36C24219B0022-0002001.pdf
PDF 3 MB Posted
- Attached to
- 528A6-17-606 PROVIDE ACCESSIBILITY B32 Federal contract opportunity
- Solicitation number
- 36C24219B0022
About this file
36C24219B0022 0002 S06 - Amendment Attachment.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24219C0141-000.docx | DOCX document | |
| 36C24219B0022-0002000.docx | DOCX document | |
| 36C24219B0022-0001000.docx | DOCX document | |
| 36C24219B0022-003.zip | ZIP file | |
| 36C24219B0022-002.zip | ZIP file | |
| 36C24219B0022-001.docx | DOCX document | |
| 36C24219B0022-000.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Centrifugal Ceiling Exhaust and Inline Cabinet Fans Models SP and CSP
November
See ENERGY STAR® Models on Pages 10-12
Great things come in small packages, as do our
SP ceiling exhaust fan and CSP inline cabinet fan models. Be assured when you buy any Greenheck product, it is a quality product at a competitive price. Plus, we guarantee our SP and CSP fans with a three-year warranty. We are your market leader for the most comprehensive ceiling and cabinet fan line in the market.
Table of Contents
Standard Construction Features . . . . . . . . . . . . . .4-5
Power Ratings
Certifications
Vari-Green® Motors and Controls
Sound and Fan Selection
ENERGY STAR® Approval . . . . . . . . . . . . . . . . . .9-12
Model Number Code
Model SP-VG
Model SP-A . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-11
Model SP-B and SP-C
Model CSP-B
Model CSP-A . . . . . . . . . . . . . . . . . . . . . . . . . . .13-14
Model SP (50 cycle)
Model CSP (50 cycle)
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . .17-24
Electrical Accessories . . . . . . . . . . . . . . . . . . .21-22
Discharge Accessories . . . . . . . . . . . . . . . . . .23-24
Pressure Drop
Specifications Vari-Green
Model Specifications . . . . . . . . . . . . . . . . . . . . .26-27
Benefits
• Low sound levels
• Compact size
• Wide range of performance
• Available with EC motors for higher efficiency and more controllability
Typical Installations
• Multifamily housing
• Hotels
• Hospitals
• Schools
• Bathrooms
• Storage rooms
Models SP and CSP Ceiling and Cabinet Fans
Model Comparison
Model
Location Mounting Airflow Application Drive Type
Impeller Type Performance
O u td o o r
In d o o r
R o o f
C u rb
B a s e
/F lo o r
H a n g in g
W a ll
C e il in g M o u n te d
E x h a u s t
S u p p ly
R e v e rs ib le
R e c ir c u la te
G e n e ra l/
C le a n
A ir
C o n ta m in a te d A ir
S p a rk
R e s is ta n t
G re a s e
U
L
S m o k e C o n tr o l (U
L
H ig h W in d m p h
H ig h T e m p a b o v e
°F
B e lt
D ir e c t
C e n tr if u g a l
P ro p e ll e r/ A x ia l
M ix e d
F lo w
M a x im u m
V o lu m e (c fm
M a x im u m
S ta ti c
P re s s u re
(i n w g
SP 1,600 1
CSP 3,800 1
Model Level of
Construction Description
Profile min. height
Sound min. sones
Air Volume max. cfm UL Listing
C e il in g F a n s
SP VG
Premium Plus:
Green/energy efficient highest performing
7 inches (178 mm)
<0.3 710 cfm
(1206 m3/hr)
UL/cUL Listed for above bathtub/ shower with GFCI branch protected circuit
SP A
Premium Ceiling Fan:
Widest selection to meet sound requirements.
9 inches (229 mm)
<0.3 1,600 cfm
(2718 m3/hr)
UL/cUL Listed for above bathtub/ shower with GFCI branch protected circuit (Sizes A390 and smaller)
SP B
Deluxe Ceiling Fan:
Compact to fit most applications with quiet operation.
7 inches (178 mm)
1.2 200 cfm
(340 m3/hr)
UL/cUL Listed for above bathtub/ shower with GFCI branch protected circuit
SP C
Economy Ceiling Fan:
Designed for light commercial applications.
35⁄8 inches (86 mm)
3.0 50 cfm
(85 m3/hr) UL Listed
In li n e F a n s CSP A
Premium Inline Fan:
Outperforms the competition and is preferred by specifying engineers.
9 inches (229 mm)
0.8 3,775 cfm
(6414 m3/hr) UL/cUL Listed
CSP B
Deluxe Inline Fan:
Compact design to fit in small remote spaces.
7 inches (178 mm)
1.5 185 cfm
(314 m3/hr) UL/cUL Listed
SP fans are designed for ceiling mounted exhaust applications.
CSP fans are designed for inline supply or exhaust applications.
d for aust
Models SP and CSP Ceiling and Cabinet Fans
All dimensions are in inches (millimeters)
Model SP-A
Model SP-C
Model SP-B
Model CSP-A
Model CSP-B
6 5
8 10
Model SP-VGodel SP VG
Standard Construction Features
Number and Description Specific Features for Each Model
SP-VG SP-A SP-B SP-C CSP-A CSP-B
1 Backdraft Damper
Durable plastic to reduce backdrafts 50-90
Aluminum to reduce backdrafts 110-
2 Outlet Round - For quick and easy connections 50-90
Square - For quick and easy connections 110-
3 Power Pack Removes quickly for maintenance
Includes conversion from horizontal to vertical discharge
4 Electrical Access
Vertical electrical access to eliminate drilling holes
External electrical access to save installation time
5 Electrical Knockouts
Eliminates drilling holes (horizontal or vertical)
6 Acoustic Insulation
Absorbs sound
7 Disconnect Servicing is quick and safe
8 Electrical Junction Box
Large for easy wiring
9 Grille Concealed attachment screws securely fasten grille to housing for quiet, rattle free operation
10 Mounting Brackets
Adjustable for multiple installation conditions
11 Housing Embossed galvanized steel for rigidity
A low profile for height restricted areas
12 Motors
Motors are compatible for use with speed controls and have thermal overload protection
Domestic & International
• 50 cycle, 220v or 240v
• 60 cycle, 115v, 208v, 220v, 230v, & 277v options (See CAPS or pg. 12 for availability)
60 cycle, 115v only
60 cycle, 115v only
13 Access Panel Gain easy access to internal components once installed
Exclusive Electrical Wiring Feature
Electrical access cover located on the housing exterior. This feature permits external wiring without removing the power assembly, saving installation time and cost. Available on models SP-A and CSP-A.
Double-Wide Fans
Available for applications requiring 700 cfm or greater.
Double-wide fans have two double-width forward-curved wheels, which are housed in separate scrolls and driven by a single motor.
Available on models SP-A and CSP-A.
Vertical Discharge
Exhaust outlet duct installed in the optional vertical position.
The power assembly must be rotated to match the duct adapter position.
Available on SP-A and CSP-A models.
Standard Construction Features
Available Motor Voltage and Cycle Ratings
Power Rating V/Hz
Models Available (X)
115V/ 60Hz
115V/ 50Hz
220-240V/ 50Hz
220-240V/ 60Hz 277V
Vari-Green Motor Option
SP-A50 x
SP-A70 x
SP-A90 x
SP-A110 x x x x x
SP-A125 x x
SP-A190 x x x x x
SP-A200 x
SP-A250 x
SP-A290 x x x x
SP-A390 x x x x
SP-A410 x
SP-A510 x x x x x
SP-A700 x
SP-A710 x x
SP-A780 x x x x
SP-A900 x
SP-A1050 x x x x
SP-A1410 x
SP-A1550 x x x x
SP-B50 x
SP-B70 x
SP-B80 x
SP-B90 x x x x
SP-B110 x x x x x
SP-B150 x x x x x
SP-B200 x x x x x
Available Motor Voltage and Cycle Ratings
Power Rating V/Hz
Models Available (X)
115V/ 60Hz
115V/ 50Hz
220-240V/ 50Hz
220-240V/ 60Hz 277V
Vari-Green Motor Option
SP-C50 x
SP-80 x x
SP-80L x x
SP-110 x x
SP-110L x x
CSP-A110 x x x x x
CSP-A125 x x
CSP-A190 x x x x x
CSP-A200 x
CSP-A250 x
CSP-A290 x x x
CSP-A390 x x x x
CSP-A410 x
CSP-A510 x x x x
CSP-A700 x
CSP-A710 x x
CSP-A780 x x x x
CSP-A900 x
CSP-A1050 x x x x
CSP-A1410 x
CSP-A1550 x x x x
CSP-A1750 x
CSP-A2150 x
CSP-A3600 x x x
CSP-B110 x x x x x
CSP-B150 x x x x x
CSP-B200 x x x x x
Power Ratings
Models SP and CSP are listed electric fans (UL/cUL 507).
Ceiling Exhaust Fans are also UL Listed for above bathtub/ shower with GFCI branch protected circuit. File no. E33599.
Note: SP/CSP fans are rated for direct contact with insulation
Greenheck Fan Corporation certifies that the SP models shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program. The SP models are not AMCA certified with 50 hertz motors.
Greenheck Fan Corporation certifies that the CSP models shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and comply with the requirements of the AMCA Certified Ratings Program. The CSP models are not AMCA certified with 50 hertz motors.
Products that earn the ENERGY STAR® prevent greenhouse gas emissions by meeting strict energy efficiency guidelines set by the U.S. Environmental Protection Agency and the U.S.
Department of Energy.
Fans that are ENERGY STAR qualified include: SP-A70, SP-A90, SP-A110, SP-A125, SP-A190, SP-A200, SP-A250, SP-B70, SP-B80, SP-B90, SP-80-VG, SP-80L-VG, SP-110-VG and SP-110L-VG.
Vari-Green® Motor
EC Motor Technology Information & Advantages -
Greenheck’s Electronically Commutated (EC) Vari-Green (VG) motor combines motor technology, controllability and energy-efficiency into one single low maintenance unit and is the industry's first fully controllable motor.
The EC motor operates on AC power that is converted to DC – providing a more efficient motor operation as compared to an AC operation. Controllability allows for variable volume systems that save conditioned air from being exhausted when it is not needed and helps prevent over or under ventilating the space.
Vari-Green® Controls
Air Quality – VOC - Control a Vari-Green motor via changes in Volatile Organic Compounds (VOC’s).
VOC’s are gasses that are emitted from humans, building materials, perfumes, foods, and furniture off-gassing. Range is 0-2000 CO2 ppm equivalent.
• Institutional facilities – Schools, court houses, hospitals; bathrooms, waiting rooms, cafeterias.
• Commercial buildings – Office spaces, conference rooms, bathrooms, break rooms.
Air Quality – Temperature and Humidity - Control Vari-Green motor via changes in temperature, humidity, or both. Range is 32 to 120°F (0-49°C) and 0 to 100% relative humidity.
• Multifamily structures – Apartments, condos, hotels;
bathrooms, utility rooms.
• Commercial buildings – Office buildings; office spaces, conference rooms, utility rooms, bathrooms.
Transformer - Provides 24V power from the existing line voltage at the fan to the Vari-Green motor and controls. Dual voltage primary (120/240V) transformer provided with the fan.
Remote Dial or Touch Remote - allows the user to manually adjust a fan’s speed from a remote location and mounts to a wall using a 2x4 junction box. The 24VDC transformer, described above, is included with all orders. A wall cover plate is supplied.
• The Touch Remote includes a count down timer to automatically turn the fan off after 10, 30, 60 or 90 minutes.
• Recommended for use in commercial buildings and restaurants.
Two-speed Control with Integral Transformer - Control allows motor RPM to be set at two independent speeds (high or low). Meets minimum airflow requirements with the ability to bump up to high speed in an emergency or meet maximum airflow requirements, or reset to low for energy conservation.
Constant Pressure Control - Control Vari-Green motors via static (variable volume) or velocity (constant CFM) pressure on the inlet or outlet side of the fan.
Optional, one or two, duct or room probes for use in:
• Multifamily structures - Apartments, condos, hotels;
dryers, residential kitchens and bathrooms.
• Institutional facilities - Schools, prisons, multistory office buildings; bathrooms.
Vari-Green® Motor & Controls
Available Vari-Green Controls and Models
Controls
Models
SP-
80(L)-VG
SP-
110(L)-VG
SP/CSP-
A510-VG
SP/CSP-
A710-VG
VOC X X
Temp./Humidity X X
Two-speed X X
Remote Dial X X
Touch Remote X X
Constant Pressure X X
Transformer X X
Built-in Time Delay X X
Built-in Two Speed X X
See Greenheck's Vari-Green Motor and Vari-Green Controls brochures for more information.
Sound Data
The sound data shown in this catalog has been presented to aid the system designer in selecting a fan which will meet the desired sound criteria. Sone levels have been included on the performance pages to provide a means of quickly evaluating the relative loudness of a fan selection.
What is a sone?
Sones are an internationally recognized unit of loudness. In practical terms, the loudness of one sone is equivalent to the sound of a quiet refrigerator measured from five feet away in an acoustically average room. A sone is a single number rating, which indicates the inlet noise derived from the eight audible octave bands. Sones are a linear measurement of sound level.
For example, a sound level of 10 sones is twice as loud as 5 sones.
Can radiated noise increase the sound levels?
Radiated noise from fan housings can cause unacceptable sound levels on any brand of fan.
The size of these fans allows them to be placed in areas where this noise will be transmitted to the conditioned space through walls or ceilings. Where possible, cabinet fans should be located in remote parts of the ventilation system.
When should an SP or CSP fan be used?
Model SP and CSP fans are designed for the lowest possible sound levels. Forward-curved wheels, optional insulated housings and vibration isolators between
Model CFM Inches WG FRPM Sones
SP-A410 405 1/8 1000 3.0
CSP-A410 403 1/8 1000 1.5
*Sone value on CSP is with insulated inlet duct.
Sound and Fan Selection Things to know when sound is critical
The compact size of the SP and CSP fans provides the system designer greater flexibility in locating these fans for lowest sound levels. In critical sound areas, insulated ductwork, flexible duct connections, or placing the fan in a remote section of the ductwork (away from the critical sound area) offers the best means of meeting desired sound levels.
Remote mounted model CSP with vibration isolators and insulated ductwork provides the quietest installation.
Fiberglass the motor and housing contribute to quiet, efficient operation. Applied and installed as recommended, SP and CSP sound levels will fall well within the ranges shown in the Suggested Limits for Room Loudness chart (shown below). For applications where sound levels are critical, a remote mounted CSP with ductboard is recommended. Placement of SP and CSP fans should take into account the desired sound level at the location of the listener.
Suggested Limits for Room Loudness
Sones dBA
1.3-4 32-48 Private homes (rural and suburban)
1.7-5 36-51 Conference rooms
2-6 38-54 Hotel rooms, libraries, movie theatres, executive offices
2.5-8 41-58 Schools and classrooms, hospital wards and operating rooms
3-9 44-60 Court rooms, museums, apartment houses, private homes (urban)
4-12 48-64 Restaurants, lobbies, general open offices, banks
5-15 51-67 Corridors and halls, cocktail lounges, washrooms and toilets
7-21 56-72 Hotel kitchens and laundries, supermarkets
Reprinted from AMCA Publication 302 Application of Sone Ratings for Non-Ducted Air Moving Devices (with room, sone and dBA correlations) with the written permission from AMCA International, Inc., 30 West University Drive, Arlington Heights, IL 60004-1893.
NOTE: Values above are for room loudness and are not sound ratings. Room loudness is the resulting level in a conditioned space after the acoustical qualities of the room have been accounted for.
When room sound levels are critical, such as in executive offices, conference rooms, hospital operating rooms, and school study areas, a CSP fan is the best choice. Shown here is a comparison of SP and CSP fans of the same size, with equal performance in typical installations. The CSP shows lower sone values.
ENERGY STAR®
Model Number Code
The model number code system is designed to completely identify the fan. The correct code letters must be specified to designate belt or direct drive. The remainder of the model code is determined by the size and performance.
ENERGY STAR is a market-based partnership formed to reduce greenhouse gas emissions through energy efficiency and make it easier for consumers to identify energy-efficient products that offer savings, performance, features, and comfort.
To earn the ENERGY STAR label, products must meet strict energy efficiency standards set by the U.S.
Environmental Protection Agency (EPA) for energy consumption, air and sound performance. Fan models that are ENERGY STAR qualified are identified in this catalog.
Note: Energy Star is only for products 500 cfm or less.
Light Options:
L - Fan/Light (Incandescent) Combination FL - Fan/Light (Fluorescent) Combination
Nominal CFM at 0.10 inches static pressure
Level of Construction:
A - Premium unit; lowest sound, insulated housing B - Deluxe unit; low sound, low profile C - Standard unit; lowest profile, inexpensive
C - No letter designation identifies model as Premium Plus with a Vari-Green motor.
Model:
SP - Silent Partner CSP - Cabinet Silent Partner
SP - A 50 FL - VG
Vari-Green®:
EC Motor Option
Products that earn the ENERGY STAR® prevent greenhouse gas emissions by meeting strict energy efficiency guidelines set by the U.S. Environmental Protection Agency and the U.S.
Department of Energy.
Fans that are ENERGY STAR qualified include: SP-A70, SP-A90, SP-A110, SP-A125, SP-A190, SP-A200, SP-A250, SP-B70, SP-B80, SP-B90, SP-80-VG, SP-80L-VG, SP-110-VG and SP-110L-VG.
Performance certified is for model SP exhaust for installation type B: Free inlet, Ducted outlet. Performance ratings include the effects of an inlet grille and backdraft damper. Speed (rpm) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in spherical fan sones at 5 ft (1.5m) in a spherical free field calculated per Annex B of AMCA 311. Values shown are for installation type B: free inlet spherical fan sone levels.
Model SP-VG and SP-A Premium Plus and Premium Ceiling Exhaust Fan
B
C
A
E
D
Model SP-VG Dimensions
Model A B C D E Designer Grille*
Decorative Grille
Unit Weight
80(L), 110(L) 113⁄8 (289)
101⁄2 (267)
7 5⁄8 (194)
(152)
(102)
147⁄8 x 131⁄4 (378 x 337)
151⁄4 (387) square
(5)
All dimensions are in inches (millimeters) and weight in pounds (kilograms).
Outlet connection width is 1 in. (25 mm) - Mounting bracket width is 1½ in. (38 mm).
For complete dimensional information, see CAPS submittal drawings.
SP-VG 80, 110
Model SP-VG Performance
Model ENERGY STAR® RPM Amps*
Max.
Input Watts
CFM / Static Pressure in Inches wg
0 0.1 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1
SP-80(L)-VG 935 0.1 6.1
CFM 80 80 80 80 78 66 38
Sones <0.3 <0.3 <0.3 0.6 1.4 2.2 3.0
SP-110(L)-VG 940 0.2 8.4 CFM 110 110 110 109 100 62 28
Sones <0.3 <0.3 <0.3 1.4 8.3 3.0 3.6
Model SP-VG
Model SP-A Dimensions
Model A B C D E Designer Grille
Decorative Grille
Unit Weight
50, 70, 90 131⁄4 (337)
105⁄8 (270)
(229)
(152)
147⁄8 x 131⁄4 (378 x 337)
151⁄4
(387) sq.
(5)
110, 125, 190 131⁄4 (337)
105⁄8 (270)
(229)
(203)
(152)
(8)
200, 250, 290, (356)
117⁄8 (302)
111⁄4 (286)
(203)
(203)
(11)
410, 510 18 (457)
143⁄8 (365)
141⁄2 (368)
(203)
(203)
193⁄8 x 163⁄8 (492 x 416)
(14)
700 235⁄8 (600)
115⁄8 (295)
115⁄8 (295)
191⁄2 (495)
(203)
251⁄8 x 131⁄2 (638 x 343)
(15)
710, 780 18 (457)
143⁄8 (365)
141⁄2 (368)
(254)
(203)
193⁄8 x 163⁄8 (492 x 416)
(15)
900, 1050, 1410, 1550
233⁄4 (603)
143⁄8 (365)
141⁄2 (368)
177/16 (443)
(203)
25 x 163⁄8 (635 x 416)
(25)
Model SP-A
AB
C D
E
SP-A 110-510,
710, 780
A B
C D
E
SP-A 700,
900-1550
B
C
A
E
D
SP-A 50-90
*Amp and Watt draw is approximate and may vary based on motor manufacturer. Below performance is for 115V.
All dimensions are in inches (millimeters) and weight in pounds (kilograms).
Outlet connection width is 1 in. (25 mm) - Mounting bracket width is 1½ in. (38 mm).
For complete dimensional information, see CAPS submittal drawings.
SP-A 50-90
131⁄1 105⁄5 9 6 50, 70, 90 ⁄4⁄⁄ ⁄8⁄⁄
(337) (270) (229) (152)
147⁄7 x 131⁄1 151⁄1⁄8⁄⁄ ⁄4⁄⁄ ⁄4⁄⁄⁄4⁄⁄ sq.(378 x 337) (387)
(5)
Model SP-A Premium Ceiling Exhaust Fan
Model SP-A Performance
Model ENERGY STAR® RPM Amps*
Max.
Input
Watts*
CFM / Static Pressure in Inches wg
0 0.1 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1
SP-A50 790 0.33 25.9
CFM 89 66 61 31
Sones 0.4 0.6 0.6 0.9
SP-A70 790 0.14 15.6
CFM 88 74 71 54
Sones <0.3 <0.3 <0.3 <0.3
CFM/Watt* 5.64 4.97 4.83 4.12 Watts* 15.6 14.9 14.7 13.1
SP-A90 870 0.14 16.9
CFM 114 101 98 80
Sones <0.3 <0.3 <0.3 0.4
CFM/Watt* 6.75 6.20 6.95 5.33 Watts* 16.9 16.3 14.1 15
SP-A110 950 0.16 19.4
CFM 130 119 115 98
Sones <0.3 <0.3 <0.3 0.5
CFM/Watt* 6.70 6.33 6.15 5.54 Watts* 19.4 18.8 18.7 17.7
SP-A125 1010 0.19 23
CFM 144 130 127 109
Sones 0.4 0.4 0.4 0.6
CFM/Watt* 6.26 5.73 5.62 5.00 Watts* 23 22.7 22.6 21.8
SP-A190 1400 0.45 54.2
CFM 229 214 210 186 156
Sones 2.5 2.1 2.1 1.8 1.6
CFM/Watt* 4.23 4.08 4.05 3.78 3.36 Watts* 54.2 52.5 51.9 49.2 46.4
SP-A200 900 0.47 56.1
CFM 267 246 242 224 199 162 109 68
Sones 2 2 2 2.5 3 3.5 4 4.5
CFM/Watt* 4.76 4.42 4.34 4.10 3.75 3.19 2.29 1.49 Watts* 56.1 55.7 55.7 54.7 53.1 50.8 47.6 45.7
SP-A250 1000 0.56 67
CFM 294 274 271 250 230 201 147 92
Sones 2.5 2.5 2.5 3 3.5 4 5 5
CFM/Watt* 4.39 4.18 4.12 3.89 3.67 3.36 2.65 1.80 Watts* 67.0 65.6 65.8 64.2 62.6 59.8 55.4 51.2
SP-A290 1050 0.72 80.7
CFM 315 293 287 257 231 207 175 124
Sones 2.5 2.5 2.5 3.0 3.0 3.5 3.5 4.5
SP-A390 1350 1.34 135
CFM 410 395 391 368 345 325 307 279
Sones 4.5 4.5 4.5 4.5 5.0 5.0 5.5 5.5
SP-A410 1000 1.74 121
CFM 443 413 405 351 306
Sones 3.5 3.0 3.0 3.0 3.5
SP-A510 1070 3.30 224
CFM 557 512 501 439 392 325
Sones 5.0 4.5 4.5 4.5 4.5 4.0
SP-A700 1100 3.20 350
CFM 757 730 723 700 679 649 613 560 494 396
Sones 5.0 5.0 5.0 5.5 5.5 6.0 6.0 6.5 6.5 6.5
SP-A710 1080 4.40 285
CFM 752 714 701 653 588 486 320
Sones 6.0 6.0 6.0 6.0 6.0 5.5 5.5
SP-A780 1600 3.30 348
CFM 812 782 775 741 704 665 625 581
Sones 8.5 8.5 8.5 8.0 8.0 8.0 8.0 8.0
SP-A900 950 4.00 285
CFM 955 907 896 841 773 701
Sones 4.0 5.0 5.0 5.0 5.0 5.0
SP-A1050 1095 6.30 420
CFM 1125 1059 1043 964 885 796 662
Sones 6.0 6.0 6.0 6.0 5.5 5.5 5.5
SP-A1410 1450 7.40 786
CFM 1455 1415 1404 1353 1307 1262 1218 1174
Sones 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0
SP-A1550 1610 8.60 818
CFM 1607 1558 1558 1506 1449 1407 1369 1323
Sones 10.5 10.0 10.0 10.0 10.0 10.5 11.5 13.0
*Amp and Watt draw is approximate and may vary based on motor manufacturer. Below performance is for 115V.
Performance certified is for model SP exhaust for installation type B: Free inlet, Ducted outlet. Performance ratings include the effects of an inlet grille and backdraft damper. Speed (rpm) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in spherical fan sones at 5 ft (1.5m) in a spherical free field calculated per Annex B of AMCA 311. Values shown are for installation type B: free inlet spherical fan sone levels.
Model SP-A Premmium Ceiling Exhaust Fan
CFM 114 101 98 80
Sones <0.3 <0.3 <0.3 0.4
SP-A90 870 0.14 16.9
CFM/Watt* 6.75 6.20 6.95 5.33 Watts* 16.9 16.3 14.1 15
Model SP-B and SP-C Deluxe and Standard Ceiling Exhaust Fan
Model SP-B Dimensions
Model A B C* D E Designer Grille
Decorative Grille
Unit Weight
50, 70 & 80 137⁄8 (352)
111⁄2 (292)
(179)
(152)
11⁄4
(32) 147⁄8 x 131⁄4
(378 x 337) 151⁄4 (387) sq.
(4)
90, 110, 150, 137⁄8 (352)
111⁄2 (292)
(179)
(152)
11⁄4 (32)
(5)
All dimensions are in inches (millimeters) and weight in pounds (kilograms). *Add 1½ in. (38 mm) to C dimension for incandescent light. Mounting bracket width is 1½ in. (38 mm). For complete dimensional information, see CAPS submittal drawings.
Model SP-C Dimensions
Model A B C D E F Decorative Grille
Unit Weight
50 71⁄2 (191)
71⁄2 (191)
35⁄8 (92)
(76)
15⁄8 (41)
1/2 (13)
91⁄4 x 9 (235 x 229)
(2)
All dimensions are in inches (millimeters) and weight in pounds (kilograms). For complete dimensional information, see CAPS submittal drawings.
AB
CD
E
B
C
F
E D
A
Model ENERGY STAR® RPM Amps*
Max.
Input
Watts*
CFM / Static Pressure in Inches wg
0 0.1 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1
SP-B50 625 0.50 37.8
CFM 67 54 51 40 29
Sones 1.2 1.4 1.4 2.0 3.0
SP-B70 675 0.16 17.1
CFM 89 75 71 54 35
Sones 0.8 0.8 0.9 1.4 2
CFM/Watt* 5.20 4.46 4.25 3.27 2.27 Watts* 17.10 16.80 16.70 16.50 15.41
SP-B80 900 0.16 18.6
CFM 94 81 77 62 46
Sones 0.8 0.9 0.9 1.3 2
CFM/Watt* 5.05 4.40 4.21 3.44 2.71 Watts* 18.60 18.40 18.30 18.00 16.95
SP-B90 700 0.18 21.1
CFM 104 92 89 72 57
Sones 1 1 1 1.5 2
CFM/Watt* 4.93 4.40 4.24 3.48 2.88 Watts* 21.10 20.90 21.00 20.70 19.77
SP-B110 950 1.14 80.2
CFM 133 114 110 97 95 94 91 85 72 50
Sones 1.5 1.5 1.5 2.0 2.0 2.0 3.0 3.5 4.0 4.5
SP-B150 1050 1.70 128
CFM 160 156 155 154 152 149 147 138 123 92
Sones 2.5 2.5 2.5 3.0 3.5 3.5 4.0 4.5 4.5 5.0
SP-B200 1100 2.20 172
CFM 197 195 194 191 187 184 181 166 151 128
Sones 3.5 4.0 4.0 4.5 4.5 5.0 5.0 5.5 5.5 5.5
Performance certified is for model SP exhaust for installation type B: Free inlet, Ducted outlet. Performance ratings include the effects of an inlet grille and backdraft damper. Speed (rpm) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in spherical fan sones at 5 ft (1.5m) in a spherical free field calculated per Annex B of AMCA 311. Values shown are for installation type B: free inlet spherical fan sone levels.
Performance certified is for model SP exhaust for installation type B: Free inlet, Ducted outlet. Performance ratings include the effects of an inlet grille and backdraft damper.
Speed (rpm) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in spherical fan sones at 5 ft (1.5m) in a spherical free field calculated per Annex B of AMCA 311. Values shown are for installation type B: free inlet spherical fan sone levels.
*Note: Amp and watt draw is approximate and may vary based on motor manufacturer. Below performance is for 115V.
*Amp and Watt draw is approximate and may vary based on motor manufacturer. Below performance is for 115V.
Model SP-C
Model RPM Amps* Max.
Input
Watts*
CFM / Static Pressure in Inches wg
0 0.1 0.125 0.25 0.375 0.5 0.625
SP-C50 1680 0.80 46
CFM 52 49 49 47 44 38 29
Sones 3.0 3.0 3.0 3.0 3.5 4.0 4.0
Model SP-B
Model CSP-A
Premium Inline Exhaust Fan (Performance on pg 14)
Model CSP-A Dimensions
Model A B C D E F G Unit Weight
110, 125, 190 131⁄4 (337)
105⁄8 (270)
(229)
(203)
(152)
(305)
91⁄4 (235)
(7)
200, 250, 290, (356)
117⁄8 (302)
111⁄4 (286)
(203)
(203)
127⁄8 (327)
(254)
(10)
410, 510 18 (457)
143⁄8 (365)
141⁄2 (368)
(203)
(203)
167⁄8 (429)
131⁄4 (337)
(16)
700 235⁄8 (600)
115⁄8 (295)
115⁄8 (295)
191⁄2 (495)
(203)
225⁄8 (575)
101⁄2 (267)
(15)
710, 780 18 (457)
143⁄8 (365)
141⁄2 (368)
(254)
(203)
167⁄8 (429)
131⁄4 (337)
(16)
900, 1050, 1410, 1550
233⁄4 (603)
143⁄8 (365)
141⁄2 (368)
177⁄16 (443)
(203)
225⁄8 (575)
131⁄4 (337)
(27)
1750, 2150 35 (889)
143⁄4 (375)
143⁄4 (375)
(711)
(152)
323⁄4 (832)
(330)
(31)
3600 451⁄2 (1156)
161⁄2 (419)
161⁄2 (419)
(1016)
(279)
431⁄4 (1099)
145⁄8 (371)
(55)
All dimensions are in inches (millimeters) and weight in pounds (kilograms). Inlet and outlet connection widths are 1 in. (25 mm) - Mounting bracket width is 1½ in. (38 mm). For complete dimensional information, see CAPS submittal drawings.
A
E D
C
B
F
G
A B
C D
E
F Inlet
G
CSP-110-510,
710, 780
CSP-700,
900-3600
Performance certified is for model CSP inline for installation type D: Ducted inlet, Ducted outlet. Performance ratings include the effects of a backdraft damper.
Speed (rpm) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in spherical fan sones at 5 ft (1.5m) in a spherical free field calculated per Annex B of AMCA 311. Values shown are for installation type D: ducted inlet spherical fan sone levels. Ratings do not include the effect of duct end correction. Ratings are based on 10 ft of insulated duct.
Model CSP-B Dimensions
Model A B C D E F G Unit Weight
110, 150, 200 137⁄8 (352)
111⁄2 (292)
(178)
(152)
11⁄4 (32)
131⁄2 (260)
31⁄4 (83)
101⁄4 (5)
All dimensions are in inches (millimeters) and weight in pounds (kilograms).
Outlet connection width is 1 in. (25 mm) - Mounting bracket width is 1½ in. (38 mm).
For complete dimensional information, see CAPS submittal drawings.
Model RPM Amps* Max.
Input
Watts*
CFM / Static Pressure in Inches wg
0 0.1 0.125 0.25 0.375 0.5 0.625 0.75
CSP-B110 950 1.14 80
CFM 103 100 100 98 97 96 94 86
Sones 1.5 1.5 1.5 2.0 2.0 2.0 2.5 2.5 Watts* 92.3 92.2 92.2 92.1 92.0 92.0 91.9 91.4
CSP-B150 1050 1.70 129
CFM 151 150 149 148 144 146 142 135
Sones 2.0 2.0 2.0 2.0 2.5 2.5 3.0 3.0 Watts* 145.0 145.0 145.0 145.0 144.9 144.9 144.9 144.7
CSP-B200 1100 2.20 173
CFM 186 184 184 182 181 179 175 170
Sones 3.0 3.0 3.0 3.0 3.5 3.5 3.5 3.5 Watts* 183.0 182.4 182.4 181.8 181.5 180.9 179.7 178.2
C
AB
D - diameterInlet FxG
E
*Amp and Watt draw is approximate and may vary based on motor manufacturer. Below performance is for 115V.
Model CSP-B and CSP-A Deluxe Inline Cabinet Fan
Model CSP-B
Model RPM Amps* Max.
Input
Watts*
CFM / Static Pressure in Inches wg
0 0.1 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1
CSP-A110 950 0.62 20.3
CFM 124 112 110 102 77
Sones 0.8 0.8 0.8 0.9 0.9 Watts* 20.3 20.0 19.9 19.7 18.4
CSP-A125 1100 0.63 22.5
CFM 138 126 124 114 91
Sones 1.1 1.1 1.1 1.0 1.2 Watts* 22.5 22.3 22.2 22.1 21.3
CSP-A190 1400 1.10 55.1
CFM 215 202 198 180 159 121
Sones 2.0 1.5 2.0 2.0 2.5 2.5 Watts* 55.1 54.1 53.7 51.9 49.8 46.0
CSP-A200 900 0.43 57.9
CFM 254 231 226 203 178 145 109 70
Sones 0.6 0.4 0.5 0.9 1.0 1.3 1.5 1.5 Watts* 57.9 57.3 57.1 56.1 54.6 52.5 50.3 48.0
CSP-A250 1000 0.79 66.5
CFM 266 246 241 221 205 187 165 132
Sones 0.9 1.0 1.0 2.0 2.5 3.0 2.5 2.5 Watts* 66.5 65.6 65.4 64.0 62.7 61.2 59.4 56.6
CSP-A290 1050 0.71 102.2
CFM 318 299 292 265 248 229 201 144
Sones 1.1 1.2 1.3 2.0 2.5 3.5 3.0 3.0 Watts* 102.2 100.9 100.4 98.3 96.9 95.0 90.5 81.3
CSP-A390 1350 1.33 160.8
CFM 412 400 397 382 363 339 324 309
Sones 2.0 2.0 2.0 2.5 3.0 4.0 4.5 4.5 Watts* 160.8 158.5 157.9 152.4 147.9 141.8 135.4 130.0
CSP-A410 1000 1.87 132.2
CFM 447 441 403 364 317 217
Sones 1.5 1.5 1.5 2.0 2.0 2.0 Watts* 132.2 131.7 128.7 125.6 120.5 112.4
CSP-A510 1070 3.11 218.2
CFM 545 514 506 464 405 324
Sones 2.5 2.0 2.0 2.0 2.0 2.5 Watts* 218.2 214.3 213.3 207.0 196.4 182.8
CSP-A700 1100 3.20 352.1
CFM 766 755 752 739 726 702 678 635 549 418
Sones 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.5 2.5 4.0 Watts* 352.1 350.7 350.3 348.7 346.3 340.7 332.6 315.5 289.1 256.1
CSP-A710 1080 4.40 332.5
CFM 737 698 688 635 567 475 334
Sones 2.5 2.5 2.5 2.5 2.0 2.0 2.0 Watts* 332.5 324.1 322.0 310.8 295.8 277.4 255.2
CSP-A780 1600 3.77 496.4
CFM 813 784 777 742 707 672 638 603 567 527
Sones 3.0 3.0 3.0 3.0 3.0 2.0 3.0 3.0 3.0 3.5 Watts* 496.4 493.0 492.2 488.0 467.5 453.1 441.8 423.1 407.2
CSP-A900 950 4.87 335
CFM 908 852 841 782 715 631
Sones 1.4 1.4 1.4 2.0 2.5 3.0 Watts* 335.0 288.6 286.0 272.7 259.9 245.5
CSP-A1050 1095 6.65 468.8
CFM 1182 1110 1093 1013 922 832 743
Sones 2.5 2.5 2.5 2.5 2.5 2.5 2.5 Watts* 468.8 455.9 453.3 440.8 424.9 411.0 399.2
CSP-A1410 1450 7.80 870.8
CFM 1584 1543 1533 1483 1439 1395 1345 1293 1238 1181
Sones 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 4.0 4.0 Watts* 870.8 837.9 829.9 788.2 751.0 728.3 696.3 661.8 628.8 595.9
CSP-A1550 1610 8.32 912.8
CFM 1672 1618 1604 1543 1484 1427 1367 1307 1240 1172
Sones 5.0 4.5 4.5 4.5 4.5 4.0 4.0 4.5 4.5 4.5 Watts* 912.8 877.4 868.4 829.3 802.9 778.0 744.3 710.7 679.1 647.4
CSP-A1750 1130 6.60 599.8
CFM 1842 1768 1749 1619 1464 1284 1032 772 484
Sones 5.0 5.0 5.0 4.5 4.0 4.0 3.5 3.0 3.0 Watts* 599.8 570.5 563.0 515.0 470.9 420.3 366.1 317.2 276.5
CSP-A2150 1100 7.80 760.8
CFM 2249 2175 2156 2044 1900 1701 1424 1114
Sones 5.0 4.5 4.5 4.0 4.0 4.0 3.0 3.0 Watts* 760.8 731.5 724.0 679.7 622.7 544.0 459.7 382.3
CSP-A3600 1100 7.10 1313.7
CFM 3778 3653 3622 3460 3280 3091 2844 2551 2232 1750
Sones 5.0 5.0 5.0 5.0 4.5 4.0 4.0 4.0 3.5 3.5 Watts* 1313.7 1253.3 1238.3 1160.0 1084.0 1041.5 971.1 871.9 766.5 649.5
*Amp and Watt draw is approximate and may vary based on motor manufacturer. Below performance is for 115V.
Model CSP-A Premium Inline Cabinet Fan
Performance certified is for model CSP inline for installation type D: Ducted inlet, Ducted outlet. Performance ratings include the effects of a backdraft damper.
Speed (rpm) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in spherical fan sones at 5 ft (1.5m) in a spherical free field calculated per Annex B of AMCA 311. Values shown are for installation type D: ducted inlet spherical fan sone levels. Ratings do not include the effect of duct end correction. Ratings are based on 10 ft of insulated duct.
Model SP 50 Cycle Performance
Model RPM Amps* Max.
Input
Watts*
CFM / Static Pressure in Inches of wg.
0.000 0.050 0.100 0.125 0.150 0.250 0.375 0.500
SP-A110
(50 Hertz Motor)
950 0.29 49
CFM 119 115 110 106 103 88
Sones 1.3 1.3 1.2 1.2 1.3 1.6
SP-A190
(50 Hertz Motor)
1400 0.65 113
CFM 216 206 197 192 187 167 133
Sones 3.2 3.0 2.8 2.9 2.9 3.1 3.4
SP-A290
(50 Hertz Motor)
1050 0.36 81
CFM 329 315 302 296 290 262 222 164
Sones 3.2 3.3 3.3 3.3 3.4 3.7 4.0 4.9
SP-A390
(50 Hertz Motor)
1350 0.67 135
CFM 410 402 395 392 387 368 345 325
Sones 5.4 5.4 5.4 5.4 5.5 5.7 6.0 6.3
SP-A510
(50 Hertz Motor)
900 1.65 224
CFM 447 425 400 388 376 315 159
Sones 3.7 3.5 3.3 3.3 3.3 3.1 2.6
SP-A780
(50 Hertz Motor)
1334 1.65 348
CFM 677 659 642 633 625 591 544 493
Sones 8.8 8.9 8.8 8.7 8.6 8.2 8.1 8.1
SP-A1050
(50 Hertz Motor)
950 3.15 420
CFM 990 945 905 886 867 769 531
Sones 7.2 7.0 6.8 6.8 6.8 6.6 6.5
SP-A1550
(50 Hertz Motor)
1340 4.3 818
CFM 1337 1314 1290 1279 1266 1211 1161 1112
Sones 11.1 10.7 10.6 10.6 10.6 10.5 11.6 13.5
SP-B90
(50 Hertz Motor)
700 0.325 50
CFM 102 97 92 88 86 75 59 45
Sones 1.9 2.2 2.6 2.7 2.7 3.0 3.6 4.1
SP-B110
(50 Hertz Motor)
950 0.57 80
CFM 133 124 114 110 107 97 95 94
Sones 2.0 2.0 2.1 2.2 2.2 2.4 2.7 2.8
SP-B150
(50 Hertz Motor)
1050 0.85 129
CFM 160 158 156 155 155 154 152 149
Sones 3.0 3.1 3.3 3.3 3.4 3.7 4.3 4.5
SP-B200
(50 Hertz Motor)
1100 1.1 173
CFM 197 196 195 194 194 191 187 184
Sones 4.4 4.7 4.6 4.7 4.9 5.1 5.6 5.8
Model SP Dimensions
SP-A A B C D E Designer Grille
Decorative Grille
Unit Weight
50, 70, 90 131⁄4 (337)
105⁄8 (270)
(229)
(152)
147⁄8 x 131⁄4 (378 x 337)
151⁄4 (387) square
(5)
110, 125, 190 131⁄4 (337)
105⁄8 (270)
(229)
(203)
(152)
(8)
200, 250, 290, (356)
117⁄8 (302)
111⁄4 (286)
(203)
(203)
(11)
410, 510 18 (457)
143⁄8 (365)
141⁄2 (368)
(203)
(203)
193⁄8 x 163⁄8 (492 x 416)
(14)
710, 780 18 (457)
143⁄8 (365)
141⁄2 (368)
(254)
(203)
193⁄8 x 163⁄8 (492 x 416)
(15)
900, 1050, 1410, 1550
233⁄4 (603)
143⁄8 (365)
141⁄2 (368)
183⁄4 (476)
(203)
25 x 163⁄8 (635 x 416)
(25)
Outlet connection width is 1 in. (25 mm) - Mounting bracket width is 1½ in. (38 mm).
SP-B A B C D E Designer Grille
Decorative Grille
Unit Weight
50, 70 & 80 137⁄8 (352)
111⁄2 (292)
(178)
(152)
11⁄4 (32)
147⁄8 x 131⁄4 (378 x 337) 151⁄4 (387) square
(4)
90, 110, 150, 137⁄8 (352)
111⁄2 (292)
(152)
(152)
11⁄4 (32)
147⁄8 x 131⁄4 (378 x 337)
(5)
All dimensions are in inches (millimeters) and weight in pounds (kilograms). Mounting bracket width is 1½ in. (38 mm). For complete dimensional information, see CAPS submittal drawings.
For uses in countries with 50 cycle (50 Hz) power, Greenheck offers the same reliability and performance for ceiling mounted exhaust fans model SP.
• Same dimensions and outlet options
• Performance shown in 50 cycle RPMs
• Full-line of grille and discharge accessories available
A B
C D
E
AB
CD
E
*Note: Amp and Watt draw is approximate and may vary based on motor manufacturer. Below performance is for 115V.
AB
C D
E
SP-A 110-510, 710, 780
SP-A (double wide) 700, 900-1550
SP-B 50-200
B
C
A
E
D
SP-A 50-90
Model CSP 50 Cycle Performance
Model RPM Amps* Max Input
Watts*
CFM / Static Pressure in Inches of wg
0.000 0.050 0.100 0.125 0.150 0.250 0.375 0.500 0.625
CSP-A110
(50 Hertz Motor)
950 0.31 51
CFM 124 116 112 110 109 102 77
Sones 1.1 1.1 1.1 1.1 1.1 1.3 1.3
CSP-A190
(50 Hertz Motor)
1400 0.55 100
CFM 215 202 198 180 159 121
Sones 2.3 2.0 2.2 2.7 2.9 3.0
CSP-A390
(50 Hertz Motor)
1350 0.665 144
CFM 412 400 397 382 363 339 324 309
Sones 2.8 2.7 2.8 3.2 3.7 4.7 5.5 6.5
CSP-A780
(50 Hertz Motor)
1334 1.885 405
CFM 685 656 648 609 562 520 481
Sones 5.0 4.9 4.8 4.7 4.6 4.7 4.9
CSP-A1050
(50 Hertz Motor)
950 3.325 455
CFM 1079 1031 982 957 934 841 655
Sones 6.3 6.3 6.0 5.9 5.9 6.0 5.5
CSP-A1550
(50 Hertz Motor)
1340 4.16 830
CFM 1391 1326 1311 1240 1171 1098 1019 929
Sones 7.5 7.4 7.4 7.3 7.4 7.3 7.3 7.2
CSP-B110
(50 Hertz Motor)
950 0.57 80
CFM 103 102 100 99 99 98 97 96 93
Sones 2.0 1.9 2.0 2.1 2.1 2.3 2.6 2.7 3.1
CSP-B150
(50 Hertz Motor)
1050 0.85 129
CFM 151 150 149 149 149 148 148 145 142
Sones 2.5 2.7 2.7 2.7 2.7 2.9 3.1 3.4 3.6
CSP-B200
(50 Hertz Motor)
1100 1.1 173
CFM 186 185 184 183 183 182 180 178 175
Sones 3.4 3.7 3.6 3.7 3.7 4.0 4.1 4.1 4.3
Model CSP Dimensions
CSP-A A B C D E F G Unit Weight
110, 125, 190 131⁄4 (337)
105⁄8 (270)
(229)
(203)
(152)
(305)
(235)
(7)
200, 250, 290, (356)
117⁄8 (302)
111⁄4 (286)
(203)
(203)
127⁄8 (327)
(254)
(10)
410, 510 18 (457)
143⁄8 (365)
141⁄2 (368)
(203)
(203)
167⁄8 (429)
131⁄4 (337)
(16)
700 235⁄8 (600)
115⁄8 (295)
115⁄8 (295)
191⁄2 (495)
(203)
225⁄8 (575)
101⁄2 (267)
(15)
710, 780 18 (457)
143⁄8 (365)
141⁄2 (368)
(254)
(203)
167⁄8 (429)
131⁄4 (337)
(16)
900, 1050, 1410, 1550
233⁄4 (603)
143⁄8 (365)
141⁄2 (368)
183⁄4 (476)
(203)
225⁄8 (575)
131⁄4 (337)
(27)
1750, 2150 35 (889)
143⁄4 (375)
143⁄4 (375)
(711)
(152)
323⁄4 (832)
(330)
(31)
3600 451⁄2 (1156)
161⁄2 (419)
161⁄2 (419)
(1016)
(279)
431⁄4 (1099)
145⁄8 (371)
(55)
CSP-B A B C D E F G Unit Weight
110, 150, 200 137⁄8 (352)
111⁄2 (292)
(178)
(152)
11⁄4 (32)
101⁄4 (260)
31⁄4 (83)
101⁄4 (5)
All dimensions are in inches (millimeters) and weight in pounds (kilograms). Inlet and outlet connection widths are 1 in. (25 mm) - Mounting bracket width is 1½ in. (38 mm). For complete dimensional information, see CAPS submittal drawings.
For uses in countries with 50 cycle (50 Hz) power, Greenheck offers the same reliability and performance for inline cabinet fans model CSP.
• Same dimensions and outlet options
• Performance shown in 50 cycle RPMs
• Full line of discharge accessories available
A
E D
C
B
F
G
A B
C D
E
F Inlet
G
C
AB
D - diameterInlet FxG
E
*Note: Amp and Watt draw is approximate and may vary based on motor manufacturer. Below performance is for 115V.
CSP-A 110-510, 710, 780
CSP-A (double wide) 700, 900-3600
CSP-B
Polypropylene
Steel AluminumSteel
Wheel Options
Greenheck’s ceiling and cabinet fans (models SP and CSP) deliver high performance from a forward-curved wheel. The forward-curved wheel design offers both high-efficiency and low sound. Fan wheels are constructed of polypropylene or steel as standard, and most models offer an aluminum wheel option.
• Level A models utilize steel or polypropylene (standard) wheel construction depending on size.
• Level B models are standard with a polypropylene wheel.
Accessories
SP-B Replacement Power Packs Save installation and down time by replacing the entire power pack instead of individual components. Available as a replacement part on all current and previous SP-B models.
Designer - standard Available in white polystyrene finish, with or without motion detector with time delay. Standard on SP models A50-A390 and B50-B200.
Aluminum White enamel finish standard for models A410-A1550.
Optional for models A50-A390 and B50-B200.
Decorative White plastic finish, with or without light, motion detector with time delay.
Optional for models A50-A390 and B50-B200.
Stainless Steel Polished stainless steel finish optional for models A50-A390 and B50-B200.
Contractor 4 Packs
Save installation time and labor by installing the housing first, then installing the internal components after sheetrocking, plastering and finishing are done.
Housings are packaged in one box, power assemblies and grilles are packaged in another box. Components are shipped to coincide with the phase of your project.
(Model SP-B only).
Custom Molded polystyrene available in an array of colors.
Includes all the same accessory options as the standard grilles. For more information on the many ways this grille option can be used, please contact your Greenheck representative.
Customized Grille Lens Lenses can be customized with formed shapes or logos. Contact your Greenheck representative for details.
s
Greenheck’s fan and light combinations include either a prismatic or a frosted lens and either compact fluorescent or incandescent lamps. Our unique light box is manufactured with a reflective material to increase the light given off by either type of lamp. UL Listed for above bathtub and showers with GFCI branch protected circuit.
Model SP-A, sizes 50 - 390 Model SP-B, sizes 50 - 200
Note: When selecting a lighted grille it will add height to the fan assembly. See CAPS drawings for exact values.
Lighted Grille Options
Prismatic Lens The prismatic lens design provides approximately 25% more light than a traditional frosted lens. The lens may be easily removed to replace light bulbs.
Frosted Lens The frosted lens option is a traditional design which lets approximately 80% of light through the lens. The lens may be easily removed to replace light bulbs.
Note: Compact Fluorescent light bulbs are ENERGY STAR® certified. Not all fan/lighted grill options are ENERGY STAR® certified. See CAPS for availability.
Accessories
Grille Options
• Replaces the standard square discharge duct-connector and damper
• Uses existing mounting holes
• RDC-6 includes a damper (polypropylene construction)
• RDC-8 does not include a damper (galvanized construction)
Filters
Fans used in most applications will collect airborne dirt on wheels and motors over time, even where air is not excessively dirty. Accumulations of dirt on the fan wheel will sharply reduce performance and cause imbalance.
Dirt buildup on the motor can cause it to overheat. All of these conditions will shorten the life of the fan. To help reduce this accumulation, washable aluminum mesh filters are available to trap dirt before it enters the fan.
These filters should be regularly cleaned to maintain performance. The Filter Loss Chart shows the effect the filter will have on performance. To determine the added resistance, divide the desired CFM by the filter area (ft2).
This will give ft/min. Use this with the filter loss chart to get the added resistance.
Filters reduce sound levels, in addition to reducing dirt accumulations on the motor and wheel.
Mesh Filter
SP
Grille
Filter Loss Chart
SP Model Filter Model
Filter Area (ft2)Designer
Grille *Metal Grille
SP-A50 - A190 F-200 F-210 0.739
SP-B50 - B200, A200 - A390 F-200 F-220 0.911
SP-A410 - A510
SP-A710 - A780 NA F-250 1.518
SP-A900 - A155 NA F-260 2.078
*Aluminum or Stainless Steel Grille.
(See pg. 24 for filter loss graph)
Model For use with sizes:
473324
B50-B200
A50-A90
A110-A190*
6x4 - Transition
Duct Reducer
• Reduces duct from 6 to 4 inches.
• Durable plastic construction
RDC
Model Use with sizes: Diameter
RDC-6 A110-A190 6 (152)
RDC-8 A200-A510 8 (203)
All dimensions shown in inches (millimeters).
Unit Size A B
B50-B200 41⁄2 (114) 155⁄8 (397)
A50-A190 51⁄2 (140) 145⁄8 (371)
A200-A390 63⁄4 (171) 151⁄2 (394)
A410, A510, A710, A780 91⁄4 (235) 195⁄8 (498)
A700 51⁄2 (140) 251⁄8 (638)
A900, A1050, A1410, A1550 91⁄4 (235) 253⁄8 (645)
A1750, A2150 91⁄4 (235) 363⁄4 (933)
A3600 91⁄4 (235) 485⁄8 (1235)
All dimensions shown in inches (millimeters).
Hanging Vibration Isolators
Vibration isolator kits are available for suspended installations. Kits include all hardware necessary to mount one unit, with the exception of 1/4-20 threaded rod to be supplied by others.
Fan mounting brackets include prepunched mounting holes for ease of installation.
Model RDC -
Round Duct Connector
Accessories
6 5/32 (157)
4 15/32 (114)
3 15/16 (100)
A B
1/4-20 hanging support rod by others
All dimensions shown in inches (millimeters).
* Used in conjunction with RDC-6
RDC-6
Ceiling Radiation Damper
The National Fire Protection Association (NFPA) Standard 90A requires openings in fire rated ceiling assemblies to be protected by appropriately rated ceiling radiation dampers. As a result, many local codes require fans installed in fire rated ceilings to be protected by dampers which are insulated against both heat and flame.
Greenheck's ceiling radiation dampers are also Warnock Hersey Listed to go into a one hour combustible (wood) installation. Greenheck's UL Classified ceiling radiation dampers are rated for three hours of fire resistance in a noncombustible installation.
Model SP-A
Model SP-B
SP-B Fan
Hanging Vibration Isolation
Ceiling Radiation Damper
Fire Rated Ceiling
Grille
3 in.
AxB
SP Model CRD Length (A) Width (B) Height UL W.H.
A50 - A190 310 131⁄2 (343)
111⁄8 (283)
(76)
310L 310
B50 - B200 A200 - A390 320 143⁄8
(365) 121⁄4 (311)
(76)
320L 320
A410 - A510 A710 - A780 350 187⁄16
(468) 1415⁄16 (379)
(76) 350 350
A700 700 243⁄16 (614)
121⁄4 (311)
(76) 700 NA
A900 - A1550 360 243⁄16 (614)
1415⁄16 (379)
(76) 360 360
All dimensions shown in inches (millimeters). Add an “L” to all CRD models if fan & light combo is used. *CRD is approximately 1/4 inch (6 mm) larger than housing dimension. (See Installation, Operation and Maintenance Manual)
SP-A Fan
Hanging Vibration Isolation
Ceiling Radiation Damper
Fire Rated Ceiling
GrilleAxB
3 in.
Accessories
Model RJ - Pitched Roof Cap
• Steel construction with black enamel finish
• Integral flashing flange
• Built-in birdscreen and damper
Model Use for sizes: A B C D E Throat
RJ-4 80, 80L, C50,
B50-B80
(279)
91⁄4 (235)
81⁄4 (210)
55⁄16 (135)
41⁄2 (114)
4 (102) diameter
RJ-6x9 110, 100L B90-B200, A50-A390
183⁄4 (476)
141⁄4 (362)
141⁄2 (368)
103⁄8 (264)
61⁄2 (165)
6 x 9 (152 x 229)
RJ-10x10 A410-A1050 181⁄2 (470)
271⁄2 (699)
153⁄4 (400)
235⁄8 (600)
91⁄2 (241)
10 x 10 (254 x 254)
All dimensions shown in inches (millimeters).
RJ-4 and RJ-6x9 D C
B A
ERJ-4 and RJ-6x9
RJ-10x10
CD
E
A B
RJ-10x10
3.5 (89)
(254)
11.125 (283)
2.875 (73)
6.5 (165)
1.625 (42)
9.375 (238)
11.5 (292)5.125 (130)
3.375 (86)
All dimensions shown in inches (millimeters).
Model EL-10x3 -
Elbow Discharge with Grille
• Designed for installation under roof eaves
• Black epoxy finish (elbow and grille)
• Built-in damper
• SP and CSP sizes 50-290
Speed Controls
Speed controls may be used on model SP and CSP fans for manual adjustment of the fan’s performance (for final system balancing) or to control the fan’s output in confined spaces, such as conference or meeting rooms.
The fan can be adjusted to 60% of design airflow with a speed control.
This reduction in airflow and fan speed is also accompanied by a reduction in noise level. Solid state speed controls are available for a range of applications up to 15 amps. Speed controls can be used to operate more than one fan if the combined total amperage of the fans does not exceed the control rating.
Internal Mounting
Electrical Accessories
Dehumidistat
Dehumidistats are available with models SP and CSP fans to ventilate humid spaces. The sensor automatically detects excess humidity and activates a ventilation fan for control of excess condensation. There are automatic, manual, or air cycle modes. This can replace a single pole switch for control of a ventilating fan.
• Rated for 120V, 3A, 1/6 HP
• UL Listed
Note: All switch covers are standard white.
Other colors available upon request.
SPEED CONTROL INTERNAL AND/OR EXTERNAL MOUNTING OPTIONS
Model Voltage Rating
Amp Rating
Fan Sizes
50 70 80 90 110 125 150 190 200 250 290 390 410 510 700 710 780 900 1050 1410 1550 1750 2150 3600
6WSSC
115 - 127V
6 Amp I/E I/E I/E I/E I/E I/E I/E I/E I/E I/E I/E I/E I/E I/E I/E I/E I/E I/E No No No No No No
10WSSC
115 - 127V
10 Amp E E E E E E E E E E E E E E E E E E E E E E E No
15WSSC
115 - 127V
15 Amp E E E E E E E E E E E E E E E E E E E E E E E No
5W240 220 - 240V
5 Amp No No No *I/E I/E No I/E I/E *I/E No I/E I/E No I/E No No I/E No I/E No I/E No No No
8WSSC
220 - 240V
8 Amp No No No *E E No E E *E No E E No E No No E No E No E No No No
5W277 227V
5 Amp No No No No I/E I/E I/E I/E *I/E No No No No No No No No No No No No No No No
KEY:
E = External mounted only I/E = Available Internal and External Mounted
* Only available on the B-series (A-series is not available) No = Not available
NOTES: Speed controllers are not available for 208V applications. SP-C50 Speed Controller is shipped loose only.
All speed controller options listed in table are UL Listed.
Handy Box sizes are 2x4 for all options above except 10WSSC and 15WSSC, which are 4x4.
Motion Detectors
Motion detectors may be used with SP and CSP fans or fan and light combinations. Motion detectors use a passive infrared motion detector to automatically turn the fan on when a change in motion is sensed. They have a viewing area of 180 degrees, however they must be placed in the line-of-sight.
Grille Mounted Available on models SP-A50 through SP-A390 and SP-B50 through SP-B200.
• Rated for 115V
• UL Listed
Wall Mounted For use on fan or lights. Available shipped loose.
• Rated for 115V
• UL Listed
• Requires 2x4 handy box
• Time delay can be set for
30 seconds to 30 minutes in 5 minute increments
Switches
Switches may be used on model SP and CSP fans to enable manual control of your fan or fan and light combination.
1 Function Single pole rocker switch assembly
• Rated for 120-277V, 15A
• UL Listed
1 Function with Pilot Light
Single pole light combination switch assembly
• Rated for 120V, 15A
• UL Listed
2 Function
Two single pole combination switch assembly
• Rated for 120V, 15A
• UL Listed
Time Delay Switch
Time delay switches save energy by automatically turning off the fan or fan/ light combination unit. Activating the switch allows operation for an extended period of time. This switch includes four preset time delay settings of 10, 20, 30 and 60 minutes and off. This switch may be used with SP, CSP or fan/light combination fans.
Model Voltage Ratings Amp Rating
T-2.0 230/277V to 115 2.0 Amps
T-4.3 230/277V to 115 4.3 Amps
T-6.5 230/277V to 115 6.5 Amps
T-8.6 230/277V to 115 8.6 Amps
Transformers
Transformers are available for applications requiring voltage reduction. Selection is based on motor amperage. All transformers are shipped loose. See performance pages for motor amp ratings.
Electrical Accessories
Note: All switch covers are standard white.
Other colors available upon request.
Minimum Ventilation Control
This control contains a microprocessor that monitors the operation of the fan to make sure that the space is receiving the correct amount of ventilation per
ASHRAE 62.2
• 120V, 2.5A
• UL Listed
Discharge Accessories
Model WC - Hooded Wall Cap
(Round Connection)
• Aluminum construction - aluminum finish
• For outside wall applications
• Built-in birdscreen (not available on WC-4) and damper
Model Use with sizes A B C D E
WL-10x3 50-290 12 (305)
51⁄4
(133)
(254) 73⁄4
(197) 31⁄2
(89)
WL-18x6 390-1550 193⁄4
(502)
(203)
(457)
(229)
(152)
All dimensions shown in inches (millimeters).
B
ECA
DE
E B
C
A D
Model Use with sizes A B C D E
WC-4 C50 61⁄2
(165)
(152)
(101)
(101)
(127)
WC-6 B50-B200, 80, 80L
A50-A190, 110, 110L
(203)
(203)
(152)
41⁄8
(105)
(127)
WC-8 A200-A510 11
(279)
(279)
(203)
51⁄8
(130) 31⁄2
(89)
All dimensions shown in inches (millimeters).
Model WC - Hooded Wall Cap
(Square or Rectangular Connections)
• Steel construction with black enamel finish
• For outside wall applications
• Built-in birdscreen and damper
Model Use with sizes A B C D E F G
WC-10x3 50-290 51⁄2 (140)
123⁄4 (324)
31⁄2 (89)
101⁄4 (260)
111⁄8 (283)
41⁄4 (108)
(127)
WC-8x8 200-510 101⁄4 (260)
101⁄4 (260)
81⁄4 (210)
81⁄4 (210)
81⁄4 (210)
63⁄4 (171)
(127)
WC-18x8 700-1550 101⁄4 (260)
201⁄4 (514)
81⁄4 (210)
181⁄4 (464)
181⁄4 (464)
63⁄4 (171)
(127)
All dimensions shown in inches (millimeters).
D
A
G
C
B
E
F
Model Use with sizes A B C
BVE808 50-290 81⁄8
(206)
73⁄4 (197)
(102)
BVE128 390-510 12
(305)
73⁄4 (197)
(102)
BVE157 700-1050 155⁄8
(397)
73⁄4 (197)
(102)
All dimensions shown in inches (millimeters).
Model WL - Wall Louvered Discharge
• Anodized aluminum grille
• Built-in damper
• Not recommended for exterior applications exposed to severe weather conditions. An external wall louver is recommended for such applications.
Model BVE - Brick Vent
• Designed for…