36C24219B0022-0002001.pdf

PDF 3 MB Posted

Attached to
528A6-17-606 PROVIDE ACCESSIBILITY B32 Federal contract opportunity
Solicitation number
36C24219B0022
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

36C24219B0022 0002 S06 - Amendment Attachment.pdf

View the file

Other files for this federal contract opportunity

Other files attached to 528A6-17-606 PROVIDE ACCESSIBILITY B32, newest first.
File Type Posted
36C24219C0141-000.docx DOCX document
36C24219B0022-0002000.docx DOCX document
36C24219B0022-0001000.docx DOCX document
36C24219B0022-003.zip ZIP file
36C24219B0022-002.zip ZIP file
36C24219B0022-001.docx DOCX document
36C24219B0022-000.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Centrifugal Ceiling Exhaust and Inline Cabinet Fans Models SP and CSP

November

See ENERGY STAR® Models on Pages 10-12

Great things come in small packages, as do our

SP ceiling exhaust fan and CSP inline cabinet fan models. Be assured when you buy any Greenheck product, it is a quality product at a competitive price. Plus, we guarantee our SP and CSP fans with a three-year warranty. We are your market leader for the most comprehensive ceiling and cabinet fan line in the market.

Table of Contents

Standard Construction Features . . . . . . . . . . . . . .4-5

Power Ratings

Certifications

Vari-Green® Motors and Controls

Sound and Fan Selection

ENERGY STAR® Approval . . . . . . . . . . . . . . . . . .9-12

Model Number Code

Model SP-VG

Model SP-A . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-11

Model SP-B and SP-C

Model CSP-B

Model CSP-A . . . . . . . . . . . . . . . . . . . . . . . . . . .13-14

Model SP (50 cycle)

Model CSP (50 cycle)

Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . .17-24

Electrical Accessories . . . . . . . . . . . . . . . . . . .21-22

Discharge Accessories . . . . . . . . . . . . . . . . . .23-24

Pressure Drop

Specifications Vari-Green

Model Specifications . . . . . . . . . . . . . . . . . . . . .26-27

Benefits

• Low sound levels

• Compact size

• Wide range of performance

• Available with EC motors for higher efficiency and more controllability

Typical Installations

• Multifamily housing

• Hotels

• Hospitals

• Schools

• Bathrooms

• Storage rooms

Models SP and CSP Ceiling and Cabinet Fans

Model Comparison

Model

Location Mounting Airflow Application Drive Type

Impeller Type Performance

O u td o o r

In d o o r

R o o f

C u rb

B a s e

/F lo o r

H a n g in g

W a ll

C e il in g M o u n te d

E x h a u s t

S u p p ly

R e v e rs ib le

R e c ir c u la te

G e n e ra l/

C le a n

A ir

C o n ta m in a te d A ir

S p a rk

R e s is ta n t

G re a s e

U

L

S m o k e C o n tr o l (U

L

H ig h W in d m p h

H ig h T e m p a b o v e

°F

B e lt

D ir e c t

C e n tr if u g a l

P ro p e ll e r/ A x ia l

M ix e d

F lo w

M a x im u m

V o lu m e (c fm

M a x im u m

S ta ti c

P re s s u re

(i n w g

SP 1,600 1

CSP 3,800 1

Model Level of

Construction Description

Profile min. height

Sound min. sones

Air Volume max. cfm UL Listing

C e il in g F a n s

SP VG

Premium Plus:

Green/energy efficient highest performing

7 inches (178 mm)

<0.3 710 cfm

(1206 m3/hr)

UL/cUL Listed for above bathtub/ shower with GFCI branch protected circuit

SP A

Premium Ceiling Fan:

Widest selection to meet sound requirements.

9 inches (229 mm)

<0.3 1,600 cfm

(2718 m3/hr)

UL/cUL Listed for above bathtub/ shower with GFCI branch protected circuit (Sizes A390 and smaller)

SP B

Deluxe Ceiling Fan:

Compact to fit most applications with quiet operation.

7 inches (178 mm)

1.2 200 cfm

(340 m3/hr)

UL/cUL Listed for above bathtub/ shower with GFCI branch protected circuit

SP C

Economy Ceiling Fan:

Designed for light commercial applications.

35⁄8 inches (86 mm)

3.0 50 cfm

(85 m3/hr) UL Listed

In li n e F a n s CSP A

Premium Inline Fan:

Outperforms the competition and is preferred by specifying engineers.

9 inches (229 mm)

0.8 3,775 cfm

(6414 m3/hr) UL/cUL Listed

CSP B

Deluxe Inline Fan:

Compact design to fit in small remote spaces.

7 inches (178 mm)

1.5 185 cfm

(314 m3/hr) UL/cUL Listed

SP fans are designed for ceiling mounted exhaust applications.

CSP fans are designed for inline supply or exhaust applications.

d for aust

Models SP and CSP Ceiling and Cabinet Fans

All dimensions are in inches (millimeters)

Model SP-A

Model SP-C

Model SP-B

Model CSP-A

Model CSP-B

6 5

8 10

Model SP-VGodel SP VG

Standard Construction Features

Number and Description Specific Features for Each Model

SP-VG SP-A SP-B SP-C CSP-A CSP-B

1 Backdraft Damper

Durable plastic to reduce backdrafts 50-90

Aluminum to reduce backdrafts 110-

2 Outlet Round - For quick and easy connections 50-90

Square - For quick and easy connections 110-

3 Power Pack Removes quickly for maintenance

Includes conversion from horizontal to vertical discharge

4 Electrical Access

Vertical electrical access to eliminate drilling holes

External electrical access to save installation time

5 Electrical Knockouts

Eliminates drilling holes (horizontal or vertical)

6 Acoustic Insulation

Absorbs sound

7 Disconnect Servicing is quick and safe

8 Electrical Junction Box

Large for easy wiring

9 Grille Concealed attachment screws securely fasten grille to housing for quiet, rattle free operation

10 Mounting Brackets

Adjustable for multiple installation conditions

11 Housing Embossed galvanized steel for rigidity

A low profile for height restricted areas

12 Motors

Motors are compatible for use with speed controls and have thermal overload protection

Domestic & International

• 50 cycle, 220v or 240v

• 60 cycle, 115v, 208v, 220v, 230v, & 277v options (See CAPS or pg. 12 for availability)

60 cycle, 115v only

60 cycle, 115v only

13 Access Panel Gain easy access to internal components once installed

Exclusive Electrical Wiring Feature

Electrical access cover located on the housing exterior. This feature permits external wiring without removing the power assembly, saving installation time and cost. Available on models SP-A and CSP-A.

Double-Wide Fans

Available for applications requiring 700 cfm or greater.

Double-wide fans have two double-width forward-curved wheels, which are housed in separate scrolls and driven by a single motor.

Available on models SP-A and CSP-A.

Vertical Discharge

Exhaust outlet duct installed in the optional vertical position.

The power assembly must be rotated to match the duct adapter position.

Available on SP-A and CSP-A models.

Standard Construction Features

Available Motor Voltage and Cycle Ratings

Power Rating V/Hz

Models Available (X)

115V/ 60Hz

115V/ 50Hz

220-240V/ 50Hz

220-240V/ 60Hz 277V

Vari-Green Motor Option

SP-A50 x

SP-A70 x

SP-A90 x

SP-A110 x x x x x

SP-A125 x x

SP-A190 x x x x x

SP-A200 x

SP-A250 x

SP-A290 x x x x

SP-A390 x x x x

SP-A410 x

SP-A510 x x x x x

SP-A700 x

SP-A710 x x

SP-A780 x x x x

SP-A900 x

SP-A1050 x x x x

SP-A1410 x

SP-A1550 x x x x

SP-B50 x

SP-B70 x

SP-B80 x

SP-B90 x x x x

SP-B110 x x x x x

SP-B150 x x x x x

SP-B200 x x x x x

Available Motor Voltage and Cycle Ratings

Power Rating V/Hz

Models Available (X)

115V/ 60Hz

115V/ 50Hz

220-240V/ 50Hz

220-240V/ 60Hz 277V

Vari-Green Motor Option

SP-C50 x

SP-80 x x

SP-80L x x

SP-110 x x

SP-110L x x

CSP-A110 x x x x x

CSP-A125 x x

CSP-A190 x x x x x

CSP-A200 x

CSP-A250 x

CSP-A290 x x x

CSP-A390 x x x x

CSP-A410 x

CSP-A510 x x x x

CSP-A700 x

CSP-A710 x x

CSP-A780 x x x x

CSP-A900 x

CSP-A1050 x x x x

CSP-A1410 x

CSP-A1550 x x x x

CSP-A1750 x

CSP-A2150 x

CSP-A3600 x x x

CSP-B110 x x x x x

CSP-B150 x x x x x

CSP-B200 x x x x x

Power Ratings

Models SP and CSP are listed electric fans (UL/cUL 507).

Ceiling Exhaust Fans are also UL Listed for above bathtub/ shower with GFCI branch protected circuit. File no. E33599.

Note: SP/CSP fans are rated for direct contact with insulation

Greenheck Fan Corporation certifies that the SP models shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program. The SP models are not AMCA certified with 50 hertz motors.

Greenheck Fan Corporation certifies that the CSP models shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and comply with the requirements of the AMCA Certified Ratings Program. The CSP models are not AMCA certified with 50 hertz motors.

Products that earn the ENERGY STAR® prevent greenhouse gas emissions by meeting strict energy efficiency guidelines set by the U.S. Environmental Protection Agency and the U.S.

Department of Energy.

Fans that are ENERGY STAR qualified include: SP-A70, SP-A90, SP-A110, SP-A125, SP-A190, SP-A200, SP-A250, SP-B70, SP-B80, SP-B90, SP-80-VG, SP-80L-VG, SP-110-VG and SP-110L-VG.

Vari-Green® Motor

EC Motor Technology Information & Advantages -

Greenheck’s Electronically Commutated (EC) Vari-Green (VG) motor combines motor technology, controllability and energy-efficiency into one single low maintenance unit and is the industry's first fully controllable motor.

The EC motor operates on AC power that is converted to DC – providing a more efficient motor operation as compared to an AC operation. Controllability allows for variable volume systems that save conditioned air from being exhausted when it is not needed and helps prevent over or under ventilating the space.

Vari-Green® Controls

Air Quality – VOC - Control a Vari-Green motor via changes in Volatile Organic Compounds (VOC’s).

VOC’s are gasses that are emitted from humans, building materials, perfumes, foods, and furniture off-gassing. Range is 0-2000 CO2 ppm equivalent.

• Institutional facilities – Schools, court houses, hospitals; bathrooms, waiting rooms, cafeterias.

• Commercial buildings – Office spaces, conference rooms, bathrooms, break rooms.

Air Quality – Temperature and Humidity - Control Vari-Green motor via changes in temperature, humidity, or both. Range is 32 to 120°F (0-49°C) and 0 to 100% relative humidity.

• Multifamily structures – Apartments, condos, hotels;

bathrooms, utility rooms.

• Commercial buildings – Office buildings; office spaces, conference rooms, utility rooms, bathrooms.

Transformer - Provides 24V power from the existing line voltage at the fan to the Vari-Green motor and controls. Dual voltage primary (120/240V) transformer provided with the fan.

Remote Dial or Touch Remote - allows the user to manually adjust a fan’s speed from a remote location and mounts to a wall using a 2x4 junction box. The 24VDC transformer, described above, is included with all orders. A wall cover plate is supplied.

• The Touch Remote includes a count down timer to automatically turn the fan off after 10, 30, 60 or 90 minutes.

• Recommended for use in commercial buildings and restaurants.

Two-speed Control with Integral Transformer - Control allows motor RPM to be set at two independent speeds (high or low). Meets minimum airflow requirements with the ability to bump up to high speed in an emergency or meet maximum airflow requirements, or reset to low for energy conservation.

Constant Pressure Control - Control Vari-Green motors via static (variable volume) or velocity (constant CFM) pressure on the inlet or outlet side of the fan.

Optional, one or two, duct or room probes for use in:

• Multifamily structures - Apartments, condos, hotels;

dryers, residential kitchens and bathrooms.

• Institutional facilities - Schools, prisons, multistory office buildings; bathrooms.

Vari-Green® Motor & Controls

Available Vari-Green Controls and Models

Controls

Models

SP-

80(L)-VG

SP-

110(L)-VG

SP/CSP-

A510-VG

SP/CSP-

A710-VG

VOC X X

Temp./Humidity X X

Two-speed X X

Remote Dial X X

Touch Remote X X

Constant Pressure X X

Transformer X X

Built-in Time Delay X X

Built-in Two Speed X X

See Greenheck's Vari-Green Motor and Vari-Green Controls brochures for more information.

Sound Data

The sound data shown in this catalog has been presented to aid the system designer in selecting a fan which will meet the desired sound criteria. Sone levels have been included on the performance pages to provide a means of quickly evaluating the relative loudness of a fan selection.

What is a sone?

Sones are an internationally recognized unit of loudness. In practical terms, the loudness of one sone is equivalent to the sound of a quiet refrigerator measured from five feet away in an acoustically average room. A sone is a single number rating, which indicates the inlet noise derived from the eight audible octave bands. Sones are a linear measurement of sound level.

For example, a sound level of 10 sones is twice as loud as 5 sones.

Can radiated noise increase the sound levels?

Radiated noise from fan housings can cause unacceptable sound levels on any brand of fan.

The size of these fans allows them to be placed in areas where this noise will be transmitted to the conditioned space through walls or ceilings. Where possible, cabinet fans should be located in remote parts of the ventilation system.

When should an SP or CSP fan be used?

Model SP and CSP fans are designed for the lowest possible sound levels. Forward-curved wheels, optional insulated housings and vibration isolators between

Model CFM Inches WG FRPM Sones

SP-A410 405 1/8 1000 3.0

CSP-A410 403 1/8 1000 1.5

*Sone value on CSP is with insulated inlet duct.

Sound and Fan Selection Things to know when sound is critical

The compact size of the SP and CSP fans provides the system designer greater flexibility in locating these fans for lowest sound levels. In critical sound areas, insulated ductwork, flexible duct connections, or placing the fan in a remote section of the ductwork (away from the critical sound area) offers the best means of meeting desired sound levels.

Remote mounted model CSP with vibration isolators and insulated ductwork provides the quietest installation.

Fiberglass the motor and housing contribute to quiet, efficient operation. Applied and installed as recommended, SP and CSP sound levels will fall well within the ranges shown in the Suggested Limits for Room Loudness chart (shown below). For applications where sound levels are critical, a remote mounted CSP with ductboard is recommended. Placement of SP and CSP fans should take into account the desired sound level at the location of the listener.

Suggested Limits for Room Loudness

Sones dBA

1.3-4 32-48 Private homes (rural and suburban)

1.7-5 36-51 Conference rooms

2-6 38-54 Hotel rooms, libraries, movie theatres, executive offices

2.5-8 41-58 Schools and classrooms, hospital wards and operating rooms

3-9 44-60 Court rooms, museums, apartment houses, private homes (urban)

4-12 48-64 Restaurants, lobbies, general open offices, banks

5-15 51-67 Corridors and halls, cocktail lounges, washrooms and toilets

7-21 56-72 Hotel kitchens and laundries, supermarkets

Reprinted from AMCA Publication 302 Application of Sone Ratings for Non-Ducted Air Moving Devices (with room, sone and dBA correlations) with the written permission from AMCA International, Inc., 30 West University Drive, Arlington Heights, IL 60004-1893.

NOTE: Values above are for room loudness and are not sound ratings. Room loudness is the resulting level in a conditioned space after the acoustical qualities of the room have been accounted for.

When room sound levels are critical, such as in executive offices, conference rooms, hospital operating rooms, and school study areas, a CSP fan is the best choice. Shown here is a comparison of SP and CSP fans of the same size, with equal performance in typical installations. The CSP shows lower sone values.

ENERGY STAR®

Model Number Code

The model number code system is designed to completely identify the fan. The correct code letters must be specified to designate belt or direct drive. The remainder of the model code is determined by the size and performance.

ENERGY STAR is a market-based partnership formed to reduce greenhouse gas emissions through energy efficiency and make it easier for consumers to identify energy-efficient products that offer savings, performance, features, and comfort.

To earn the ENERGY STAR label, products must meet strict energy efficiency standards set by the U.S.

Environmental Protection Agency (EPA) for energy consumption, air and sound performance. Fan models that are ENERGY STAR qualified are identified in this catalog.

Note: Energy Star is only for products 500 cfm or less.

Light Options:

L - Fan/Light (Incandescent) Combination FL - Fan/Light (Fluorescent) Combination

Nominal CFM at 0.10 inches static pressure

Level of Construction:

A - Premium unit; lowest sound, insulated housing B - Deluxe unit; low sound, low profile C - Standard unit; lowest profile, inexpensive

C - No letter designation identifies model as Premium Plus with a Vari-Green motor.

Model:

SP - Silent Partner CSP - Cabinet Silent Partner

SP - A 50 FL - VG

Vari-Green®:

EC Motor Option

Products that earn the ENERGY STAR® prevent greenhouse gas emissions by meeting strict energy efficiency guidelines set by the U.S. Environmental Protection Agency and the U.S.

Department of Energy.

Fans that are ENERGY STAR qualified include: SP-A70, SP-A90, SP-A110, SP-A125, SP-A190, SP-A200, SP-A250, SP-B70, SP-B80, SP-B90, SP-80-VG, SP-80L-VG, SP-110-VG and SP-110L-VG.

Performance certified is for model SP exhaust for installation type B: Free inlet, Ducted outlet. Performance ratings include the effects of an inlet grille and backdraft damper. Speed (rpm) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in spherical fan sones at 5 ft (1.5m) in a spherical free field calculated per Annex B of AMCA 311. Values shown are for installation type B: free inlet spherical fan sone levels.

Model SP-VG and SP-A Premium Plus and Premium Ceiling Exhaust Fan

B

C

A

E

D

Model SP-VG Dimensions

Model A B C D E Designer Grille*

Decorative Grille

Unit Weight

80(L), 110(L) 113⁄8 (289)

101⁄2 (267)

7 5⁄8 (194)

(152)

(102)

147⁄8 x 131⁄4 (378 x 337)

151⁄4 (387) square

(5)

All dimensions are in inches (millimeters) and weight in pounds (kilograms).

Outlet connection width is 1 in. (25 mm) - Mounting bracket width is 1½ in. (38 mm).

For complete dimensional information, see CAPS submittal drawings.

SP-VG 80, 110

Model SP-VG Performance

Model ENERGY STAR® RPM Amps*

Max.

Input Watts

CFM / Static Pressure in Inches wg

0 0.1 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1

SP-80(L)-VG 935 0.1 6.1

CFM 80 80 80 80 78 66 38

Sones <0.3 <0.3 <0.3 0.6 1.4 2.2 3.0

SP-110(L)-VG 940 0.2 8.4 CFM 110 110 110 109 100 62 28

Sones <0.3 <0.3 <0.3 1.4 8.3 3.0 3.6

Model SP-VG

Model SP-A Dimensions

Model A B C D E Designer Grille

Decorative Grille

Unit Weight

50, 70, 90 131⁄4 (337)

105⁄8 (270)

(229)

(152)

147⁄8 x 131⁄4 (378 x 337)

151⁄4

(387) sq.

(5)

110, 125, 190 131⁄4 (337)

105⁄8 (270)

(229)

(203)

(152)

(8)

200, 250, 290, (356)

117⁄8 (302)

111⁄4 (286)

(203)

(203)

(11)

410, 510 18 (457)

143⁄8 (365)

141⁄2 (368)

(203)

(203)

193⁄8 x 163⁄8 (492 x 416)

(14)

700 235⁄8 (600)

115⁄8 (295)

115⁄8 (295)

191⁄2 (495)

(203)

251⁄8 x 131⁄2 (638 x 343)

(15)

710, 780 18 (457)

143⁄8 (365)

141⁄2 (368)

(254)

(203)

193⁄8 x 163⁄8 (492 x 416)

(15)

900, 1050, 1410, 1550

233⁄4 (603)

143⁄8 (365)

141⁄2 (368)

177/16 (443)

(203)

25 x 163⁄8 (635 x 416)

(25)

Model SP-A

AB

C D

E

SP-A 110-510,

710, 780

A B

C D

E

SP-A 700,

900-1550

B

C

A

E

D

SP-A 50-90

*Amp and Watt draw is approximate and may vary based on motor manufacturer. Below performance is for 115V.

All dimensions are in inches (millimeters) and weight in pounds (kilograms).

Outlet connection width is 1 in. (25 mm) - Mounting bracket width is 1½ in. (38 mm).

For complete dimensional information, see CAPS submittal drawings.

SP-A 50-90

131⁄1 105⁄5 9 6 50, 70, 90 ⁄4⁄⁄ ⁄8⁄⁄

(337) (270) (229) (152)

147⁄7 x 131⁄1 151⁄1⁄8⁄⁄ ⁄4⁄⁄ ⁄4⁄⁄⁄4⁄⁄ sq.(378 x 337) (387)

(5)

Model SP-A Premium Ceiling Exhaust Fan

Model SP-A Performance

Model ENERGY STAR® RPM Amps*

Max.

Input

Watts*

CFM / Static Pressure in Inches wg

0 0.1 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1

SP-A50 790 0.33 25.9

CFM 89 66 61 31

Sones 0.4 0.6 0.6 0.9

SP-A70 790 0.14 15.6

CFM 88 74 71 54

Sones <0.3 <0.3 <0.3 <0.3

CFM/Watt* 5.64 4.97 4.83 4.12 Watts* 15.6 14.9 14.7 13.1

SP-A90 870 0.14 16.9

CFM 114 101 98 80

Sones <0.3 <0.3 <0.3 0.4

CFM/Watt* 6.75 6.20 6.95 5.33 Watts* 16.9 16.3 14.1 15

SP-A110 950 0.16 19.4

CFM 130 119 115 98

Sones <0.3 <0.3 <0.3 0.5

CFM/Watt* 6.70 6.33 6.15 5.54 Watts* 19.4 18.8 18.7 17.7

SP-A125 1010 0.19 23

CFM 144 130 127 109

Sones 0.4 0.4 0.4 0.6

CFM/Watt* 6.26 5.73 5.62 5.00 Watts* 23 22.7 22.6 21.8

SP-A190 1400 0.45 54.2

CFM 229 214 210 186 156

Sones 2.5 2.1 2.1 1.8 1.6

CFM/Watt* 4.23 4.08 4.05 3.78 3.36 Watts* 54.2 52.5 51.9 49.2 46.4

SP-A200 900 0.47 56.1

CFM 267 246 242 224 199 162 109 68

Sones 2 2 2 2.5 3 3.5 4 4.5

CFM/Watt* 4.76 4.42 4.34 4.10 3.75 3.19 2.29 1.49 Watts* 56.1 55.7 55.7 54.7 53.1 50.8 47.6 45.7

SP-A250 1000 0.56 67

CFM 294 274 271 250 230 201 147 92

Sones 2.5 2.5 2.5 3 3.5 4 5 5

CFM/Watt* 4.39 4.18 4.12 3.89 3.67 3.36 2.65 1.80 Watts* 67.0 65.6 65.8 64.2 62.6 59.8 55.4 51.2

SP-A290 1050 0.72 80.7

CFM 315 293 287 257 231 207 175 124

Sones 2.5 2.5 2.5 3.0 3.0 3.5 3.5 4.5

SP-A390 1350 1.34 135

CFM 410 395 391 368 345 325 307 279

Sones 4.5 4.5 4.5 4.5 5.0 5.0 5.5 5.5

SP-A410 1000 1.74 121

CFM 443 413 405 351 306

Sones 3.5 3.0 3.0 3.0 3.5

SP-A510 1070 3.30 224

CFM 557 512 501 439 392 325

Sones 5.0 4.5 4.5 4.5 4.5 4.0

SP-A700 1100 3.20 350

CFM 757 730 723 700 679 649 613 560 494 396

Sones 5.0 5.0 5.0 5.5 5.5 6.0 6.0 6.5 6.5 6.5

SP-A710 1080 4.40 285

CFM 752 714 701 653 588 486 320

Sones 6.0 6.0 6.0 6.0 6.0 5.5 5.5

SP-A780 1600 3.30 348

CFM 812 782 775 741 704 665 625 581

Sones 8.5 8.5 8.5 8.0 8.0 8.0 8.0 8.0

SP-A900 950 4.00 285

CFM 955 907 896 841 773 701

Sones 4.0 5.0 5.0 5.0 5.0 5.0

SP-A1050 1095 6.30 420

CFM 1125 1059 1043 964 885 796 662

Sones 6.0 6.0 6.0 6.0 5.5 5.5 5.5

SP-A1410 1450 7.40 786

CFM 1455 1415 1404 1353 1307 1262 1218 1174

Sones 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0

SP-A1550 1610 8.60 818

CFM 1607 1558 1558 1506 1449 1407 1369 1323

Sones 10.5 10.0 10.0 10.0 10.0 10.5 11.5 13.0

*Amp and Watt draw is approximate and may vary based on motor manufacturer. Below performance is for 115V.

Performance certified is for model SP exhaust for installation type B: Free inlet, Ducted outlet. Performance ratings include the effects of an inlet grille and backdraft damper. Speed (rpm) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in spherical fan sones at 5 ft (1.5m) in a spherical free field calculated per Annex B of AMCA 311. Values shown are for installation type B: free inlet spherical fan sone levels.

Model SP-A Premmium Ceiling Exhaust Fan

CFM 114 101 98 80

Sones <0.3 <0.3 <0.3 0.4

SP-A90 870 0.14 16.9

CFM/Watt* 6.75 6.20 6.95 5.33 Watts* 16.9 16.3 14.1 15

Model SP-B and SP-C Deluxe and Standard Ceiling Exhaust Fan

Model SP-B Dimensions

Model A B C* D E Designer Grille

Decorative Grille

Unit Weight

50, 70 & 80 137⁄8 (352)

111⁄2 (292)

(179)

(152)

11⁄4

(32) 147⁄8 x 131⁄4

(378 x 337) 151⁄4 (387) sq.

(4)

90, 110, 150, 137⁄8 (352)

111⁄2 (292)

(179)

(152)

11⁄4 (32)

(5)

All dimensions are in inches (millimeters) and weight in pounds (kilograms). *Add 1½ in. (38 mm) to C dimension for incandescent light. Mounting bracket width is 1½ in. (38 mm). For complete dimensional information, see CAPS submittal drawings.

Model SP-C Dimensions

Model A B C D E F Decorative Grille

Unit Weight

50 71⁄2 (191)

71⁄2 (191)

35⁄8 (92)

(76)

15⁄8 (41)

1/2 (13)

91⁄4 x 9 (235 x 229)

(2)

All dimensions are in inches (millimeters) and weight in pounds (kilograms). For complete dimensional information, see CAPS submittal drawings.

AB

CD

E

B

C

F

E D

A

Model ENERGY STAR® RPM Amps*

Max.

Input

Watts*

CFM / Static Pressure in Inches wg

0 0.1 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1

SP-B50 625 0.50 37.8

CFM 67 54 51 40 29

Sones 1.2 1.4 1.4 2.0 3.0

SP-B70 675 0.16 17.1

CFM 89 75 71 54 35

Sones 0.8 0.8 0.9 1.4 2

CFM/Watt* 5.20 4.46 4.25 3.27 2.27 Watts* 17.10 16.80 16.70 16.50 15.41

SP-B80 900 0.16 18.6

CFM 94 81 77 62 46

Sones 0.8 0.9 0.9 1.3 2

CFM/Watt* 5.05 4.40 4.21 3.44 2.71 Watts* 18.60 18.40 18.30 18.00 16.95

SP-B90 700 0.18 21.1

CFM 104 92 89 72 57

Sones 1 1 1 1.5 2

CFM/Watt* 4.93 4.40 4.24 3.48 2.88 Watts* 21.10 20.90 21.00 20.70 19.77

SP-B110 950 1.14 80.2

CFM 133 114 110 97 95 94 91 85 72 50

Sones 1.5 1.5 1.5 2.0 2.0 2.0 3.0 3.5 4.0 4.5

SP-B150 1050 1.70 128

CFM 160 156 155 154 152 149 147 138 123 92

Sones 2.5 2.5 2.5 3.0 3.5 3.5 4.0 4.5 4.5 5.0

SP-B200 1100 2.20 172

CFM 197 195 194 191 187 184 181 166 151 128

Sones 3.5 4.0 4.0 4.5 4.5 5.0 5.0 5.5 5.5 5.5

Performance certified is for model SP exhaust for installation type B: Free inlet, Ducted outlet. Performance ratings include the effects of an inlet grille and backdraft damper. Speed (rpm) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in spherical fan sones at 5 ft (1.5m) in a spherical free field calculated per Annex B of AMCA 311. Values shown are for installation type B: free inlet spherical fan sone levels.

Performance certified is for model SP exhaust for installation type B: Free inlet, Ducted outlet. Performance ratings include the effects of an inlet grille and backdraft damper.

Speed (rpm) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in spherical fan sones at 5 ft (1.5m) in a spherical free field calculated per Annex B of AMCA 311. Values shown are for installation type B: free inlet spherical fan sone levels.

*Note: Amp and watt draw is approximate and may vary based on motor manufacturer. Below performance is for 115V.

*Amp and Watt draw is approximate and may vary based on motor manufacturer. Below performance is for 115V.

Model SP-C

Model RPM Amps* Max.

Input

Watts*

CFM / Static Pressure in Inches wg

0 0.1 0.125 0.25 0.375 0.5 0.625

SP-C50 1680 0.80 46

CFM 52 49 49 47 44 38 29

Sones 3.0 3.0 3.0 3.0 3.5 4.0 4.0

Model SP-B

Model CSP-A

Premium Inline Exhaust Fan (Performance on pg 14)

Model CSP-A Dimensions

Model A B C D E F G Unit Weight

110, 125, 190 131⁄4 (337)

105⁄8 (270)

(229)

(203)

(152)

(305)

91⁄4 (235)

(7)

200, 250, 290, (356)

117⁄8 (302)

111⁄4 (286)

(203)

(203)

127⁄8 (327)

(254)

(10)

410, 510 18 (457)

143⁄8 (365)

141⁄2 (368)

(203)

(203)

167⁄8 (429)

131⁄4 (337)

(16)

700 235⁄8 (600)

115⁄8 (295)

115⁄8 (295)

191⁄2 (495)

(203)

225⁄8 (575)

101⁄2 (267)

(15)

710, 780 18 (457)

143⁄8 (365)

141⁄2 (368)

(254)

(203)

167⁄8 (429)

131⁄4 (337)

(16)

900, 1050, 1410, 1550

233⁄4 (603)

143⁄8 (365)

141⁄2 (368)

177⁄16 (443)

(203)

225⁄8 (575)

131⁄4 (337)

(27)

1750, 2150 35 (889)

143⁄4 (375)

143⁄4 (375)

(711)

(152)

323⁄4 (832)

(330)

(31)

3600 451⁄2 (1156)

161⁄2 (419)

161⁄2 (419)

(1016)

(279)

431⁄4 (1099)

145⁄8 (371)

(55)

All dimensions are in inches (millimeters) and weight in pounds (kilograms). Inlet and outlet connection widths are 1 in. (25 mm) - Mounting bracket width is 1½ in. (38 mm). For complete dimensional information, see CAPS submittal drawings.

A

E D

C

B

F

G

A B

C D

E

F Inlet

G

CSP-110-510,

710, 780

CSP-700,

900-3600

Performance certified is for model CSP inline for installation type D: Ducted inlet, Ducted outlet. Performance ratings include the effects of a backdraft damper.

Speed (rpm) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in spherical fan sones at 5 ft (1.5m) in a spherical free field calculated per Annex B of AMCA 311. Values shown are for installation type D: ducted inlet spherical fan sone levels. Ratings do not include the effect of duct end correction. Ratings are based on 10 ft of insulated duct.

Model CSP-B Dimensions

Model A B C D E F G Unit Weight

110, 150, 200 137⁄8 (352)

111⁄2 (292)

(178)

(152)

11⁄4 (32)

131⁄2 (260)

31⁄4 (83)

101⁄4 (5)

All dimensions are in inches (millimeters) and weight in pounds (kilograms).

Outlet connection width is 1 in. (25 mm) - Mounting bracket width is 1½ in. (38 mm).

For complete dimensional information, see CAPS submittal drawings.

Model RPM Amps* Max.

Input

Watts*

CFM / Static Pressure in Inches wg

0 0.1 0.125 0.25 0.375 0.5 0.625 0.75

CSP-B110 950 1.14 80

CFM 103 100 100 98 97 96 94 86

Sones 1.5 1.5 1.5 2.0 2.0 2.0 2.5 2.5 Watts* 92.3 92.2 92.2 92.1 92.0 92.0 91.9 91.4

CSP-B150 1050 1.70 129

CFM 151 150 149 148 144 146 142 135

Sones 2.0 2.0 2.0 2.0 2.5 2.5 3.0 3.0 Watts* 145.0 145.0 145.0 145.0 144.9 144.9 144.9 144.7

CSP-B200 1100 2.20 173

CFM 186 184 184 182 181 179 175 170

Sones 3.0 3.0 3.0 3.0 3.5 3.5 3.5 3.5 Watts* 183.0 182.4 182.4 181.8 181.5 180.9 179.7 178.2

C

AB

D - diameterInlet FxG

E

*Amp and Watt draw is approximate and may vary based on motor manufacturer. Below performance is for 115V.

Model CSP-B and CSP-A Deluxe Inline Cabinet Fan

Model CSP-B

Model RPM Amps* Max.

Input

Watts*

CFM / Static Pressure in Inches wg

0 0.1 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1

CSP-A110 950 0.62 20.3

CFM 124 112 110 102 77

Sones 0.8 0.8 0.8 0.9 0.9 Watts* 20.3 20.0 19.9 19.7 18.4

CSP-A125 1100 0.63 22.5

CFM 138 126 124 114 91

Sones 1.1 1.1 1.1 1.0 1.2 Watts* 22.5 22.3 22.2 22.1 21.3

CSP-A190 1400 1.10 55.1

CFM 215 202 198 180 159 121

Sones 2.0 1.5 2.0 2.0 2.5 2.5 Watts* 55.1 54.1 53.7 51.9 49.8 46.0

CSP-A200 900 0.43 57.9

CFM 254 231 226 203 178 145 109 70

Sones 0.6 0.4 0.5 0.9 1.0 1.3 1.5 1.5 Watts* 57.9 57.3 57.1 56.1 54.6 52.5 50.3 48.0

CSP-A250 1000 0.79 66.5

CFM 266 246 241 221 205 187 165 132

Sones 0.9 1.0 1.0 2.0 2.5 3.0 2.5 2.5 Watts* 66.5 65.6 65.4 64.0 62.7 61.2 59.4 56.6

CSP-A290 1050 0.71 102.2

CFM 318 299 292 265 248 229 201 144

Sones 1.1 1.2 1.3 2.0 2.5 3.5 3.0 3.0 Watts* 102.2 100.9 100.4 98.3 96.9 95.0 90.5 81.3

CSP-A390 1350 1.33 160.8

CFM 412 400 397 382 363 339 324 309

Sones 2.0 2.0 2.0 2.5 3.0 4.0 4.5 4.5 Watts* 160.8 158.5 157.9 152.4 147.9 141.8 135.4 130.0

CSP-A410 1000 1.87 132.2

CFM 447 441 403 364 317 217

Sones 1.5 1.5 1.5 2.0 2.0 2.0 Watts* 132.2 131.7 128.7 125.6 120.5 112.4

CSP-A510 1070 3.11 218.2

CFM 545 514 506 464 405 324

Sones 2.5 2.0 2.0 2.0 2.0 2.5 Watts* 218.2 214.3 213.3 207.0 196.4 182.8

CSP-A700 1100 3.20 352.1

CFM 766 755 752 739 726 702 678 635 549 418

Sones 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.5 2.5 4.0 Watts* 352.1 350.7 350.3 348.7 346.3 340.7 332.6 315.5 289.1 256.1

CSP-A710 1080 4.40 332.5

CFM 737 698 688 635 567 475 334

Sones 2.5 2.5 2.5 2.5 2.0 2.0 2.0 Watts* 332.5 324.1 322.0 310.8 295.8 277.4 255.2

CSP-A780 1600 3.77 496.4

CFM 813 784 777 742 707 672 638 603 567 527

Sones 3.0 3.0 3.0 3.0 3.0 2.0 3.0 3.0 3.0 3.5 Watts* 496.4 493.0 492.2 488.0 467.5 453.1 441.8 423.1 407.2

CSP-A900 950 4.87 335

CFM 908 852 841 782 715 631

Sones 1.4 1.4 1.4 2.0 2.5 3.0 Watts* 335.0 288.6 286.0 272.7 259.9 245.5

CSP-A1050 1095 6.65 468.8

CFM 1182 1110 1093 1013 922 832 743

Sones 2.5 2.5 2.5 2.5 2.5 2.5 2.5 Watts* 468.8 455.9 453.3 440.8 424.9 411.0 399.2

CSP-A1410 1450 7.80 870.8

CFM 1584 1543 1533 1483 1439 1395 1345 1293 1238 1181

Sones 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 4.0 4.0 Watts* 870.8 837.9 829.9 788.2 751.0 728.3 696.3 661.8 628.8 595.9

CSP-A1550 1610 8.32 912.8

CFM 1672 1618 1604 1543 1484 1427 1367 1307 1240 1172

Sones 5.0 4.5 4.5 4.5 4.5 4.0 4.0 4.5 4.5 4.5 Watts* 912.8 877.4 868.4 829.3 802.9 778.0 744.3 710.7 679.1 647.4

CSP-A1750 1130 6.60 599.8

CFM 1842 1768 1749 1619 1464 1284 1032 772 484

Sones 5.0 5.0 5.0 4.5 4.0 4.0 3.5 3.0 3.0 Watts* 599.8 570.5 563.0 515.0 470.9 420.3 366.1 317.2 276.5

CSP-A2150 1100 7.80 760.8

CFM 2249 2175 2156 2044 1900 1701 1424 1114

Sones 5.0 4.5 4.5 4.0 4.0 4.0 3.0 3.0 Watts* 760.8 731.5 724.0 679.7 622.7 544.0 459.7 382.3

CSP-A3600 1100 7.10 1313.7

CFM 3778 3653 3622 3460 3280 3091 2844 2551 2232 1750

Sones 5.0 5.0 5.0 5.0 4.5 4.0 4.0 4.0 3.5 3.5 Watts* 1313.7 1253.3 1238.3 1160.0 1084.0 1041.5 971.1 871.9 766.5 649.5

*Amp and Watt draw is approximate and may vary based on motor manufacturer. Below performance is for 115V.

Model CSP-A Premium Inline Cabinet Fan

Performance certified is for model CSP inline for installation type D: Ducted inlet, Ducted outlet. Performance ratings include the effects of a backdraft damper.

Speed (rpm) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in spherical fan sones at 5 ft (1.5m) in a spherical free field calculated per Annex B of AMCA 311. Values shown are for installation type D: ducted inlet spherical fan sone levels. Ratings do not include the effect of duct end correction. Ratings are based on 10 ft of insulated duct.

Model SP 50 Cycle Performance

Model RPM Amps* Max.

Input

Watts*

CFM / Static Pressure in Inches of wg.

0.000 0.050 0.100 0.125 0.150 0.250 0.375 0.500

SP-A110

(50 Hertz Motor)

950 0.29 49

CFM 119 115 110 106 103 88

Sones 1.3 1.3 1.2 1.2 1.3 1.6

SP-A190

(50 Hertz Motor)

1400 0.65 113

CFM 216 206 197 192 187 167 133

Sones 3.2 3.0 2.8 2.9 2.9 3.1 3.4

SP-A290

(50 Hertz Motor)

1050 0.36 81

CFM 329 315 302 296 290 262 222 164

Sones 3.2 3.3 3.3 3.3 3.4 3.7 4.0 4.9

SP-A390

(50 Hertz Motor)

1350 0.67 135

CFM 410 402 395 392 387 368 345 325

Sones 5.4 5.4 5.4 5.4 5.5 5.7 6.0 6.3

SP-A510

(50 Hertz Motor)

900 1.65 224

CFM 447 425 400 388 376 315 159

Sones 3.7 3.5 3.3 3.3 3.3 3.1 2.6

SP-A780

(50 Hertz Motor)

1334 1.65 348

CFM 677 659 642 633 625 591 544 493

Sones 8.8 8.9 8.8 8.7 8.6 8.2 8.1 8.1

SP-A1050

(50 Hertz Motor)

950 3.15 420

CFM 990 945 905 886 867 769 531

Sones 7.2 7.0 6.8 6.8 6.8 6.6 6.5

SP-A1550

(50 Hertz Motor)

1340 4.3 818

CFM 1337 1314 1290 1279 1266 1211 1161 1112

Sones 11.1 10.7 10.6 10.6 10.6 10.5 11.6 13.5

SP-B90

(50 Hertz Motor)

700 0.325 50

CFM 102 97 92 88 86 75 59 45

Sones 1.9 2.2 2.6 2.7 2.7 3.0 3.6 4.1

SP-B110

(50 Hertz Motor)

950 0.57 80

CFM 133 124 114 110 107 97 95 94

Sones 2.0 2.0 2.1 2.2 2.2 2.4 2.7 2.8

SP-B150

(50 Hertz Motor)

1050 0.85 129

CFM 160 158 156 155 155 154 152 149

Sones 3.0 3.1 3.3 3.3 3.4 3.7 4.3 4.5

SP-B200

(50 Hertz Motor)

1100 1.1 173

CFM 197 196 195 194 194 191 187 184

Sones 4.4 4.7 4.6 4.7 4.9 5.1 5.6 5.8

Model SP Dimensions

SP-A A B C D E Designer Grille

Decorative Grille

Unit Weight

50, 70, 90 131⁄4 (337)

105⁄8 (270)

(229)

(152)

147⁄8 x 131⁄4 (378 x 337)

151⁄4 (387) square

(5)

110, 125, 190 131⁄4 (337)

105⁄8 (270)

(229)

(203)

(152)

(8)

200, 250, 290, (356)

117⁄8 (302)

111⁄4 (286)

(203)

(203)

(11)

410, 510 18 (457)

143⁄8 (365)

141⁄2 (368)

(203)

(203)

193⁄8 x 163⁄8 (492 x 416)

(14)

710, 780 18 (457)

143⁄8 (365)

141⁄2 (368)

(254)

(203)

193⁄8 x 163⁄8 (492 x 416)

(15)

900, 1050, 1410, 1550

233⁄4 (603)

143⁄8 (365)

141⁄2 (368)

183⁄4 (476)

(203)

25 x 163⁄8 (635 x 416)

(25)

Outlet connection width is 1 in. (25 mm) - Mounting bracket width is 1½ in. (38 mm).

SP-B A B C D E Designer Grille

Decorative Grille

Unit Weight

50, 70 & 80 137⁄8 (352)

111⁄2 (292)

(178)

(152)

11⁄4 (32)

147⁄8 x 131⁄4 (378 x 337) 151⁄4 (387) square

(4)

90, 110, 150, 137⁄8 (352)

111⁄2 (292)

(152)

(152)

11⁄4 (32)

147⁄8 x 131⁄4 (378 x 337)

(5)

All dimensions are in inches (millimeters) and weight in pounds (kilograms). Mounting bracket width is 1½ in. (38 mm). For complete dimensional information, see CAPS submittal drawings.

For uses in countries with 50 cycle (50 Hz) power, Greenheck offers the same reliability and performance for ceiling mounted exhaust fans model SP.

• Same dimensions and outlet options

• Performance shown in 50 cycle RPMs

• Full-line of grille and discharge accessories available

A B

C D

E

AB

CD

E

*Note: Amp and Watt draw is approximate and may vary based on motor manufacturer. Below performance is for 115V.

AB

C D

E

SP-A 110-510, 710, 780

SP-A (double wide) 700, 900-1550

SP-B 50-200

B

C

A

E

D

SP-A 50-90

Model CSP 50 Cycle Performance

Model RPM Amps* Max Input

Watts*

CFM / Static Pressure in Inches of wg

0.000 0.050 0.100 0.125 0.150 0.250 0.375 0.500 0.625

CSP-A110

(50 Hertz Motor)

950 0.31 51

CFM 124 116 112 110 109 102 77

Sones 1.1 1.1 1.1 1.1 1.1 1.3 1.3

CSP-A190

(50 Hertz Motor)

1400 0.55 100

CFM 215 202 198 180 159 121

Sones 2.3 2.0 2.2 2.7 2.9 3.0

CSP-A390

(50 Hertz Motor)

1350 0.665 144

CFM 412 400 397 382 363 339 324 309

Sones 2.8 2.7 2.8 3.2 3.7 4.7 5.5 6.5

CSP-A780

(50 Hertz Motor)

1334 1.885 405

CFM 685 656 648 609 562 520 481

Sones 5.0 4.9 4.8 4.7 4.6 4.7 4.9

CSP-A1050

(50 Hertz Motor)

950 3.325 455

CFM 1079 1031 982 957 934 841 655

Sones 6.3 6.3 6.0 5.9 5.9 6.0 5.5

CSP-A1550

(50 Hertz Motor)

1340 4.16 830

CFM 1391 1326 1311 1240 1171 1098 1019 929

Sones 7.5 7.4 7.4 7.3 7.4 7.3 7.3 7.2

CSP-B110

(50 Hertz Motor)

950 0.57 80

CFM 103 102 100 99 99 98 97 96 93

Sones 2.0 1.9 2.0 2.1 2.1 2.3 2.6 2.7 3.1

CSP-B150

(50 Hertz Motor)

1050 0.85 129

CFM 151 150 149 149 149 148 148 145 142

Sones 2.5 2.7 2.7 2.7 2.7 2.9 3.1 3.4 3.6

CSP-B200

(50 Hertz Motor)

1100 1.1 173

CFM 186 185 184 183 183 182 180 178 175

Sones 3.4 3.7 3.6 3.7 3.7 4.0 4.1 4.1 4.3

Model CSP Dimensions

CSP-A A B C D E F G Unit Weight

110, 125, 190 131⁄4 (337)

105⁄8 (270)

(229)

(203)

(152)

(305)

(235)

(7)

200, 250, 290, (356)

117⁄8 (302)

111⁄4 (286)

(203)

(203)

127⁄8 (327)

(254)

(10)

410, 510 18 (457)

143⁄8 (365)

141⁄2 (368)

(203)

(203)

167⁄8 (429)

131⁄4 (337)

(16)

700 235⁄8 (600)

115⁄8 (295)

115⁄8 (295)

191⁄2 (495)

(203)

225⁄8 (575)

101⁄2 (267)

(15)

710, 780 18 (457)

143⁄8 (365)

141⁄2 (368)

(254)

(203)

167⁄8 (429)

131⁄4 (337)

(16)

900, 1050, 1410, 1550

233⁄4 (603)

143⁄8 (365)

141⁄2 (368)

183⁄4 (476)

(203)

225⁄8 (575)

131⁄4 (337)

(27)

1750, 2150 35 (889)

143⁄4 (375)

143⁄4 (375)

(711)

(152)

323⁄4 (832)

(330)

(31)

3600 451⁄2 (1156)

161⁄2 (419)

161⁄2 (419)

(1016)

(279)

431⁄4 (1099)

145⁄8 (371)

(55)

CSP-B A B C D E F G Unit Weight

110, 150, 200 137⁄8 (352)

111⁄2 (292)

(178)

(152)

11⁄4 (32)

101⁄4 (260)

31⁄4 (83)

101⁄4 (5)

All dimensions are in inches (millimeters) and weight in pounds (kilograms). Inlet and outlet connection widths are 1 in. (25 mm) - Mounting bracket width is 1½ in. (38 mm). For complete dimensional information, see CAPS submittal drawings.

For uses in countries with 50 cycle (50 Hz) power, Greenheck offers the same reliability and performance for inline cabinet fans model CSP.

• Same dimensions and outlet options

• Performance shown in 50 cycle RPMs

• Full line of discharge accessories available

A

E D

C

B

F

G

A B

C D

E

F Inlet

G

C

AB

D - diameterInlet FxG

E

*Note: Amp and Watt draw is approximate and may vary based on motor manufacturer. Below performance is for 115V.

CSP-A 110-510, 710, 780

CSP-A (double wide) 700, 900-3600

CSP-B

Polypropylene

Steel AluminumSteel

Wheel Options

Greenheck’s ceiling and cabinet fans (models SP and CSP) deliver high performance from a forward-curved wheel. The forward-curved wheel design offers both high-efficiency and low sound. Fan wheels are constructed of polypropylene or steel as standard, and most models offer an aluminum wheel option.

• Level A models utilize steel or polypropylene (standard) wheel construction depending on size.

• Level B models are standard with a polypropylene wheel.

Accessories

SP-B Replacement Power Packs Save installation and down time by replacing the entire power pack instead of individual components. Available as a replacement part on all current and previous SP-B models.

Designer - standard Available in white polystyrene finish, with or without motion detector with time delay. Standard on SP models A50-A390 and B50-B200.

Aluminum White enamel finish standard for models A410-A1550.

Optional for models A50-A390 and B50-B200.

Decorative White plastic finish, with or without light, motion detector with time delay.

Optional for models A50-A390 and B50-B200.

Stainless Steel Polished stainless steel finish optional for models A50-A390 and B50-B200.

Contractor 4 Packs

Save installation time and labor by installing the housing first, then installing the internal components after sheetrocking, plastering and finishing are done.

Housings are packaged in one box, power assemblies and grilles are packaged in another box. Components are shipped to coincide with the phase of your project.

(Model SP-B only).

Custom Molded polystyrene available in an array of colors.

Includes all the same accessory options as the standard grilles. For more information on the many ways this grille option can be used, please contact your Greenheck representative.

Customized Grille Lens Lenses can be customized with formed shapes or logos. Contact your Greenheck representative for details.

s

Greenheck’s fan and light combinations include either a prismatic or a frosted lens and either compact fluorescent or incandescent lamps. Our unique light box is manufactured with a reflective material to increase the light given off by either type of lamp. UL Listed for above bathtub and showers with GFCI branch protected circuit.

Model SP-A, sizes 50 - 390 Model SP-B, sizes 50 - 200

Note: When selecting a lighted grille it will add height to the fan assembly. See CAPS drawings for exact values.

Lighted Grille Options

Prismatic Lens The prismatic lens design provides approximately 25% more light than a traditional frosted lens. The lens may be easily removed to replace light bulbs.

Frosted Lens The frosted lens option is a traditional design which lets approximately 80% of light through the lens. The lens may be easily removed to replace light bulbs.

Note: Compact Fluorescent light bulbs are ENERGY STAR® certified. Not all fan/lighted grill options are ENERGY STAR® certified. See CAPS for availability.

Accessories

Grille Options

• Replaces the standard square discharge duct-connector and damper

• Uses existing mounting holes

• RDC-6 includes a damper (polypropylene construction)

• RDC-8 does not include a damper (galvanized construction)

Filters

Fans used in most applications will collect airborne dirt on wheels and motors over time, even where air is not excessively dirty. Accumulations of dirt on the fan wheel will sharply reduce performance and cause imbalance.

Dirt buildup on the motor can cause it to overheat. All of these conditions will shorten the life of the fan. To help reduce this accumulation, washable aluminum mesh filters are available to trap dirt before it enters the fan.

These filters should be regularly cleaned to maintain performance. The Filter Loss Chart shows the effect the filter will have on performance. To determine the added resistance, divide the desired CFM by the filter area (ft2).

This will give ft/min. Use this with the filter loss chart to get the added resistance.

Filters reduce sound levels, in addition to reducing dirt accumulations on the motor and wheel.

Mesh Filter

SP

Grille

Filter Loss Chart

SP Model Filter Model

Filter Area (ft2)Designer

Grille *Metal Grille

SP-A50 - A190 F-200 F-210 0.739

SP-B50 - B200, A200 - A390 F-200 F-220 0.911

SP-A410 - A510

SP-A710 - A780 NA F-250 1.518

SP-A900 - A155 NA F-260 2.078

*Aluminum or Stainless Steel Grille.

(See pg. 24 for filter loss graph)

Model For use with sizes:

473324

B50-B200

A50-A90

A110-A190*

6x4 - Transition

Duct Reducer

• Reduces duct from 6 to 4 inches.

• Durable plastic construction

RDC

Model Use with sizes: Diameter

RDC-6 A110-A190 6 (152)

RDC-8 A200-A510 8 (203)

All dimensions shown in inches (millimeters).

Unit Size A B

B50-B200 41⁄2 (114) 155⁄8 (397)

A50-A190 51⁄2 (140) 145⁄8 (371)

A200-A390 63⁄4 (171) 151⁄2 (394)

A410, A510, A710, A780 91⁄4 (235) 195⁄8 (498)

A700 51⁄2 (140) 251⁄8 (638)

A900, A1050, A1410, A1550 91⁄4 (235) 253⁄8 (645)

A1750, A2150 91⁄4 (235) 363⁄4 (933)

A3600 91⁄4 (235) 485⁄8 (1235)

All dimensions shown in inches (millimeters).

Hanging Vibration Isolators

Vibration isolator kits are available for suspended installations. Kits include all hardware necessary to mount one unit, with the exception of 1/4-20 threaded rod to be supplied by others.

Fan mounting brackets include prepunched mounting holes for ease of installation.

Model RDC -

Round Duct Connector

Accessories

6 5/32 (157)

4 15/32 (114)

3 15/16 (100)

A B

1/4-20 hanging support rod by others

All dimensions shown in inches (millimeters).

* Used in conjunction with RDC-6

RDC-6

Ceiling Radiation Damper

The National Fire Protection Association (NFPA) Standard 90A requires openings in fire rated ceiling assemblies to be protected by appropriately rated ceiling radiation dampers. As a result, many local codes require fans installed in fire rated ceilings to be protected by dampers which are insulated against both heat and flame.

Greenheck's ceiling radiation dampers are also Warnock Hersey Listed to go into a one hour combustible (wood) installation. Greenheck's UL Classified ceiling radiation dampers are rated for three hours of fire resistance in a noncombustible installation.

Model SP-A

Model SP-B

SP-B Fan

Hanging Vibration Isolation

Ceiling Radiation Damper

Fire Rated Ceiling

Grille

3 in.

AxB

SP Model CRD Length (A) Width (B) Height UL W.H.

A50 - A190 310 131⁄2 (343)

111⁄8 (283)

(76)

310L 310

B50 - B200 A200 - A390 320 143⁄8

(365) 121⁄4 (311)

(76)

320L 320

A410 - A510 A710 - A780 350 187⁄16

(468) 1415⁄16 (379)

(76) 350 350

A700 700 243⁄16 (614)

121⁄4 (311)

(76) 700 NA

A900 - A1550 360 243⁄16 (614)

1415⁄16 (379)

(76) 360 360

All dimensions shown in inches (millimeters). Add an “L” to all CRD models if fan & light combo is used. *CRD is approximately 1/4 inch (6 mm) larger than housing dimension. (See Installation, Operation and Maintenance Manual)

SP-A Fan

Hanging Vibration Isolation

Ceiling Radiation Damper

Fire Rated Ceiling

GrilleAxB

3 in.

Accessories

Model RJ - Pitched Roof Cap

• Steel construction with black enamel finish

• Integral flashing flange

• Built-in birdscreen and damper

Model Use for sizes: A B C D E Throat

RJ-4 80, 80L, C50,

B50-B80

(279)

91⁄4 (235)

81⁄4 (210)

55⁄16 (135)

41⁄2 (114)

4 (102) diameter

RJ-6x9 110, 100L B90-B200, A50-A390

183⁄4 (476)

141⁄4 (362)

141⁄2 (368)

103⁄8 (264)

61⁄2 (165)

6 x 9 (152 x 229)

RJ-10x10 A410-A1050 181⁄2 (470)

271⁄2 (699)

153⁄4 (400)

235⁄8 (600)

91⁄2 (241)

10 x 10 (254 x 254)

All dimensions shown in inches (millimeters).

RJ-4 and RJ-6x9 D C

B A

ERJ-4 and RJ-6x9

RJ-10x10

CD

E

A B

RJ-10x10

3.5 (89)

(254)

11.125 (283)

2.875 (73)

6.5 (165)

1.625 (42)

9.375 (238)

11.5 (292)5.125 (130)

3.375 (86)

All dimensions shown in inches (millimeters).

Model EL-10x3 -

Elbow Discharge with Grille

• Designed for installation under roof eaves

• Black epoxy finish (elbow and grille)

• Built-in damper

• SP and CSP sizes 50-290

Speed Controls

Speed controls may be used on model SP and CSP fans for manual adjustment of the fan’s performance (for final system balancing) or to control the fan’s output in confined spaces, such as conference or meeting rooms.

The fan can be adjusted to 60% of design airflow with a speed control.

This reduction in airflow and fan speed is also accompanied by a reduction in noise level. Solid state speed controls are available for a range of applications up to 15 amps. Speed controls can be used to operate more than one fan if the combined total amperage of the fans does not exceed the control rating.

Internal Mounting

Electrical Accessories

Dehumidistat

Dehumidistats are available with models SP and CSP fans to ventilate humid spaces. The sensor automatically detects excess humidity and activates a ventilation fan for control of excess condensation. There are automatic, manual, or air cycle modes. This can replace a single pole switch for control of a ventilating fan.

• Rated for 120V, 3A, 1/6 HP

• UL Listed

Note: All switch covers are standard white.

Other colors available upon request.

SPEED CONTROL INTERNAL AND/OR EXTERNAL MOUNTING OPTIONS

Model Voltage Rating

Amp Rating

Fan Sizes

50 70 80 90 110 125 150 190 200 250 290 390 410 510 700 710 780 900 1050 1410 1550 1750 2150 3600

6WSSC

115 - 127V

6 Amp I/E I/E I/E I/E I/E I/E I/E I/E I/E I/E I/E I/E I/E I/E I/E I/E I/E I/E No No No No No No

10WSSC

115 - 127V

10 Amp E E E E E E E E E E E E E E E E E E E E E E E No

15WSSC

115 - 127V

15 Amp E E E E E E E E E E E E E E E E E E E E E E E No

5W240 220 - 240V

5 Amp No No No *I/E I/E No I/E I/E *I/E No I/E I/E No I/E No No I/E No I/E No I/E No No No

8WSSC

220 - 240V

8 Amp No No No *E E No E E *E No E E No E No No E No E No E No No No

5W277 227V

5 Amp No No No No I/E I/E I/E I/E *I/E No No No No No No No No No No No No No No No

KEY:

E = External mounted only I/E = Available Internal and External Mounted

* Only available on the B-series (A-series is not available) No = Not available

NOTES: Speed controllers are not available for 208V applications. SP-C50 Speed Controller is shipped loose only.

All speed controller options listed in table are UL Listed.

Handy Box sizes are 2x4 for all options above except 10WSSC and 15WSSC, which are 4x4.

Motion Detectors

Motion detectors may be used with SP and CSP fans or fan and light combinations. Motion detectors use a passive infrared motion detector to automatically turn the fan on when a change in motion is sensed. They have a viewing area of 180 degrees, however they must be placed in the line-of-sight.

Grille Mounted Available on models SP-A50 through SP-A390 and SP-B50 through SP-B200.

• Rated for 115V

• UL Listed

Wall Mounted For use on fan or lights. Available shipped loose.

• Rated for 115V

• UL Listed

• Requires 2x4 handy box

• Time delay can be set for

30 seconds to 30 minutes in 5 minute increments

Switches

Switches may be used on model SP and CSP fans to enable manual control of your fan or fan and light combination.

1 Function Single pole rocker switch assembly

• Rated for 120-277V, 15A

• UL Listed

1 Function with Pilot Light

Single pole light combination switch assembly

• Rated for 120V, 15A

• UL Listed

2 Function

Two single pole combination switch assembly

• Rated for 120V, 15A

• UL Listed

Time Delay Switch

Time delay switches save energy by automatically turning off the fan or fan/ light combination unit. Activating the switch allows operation for an extended period of time. This switch includes four preset time delay settings of 10, 20, 30 and 60 minutes and off. This switch may be used with SP, CSP or fan/light combination fans.

Model Voltage Ratings Amp Rating

T-2.0 230/277V to 115 2.0 Amps

T-4.3 230/277V to 115 4.3 Amps

T-6.5 230/277V to 115 6.5 Amps

T-8.6 230/277V to 115 8.6 Amps

Transformers

Transformers are available for applications requiring voltage reduction. Selection is based on motor amperage. All transformers are shipped loose. See performance pages for motor amp ratings.

Electrical Accessories

Note: All switch covers are standard white.

Other colors available upon request.

Minimum Ventilation Control

This control contains a microprocessor that monitors the operation of the fan to make sure that the space is receiving the correct amount of ventilation per

ASHRAE 62.2

• 120V, 2.5A

• UL Listed

Discharge Accessories

Model WC - Hooded Wall Cap

(Round Connection)

• Aluminum construction - aluminum finish

• For outside wall applications

• Built-in birdscreen (not available on WC-4) and damper

Model Use with sizes A B C D E

WL-10x3 50-290 12 (305)

51⁄4

(133)

(254) 73⁄4

(197) 31⁄2

(89)

WL-18x6 390-1550 193⁄4

(502)

(203)

(457)

(229)

(152)

All dimensions shown in inches (millimeters).

B

ECA

DE

E B

C

A D

Model Use with sizes A B C D E

WC-4 C50 61⁄2

(165)

(152)

(101)

(101)

(127)

WC-6 B50-B200, 80, 80L

A50-A190, 110, 110L

(203)

(203)

(152)

41⁄8

(105)

(127)

WC-8 A200-A510 11

(279)

(279)

(203)

51⁄8

(130) 31⁄2

(89)

All dimensions shown in inches (millimeters).

Model WC - Hooded Wall Cap

(Square or Rectangular Connections)

• Steel construction with black enamel finish

• For outside wall applications

• Built-in birdscreen and damper

Model Use with sizes A B C D E F G

WC-10x3 50-290 51⁄2 (140)

123⁄4 (324)

31⁄2 (89)

101⁄4 (260)

111⁄8 (283)

41⁄4 (108)

(127)

WC-8x8 200-510 101⁄4 (260)

101⁄4 (260)

81⁄4 (210)

81⁄4 (210)

81⁄4 (210)

63⁄4 (171)

(127)

WC-18x8 700-1550 101⁄4 (260)

201⁄4 (514)

81⁄4 (210)

181⁄4 (464)

181⁄4 (464)

63⁄4 (171)

(127)

All dimensions shown in inches (millimeters).

D

A

G

C

B

E

F

Model Use with sizes A B C

BVE808 50-290 81⁄8

(206)

73⁄4 (197)

(102)

BVE128 390-510 12

(305)

73⁄4 (197)

(102)

BVE157 700-1050 155⁄8

(397)

73⁄4 (197)

(102)

All dimensions shown in inches (millimeters).

Model WL - Wall Louvered Discharge

• Anodized aluminum grille

• Built-in damper

• Not recommended for exterior applications exposed to severe weather conditions. An external wall louver is recommended for such applications.

Model BVE - Brick Vent

• Designed for…