRACUSE VAMC, SYRACUSE, NY
Project Director
03/08/2019 JWE JAHRevisions: Date:
528A7-18-708
A-103
THIRD AND FOURTH FLOOR
KEYPLANS
THIRD FLOOR KEYPLAN F1
A1031/32"=1'-0"SCALE:
FOURTH FLOOR KEYPLAN F6
A1031/32"=1'-0"SCALE:
SEE PARTIAL FLOOR
PLAN C2 ON SHEET E-116
(PANEL 3B-D)
SEE PARTIAL FLOOR
PLAN C5 ON SHEET E-116
(PANEL E3A-C)
SEE PARTIAL FLOOR
PLAN C2 ON SHEET E-117
(PANELS 4A-D AND 4A-A)
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100%
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827
(607) 223-4334
REPLACE OBSOLETE
PANEL BOARDS
SYRACUSE VAMC, SYRACUSE, NY
Project Director
03/08/2019 JWE JAHRevisions: Date:
528A7-18-708
A-104
FIFTH AND SIXTH FLOOR
KEYPLANS
FIFTH FLOOR KEYPLAN F1
A1041/32"=1'-0"SCALE:
SIXTH FLOOR KEYPLAN F6
A1041/32"=1'-0"SCALE:
SEE PARTIAL FLOOR PLAN
C2 ON SHEET E-118
(PANELS 5B-A AND E5A-A)
SEE PARTIAL FLOOR PLAN
C2 ON SHEET E-120
(PANEL 6B-A)
SEE PARTIAL FLOOR PLAN C2
ON SHEET E-119
(PANELS 6A-A, E6A-A AND 6A-D)
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100%
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827
(607) 223-4334
REPLACE OBSOLETE
PANEL BOARDS
SYRACUSE VAMC, SYRACUSE, NY
Project Director
03/08/2019 JWE JAHRevisions: Date:
528A7-18-708
A-105
SEVENTH AND EIGHTH
FLOOR KEYPLANS
SEVENTH FLOOR KEYPLAN F1
A1051/32"=1'-0"SCALE:
EIGHTH FLOOR KEYPLAN F6
A1051/32"=1'-0"SCALE:
SEE PARTIAL FLOOR PLAN
C2 ON SHEET E-121
(PANELS 7A-C, E7-AB, 7A-B)
SEE PARTIAL FLOOR PLAN
C2 ON SHEET E-122
(PANELS 7A-A, AND 7B-A)
SEE PARTIAL FLOOR PLAN
C2 ON SHEET E-123
(PANEL 8B-A)
ELC-G
ELC-B SECT 1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100%
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827
(607) 223-4334
REPLACE OBSOLETE
PANEL BOARDS
SYRACUSE VAMC, SYRACUSE, NY
Project Director
03/08/2019 JWE JAHRevisions: Date:
528A7-18-708
E-101
BASEMENT PANELS (1 OF 6)
BASEMENT ROOM CL 09 C2
E-1011/4"=1'-0"SCALE:
FLOOR ROOM PANEL
FRAME MAIN
DIMENSIONS (SEE NOTE 1)
EXISTING MAKE/MODEL # OF
SPACES
# OF
SPARES
# OF
EMPTY REPLACE RETROFIT FEED
LOCATIONRECESSED/
SURFACE V/PHASE RATING
(A)
MCB
RATING H W D FLANGE W RECESSED
DIMENSION
B CL09 ELC-G S 208/3 100 100 38" 20" 5 3/4" N/A N/A SQ D/CAT NO. 44-76874-7E 30
1-3Ø 1-2Ø 3-1Ø
0 X T
B CL09 ELC-B SECT 1 S 208/3 200 200 53" 20" 5 3/4" N/A N/A SQ D/CAT NO. 44-65937-15A 54 2-3Ø 7-1Ø 0 X T
B CL09 ELC-B SECT 2 S 208/3 200 MLO 44" 20" 5 3/4" N/A N/A SQ D/CAT NO. 44-65937-14D 54 1-3Ø 3-1Ø 12 X B
BRANCH PANEL: ELC-G
LOCATION: CL09
SUPPLY FROM: ELC-DPB
MOUNTING: SURFACE
ENCLOSURE: TYPE 1
VOLTS: 120/208
PHASE: 3
WIRES: 4
A.I.C. RATING: 22 KAIC
MAINS TYPE: MCB (TOP)
MAINS RATING: 100A
MCB RATING: 100A
PANEL
SECTION
NO.
BREAKER
RATING (A)
LOAD DESCRIPTION LOAD DESCRIPTION
BREAKER
RATING (A)
PANEL
SECTION
NO.
1 20 CL09 LIGHTS RECEPTACLE CL03 20 2
3 20 RECEP CL08A RECEPTACLE CL03 30 4
5 20 RECEP CL08A EXHAUST
FAN/DAMPER CL10A 30 6
7 20 RECEP CL08A
SPARE 80
9 20
LIGHTS, MECH
ROOM LOADING
DOCK, AAD
11 20 TRANE EMS PANEL 12
13 20
TEMP MONITOR
CL06 RECEP CL08A 20 14
15 20
JOHNSON CONTROL
FIRE PANEL RECEP CL08A 20 16
17 20 EXHAUST FAN CL09 RECEP CL08A 20 18
19 20 RECEP CL08
RECEP 2-POLE 30A 30
21 20 RECEP CL08 22
23 20 SPARE IN JBOX CL08
RECEP 2-POLE 20A 20
25 20 SPARE 26
27 20 SPARE
SPARE 30
29 20 SPARE 30
BRANCH PANEL: ELC-B
SECTION 1
LOCATION: CL09
SUPPLY FROM: EEQ-LCA1
MOUNTING: SURFACE
ENCLOSURE: TYPE 1
VOLTS: 120/208
PHASE: 3
WIRES: 4
A.I.C. RATING: 22 KAIC
MAINS TYPE: MCB
(TOP)
MAINS RATING: 200A
MCB RATING: 200A
PANEL
SECTION
NO.
BREAKER
RATING (A)
LOAD DESCRIPTION LOAD DESCRIPTION
BREAKER
RATING
(A)
PANEL
SECTION
NO.
1 20 AIR DRYER
DOCK LIFT #2 20
3 20 COFFEE POT BL08 4
5 20 REFRIGERATOR BL08 6
60 SPARE 3-POLE 60A
SPOTLIGHTS / HEATER ON
LOADING DOCK & CL10A 20
9 10
MIDDLE DOCK ELECTRIC DOOR
OPENER 20 12
13 20 GFCI RECEP W WALL DOCK WAREHOUSE RECEP. 20 14
15 20 LIGHTS BL10A
SPEED AIR - AIR COMPRESSOR 15
17 20 AUTO DOOR DOCK 18
80 DOCK LIFT #1
WALK IN FREEZER DOOR
HEATER BL06A 20 20
WALK IN FREEZER LIGHTS
BL06A 20 22
WALK IN FREEZER LIGHTS
BL06B 30 24
20 SPARE 3-POLE 20A
Lights CL06c 20 26
ROOF AIR HANDELER RECEP.
AND LIGHTS 20 28
29 FREEZER HEAT TAPE 20 30
31 20
RECEP COMPRESSOR ETO
STERILIZER SPARE 20 32
33 20
RECEP COMPRESSOR ETO
STERILIZER SPARE 20 34
35 20 SPARE SPARE 20 36
50 TRASH COMPACTOR BL12
SPARE 20 38
39 SPARE 20 40
41 SPARE 20 42
NOTE:
1. PANEL SHALL BE PROVIDED WITH THROUGH FEED LUGS ON BOTTOM TO FEED BLC-B SECTION 2.
BL06A
CL09
CL10
ELC-B SECT 2
PANEL SCHEDULES B6
E-101N/ASCALE:
PANEL DATA E5
E-101N/ASCALE:
100A/3P
ELC-G
CL09
100A/3P
ELC-DPA
1200A-120/208V,3Ø,4W+G
SECTION 2
CL02
200A/3P
EEQ-LCA1 CL02AGF
200A/3P
ELC-B
SECTION
ELC-B
SECTION
CL09
ELC-G AND ELC-B PARTIAL ONE-LINE DIAGRAMS E2
E-101N.T.S.SCALE:
BRANCH PANEL: ELC-B
SECTION 2
LOCATION: CL09
SUPPLY FROM: EEQ-LCA1
MOUNTING: SURFACE
ENCLOSURE: TYPE 1
VOLTS: 120/208
PHASE: 3
WIRES: 4
A.I.C. RATING: 22 KAIC
MAINS TYPE: MLO (BOTTOM
FEED)
MAINS RATING: 200A
MCB RATING: N/A
PANEL
SECTION NO.
BREAKER
RATING (A)
LOAD DESCRIPTION LOAD DESCRIPTION
BREAKER
RATING (A)
PANEL
SECTION NO.
1 20 TIME CLOCK - COMP #5 RECEP TOW MOTOR, BY
BL05 DOOR 20 2
3 20
RECEPT BL08, BL08A
LARGE FREEZER UNIT A 30
5 20
Fire Alarm Door Panel Holders 6
20 DOCK LIFT #3
9 LIGHTS BL05 20 10
11 BL08 A/C 28 & EF-28 20 12
13 20
WAREHOUSE BREAK
ROOM
COMPRESSOR RACK "B" 20
15 20
WAREHOUSE BREAK
ROOM 16
17 20
WAREHOUSE BREAK
ROOM 18
SMALL COOLER
COMPRESSOR
SMALL COOLER FAN 20 20
WALL EXHAUST FAN IN
CL09 20 22
FAN COIL UNIT IN CL16 20
COMPRESSOR RACK "A"
PANEL
FAN COIL UNIT IN CL16 20
29 30
30 SMALL FREEZER LARGE FREEZER UNIT B 30
33 34
35 36
80 SPARE
SPARE 20 38
39 SPARE 20 40
41 SPARE 20 42
43 SPACE SPACE 44
45 SPACE SPACE 46
47 SPACE SPACE 48
49 SPACE SPACE 50
51 SPACE SPACE 52
53 SPACE SPACE 54
NOTE:
1. SEE SHEET E501 DETAIL C2 FOR DIMENSION DESCRIPTION.
2. EXISTING EMPTY CONDUITS BELOW PANEL ELC-B SECTION 2 (RIGHT) SHALL BE DEMOLISHED TO FLOOR AND FILLED APPROPRIATELY.
ELC-G1
(FUTURE)
ELC-B1
(FUTURE)
80A/3P
80A/3P
CONTRACTOR IS RESPONSIBLE FOR REMOVAL OF ALL
INSULATING FOAM LOCATED ABOVE ELC-B PANELS,
AND INSTALLATION OF APPROPRIATE FIRESTOPPING
AROUND CONDUITS PER SPEC 078400.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100%
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827
(607) 223-4334
REPLACE OBSOLETE
PANEL BOARDS
SYRACUSE VAMC, SYRACUSE, NY
Project Director
03/08/2019 JWE JAHRevisions: Date:
528A7-18-708
E-102
BASEMENT PANELS (2 OF 6)
BASEMENT ROOM LOWER NL30A D2
E-1023/8"=1'-0"SCALE:
FLOOR ROOM PANEL
FRAME MAIN
DIMENSIONS (SEE NOTE 2)
EXISTING MAKE/MODEL # OF
SPACES
# OF
SPARES
# OF
EMPTY REPLACE FEED
LOCATION NOTERECESSED/
SURFACE V/PHASE RATING
(A)
MCB/
MLO H W D FLANGE W RECESSED
DIMENSION
B NL30A ELC-AC S 208/3 300 300 38" 20" 5 3/4" N/A N/A SIEMENS ITE/TYPE CDP-7 SERIES 8A 42 8-1Ø 1-3Ø 12 X B 1
BRANCH PANEL: ELC-AC
LOCATION: NL30A
SUPPLY FROM: EEQ-GE-DP
MOUNTING: SURFACE
ENCLOSURE: TYPE 1
VOLTS: 120/208
PHASE: 3
WIRES: 4
A.I.C. RATING: 22 KAIC
MAINS TYPE: MCB (TOP)
MAINS RATING: 300A
MCB RATING: 300A
PANEL
SECTION NO.
BREAKER
RATING (A)
LOAD
DESCRIPTION
LOAD
DESCRIPTION
BREAKER
RATING
(A)
PANEL
SECTION NO.
1 20
UH-52, 70, 71
AND FC-31, 32,
SPARE 20 2
3 20 SPARE SPARE 20 4
5 20 SPARE SPARE 20 6
7 SPACE
HRP-32 15
9 SPACE 10
30 HWP-902
HCP-32 15
15 16
15 SPARE
EF-32 20
21 22
40 AC-32
25 SPACE 26
27 SPACE 28
29 20 SPARE SPACE 30
31 20 SPARE SPACE 32
33 20 SPARE SPACE 34
BUILDING 2
FEED
SPACE 36
37 SPACE 38
39 SPACE 40
41 SPACE SPACE 42
E L C
A
C
LOWER
NL30A
PANEL SCHEDULE F6
E-102N/ASCALE:
PANEL DATA F9
E-102N/ASCALE:
EEQ-GE-DP
600A-208/120V,3Ø,4W+G
100/3P
100/3P
100/3P
100/3P
150A/
3P
200A/
3P
E2-LA
BLDG 2
E2-1A
BLDG 2
E2-2A
BLDG 2
E2-3A
BLDG 2
200/3P
DP-1
BLDG 2
BUILDING
2 RISER
400AF
300AT
3P
ELC-AC PARTIAL ONE-LINE DIAGRAM F2
E-102N.T.S.SCALE:
NOTE:
1. PANEL ELC-AC SHALL BE RELOCATED TO UPPER MEZZANINE. FINAL LOCATION OF PANEL SHALL BE COORDINATED WITH COR. CONTRACTOR IS RESPONSIBLE FOR REROUTING EXISTING CONDUCTORS TO NEW PANEL LOCATION.
2. SEE SHEET E501 DETAIL C2 FOR DIMENSION DESCRIPTION.
ELC-AC
300A/3P
250A/3P
BASEMENT ROOM UPPER NL30A D8
E-1023/8"=1'-0"SCALE:
ELC-AC
UPPER
NL30A
DEMOLISH ALL EQUIPMENT INSIDE
PANEL. LEAVE BOX AS JUNCTION BOX
CORE DRILL THROUGH FLOOR ABOVE. RUN
EXISTING CIRCUITS TO NEW PANEL ABOVE.
DEMOLISH FIRE ALARM PULL STATION
AND CONDUIT TO JUNCTION BOX.
MOVE 8x8 FIRE ALARM JUNCTION BOX TO
OTHER SIDE OF WALL TO REPLACE 4x4 BOX.
DEMOLISH 4x4 FIRE ALARM BOX. REPLACE
WITH 8x8 BOX FROM OTHER SIDE OF WALL.
PROPOSED LOCATION FOR NEW PANEL. INTERCEPT BUILDING 2 RISER
AND FEED NEW ELC-AC PANEL. RECONNECT ALL EXISTING CIRCUITS
FROM BELOW. CORE DRILL WALL BELOW BOX AND RECONNECT
CONDUCTORS TO BUILDING 2 JUNCTION BOX.
J-BOX
300 KCMIL
300 KCMIL
J-BOX
PARTIAL RISER DIAGRAM E9
E-102N.T.S.SCALE:
SUB-BASEMENT
BASEMENT
FIRST FLOOR
NL30A
UPPER
NL30A
LOWER
EEQ-GE-DP
J-BOX
TO
BLDG 2
ELC-AC
SUB-BASEMENT
BASEMENT
FIRST FLOOR
NL30A
UPPER
NL30A
LOWER
EEQ-GE-DP
J-BOX
TO
BLDG 2
J-BOX
TO
LOADS
TO
LOADS
ELC-AC
EXISTING PROPOSED
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100%
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827
(607) 223-4334
REPLACE OBSOLETE
PANEL BOARDS
SYRACUSE VAMC, SYRACUSE, NY
Project Director
03/08/2019 JWE JAHRevisions: Date:
528A7-18-708
E-103
BASEMENT PANELS (3 OF 6)
BASEMENT ROOM CL 24 DEMO PLAN C2
E-1031/4"=1'-0"SCALE:
FLOOR ROOM PANEL
FRAME MAIN
DIMENSIONS (SEE NOTE 1)
EXISTING MAKE/MODEL # OF
SPACES
# OF
SPARES
# OF
EMPTY REPLACE FEED
LOCATIONRECESSED/
SURFACE V/PHASE RATING
(A)
MCB/
MLO H W D FLANGE W RECESSED
DIMENSION
B CL24 LC-E SECTION 2 S 208/3
400 MLO 35" 20" 5 3/4" N/A N/A SQ D/CAT NO. 44-76874-7C 54 9-1Ø
1-2Ø 2 X B
B CL24 LC-E SECTION 1 S 208/3 400 400 35" 20" 5 3/4" N/A N/A SQ D/CAT NO. 44-76874-7B 54 1-1Ø 1-3Ø 0 X T
BRANCH PANEL: LC-E SECT. 2
LOCATION: CL24
SUPPLY FROM: LC-DPF
MOUNTING: SURFACE
ENCLOSURE: TYPE 1
VOLTS: 120/208
PHASE: 3
WIRES: 4
A.I.C. RATING: 22 KAIC
MAINS TYPE: MLO
(BOTTOM)
MAINS RATING: 400A
MCB RATING: N/A
PANEL
SECTION NO.
BREAKER
RATING (A)
LOAD
DESCRIPTION
LOAD
DESCRIPTION
BREAKER
RATING (A)
PANEL
SECTION NO.
1 20 CL27 LIGHTS
RECPT WEST
WALL
AUDITORIUM
CG43
20 2
3 20
CORR RECP
OUTSIDE CL28,
LIGHTS CL30A &
JC CONTRL
CL27 UNIT
HEATER 20 4
5 20
RECPS
WORKBENCH IN
PAINT SHOP
M006
CL27 EXH FAN,
CL24 GRINDER, 7
RECPTS E. WALL
CL24
20 6
7 20
LIGHTS PAINT
SHOP M006
CL27 RECPT
EAST WALL 20 8
9 20 CL29 HEATER
CL27
THREADING
MACHINE
20 10
11 20 CL29 LIGHTS
RECPT GFCI
MEN'S BATHRM
CL26
20 12
13 20
RECPT SOUTH
WALL & OFFICE
CL27
PIPE THREADING
MACHINE 20 14
3P-40A CL24
3-PHASE
WELDER
3P-15A HRP-37 15
17 18
19 20
3P-20A RECEP
208V CL27
3P-70A PANEL
1CC-COUMADIN
CLINIC BY C129
23 24
25 26
27 20 1P-20A SPARE 3P-70A PANEL
2CD - 3-PHASE
208V
(AUDITORIUM
ROOF)
29 21 1P-20A SPARE 30
31 22 1P-20A SPARE 32
3P-100A PANEL
LCE-1 CL25
(LOWER BIOMED
SHOP)
2P-50A CL27
SPARE 50
35 36
37 3P-100A PANEL
GCD -
AUDITORIUM
15 3P-15A HCP-37
41 42
43 SPARE 20 44
3P-150A PANEL
2CE STAGE
HATCH
SPARE 20 46
47 SPARE 20 48
49 SPARE 20 50
51 SPACE SPARE 20 52
53 SPACE SPARE 20 54
BRANCH PANEL: LC-E SECT. 1
LOCATION: CL24
SUPPLY FROM: LC-DPF
MOUNTING: SURFACE
ENCLOSURE: TYPE 1
VOLTS: 120/208
PHASE: 3
WIRES: 4
A.I.C. RATING: 22 KAIC
MAINS TYPE: MCB (TOP)
MAINS RATING: 400A
MCB RATING: 400A
PANEL
SECTION NO.
BREAKER
RATING (A)
LOAD
DESCRIPTION
LOAD
DESCRIPTION
BREAKER
RATING (A)
PANEL
SECTION NO.
1 20
MEN'S
BATHROOM
LIGHTS CL26
EXHAUST FAN
CL23 20 2
3 20
UNIT HEATER
CL23
RECPT CL23 &
UNIT HEATER 20 4
5 20
RECP CL24
NORTH WALL
(2), EAST
WALL (1)
OUTSIDE
LIGHTS,
LIGHTS CL23
20 6
7 20
UNIT HEATER
CL23, RECP
CL24 EAST
WALL
OUTSIDE
LIGHTS, CL24 S
WALL RECPT
20 8
9 20
COMPUTER
RECEPTACLE
CL24
LIGHTS CL24 20 10
11 20
WATER
FOUNTAIN &
LIGHTS FOR
BILLBOARD IN
HALL
RECEPT
NORTH WALL
CL24
20 12
13 20
HANGING
RECEPTACLE
CL24
2P-50A
RECEPT 208V
RANGE IN
AUDITORIUM
15 20
RECEPTACLE
BAND SAW
CL24
17 20
UNIT HEATER -
PAINT SHOP 2P-20A 208V
CL24 DRILL
PRESS
3P-30A
RECEPT 208V
CANTEEN AIR
CONDITIONER
21 2P-20A 208V
CL24 LATHE 20
23 24
25 20 1P-20A SPARE
3P-20A 208V
RECEPT AIR
COMPRESSOR
CL25
2P-20A 208V
RECEPT
MILLING
MACHINE
CL24
29 30
3P-30A SPARE
30 AMP
3P-20A
RECEPT 208V
HYDRAULIC
LIFT
33 34
35 36
40 3P-40A AC37 3P-60A EF37 60
39 40
41 42
NOTES:
1. PANEL SHALL BE PROVIDED WITH THROUGH FEED LUGS ON BOTTOM TO FEED LC-E
SECTION 2
LC-E SECTION 2
CL24
LC-E SECTION 1
PANEL SCHEDULES C6
E-103N/ASCALE:
PANEL DATA E6
E-103N/ASCALE:
100A/3P
100A/3P100A/3P 70A/3P60A/3P
400A/3P
LC-E
GC-D
CL25
STAGE
LC-DPF
2000A-208V, 3ɸ,4W
400A/3P
40A/3P
LC-E1
CL25
70A/3P
2C-D
STAGE
HATCH
1C-C
C128-
CORRIDOR
70A/3P 70A/3P
LC-E PARTIAL ONE-LINE DIAGRAM E2
E-103N.T.S.SCALE:
NOTE:
1. SEE SHEET E501 DETAIL C2 FOR DIMENSION DESCRIPTION.
150A/3P
2C-E
STAGE
HATCH
150A/3P
PROPOSED BASEMENT ROOM CL 24 C6
E-1031/4"=1'-0"SCALE:
LC-E
SECT. 2
CL24
LC-E
SECT. 1
DEMOLISH EXISTING
JUNCTION BOXES
DEMOLISH EXISTING PANELS
EXISTING
WIRE DUCT,
TO REMAIN
PLACE NEW PANELS AT
LOCATION OF DEMOLISHED
JUNCTION BOXES.
EXTEND EXISTING
WIREWAY TO CAPTURE ALL
EXISTING WIRE CONDUITS
EXTEND WIREWAY TO
CONNECT TO NEW LC-E
LEFT PANEL
CONTRACTOR SHALL FIELD
VERIFY EXISTING WIREWAY IS
SUFFICIENTLY SIZED TO HOLD
ALL CONDUCTORS. UPSIZE TO
LARGER WIREWAY IF REQUIRED.
AutoCAD SHX Text
EF-37
AutoCAD SHX Text
AC-37
AutoCAD SHX Text
CL24
CL02CL02
L B
D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100%
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827
(607) 223-4334
REPLACE OBSOLETE
PANEL BOARDS
SYRACUSE VAMC, SYRACUSE, NY
Project Director
03/08/2019 JWE JAHRevisions: Date:
528A7-18-708
E-104
BASEMENT PANELS (4 OF 6)
BASEMENT ROOM BL 20 C2
E-1041/4"=1'-0"SCALE:
FLOOR ROOM PANEL
FRAME MAIN
DIMENSIONS (SEE NOTE 1)
EXISTING MAKE/MODEL # OF
SPACES
# OF
SPARES
# OF
EMPTY REPLACE FEED
LOCATIONRECESSED/
SURFACE V/PHASE RATING
(A)
MCB/
MLO H W D FLANGE W RECESSED
DIMENSION
B BL20 LB-D S 208/3 100 100 35" 20" 5 3/4" N/A N/A WESTINGHOUSE/TYPE EB-20-CDP 42 5-1Ø 24 X T
BRANCH PANEL: LB-D
LOCATION: BL20
SUPPLY FROM: MCC-1
MOUNTING: SURFACE
ENCLOSURE: TYPE 1
VOLTS: 120/208
PHASE: 3
WIRES: 4
A.I.C. RATING: 22 KAIC
MAINS TYPE: MCB
MAINS RATING: 100A
MCB RATING: 100A
PANEL
SECTION NO.
BREAKER
RATING (A)
LOAD
DESCRIPTION
LOAD
DESCRIPTION
BREAKER
RATING (A)
PANEL
SECTION NO.
1 20 LIGHTS BL20 AHU-48
CONTROLS 20 2
3 20
GFCI RECP. ON
AIR HANDLER
BL20
SUMP PUMP
CONTROL
BL20/JOHNSON
CONTROLS
20 4
5 20
RECEP AND
SPARE IN JB
UNIT HEATER
AND EXHAUST
FAN BL20
20 6
7 20 SPARE
MORGUE
DOOR DOCK
LIFT
9 20
TEMP
MORGUE 10
11 20 SPARE 12
13 20 SPARE
3P-60A
DISCONNECT
MOUNTED ON
OUTSIDE WALL
(OLD TRASH
COMPACTOR
CIRCUIT)
15 20 SPARE 16
17 20 SPARE 18
19 SPACE SPACE 20
21 SPACE SPACE 22
23 SPACE SPACE 24
25 SPACE SPACE 26
27 SPACE SPACE 28
29 SPACE SPACE 30
31 SPACE SPACE 32
33 SPACE SPACE 34
35 SPACE SPACE 36
37 SPACE SPACE 38
39 SPACE SPACE 40
41 SPACE SPACE 42
BL20
BL19B
PANEL SCHEDULES B6
E-104N/ASCALE:
PANEL DATA E6
E-104N/ASCALE:
LC-DPD CL02
2000A-208V, 3ɸ, 4W
MCC-1
(MORGUE
BL20)
BB-A
B01A
LB-D
BL20
LB-D PARTIAL ONE-LINE DIAGRAM E2
E-104N.T.S.SCALE:
NOTE:
1. SEE SHEET E501 DETAIL C2 FOR DIMENSION DESCRIPTION.
AutoCAD SHX Text
CL02
AutoCAD SHX Text
AutoCAD SHX Text 300A/3P
AC-30
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100%
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827
(607) 223-4334
REPLACE OBSOLETE
PANEL BOARDS
SYRACUSE VAMC, SYRACUSE, NY
Project Director
03/08/2019 JWE JAHRevisions: Date:
528A7-18-708
E-105
BASEMENT PANELS (5 OF 6)
BASEMENT ROOM BL 05 C2
E-1051/4"=1'-0"SCALE:
FLOOR ROOM PANEL
FRAME MAIN
DIMENSIONS (SEE NOTE 1)
EXISTING MAKE/MODEL # OF
SPACES
# OF
SPARES
# OF
EMPTY REPLACE FEED
LOCATIONRECESSED/
SURFACE V/PHASE RATING
(A)
MCB/
MLO H W D FLANGE W RECESSED
DIMENSION
B BL05 LB-AC S 208/3 225 225 38" 20" 5 3/4" N/A N/A SIEMENS ITE/TYPE CDP-7 SERIES 8A 42 3-1Ø 7 X T
BRANCH PANEL: LB-AC
LOCATION: BL05
SUPPLY FROM: LC-DPD
MOUNTING: SURFACE
ENCLOSURE: TYPE 1
VOLTS: 120/208
PHASE: 3
WIRES: 4
A.I.C. RATING: 22 KAIC
MAINS TYPE: MCB
MAINS RATING: 225A
MCB RATING: 225A
PANEL
SECTION NO.
BREAKER
RATING (A)
LOAD
DESCRIPTION
LOAD
DESCRIPTION
BREAKER
RATING (A)
PANEL
SECTION NO.
1 20
RECEPTACLE
TO RIGHT OF
PANEL
TEKMAR (ICE
MELT) 20 2
3 20
UNIT HEATER
FRONT LOBBY JC DSC A33 20 4
15 EF12 HRP-33 15
7 8
9 10
15 HCP-07 HCP-33 15
13 14
15 16
CL-16
MOTORS:
AC31, EF31,
HCP31, HRP31
PUMP 8 20
19 20
21 22
60 AC-33 EF-33 50
25 26
27 28
29 20
RECEPTACLE
ED BASEMENT
GFCI
RECEPTACLE
FOR GYCOL
TANK
20 30
31 20
RECEPTCLE
FOR SHRINK
WRAPPER
SPARE 20 32
33 20
RECEPTACLE
ED BASEMENT SPARE 20 34
35 SPACE SPARE 20 36
37 SPACE SPACE 38
39 SPACE SPACE 40
41 SPACE SPACE 42
LB-AC
BL05
CL02B
BL05A
BL05B
BL05C
PANEL SCHEDULES B7
E-105N/ASCALE:
PANEL DATA E6
E-105N/ASCALE:
LB-AC
BL05
LC-DPD CL02
2000A-208V, 3ɸ, 4W
LB-AC PARTIAL ONE-LINE DIAGRAM E2
E-105N.T.S.SCALE:
NOTE:
1. SEE SHEET E501 DETAIL C2 FOR DIMENSION DESCRIPTION.
AutoCAD SHX Text
AC33
AutoCAD SHX Text 225A/3P
AutoCAD SHX Text
CL02
AutoCAD SHX Text
AC31
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100%
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827
(607) 223-4334
REPLACE OBSOLETE
PANEL BOARDS
SYRACUSE VAMC, SYRACUSE, NY
Project Director
03/08/2019 JWE JAHRevisions: Date:
528A7-18-708
E-106
BASEMENT PANELS (6 OF 6)
BASEMENT ROOM BL 20 C2
E-1061/4"=1'-0"SCALE:
FLOOR ROOM PANEL
FRAME MAIN
DIMENSIONS (SEE NOTE 1)
EXISTING MAKE/MODEL # OF
SPACES
# OF
SPARES
# OF
EMPTY REPLACE FEED
LOCATIONRECESSED/
SURFACE V/PHASE RATING
(A)
MCB/
MLO H W D FLANGE W RECESSED
DIMENSION
B Syr Steam ELC-C1 S 208/3 150 150 32" 20" 5 3/4" N/A N/A SIEMENS ITE/TYPE CDP-7 SERIES 8A 42 5-1Ø 16 X T
BRANCH PANEL: ELC-C1
LOCATION: BL21
SUPPLY FROM: ELC-DPA
MOUNTING: SURFACE
ENCLOSURE: TYPE 1
VOLTS: 120/208
PHASE: 3
WIRES: 4
A.I.C. RATING: 22 KAIC
MAINS TYPE: MCB
MAINS RATING: 150A
MCB RATING: 150A
PANEL
SECTION NO.
BREAKER
RATING (A)
LOAD
DESCRIPTION
LOAD
DESCRIPTION
BREAKER
RATING (A)
PANEL
SECTION NO.
1 20
JOHNSON
CONTROL
LIGHT ABOVE
PANEL 20 2
15 EXHAUST FAN CONDENSATE
PUMP CP-09B 20
5 6
7 8
CONDENSATE
PUMP CP-09A DSP-01B 40
11 12
13 14
40 DSP-01A
SUPPLY
EXHAUST FAN 20 16
17 SPARE 20 18
19 SPARE 20 20
20 PUMP 7
SPARE 20 22
23 SPARE 20 24
25 SPARE 20 26
27 SPACE SPACE 28
29 SPACE SPACE 30
31 SPACE SPACE 32
33 SPACE SPACE 34
35 SPACE SPACE 36
37 SPACE SPACE 38
39 SPACE SPACE 40
41 SPACE SPACE 42
E L C
C
BL21
PANEL SCHEDULES B6
E-106N/ASCALE:
PANEL DATA E6
E-106N/ASCALE:
ELC-DPA
150A/3P
1200A-120/208V,3Ø,4W+G
ELC-C1
BL21
STEAM
RM.
SECTION 2
CL02
150A/3P
ELC-C1 PARTIAL ONE-LINE DIAGRAM E2
E-106N.T.S.SCALE:
NOTE:
1. SEE SHEET E501 DETAIL C2 FOR DIMENSION DESCRIPTION.
EGE-C
G C
A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100%
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827
(607) 223-4334
REPLACE OBSOLETE
PANEL BOARDS
SYRACUSE VAMC, SYRACUSE, NY
Project Director
03/08/2019 JWE JAHRevisions: Date:
528A7-18-708
E-107
GROUND FLOOR PANELS (1 OF 3)
GROUND FLOOR ROOM NG 15 C2
E-1071/4"=1'-0"SCALE:
GROUND FLOOR ROOM CG 29 C6
E-1071/2"=1'-0"SCALE:
FLOOR ROOM PANEL
FRAME MAIN
DIMENSIONS (SEE NOTE 1)
EXISTING MAKE/MODEL # OF
SPACES
# OF
SPARES
# OF
EMPTY RETROFIT FEED
LOCATIONRECESSED/
SURFACE V/PHASE RATING
(A)
MCB/
MLO H W D FLANGE W RECESSED
DIMENSION
G ECC-NG15 EGE-C R 208/3 100 100 31" 20" 5 3/4" 1" 1/4" SIEMENS ITE/TYPE CDP-7 SERIES 8A 30 8-1Ø 0 X B
G CG29 GC-A S 208/3 100 100 38" 20" 5 3/4" N/A N/A SQ D/CAT NO. 44-65937-13L 42 1-1Ø 0 X B
BRANCH PANEL: EGE-C
LOCATION: ECC-NG15
SUPPLY FROM: EGE-DPB
MOUNTING: SURFACE
ENCLOSURE: TYPE 1
VOLTS: 120/208
PHASE: 3
WIRES: 4
A.I.C. RATING: 22 KAIC
MAINS TYPE: MCB
MAINS RATING: 100A
MCB RATING: 100A
PANEL
SECTION NO.
BREAKER
RATING (A)
LOAD
DESCRIPTION
LOAD
DESCRIPTION
BREAKER
RATING (A)
PANEL
SECTION NO.
1 15
ECC ROOM
LIGHTS
JOHNSON
CONTROLS 20 2
3 20
CORRIDOR
LIGHTS,
BATHROOM
AND STORAGE
LIGHTS
LIGHTING 20 4
5 20
RECEPTACLES
ECC ROOM
AND GFI IN
BATHROOM
HOT WATER TANK
7 20
GENERATOR
FUEL TANK
ALARM
SYSTEM
HOT WATER TANK 8
9 20
CONTROL
POWER
HWH-904
WTP-001
ECC DELL
COMPUTER 20 10
11 20
FIRE ALARM
BOOSTER
PANEL *
METASYS UPS 20 12
13 20
FIRE ALARM
PANEL 1 *
POWER
MONITORING EGX 20 14
15 20
FIRE ALARM
PANEL 29 EF-35 20 16
17 20
TANK ALARM
RELAYS EMERGENCY LIGHT 20 18
19 20
RECEPTACLES
ECC ROOM
EXIT LIGHTS/NIGHT
LIGHTS CHILLER
PLANT
20 20
21 20
RECEPTACLES
ECC ROOM SPARE 20 22
23 20
RECEPTACLES
ECC ROOM SPARE 20 24
25 20 SPARE SPARE 20 26
27 20 SPARE SPARE 20 28
29 20 SPARE SPARE 20 30
BRANCH PANEL: GC-A
LOCATION: CG29
SUPPLY FROM: LC-DPF
MOUNTING: SURFACE
ENCLOSURE: TYPE 1
VOLTS: 120/208
PHASE: 3
WIRES: 4
A.I.C. RATING: 22 KAIC
MAINS TYPE: MCB
MAINS RATING: 100A
MCB RATING: 100A
PANEL
SECTION NO.
BREAKER
RATING (A)
LOAD
DESCRIPTION
LOAD
DESCRIPTION
BREAKER
RATING (A)
PANEL
SECTION NO.
1 20
J-BOX ABOVE
DOOR CG33
RECEPTACLES
CG29 20 2
3 20
LIGHTS CG33,
CG35, CG37
LIGHTS
CORRIDOR 20 4
5 20
J-BOX ABOVE
DOOR CG33 LIGHTS CG29 20 6
7 20
RECEPTACLES
CG40, LIGHTS
CG40, 42, 38A
LIGHTS CG27 20 8
9 20
RECEPTACLE
CG36
RECEPTACLES
NG45 N. AND
W. WALLS
20 10
11 20
LIGHTS CG: 30,
32, 36, 38, 43
LIGHTS CG: 21,
23, 25A 20 12
13 20
RECEPTACLES
CG37
RECEPTACLES
CG CG 40, CG42 20 14
15 20
RECEPTACLES
CG37
RECEPTACLES
CORRIDOR 20 16
17 20
RECEPTACLES
CG28 LIGHTING 20 18
19 20
RECEPTACLES
CG 41 LIGHTING 20 20
21 20
RECEPTACLES
CG 28 LIGHTING 20 22
23 20 SPARE J-BOX ABOVE
CG43 20 24
25 20
CXANTEEN
DOORS LIGHTING 20 26
27 20
J-BOX ABOVE
DOOR CG36 LIGHTING 20 28
29 20
DOOR TO
SMOKING
PATIO
RECEPTACLES
NG45 S. AND E.
WALLS
20 30
31 15 LIGHTS CG26
RECEPTACLE
CG42 NORTH
WALL/RIGHT
SIDE
20 32
33 20 LIGHTS CG26
RECEPTACLE
CG42 NORTH
WALL/LEFT SIDE
20 34
35 20
RECEPTACLE ON
COLUMN CG26
RECEPTACLE ON
COLUMN CG42 20 36
37 20
LIGHTS
CORRIDOR
NEAR SMOKING
PATIO
RECEPTACLES
CG35 20 38
39 20 LIGHTING NG45 RECEPTACLES
CG35 20 40
41 20
RECEPTACLE
CORRIDOR
NEAR PATIO
DOOR
RECEPTACLES
CG33 20 42
NG15
NG15C NG15B NG15A
CG29
CORRIDOR
CORRIDOR
PANEL SCHEDULES C8
E-107N/ASCALE:
PANEL DATA E6
E-107N/ASCALE:
125A/3P
ESC-B2
BUILDING 2
BSMT
CORR.
ELSA-A
CL03
ELSGE-A
CM01
EGCBEGE-C
ECC-NG15
225A/3P
60A/3P
100A/3P 40A/3P
EGE-C PARTIAL ONE-LINE DIAGRAM F2
E-107N.T.S.SCALE:
200A/3P
LC-DPF
2000A-208V, 3ɸ, 4W
100A/3P
100A/3P
175A/3P
LC-A CL40
GC-A
GG29
1C-A
C111
GC-A PARTIAL ONE-LINE DIAGRAM F2
E-107N.T.S.SCALE:
NOTE:
1. SEE SHEET E501 DETAIL C2 FOR DIMENSION DESCRIPTION.
#2 AWG
NOTE:
* PROVIDE LOCKOFF DEVICE
AutoCAD SHX Text
CL02CL02
CL40
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100%
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827
(607) 223-4334
REPLACE OBSOLETE
PANEL BOARDS
SYRACUSE VAMC, SYRACUSE, NY
Project Director
03/08/2019 JWE JAHRevisions: Date:
528A7-18-708
E-108
GROUND FLOOR PANELS (2 OF 3)
GROUND FLOOR ROOM CG26A C5
E-1081/4"=1'-0"SCALE:
GROUND FLOOR ROOM AG 03 C2
E-1081/2"=1'-0"SCALE:
FLOOR ROOM PANEL
FRAME MAIN
DIMENSIONS (SEE NOTE 1)
EXISTING MAKE/MODEL # OF
SPACES
# OF
SPARES
# OF
EMPTY RETROFIT FEED
LOCATIONRECESSED/
SURFACE V/PHASE RATING
(A)
MCB/
MLO H W D FLANGE W RECESSED
DIMENSION
G AG03 EGA-A1 S 208/3 100 70 29" 20" 5 3/4" N/A N/A SQ D/CAT NO. NQOB-304-1 SERIES 2 30 13-1Ø 4 X T
G CG26A EGD-A S 208/3 50 50 22" 20" 5 3/4" N/A N/A SQ D/CAT NO. 44-76874-9H 30 6-1Ø 1-2Ø 7 X B
BRANCH PANEL: EGA-A1
LOCATION: AG03
SUPPLY FROM: ELC-DPC
MOUNTING: SURFACE
ENCLOSURE: TYPE 1
VOLTS: 120/208
PHASE: 3
WIRES: 4
A.I.C. RATING: 22 KAIC
MAINS TYPE: MCB
MAINS RATING: 100A
MCB RATING: 70A
PANEL
SECTION NO.
BREAKER
RATING (A)
LOAD
DESCRIPTION
LOAD
DESCRIPTION
BREAKER
RATING (A)
PANEL
SECTION NO.
1 20
LIGHTS
COMP/PEN
EXAM ROOMS
AG13A,C,D,E,F,
G,H,I,J
SPARE 20 2
3 20
RECEP ABOVE
COUNTER
CORRIDOR
AG13K
SPARE 20 4
5 20
RECEP ABOVE
COUNTER
CORRIDOR
AG13K
SPARE 20 6
7 20
RECEP
RECEPTION
CG18A
SPARE 20 8
9 20 SPARE SPARE 20 10
11 20 SPARE SPARE 20 12
PANEL EGAC
RM AG16
SPARE 20 14
15 SPARE 20 16
17 SPARE 20 18
19 20
EXIT LIGHTS
CORRIDOR
AG13K,
WAITING CG18
SPACE 20
21 20 SPARE SPACE 22
23 20 SPARE SPACE 24
25 20 RECEP AL03
DATA CLOSET
RECEPTACLES
AG01
20 26
27 20
SPARE J-BOX
AL03
FAN COIL DATA
CLOSET AG01 20 28
29 20
SECURITY
PANEL POWER
SUPPLY
SPACE 30
BRANCH PANEL: EGD-A
LOCATION: CG26A
SUPPLY FROM: ELC-E
MOUNTING: SURFACE
ENCLOSURE: TYPE 1
VOLTS: 120/208
PHASE: 3
WIRES: 4
A.I.C. RATING: 22 KAIC
MAINS TYPE: MCB
MAINS RATING: 50A
MCB RATING: 50A
PANEL
SECTION NO.
BREAKER
RATING (A)
LOAD
DESCRIPTION
LOAD
DESCRIPTION
BREAKER
RATING (A)
PANEL
SECTION NO.
1 20
GROUND
FLOOR MAIN
CORRIDOR
LIGHTS
GROUND
FLOOR D-WING
CORRIDOR
LIGHTS
20 2
3 20
GRD FL CORR
LIGHTS, CG22
& CG26 LTS,
SEC. CAMERAS
GROUND
FLOOR D-WING
CORRIDOR
LIGHT
20 4
5 20
SPARE
CURCUIT TO
PULLBOX CG20
LIGHTS 20 6
7 20
BURGLAR
ALARM BACK
DOOR
CANTEEN CG26
CARD READER
MICRO
CONTROLLER
CG20
20 8
9 20
RECEPTACLE
CG26 EAST
WALL CANTEEN
RETAIL STORE
LIGHTS AND
RECEPTACLE
CG26
20 10
11 SPACE SPACE 12
13 SPACE SPACE 14
15 SPACE
EMERGENCY
EXIT LIGHT
BACK OF
CANTEEN
STORE
20 16
17 SPACE SPACE 18
19 20
RECEPTACLES
GAS METER
ROOM
SPARE 20 20
2-POLE 20 AMP
SPARE
SPARE 20 22
23 SPARE 20 24
50A MCB
SPARE 20 26
27 SPARE 20 28
29 SPARE 20 30
E G
A A
E G
D A
CG75
CG76
CG26A
CG26B
AG03
CORRIDOR
PANEL SCHEDULES B8
E-108N/ASCALE:
PANEL DATA E6
E-108N/ASCALE:
ELC-DPC
1600A-120/208V,3Ø,4W+G
EGA-C
AG16
AG03
E1A-A
A103
EGA-A1 PARTIAL ONE-LINE DIAGRAM E1
E-108N.T.S.SCALE:
ELC-E CL02
EGDA
CG26
EGDA PARTIAL ONE-LINE DIAGRAM E3
E-108N.T.S.SCALE:
EGA-A1
NOTE:
1. SEE SHEET E501 DETAIL C2 FOR DIMENSION DESCRIPTION.
AutoCAD SHX Text 300A/3P
AutoCAD SHX Text 50A/3P
AutoCAD SHX Text 70A/3P
AutoCAD SHX Text
AutoCAD SHX Text
CL02
AutoCAD SHX Text 100A/3P
AutoCAD SHX Text 150A/3P
AutoCAD SHX Text 50A/3P
AutoCAD SHX Text
CL02
50A/3P
GD-DP
GD-A
SECT. 1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100%
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827
(607) 223-4334
REPLACE OBSOLETE
PANEL BOARDS
SYRACUSE VAMC, SYRACUSE, NY
Project Director
03/08/2019 JWE JAHRevisions: Date:
528A7-18-708
E-109
GROUND FLOOR PANELS (3 OF 3)
AND FIRST FLOOR PANELS (1 OF 3)
GROUND FLOOR ROOM DG11 DEMO PLAN C2
E-1091/2"=1'-0"SCALE:
FLOOR ROOM PANEL
FRAME MAIN
DIMENSIONS (SEE NOTE 3)
EXISTING MAKE/MODEL # OF
SPACES
# OF
SPARES
# OF
EMPTY REPLACE RELABEL FEED
LOCATION NOTERECESSED/
SURFACE V/PHASE RATING
(A)
MCB/
MLO H W D FLANGE W RECESSED
DIMENSION
G DG11 GD-DP S 208/3 800 MLO 85" 38" 10 3/8" N/A N/A GE SPECTRA SERIES 12-3Ø 2-3Ø 0 X B 1
G DG11 GD-A S 208/3
350 350 70" 20" 4 3/4" N/A N/A SQ D/CAT NO. 12282504511140001 SER. E1 42 14-1Ø 2 X (GDA)
T 2
BRANCH PANEL: GD-DP
LOCATION: DG11
SUPPLY FROM: MSWGR
MOUNTING: SURFACE
ENCLOSURE: TYPE 1
VOLTS: 208
PHASE: 3
WIRES: 4
A.I.C. RATING: 22 KAIC
MAINS TYPE: MLO
MAINS RATING: 800A
MCB RATING: N/A
PANEL
SECTION NO.
BREAKER
RATING (A)
LOAD
DESCRIPTION
LOAD
DESCRIPTION
BREAKER
RATING (A)
PANEL
SECTION NO.
3P-400A
PANEL 3D-A
(D306)
3P-400A
PANEL 4D-A
(D410)
3 4
5 6
3P-400A
PANEL 2D-A
(D210)
3P-350A
PANEL GD-A
(DG11)
9 10
11 12
3P-250A
SPARE
3P-300A
PANEL 4D-AC 300
15 16
17 18
3P-225A
SPARE
3P-225A
PANEL 1C-NME 225
21 22
23 24
3P-200A
PANEL GD-B
(DG24)
3P-200A
ELEVATOR 200
27 28
29 30
3P-100A
PANEL GDA-2
3P-100A
PANEL 1D-A
(D110)
33 34
35 36
NOTES:
1. THIS PANEL AND ASSOCIATED BREAKERS SHALL BE SUPPLIED BY THE VA.
DG09
DG11
CORRIDOR
PANEL SCHEDULES B8
E-109N/ASCALE:
PANEL DATA E6
E-109N/ASCALE:
MAIN SWITCHGEAR "MSWGR"
3200A-120/208V 3ɸ, 4W CL02
SECTION 10
GD-DP DG11
1D-A
D110
4D-AC
D417
GD-B
DG24
GD-A
(NEW)
3D-A
D306
3D-A2
D313
3D-A3 3D-A4 3D-A5
D326
3D-A1
D314
3D-A7
D304
2D-A
D210
2D-A2
D217A
2D-A3
D213
2D-A4
D210
2D-A5
D222
2D-A1
D217
2D-A6
1C-NME
MAIN
ENTRY
CLOSET
1C-G
POLICE
ENTRY
CORRIDOR
4D-A
D410
4D-A1
D415
4D-A2
D402
GDA-2
DG11
GDA-1
DG18
GD-DP AND GD-A (NEW) PARTIAL ONE-LINE DIAGRAM E3
E-109N.T.S.SCALE:
NOTES:
1. PANEL GD-DP SHALL BE REPLACED WITH VA OWNED GE SPECTRA SERIES PANELBOARD. CONTRACTOR IS RESPONSIBLE FOR REMOVAL OF EXISTING PANEL AND INSTALLATION OF NEW, VA SUPPLIED PANELBOARD.
2. PANEL GD-A SECTION 1 SHALL BE DEMOLISHED, AND ALL EXISTING CONDUCTORS SHALL BE RECONNECTED TO PANEL GD-A SECTION 2. GD-A SECTION 2 SHALL BE RELABELED GDA CONTRACTOR IS RESPONSIBLE FOR REROUTING EXISTING CONDUCTORS AND INTEGRATING EXISTING
CIRCUITS INTO GDA.
PROPOSED GROUND FLOOR ROOM DG11 C2
E-1091/2"=1'-0"SCALE:
DG09
DG11
CORRIDOR
G D
A
S E
C T
G D
A
GD-DP
G D
A
G D
A
PANEL DEMOLITION PHASING PLAN:
1. INSTALL NEW PROPERLY SIZED FEED FOR FEED GDA-2 (100A) FROM GD-DP.
2. DISCONNECT GD-A SECTION 1, COORDINATE ANY ASSOCIATED OUTAGES WITH C.O.R. DEMOLISH GD-A SECTION 1.
3. GDA SECTION 2 SHALL BE DISCONNECTED. RE-ROUTE ALL EXISTING CIRCUITS FROM GD-A SECTION 1 TO GD-A SECTION 2. GD-A SECTION 2 SHALL NOW BE
TERMED GD-A. COORDINATE ANY ASSOCAITED OUTAGES WITH C.O.R.
4. INSTALL NEW 500 KCMIL FEED FOR GD-A (350A) FROM GDDP.
5. COORDINATE OUTAGE WITH COR, AND REPLACE GD-DP. NEW PANEL LOCATION SHALL BE SHIFTED TO THE RIGHT, SUCH THAT IT IS NOT BLOCKED BY
GD-A.
BRANCH PANEL: GD-A
LOCATION: DG11
SUPPLY FROM: GDDP
MOUNTING: SURFACE
ENCLOSURE: TYPE 1
VOLTS: 120/208
PHASE: 3
WIRES: 4
A.I.C. RATING: 22 KAIC
MAINS TYPE: MCB
MAINS RATING: 350A
MCB RATING: 350A
PANEL
SECTION NO.
BREAKER
RATING (A)
LOAD
DESCRIPTION
LOAD
DESCRIPTION
BREAKER
RATING (A)
PANEL
SECTION NO.
1 20
FIRE DAMPER F/S
-06G
RECP. FRESH LOCK
DG14 20 2
3 20 SPARE SPARE 20 4
5 20
LIGHTS
BASEMENT
SOUTH
SPARE 20 6
7 20
LIGHTS
BASEMENT
NORTH
RECP. BASEMENT 20 8
9 SPACE SPARE 20 10
11 SPACE SPARE 20 12
13 20
SPARE WIRE IN
WIRE WAY BELOW
PANEL
LIGHTS & RECP.
ELEVATOR SHAFT 20 14
15 20
SPARE WIRE IN
WIRE WAY BELOW
PANEL
SPARE 20 16
17 20
SPARE WIRE IN
WIRE WAY BELOW
PANEL
RECP. DG5, DG7
20 18
19 20 RECP. CG26B SPARE 20 20
21 20
SPARE WIRE IN
WIRE WAY BELOW
PANEL
UNIT HEATER
DG24 20 22
23 20
SPARE WIRE IN
WIRE WAY BELOW
PANEL
SPARE 20 24
25 20
RECP. DG19, DG20 SPARE 20 26
27 20 SPARE RECP. DG24,
FLOOR RECP. 20 28
29 20
RECP. DG3, DG5 SPARE 20 30
31 20
RECP. DG3,
FAN DG26 - FAN
REMOVED WIRES
FOR STATER IN
2-GANG BOX BY
SIGN
20 32
33 20 SPARE SPARE 20 34
35 20 LIGHTS DG9 RECP. CORRIDOR
EAST 20 36
37 20
RECP. CORRIDOR
SOUTH
GDA-1 3- POLE 100
A RM. DG18 100
39 20 SPARE 40
41 20 RECP. WEST WALL 42
NOTES:
1. MOVE UNIT HEATER DG24 FEED FROM CIRCUIT 22 TO CIRCUIT 20.
2. MOVE 30A BREAKER AND CAGE WASHER FEED FROM GDA SECTION 1 CIRCUIT 13,15,17, TO
CIRCUIT 22,24,26.
3. REMOVE CONDUCTORS FROM CIRCUIT 13,15,17. MOVE 50A BREAKER AND FEEDS FROM GDA
SECTION 1 37,39,41 TO 13,15,17.
AutoCAD SHX Text 400A/3P
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
DG11
AutoCAD SHX Text 400A/3P
AutoCAD SHX Text 400A/3P
AutoCAD SHX Text 100A/3P
AutoCAD SHX Text 150A/3P
AutoCAD SHX Text 225A/3P
AutoCAD SHX Text 300A/3P
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text 200A/3P
AutoCAD SHX Text 200A/3P
AutoCAD SHX Text 350A/3P
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
ELEVATOR
AutoCAD SHX Text 70A/3P
AutoCAD SHX Text 70A/3P
AutoCAD SHX Text 70A/3P
AutoCAD SHX Text 90A/3P
AutoCAD SHX Text 90A/3P
AutoCAD SHX Text 70A/3P
AutoCAD SHX Text 100A/3P
AutoCAD SHX Text 110A/3P
AutoCAD SHX Text 100A/3P
AutoCAD SHX Text 300A/3P
AutoCAD SHX Text 200A/3P
AutoCAD SHX Text 350A/3P
AutoCAD SHX Text 400A/3P
AutoCAD SHX Text 225A/3P
AutoCAD SHX Text 10A
AutoCAD…