36C24218B0555-003.pdf
PDF 1 MB Posted
- Attached to
- 528A7-17-720 REPLACE CANTEEN FREEZER/REPAIR SLAB | Federal contract opportunity
- Solicitation number
- 36C24218B0555
About this file
36C24218B0555 Construction Drawings - VA242-17-C-0162 Design Slab Renovation and MEP for Walk In Freezer.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24218B0555-0001001.pdf | ||
| 36C24218B0555-0001002.docx | DOCX document | |
| 36C24218B0555-0001000.docx | DOCX document | |
| 36C24218B0555-002.pdf | ||
| 36C24218B0555-001.docx | DOCX document | |
| 36C24218B0555-004.pdf | ||
| 36C24218B0555-000.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100% SUBMISSION
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEER
WATSON ENGINEERING, PC
1112 STATE ROUTE 434
OWEGO, NY 13827
0: 607-223-4334
CANTEEN FREEZER SLAB REPAIR
AND WALK-IN FREEZER
REPLACEMENT
SYRACUSE VAMC, RM CL06
528A7-17-720
Project Director
4-27-18 JWE MPLRevisions: Date:
TITLE PAGE
T101
CANTEEN FREEZER SLAB REPAIR
AND WALK-IN REPLACEMENT
SYRACUSE VAMC, NCO 2, BUILDING 1, ROOM CL06, SYRACUSE, NY 13210
CONTRACT NO: VA242-17-C-0162
PROJECT NO: 528A7-17-720
SHEET NUMBER
AD101
DRAWING INDEX
VICINITY: NTS
VICINITY MAPAERIAL MAP
T101
AERIAL: NTS
PROJECT LOCATION
PROJECT LOCATION
OCCUPANCY GROUP V
IBC 2015 (NYS)
APPLICABLE CODES
REINFORCING STEEL IBC 1908.4
CONCRETE FORMING ACI 318: 26.10.1 (b)
NFPA 101 - LIFE SAFETY (2018)
C.I.P. ANCHORS ACI 318: 17.8.2
SPECIAL INSPECTIONS
EXISTING FREEZER FOOTPRINT: 226 SQFT
PROPOSED FREEZER FOOTPRINT: 325 SQFT
CONSTRUCTION AREA FOOTPRINT: 845 SQFT
PROPOSED SLABS FOOTPRINT: 352 SQFT
PROJECT DATA
PROPOSED WALLS FOOTPRINT: 42 SQFT
SEISMIC REGION C
PG-18-10 - VA DESIGN MANUALS
DRAWING TITLE
TITLE PAGE
A501
S101
S501
S502
M102
M601
ED101
E101
NOTESG101
DEMOLITION PLAN
DOOR SCHEDULE AND DETAILS
STRUCTURAL PLAN
STRUCTURAL DETAILS
STRUCTURAL SECTION VIEWS
PROPOSED MECHANICAL REFRIGERATION PLAN
MECHANICAL SCHEDULES, NOTES, AND DETAILS
PROPOSED ELECTRICAL PLAN
FP101
ELECTRICAL DEMOLITION PLAN
FIRE PROTECTION PLAN
A101 ARCHITECTURAL PLAN
M101 MECHANICAL DUCTWORK PLAN
NFPA70 - NATIONAL ELECTRIC CODE (2017)
AutoCAD SHX Text
OCCUPANCY TYPE
AutoCAD SHX Text
APPLICABLE CODES
AutoCAD SHX Text
SPECIAL INSPECTIONS
AutoCAD SHX Text
SQUARE FOOTAGES
AutoCAD SHX Text
SEISMIC REGION
GENERAL CONSTRUCTION NOTES:
1. UNLESS INDICATED OTHERWISE, ALL PROPOSED WORK ON
THESE DRAWINGS SHALL BE CONSIDERED NEW
CONSTRUCTION, USING NEW MATERIALS AND EQUIPMENT.
2. INSTALL ALL MATERIALS IN ACCORDANCE WITH
MANUFACTURES RECOMMENDATIONS.
3. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS
AND CONDITIONS OF EXISTING CONSTRUCTION AND
REPORT ANY INCONSISTENCIES TO THE ENGINEER
BEFORE PROCEEDING WITH WORK AFFECTED BY SUCH
INCONSISTENCIES. THE CONTRACTOR IS RESPONSIBLE
FOR OBTAINING THE INTENT OF THE DESIGN AS SHOWN
ON THE PLANS. ACTUAL CONDITIONS SHALL GOVERN
OVER WRITTEN DIMENSIONS, WRITTEN DIMENSIONS SHALL
GOVERN OVER ACTUAL DRAWING REPRESENTATION.
ATTEMPTS TO UTILIZE SCALING OR ELECTRONIC MEANS
TO DETERMINE QUANTITY TAKE-OFF MAY BE AFFECTED BY
NOT TO SCALE ITEMS. THE ENGINEER IS NOT
RESPONSIBLE FOR, AND SHALL NOT BE HELD LIABLE FOR
THE ACCURACY OF RESULTS OF SUCH TAKE OFFS.
4. ALL WORK ON THIS PROJECT SHALL BE PERFORMED IN
ACCORDANCE WITH APPLICABLE FEDERAL, STATE, AND
LOCAL LAWS, RULES AND REGULATIONS CONCERNING
CONSTRUCTION SAFETY AND HEALTH.
5. THE CONTRACTOR SHALL NOT INSTALL ITEMS AS SHOWN
ON THE PLANS WHEN IT IS OBVIOUS THAT FIELD
CONDITIONS ARE DIFFERENT THAN SHOWN IN THE
DESIGN. SUCH CONDITIONS SHALL BE BROUGHT TO THE
ATTENTION OF THE ENGINEER, IN THE EVENT THE
CONTRACTOR DOES NOT NOTIFY THE ENGINEER, THE
CONTRACTOR ASSUMES FULL RESPONSIBILITY AND
EXPENSE FOR ANY REVISIONS NECESSARY. THE
ENGINEER OF RECORD SHALL NOT BE RESPONSIBLE FOR
THE CONTRACTOR'S FAILURE TO CARRY OUT THE
CONSTRUCTION WORK IN ACCORDANCE WITH THE
CONTRACT DOCUMENTS, NOR SHALL THE ENGINEER BE
REQUIRED TO SUPERVISE THE CONDUCT OF THE WORK
OR THE CONSTRUCTION PROCEDURES AND SAFETY
PROCEDURES FOLLOWED BY THE CONTRACTOR OR THE
SUBCONTRACTOR OR THEIR RESPECTIVE EMPLOYEES OR
BY ANY OTHER PERSON A THE JOB SITE OTHER THAN
THAT OF THE ENGINEER'S EMPLOYEES.
6. CONTRACTOR AGREES TO ASSUME SOLE AND COMPLETE
RESPONSIBILITY FOR THE JOB SITE CONDITIONS DURING
THE COURSE OF CONSTRUCTION OF THIS PROJECT,
INCLUDING SAFETY OF ALL PERSONS AND PROPERTY;
THAT THIS REQUIREMENT SHALL APPLY 24 HOURS A DAY
AND NOT BE LIMITED TO NORMAL WORKING HOURS. ANY
DAMAGE TO PROPERTY AND/OR ITEMS ON PROPERTY,
EXISTING OR NEW, SHALL BE REPAIRED AND/OR PAID FOR
BY THE RESPONSIBLE PARTY.
7. CONTRACTOR SHALL NOT INTERFERE WITH THE DAILY
OPERATIONS OF THE HOSPITAL, IT'S PERSONNEL, OR IT'S
CUSTOMERS AT ANY POINT DURING THE CONSTRUCTION
PROCESS.
8. CONCRETE F'c = 5,000 P.S.I. @ 28 DAYS WITH 5.0% - 9.0%
ENTRAINED AIR.
9. REINFORCING STEEL TO BE WIRE TIED AND HELD IN PLACE
WITH PLASTIC CHAIR AND REBAR STIRRUPS AS NEEDED.
10. ALL STEEL REINFORCEMENT SHALL BE ASTM A615 GRADE
60.
11. ALL STEEL REINFORCEMENT COVER SHALL BE 3" UNLESS
OTHERWISE NOTED.
12. INFECTION CONTROL NOTES LOCATED IN SPEC SECTION
01 35 26.
GENERAL NOTES AND SPECIFICATION FOR WALK-IN FREEZER
CONSTRUCTION
1. EACH PANEL SHALL CONSIST OF INNER AND OUTER METAL
SKINS, A 4” INSULATION CORE, AND BE EQUIPPED WITH
CAM-ACTION LOCKING DEVICES. THE LOCKING DEVICES
SHALL BE OPERABLE FROM INSIDE THE WALK-IN.
CONSTRUCTION SHALL BE AS APPROVED BY THE NSF
INTERNATIONAL AND SHALL BEAR THE NSF® SEAL OF
APPROVAL. ALL PANELS SHALL BE CONNECTED TO ONE
ANOTHER (E.G. TONGUE AND GROOVE) THROUGH THE
CORE INSULATION OF THE ADJACENT PANEL. THE
RESULTANT CONNECTION JOINT SHALL BE SEALED AT
BOTH SIDES BY DOUBLE BARRELED NSF® APPROVED
GASKETS. IN ORDER TO AVOID FUTURE SWELLING AND
MOLD FORMATION, NO WOOD SHALL BE PERMITTED IN THE
MANUFACTURE OF THE TONGUE AND GROOVE PANEL
PROFILE.
2. WALL PANEL INSULATION SHALL BE 4” THICK, HIGH
QUALITY, EXTRUDED POLYSTYRENE OR FOAMED-IN-PLACE
POLYURETHANE, MODULAR PANELS JOINED BY NOT LESS
THAN THREE (3) CAM-LOCK TYPE OR OTHER EQUIVALENT
DEVICES; GASKET TO SEAL BETWEEN PANELS; R-32 OR
GREATER.
3. EXTRUDED POLYSTYRENE WALLS: ALL WALL INSULATION
SHALL BE 4” THICK, HIGH QUALITY, RIGID, EXTRUDED
POLYSTYRENE, 1.6 LB DENSITY. K FACTOR OF NOT MORE
THAN 0.125 AND AN R FACTOR OF NO LESS THAN 8.1 PER
INCH, INITIAL FRESH R-32.4 MINIMUM TOTAL WALL R
FACTOR. VAPOR TRANSMISSION SHALL BE LESS THAN 1
PERM AND FOAM CORE MATERIAL MUST MEET UL 5 FLAME
SPREAD RATING WITH AVERAGE SMOKE RATING LESS
THAN 165 (UL 723 TEST).
4. FOAMED-IN-PLACE POLYURETHANE WALLS: ALL WALL AND
CEILING INSULATION SHALL BE 4" THICK, HIGH QUALITY
FOAMED IN- PLACE POLYURETHANE, 2.2 LB. DENSITY. K
FACTOR OF NOT MORE THAN .125 AND AN R FACTOR OF
NO LESS THAN 8 PER INCH, INITIAL FRESH R-32 MINIMUM
TOTAL WALLS R FACTOR. VAPOR TRANSMISSION SHALL BE
LESS THAN 1 PERM AND FOAM CORE MATERIAL MUST
MEET: UL FOAM CORE 25 FLAME SPREAD RATING WITH
AVERAGE SMOKE RATING LESS THAN 450. (ASTM E-84)
5. CEILING: PANEL INSULATION SHALL BE 4” THICK, HIGH
QUALITY, EXTRUDED POLYSTYRENE OR FOAMED-IN-PLACE
POLYURETHANE, MODULAR PANELS JOINED BY NOT LESS
THAN THREE (3) CAM-LOCK DEVICES OR OTHER
EQUIVALENT DEVICES; GASKET TO SEAL BETWEEN
PANELS; R-32 OR GREATER.
6. EXTRUDED POLYSTYRENE CEILINGS: ALL CEILING
INSULATION SHALL BE 4” THICK, HIGH
QUALITY, RIGID, EXTRUDED POLYSTYRENE, 1.6 LB
DENSITY. K FACTOR OF NOT MORE THAN 0.125 AND AN R
FACTOR OF NO LESS THAN 8.1 PER INCH, INITIAL FRESH
R-32.4 MINIMUM TOTAL WALL R FACTOR. VAPOR
TRANSMISSION SHALL BE LESS THAN 1 PERM AND FOAM
CORE MATERIAL MUST MEET UL 5 FLAME SPREAD RATING
WITH AVERAGE SMOKE RATING LESS THAN 165 (UL 723
TEST).
7. FOAMED IN-PLACE POLYURETHANE CEILINGS: ALL WALL
AND CEILING INSULATION SHALL BE 4” THICK, HIGH
QUALITY, FOAMED IN-PLACE POLYURETHANE, 2.2 LB
DENSITY. K FACTOR OF NOT LESS THAN 0.141 AND AN
R-FACTOR OF NOT LESS THAN 7.1 PER INCH, INITIAL FRESH
R-28.4 MINIMUM TOTAL WALL R FACTOR. VAPOR
TRANSMISSION SHALL BE LESS THAN 1 PERM AND FOAM
CORE MATERIAL MUST MEET: UL FOAM CORE 25 FLAME
SPREAD RATING WITH AVERAGE SMOKE RATING LESS
THAN 450. (ASTM E-84).
8. EXTERIOR FINISH: 26 GUAGE STUCCO EMBOSSED
GALVANIZED STEEL.
9. INTERIOR WALL PANEL FINISH: 26 GUAGE STUCCO
EMBOSSED GALVANIZED STEEL.
10. CEILING PANEL FINISH: 26 GUAGE STUCCO EMBOSSED
GALVANIZED STEEL.
11. FLOOR FINISH: 22 GAUGE SMOOTH STAINLESS STEEL.
12. PANEL DIMENSIONS-MAXIMUM PANEL WIDTH: 47”.
13. FLOOR: PREFABRICATED FLOOR PANELS MUST HAVE R-28
RATING OR GREATER; ALLOWABLE STATIONARY LOAD OF
600 POUNDS PER SQ. FT. WHEN PLACED ON A
CONTINUOUS CONCRETE SLAB-SEE STRUCTURAL
DRAWINGS FOR ADDITIONAL INFORMATION.
14. DOORS: R-32 OR GREATER. DOOR SHALL BE FLUSH
MOUNTED, POSITIONED AND HINGED; PROVIDED WITH
SUITABLE SWEEP AND MAGNETIC GASKETS, DOOR
CLOSER, ONE PRE-WIRED VAPOR PROOF LIGHT FIXTURE,
LIGHT SWITCH WITH PILOT LIGHT, DIAL THERMOMETER,
MANUAL INTERNAL LOCK OVERRIDE, CHROME PLATED
CAM LIFT HINGES, CHROME PLATED DOOR LATCHES WITH
STRIKE.
14.1. FREEZER DOORS SHALL HAVE A UL APPROVED
HEATER WIRE ON ALL FOUR SIDES. FREEZER DOORS
SHALL INCLUDE A HEATED PRESSURE RELIEF PORT IN
THE ADJACENT PANEL.
14.2. HINGES: ONE CAM-LIFT SPRING ASSISTED
SELF-CLOSING HINGE AND ONE CAM-LIFT HINGE.
14.3. HANDLE: KASON OR COMPONENT EQUIVALENT WITH
STEEL REINFORCED PLATE INSIDE DOOR PANEL, PULL
DOOR HANDLE WITH CYLINDER LOCK, PADLOCK HOLE
AND INTERIOR SAFETY RELEASE; PROVIDE COMMON
KEY FOR ALL WALK-IN DOORS.
14.4. DOOR CLOSER: KASON OR SPRING ASSISTED
COMPARABLE.
14.5. VISION PANEL: NOT LESS THAN 150 SQUARE INCHES;
HEATED; TRIPLE PANE GLASS.
14.6. KICK PLATE: 1/8” THICK ALUMINUM DIAMOND-TREAD
PLATE ON BOTH SIDES OF DOOR AND FRAME; EXTEND
FROM DOOR BOTTOM TO DOOR HANDLE; SECURE
WITH STAINLESS STEEL SCREWS; SEAL PERIMETER
WITH SILICONE.
14.7. LED LIGHT - SINGLE LIGHT FIXTURE.
14.8. INTERNAL RAMP: 30” DEEP, 22 GAUGE STAINLESS
STEEL, EXTRUDED
POLYSTYRENE; THREE - 8” NON-SKID STRIPS, NSF
APPROVED.
14.9. EXTERNAL RAMP: 30” DEEP, ¼” STEEL DIAMOND TREAD
PLATE, PAINTED SAFETY YELLOW.
14.10. ELECTRICAL: WIRE SURFACE MOUNTED ON DOOR
PANEL TO JUNCTION BOX TOP OF DOOR.
14.11. THERMOMETER: INSTALLED FLUSH-MOUNT ON HINGE
SIDE OF DOOR PANEL, DIGITAL WITH ALARM.
15. PRESSURE RELIEF PORT: PROVIDE HEATED RELIEF PORT
LOCATED IN EXPOSED WALL
16. LIGHTS: LED, SINGLE BULB.
17. SPRINKLER HEADS: CUT HOLES FOR EXISTING SPRINKLER
HEADS; PROVIDE STAINLESS STEEL TRIM CAP AND SEAL
HOLES.
18. INSTALLATION: MANUFACTURER APPROVED DEALER
SHALL BE RESPONSIBLE FOR INSTALLATION.
MANUFACTURER SHALL SUPPLY A SET OF INSTALLATION
INSTRUCTIONS AND LAY-OUT DRAWINGS. ALL PANELS
SHALL HAVE PANEL IDENTIFICATION CORRESPONDING
WITH THE LAY-OUT DRAWING TO FACILITATE RAPID AND
ACCURATE FIELD ERECTION.
19. REFRIGERATION SYSTEM: COMPLETE OPERATING SYSTEM
CONSISTING OF A CONDENSING UNIT AND AN
EVAPORATOR COIL. SEE SIZING CALCULATIONS FOR UNIT
REQUIREMENTS.
19.1. CONDENSING UNIT: AIR-COOLED CONDENSER WITH
BALL-BEARING PERMANENTLY LUBRICATED FAN
MOTOR. CONDENSER FAN MOTORS OF UNDER 1 H.P.
MUST USE ELECTRONICALLY COMMUTATED (EC)
MOTORS OR PERMANENT SPLIT CAPACITATOR-TYPE
(PSP) MOTORS; SPLASH LUBRICATION SYSTEM USING
MOBIL EAL ARCTIC 22 POLYESTER SYNTHETIC
REFRIGERATION OIL; OIL SIGHT GLASS; REMOVABLE
OIL DRAIN PLUG; LABEL INDICATING OIL USED;
HIGH/LOW PRESSURE CONTROL; SUCTION LINE
FILTER; SUCTION AND DISCHARGE SERVICE VALVES
AND COPPER/BRASS VIBRATION ISOLATORS;
RECEIVER WITH FUSIBLE PLUG OR RELIEF VALVE;
LIQUID LINE SHUT-OFF VALVE; SIGHT GLASS;
MOLECULAR SIEVE FILTER DRYER; MAIN POWER
SUPPLY FUSED DISCONNECT SWITCH.
19.2. EVAPORATOR COIL: FORCED CONVECTION STYLE;
MATCH TO CONDENSING UNIT AND SUSPEND WITH AIR
DISCHARGED PARALLEL TO THE CEILING; LIFETIME
SEALED MOTORS WITH INHERENT MOTOR
PROTECTION; EVAPORATOR FAN MOTORS OF UNDER 1
HP AND LESS THAN 460 VOLTS MUST USE
ELECTRONICALLY COMMUTATED (EC) MOTORS;
ENCLOSE COIL SECTION AND FANS WITHIN ALUMINUM
HOUSING. PROVIDE ELECTRIC HEATER AND
CONTROLS FOR POSITIVE AUTOMATIC DEFROST.
INSTALLATION SHALL HANG USING PLASTIC OR NYLON
FASTENERS; SPREAD COIL WEIGHT EVENLY OVER
CEILING PANELS; SUPPORT LONG SPAN CEILING
PANELS AS REQUIRED.
DEMOLITION NOTES:
1. REMOVAL AS DESCRIBED HEREIN SHALL BE
ACCOMPLISHED WITHOUT STORING EXCESSIVE
QUANTITIES OF ANY MATERIALS, RUBBISH, DIRT, DEBRIS,
OR WASTE OF ANY SORTS RESULTING FROM THE
REMOVAL OPERATIONS.
2. ALL DEBRIS SHALL BE REMOVED FROM THE
CONSTRUCTION SITE DAILY.
3. THE CONTRACTOR SHALL TAKE ALL PRECAUTIONS TO
MAINTAIN FREE PROTECTED ACCESS OF ALL TENANTS,
SERVICE PERSONNEL AND THE PUBLIC THROUGH THE
AREAS INVOLVED.
4. THE CONTRACTOR SHALL REVIEW WITH ENGINEER OF
RECORD, ANY AND ALL ITEMS OF DEMOLITION NOT
IMPLIED OR SPECIFIED ON DRAWINGS OR SPECIFICATIONS
AND TO INCLUDE SUCH COSTS IN BID UNLESS OTHERWISE
ADVISED.
5. PROVIDE ALL LABOR, MATERIAL, EQUIPMENT AND
SERVICES AND PERFORM ALL OPERATIONS REQUIRED
FOR DEMOLITION OF THE EXISTING ASPHALT AND
RELATED WORK AS DESCRIBED AND SPECIFIED HEREIN,
AND AS MAY BE REASONABLY IMPLIED AS NECESSARY TO
COMPLETE THE WORK IN ALL RESPECTS.
6. ALL WORK SHALL CONFORM TO THE LATEST EDITION OF
ALL APPLICABLE REFERENCE SPECIFICATIONS AND TO
GOVERNING BUILDING CODES AND REQUIREMENTS OF
AUTHORITIES HAVING JURISDICTION.
7. CONTRACTOR TO PROVIDE DUST BARRIER FOR
PROTECTION OF EXISTING AREAS TO REMAIN AS
REQUIRED.
8. WHEN DEMOLITION TAKES PLACE, SHOULD ANY WORK
AFFECT THE INTEGRITY OF THE STRUCTURE, WORK MUST
STOP IMMEDIATELY , AND ENGINEER NOTIFIED. UNDER NO
CIRCUMSTANCES SHALL REINFORCING OF ANY KIND BE
DAMAGED, CUT OR BROKEN.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
P
M
100% SUBMISSION
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEER
WATSON ENGINEERING, PC
1112 STATE ROUTE 434
OWEGO, NY 13827
0: 607-223-4334
CANTEEN FREEZER SLAB REPAIR
AND WALK-IN FREEZER
REPLACEMENT
SYRACUSE VAMC, RM CL06
528A7-17-720
Project Director
4-27-18 JWE MPLRevisions: Date:
NOTES
G101
WELDING NOTES:
1. WELD TO ADJOINING ANGLE AND BOLT ANGLE IRON TO
EXISTING STEEL BEAM.
2. CONTRACTOR TO CONTINUOUSLY WELD PROPOSED
STEEL PLATE TO EXISTING BEAM (IN 2" INCREMENTS).
ALLOW SECTION TO COOL BEFORE CONTINUING.
3. ALL ANGLE IRON TO BE ASTM A-36 OR GREATER.
4. USE E70 SERIES WELDING ELECTRODES.
5. CONTRACTOR TO INSTALL BOLTS PER MANUFACTURER
INSTRUCTIONS.
SCALE: 3/8" = 1'-0"
DEMOLITION PLAN
F1
NOTES:
1. PLAN VIEW IS DRAWN BASED OFF OF AS-BUILT DRAWINGS FROM
ORIGINAL DATE OF CONSTRUCTION.
2. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS. IF THERE ARE ANY
DEVIATIONS FROM THE DIMENSIONS SHOWN ON THESE DRAWINGS,
CONTACT THE COR IMMEDIATELY.
3. SEE SHEET A501 FOR EXISTING DOOR SCHEDULE.
4. CONTRACTOR TO ENSURE CONTINUED ACCESS IS AVAILABLE TO CL08A
THROUGH CL08 FOR VA STAFF FOR THE ENTIRE DURATION OF THE
PROJECT. CONTRACTOR TO SEQUENCE WORK TO ENSURE ACCESS TO
CL08A AT ALL TIMES THROUGHOUT CONSTRUCTION. THE CONTRACTOR
IS TO ENSURE THAT THERE IS AT LEAST 8 FEET OF SPACE FROM THE
EXTERIOR WALL TO THE CONSTRUCTION WALL IN CL08; ANY DEVIATION
OF THIS IS TO BE REVIEWED WITH THE COR PRIOR TO THE
CONSTRUCTION OF THE 2 HOUR FIRE BARRIER.
5. THE CONTRACTOR IS TO ENSURE THAT THERE IS AT LEAST A 36" PATH
OF EGRESS IN CORR 30A FOR EGRESS TRAFFIC; ANY DEVIATION OF
THIS IS TO BE REVIEWED BY THE COR PRIOR TO INSTALLATION OF 2
HOUR FIRE BARRIER WALL.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
P
M
100% SUBMISSION
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEER
WATSON ENGINEERING, PC
1112 STATE ROUTE 434
OWEGO, NY 13827
0: 607-223-4334
CANTEEN FREEZER SLAB REPAIR
AND WALK-IN FREEZER
REPLACEMENT
SYRACUSE VAMC, RM CL06
528A7-17-720
Project Director
4-27-18 JWE MPLRevisions: Date:
AD101
2-HOUR
CONSTRUCTION
BARRIER
DOOR TO BE
REMOVED
COLUMN
LINES
DEMOLITION PLAN
L M N O
L M N O
CL06
CL08
CL08A
CORRIDOR C30A
CL61
EXISTING DOOR TO AND FRAME TO BE DEMOLISHED.
EXISTING DOOR AND CARD READER TO BE REMOVED AND
RELOCATED/REPLACED WITH NEW DOOR AND FRAME.
DOOR TO MATCH EXISTING COMPOSITION AND COLOR
PALETTE. CONTRACTOR TO REUSE EXISTING CARD
READER FOR PROPOSED DOOR. CONTRACTOR TO INFILL
WALLS WHERE EXISTING DOOR IS LOCATED WITH
EXISTING WALL COMPOSITION UNLESS OTHERWISE
NOTED ON DRAWINGS.
EXISTING DOOR AND FRAME TO BE REMOVED.
CONTRACTOR TO PROVIDE TEMPORARY SHORING
BEFORE INFILLING WALLS WHERE DOOR IS LOCATED
WITH EXISTING WALL COMPOSITION UNLESS OTHERWISE
NOTED ON DRAWINGS.
EXISTING WALL TO BE REMOVED AND REPLACED.
CONTRACTOR TO PROVIDE TEMPORARY SHORING TO BE
IMPLEMENTED DURING TRANSITIONAL PERIOD FOR
PROPOSED SLAB.
CONTRACTOR TO REMOVE AND RELOCATE EXISTING AIR
CONDITIONING UNIT AND ASSOCIATED PIPING.
WALLS TO BE
DEMOLISHED
4 44
4 4 4
DOOR TAGS
(SEE A501 FOR
DOOR SCHEDULE)
CONTRACTOR TO PERFORM
ABATEMENT, AS REQUIRED, FOR
POTENTIAL ASBESTOS CONTAINING
MATERIAL ON EXISTING PIPES
CL15
WALL TAGS
(SEE B7/A101)
CONTRACTOR TO PERFORM
ABATEMENT, AS REQUIRED, FOR
POTENTIAL ASBESTOS CONTAINING
MATERIAL ON EXISTING PIPES
AutoCAD SHX Text
DEMOLITION NOTES
SYMBOL LEGEND
WALL REINFORCING AS
SPECIFIED IN FIELD
CMU
COMPRESSIBLE FILLER W/
SEALANT (FIRE RESISTIVE
JOINT SYSTEM AT RATED
PARTITIONS)
UNDERSIDE OF STRUCTURE
ABOVE
FINISHED CEILING
FIELD VERIFY
SCALE: 3/8" = 1'-0"
PROPOSED FLOOR PLAN
F1
NOTES:
1. PLAN VIEW IS DRAWN BASED OFF OF AS-BUILT DRAWINGS FROM
ORIGINAL DATE OF CONSTRUCTION.
2. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS. IF THERE ANY
DEVIATION FROM THE DIMENSIONS SHOWN ON THESE DRAWINGS,
CONTACT THE COR IMMEDIATELY.
3. SEE SHEET A501 FOR PROPOSED DOOR SCHEDULE AND DETAILS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
P
M
100% SUBMISSION
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEER
WATSON ENGINEERING, PC
1112 STATE ROUTE 434
OWEGO, NY 13827
0: 607-223-4334
CANTEEN FREEZER SLAB REPAIR
AND WALK-IN FREEZER
REPLACEMENT
SYRACUSE VAMC, RM CL06
528A7-17-720
Project Director
4-27-18 JWE MPLRevisions: Date:
A101
ARCHITECTURAL PLAN
L M N O
L M N O
2-HOUR
CONSTRUCTION
BARRIER
COLUMN
LINES
PROPOSED
NEW DOOR
CONTRACTOR TO PATCH WALL WHERE REQUIRED.
PROPOSED NEW DOOR AND FRAME TO MATCH EXISTING
COMPOSITION AND COLOR PALETTE. CONTRACTOR TO
REUSE EXISTING CARD READER FOR PROPOSED DOOR
LOCATION. SEE DOOR SCHEDULE FOR ADDITIONAL
DETAILS.
CONTRACTOR TO PROVIDE OPENING FOR PROPOSED
COOLER DOOR.
PROPOSED WALL COMPOSITION TO MATCH EXISTING
COMPOSITION OF MASONRY WALLS OR APPROVED
EQUIVALENT. CONTRACTOR TO REMOVE TEMPORARY
SHORING IMPLEMENTED DURING TRANSITIONAL PERIOD
UPON COMPLETION OF FABRICATED WALLS.
CONTRACTOR TO RELOCATE EXISTING AIR CONDITIONING
UNIT AND ASSOCIATED PIPING.
CONTRACTOR TO INSTALL 24" SOLID SURFACE MATERIAL
COUNTER AND MOUNT AT STANDING HEIGHT (42" AFF).
CONTRACTOR TO MODIFY INTERIOR FENCING FOR ROOM
CL08 TO MATCH EXISTING.
PROPOSED
WALLS
4 4
4 4
CL06
CL08
CL08A
CORRIDOR C30A
CL61
CL15
DOOR TAGS
(SEE A501 FOR
DOOR SCHEDULE)
2X4 STUD WALL - TEMPORARY WALL
GYP. BOARD (2 LAYER EACH SIDE)
UNDERSIDE OF
STRUCTURE
ABOVE
TOP PLATE
(2) LAYER OF 5/8"
GWB AT EACH SIDE
BOTTOM PLATE
2X4 WOOD STUD
@ 12" SPACING
FINISHED FLOOR
1WALL TAG -
SCALE: NTS
PARTITION ASSEMBLY DESIGNATION DETAILS (TYP.) - 2 HR FIRE RATED
B7
ASSEMBLY DESIGNATION - M SERIES
CMU PARTITION
2WALL TAG -
WALL TAGS
(SEE B7/A101)
PROPOSED SOLID
SURFACE MATERIAL
COUNTER
PROPOSED
INTERIOR
FENCING
AutoCAD SHX Text
KEYED NOTES
FIELD
VERIFY
F I E
L D
V
E R
I F
Y
DTF
TYPICAL FRAME
JP
JP
TYP.
F W
T Y
P
PARTITION THICKNESS
FIELD VERIFY
PARTITION THICKNESS
FIELD VERIFY
STEEL REINF.
CMU WALL
W/ BOND BEAM HEADER
SEAL ALL EDGES, ALL
SIDES TYP.
COLOR TO MATCH
WALL COLOR
GROUT FRAME
SOLID, TYP.
CMU WALL
W/ BOND BEAM HEADER
PUNCH & DIMPLE FRAME W/ 3/8" DIA
HOLE COUNTERSUNK INTO FRAME
WITH A 5" SLEEVE ANCHOR. INSTALL
EPOXY ANCHOR IN HOLE TO
ANCHOR FRAME TO EXISTING CMU
WALL (3 HOLES FOR HEAD)
SEAL ALL EDGES, ALL SIDES TYP.
COLOR TO MATCH WALL COLOR
GROUT FRAME SOLID, TYP.
STEEL REINF.
2" MIN
4" TYP
FINISHED FACE OF
INTERSECTING
PARTITION
SEAL ALL EDGES,
ALL SIDES TYP.
COLOR TO MATCH
WALL COLOR
JAMB ANCHOR
CMU WALL
FRAME JAMB
GROUT FRAME
SOLID, TYP.
CMU WALL
2" MIN
4" TYP FINISHED FACE OF
INTERSECTING PARTITION
SEAL ALL EDGES, ALL SIDES TYP.
COLOR TO MATCH WALL COLOR
PUNCH & DIMPLE FRAME W/ 3/8"
DIA HOLE COUNTERSUNK INTO
FRAME WITH A 5" SLEEVE
ANCHOR. INSTALL EPOXY
ANCHOR IN HOLE TO ANCHOR
FRAME TO EXISTING CMU WALL
(3 HOLES FOR DOOR JAMB AND
2 HOLES FOR TRANSOM JAMB)
FRAME JAMB
GROUT FRAME SOLID, TYP.
P A
R T
I T
I O
N
T
H I C
K N
E S
S
P A
R T
I T
I O
N
T
H I C
K N
E S
S
NOTES:
1. PLAN VIEW IS DRAWN BASED OFF OF AS-BUILT DRAWINGS FROM
ORIGINAL DATE OF CONSTRUCTION.
2. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS. IF THERE ANY
DEVIATION FROM THE DIMENSIONS SHOWN ON THESE DRAWINGS,
CONTACT THE COR IMMEDIATELY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
P
M
100% SUBMISSION
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEER
WATSON ENGINEERING, PC
1112 STATE ROUTE 434
OWEGO, NY 13827
0: 607-223-4334
CANTEEN FREEZER SLAB REPAIR
AND WALK-IN FREEZER
REPLACEMENT
SYRACUSE VAMC, RM CL06
528A7-17-720
Project Director
4-27-18 JWE MPLRevisions: Date:
A501
DOOR SCHEDULE AND
DETAILS
SIZE DOORS
DOOR SCHEDULE
FRAMES
BASEMENT FLOOR
D O
O R
N
W I D
T H
H E
I G
H T
T Y
P E
M A
T E
R I A
L
T H
I C
K N
E S
S
T Y
P E
M A
T E
R I A
L
H E
A
T L
J A
M B
L
S I L
L
D
T L
L A
B E
L
G L
A S
S
H D
W
G
O
U P
R E
M A
R K
S
CL08 4' - 4 1/2" 7' - 0" VLT HM 1-3/4" VIF HM D1/A501 D1/A501
SCALE: NTS
PROPOSED DOOR SCHEDULE
F7
HM HOLLOW METAL
DOOR SCHEDULE REMARKS
1. DOOR IS TO BE EQUIPPED WITH CARD READER ACCESS
2. PROVIDE AUTOMATIC OPERATORS
3. PUSH PLATE OPERATOR
4. DOOR SHALL COMPLY WITH NFPA 101, SECTION 18.2.2.2.6.
DOOR SCHEDULE LEGEND
1 1, 5
SIZE DOORS
DOOR SCHEDULE
FRAMES
BASEMENT FLOOR
CL06 3' - 6" 7' - 0" VIF VIF 1-3/4" VIF VIF -
CL08A 7' - 0" 7' - 0" VIF VIF VIF VIF VIF -
D O
N
W I D
T H
H E
I G
H T
T Y
P E
M A
T E
R I A
L
T H
I C
K N
E S
S
T Y
P E
M A
T E
R I A
L
H E
A
L
J A
B
L
S I L
L
D
T L
L A
B E
L
G L
A S
S
H D
W
G
O
U P
R E
M A
R K
S
CL08 4' - 4 1/2" 7' - 0" VIF VIF VIF VIF VIF -
SCALE: NTS
EXISTING DOOR SCHEDULE
E7
VIF --
VIF --
VIF --
5. CONTRACTOR SHALL MATCH EXISTING DOOR, FRAME AND HARDWARE AS
CLOSELY AS POSSIBLE.
SCALE: NTS
FRAMING INSTALLATION DETAILS (TYP.)
F1
JAMB DETAIL - MASONRY
HEAD DETAIL - MASONRY
VIF CONTRACTOR TO VERIFY IN FIELD
DOOR HARDWARE REMARKS
1. ALL PROPOSED DOORS TO BE YALE 8800 SERIES OR APPROVED EQUIVALENT.
SCALE: NTS
DOOR TYPES (TYP.)
C7
F
FLUSH
SCALE: NTS
FRAME TYPES - DOORS (TYP.)
C9
HEAD DETAIL - MASONRY
JAMB DETAIL - MASONRY
S130 S130S130S130
S130 S130 S130 S130
S129S129 S129 S129
S128S128 S128 S128
S127
S127
S127
S127 S127 S127 S127 S127 S118 S118 OPEN
OPENOPENOPENS118S119S119S119S119S119S119S122S122 S121
S118
P.1 Q.1 R.1
L'
CL55
MECHANICAL
CL51
CL51
CL49
CL50
CL52
CL46
CL46A
CL56
CL62
CL61
CL56
CORRIDOR
SCALE: 1/8" = 1'-0"
PLAN VIEW OF PROPOSED SLABS
F1
NOTES:
1. PLAN VIEW IS DRAWN BASED OFF OF AS-BUILT DRAWINGS FROM
ORIGINAL DATE OF CONSTRUCTION.
2. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS. IF THERE ANY
DEVIATION FROM THE DIMENSIONS SHOWN ON THESE DRAWINGS,
CONTACT THE COR IMMEDIATELY.
SCALE: 1/8" = 1'-0"
EXISTING BASEMENT SLAB LAYOUT
C1
PROPOSED SLABS TO BE REMOVED.
SEE DETAIL F1/S501.
EXISTING REFRIGERATOR FOOTPRINT
SLAB TO BE
REMOVED &
REPLACED
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
P
M
100% SUBMISSION
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEER
WATSON ENGINEERING, PC
1112 STATE ROUTE 434
OWEGO, NY 13827
0: 607-223-4334
CANTEEN FREEZER SLAB REPAIR
AND WALK-IN FREEZER
REPLACEMENT
SYRACUSE VAMC, RM CL06
528A7-17-720
Project Director
4-27-18 JWE MPLRevisions: Date:
S101
PROPOSED LOCATION OF NEW DOOR,
DOOR FRAME AND RELOCATED EXISTING
CARD READER TO ALLOW ACCESS TO CL08
2-HOUR
CONSTRUCTION
BARRIER
DOOR TO BE
REMOVED
COLUMN
LINES
EXISTING DOOR AND FRAME TO BE
DEMOLISHED; EXISTING CARD READER
TO BE REMOVED FOR RELOCATION.
EXISTING DOOR AND DOOR FRAME TO
BE REMOVED
PROPOSED
NEW DOOR
STRUCTURAL PLAN
L M N O
KJ
L M N OKJ P Q R
CONTRACTOR TO SAW CUT FOR CONNECTION BETWEEN
EXISTING AND PROPOSED SLABS
EXISTING DOOR TO BE REMOVED
PROPOSED FREEZER
FOOTPRINT
DOOR TAGS
(SEE A101 FOR
DOOR SCHEDULE)
WALL TAGS
(SEE B7/A101)
PROPOSED
INTERIOR
FENCING
DECK
DIRECTION
7"
4 3/4"
12"
36"
3"
SCALE: 1/2" = 1'-0"
PLAN VIEW OF PROPOSED NEW SLAB (TYP.)
F1
NOTES:
1. EXISTING BEAM DIMENSIONS ARE DRAWN BASED OFF OF AS-BUILT DRAWINGS PROVIDED BY
GOVERNMENT. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS FOR EXISTING BEAMS. IF THERE ANY
DEVIATION FROM THE DIMENSIONS OR DETAILS SHOWN ON THESE DRAWINGS, CONTACT THE COR
IMMEDIATELY.
2. CONCRETE F'C = 5,000 P.S.I. @ 28 DAYS WITH 5.0% - 9.0% ENTRAINED AIR.
3. ALL PROPOSED CONCRETE SHALL BE CURED FOR A MINIMUM OF 28 DAYS.
4. ALL STEEL REINFORCEMENT SHALL BE ASTM A615 GRADE 60.
5. ALL STEEL REINFORCEMENT SHALL HAVE A 3" COVER UNLESS NOTED OTHERWISE.
6. ALL STEEL REINFORCEMENT SHALL BE WIRE TIED.
7. CONCRETE PROPERTIES SHALL MEET THE FOLLOWING REQUIREMENTS.
7.1. STRENGTH: AS NOTED ON DRAWINGS.
7.2. MAX W/C = .45.
7.3. AIR = 5%+-1%.
7.4. SLUMP: 4" +-1".
8. DETAILS OF REINFORCING NOT SHOWN IN THESE PLANS SHALL BE DONE IN ACCORDANCE WITH ACI 315
AND ACI 318.
9. CONTRACTOR TO FIELD VERIFY LOCATION OF EXISTING SLAB REBAR AND ENSURE PROPER DOWELING
CONNECTION BETWEEN EXISTING AND PROPOSED CONCRETE SLABS.
PROPOSED 18'-3 1/2" X 9'-7 1/2" CONCRETE SLAB
9'-7 1/2"
SCALE: NTS
TYPICAL DECK DETAILS
D1
5,000 PSI CONCRETE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
P
M
100% SUBMISSION
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEER
WATSON ENGINEERING, PC
1112 STATE ROUTE 434
OWEGO, NY 13827
0: 607-223-4334
CANTEEN FREEZER SLAB REPAIR
AND WALK-IN FREEZER
REPLACEMENT
SYRACUSE VAMC, RM CL06
528A7-17-720
Project Director
4-27-18 JWE MPLRevisions: Date:
STRUCTURAL DETAILS
S501
VIEW A-A
DETAIL F1
ON S502
VIEW B-B
DETAIL F5
ON S502
SCALE: NTS
DECK ANGLE IRON SUPPORT CONNECTION DETAIL (TYP.)
F5
RIBBED COMPOSITE DECKING. USE
VULCRAFT 3VLI18 OR APPROVED
EQUIVALENT. SEE DETAIL D1/S101.
PROPOSED 18'-3 1/2" X 9'-7 1/2"
CONCRETE SLAB
EXISTING CONCRETE SLAB
5,000 PSI CONCRETE
PROPOSED L5-1/2" X 5-1/2" X 1/2"
PROPOSED 4" FREEZER FLOOR
4"
6"
5 1/2"
5 1/2"
EXISTING 18WF95
MANUFACTURER APPROVED
MOISTURE PROOF MEMBRANE
5"
1'-9 7/8"
TYP.
5/16"
5/16"
1/2" NEOPRENE MEMBRANE OR
APPROVED EQUIVALENT
NOTES:
1. EXISTING BEAM DIMENSIONS ARE DRAWN BASED OFF OF AS-BUILT DRAWINGS PROVIDED BY
GOVERNMENT. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS FOR EXISTING BEAMS. IF
THERE ANY DEVIATION FROM THE DIMENSIONS OR DETAILS SHOWN ON THESE DRAWINGS,
CONTACT THE COR IMMEDIATELY.
2. CONTRACTOR TO CONTINUOUSLY WELD PROPOSED ANGLE IRON TO EXISTING BEAM.
3. CONTRACTOR TO MATCH EXISTING FINISH FLOOR ELEVATION.
4. CONTRACTOR TO VERIFY THAT THERE IS SUFFICIENT CONCRETE COVERAGE (3") FROM TOP
OF EXISTING BEAM TO EXISTING FINISH FLOOR ELEVATION.
5. CONTRACTOR TO SAW CUT ENTIRE PERIMETER OF NEW DEPRESSED SLAB LOCATION.
6. CONTRACTOR TO PROVIDE TEMPORARY SHORING UNIT UNTIL PROPOSED CONCRETE HAS
ADEQUATE TIME TO CAST.
7. CONCRETE F'C = 5,000 P.S.I. @ 28 DAYS WITH 5.0% - 9.0% ENTRAINED AIR.
8. CONTRACTOR TO USE STEEL FIBERS PER SECTION SDI C-2011 OF IBC 2015.
9. USE CONCRETE FIBER SOLUTIONS CFS 150-5 OR APPROVED EQUIVALENT.
10. CONTRACTOR TO ADD 6 X 6 - W1.4 X W1.4 REINFORCING MESH IN UPPER THIRD OF
CONCRETE ABOVE THE COMPOSITE DECK PER MANUFACTURES RECOMMENDATIONS.
SCALE: 3' = 1'-0"
PROPOSED NEW W8X24 BEAM CONNECTION TO EXISTING BEAM (TYP.)
C5
10" X 10" X 3/8" STEEL PLATE, GRADE 60
PROPOSED W8X24 BEAM ACROSS CENTER
OF 9'-7 1/2" SPAN
TYP.
10"
10"
1 1/2"
7"
SECTION C-C
RIBBED COMPOSITE DECKING. USE
VULCRAFT 3VLI18 OR APPROVED
EQUIVALENT. SEE DETAIL D1/S101.
*PROPOSED W8X24 BEAM NOT SHOWN FOR CLARITY*
PROPOSED W8X24 BEAM
3/4" DIAMETER A325 BOLTS IN SLOTTED HOLES
SECTION
C-C
3/4" DIAMETER A325 BOLTS IN
SLOTTED HOLES, WITH 1/8" WASHER
3"
3"
10" X 10" X 3/8" STEEL PLATE,
GRADE 60
PROPOSED L5
" X 5
" X
5 1/2"
4'-9 3/4"
PROPOSED 7/8" X 12" PSD12/#6TX SPEED DOWEL OR APPROVED
EQUIVALENT @ 12" SPACING O.C.
PROPOSED L5
" X 5
" X
EXISTING 5" CONCRETE SLAB
1'
18'-3 1/2"
STEEL NOTES:
1. WELD TO ADJOINING ANGLE AND BOLT ANGLE IRON TO EXISTING STEEL BEAM.
2. CONTRACTOR TO CONTINUOUSLY WELD PROPOSED STEEL PLATE TO EXISTING BEAM (IN 2"
INCREMENTS). ALLOW SECTION TO COOL BEFORE CONTINUING.
3. ALL ANGLE IRON TO BE ASTM A-36 OR GREATER.
4. USE E70 SERIES WELDING ELECTRODES.
5. CONTRACTOR TO INSTALL BOLTS PER MANUFACTURER INSTRUCTIONS.
6. BOLTS TO BE GRADE 60 OR APPROVED EQUIVALENT.
7. W8X24 BEAM TO BE GRADE 60 STRUCTURAL STEEL OR APPROVED EQUIVALENT.
PROPOSED 7/8" X 12" PSD12/#6TX
SPEED DOWEL OR APPROVED
EQUIVALENT @ 12" SPACING O.C.
1 1/2"
1'
PROPOSED 7/8" X 12" PSD12/#6TX
SPEED DOWEL OR APPROVED
EQUIVALENT @ 12" SPACING O.C.
STEEL NOTES:
1. WELD TO ADJOINING ANGLE AND BOLT ANGLE IRON TO
EXISTING STEEL BEAM.
2. CONTRACTOR TO CONTINUOUSLY WELD PROPOSED STEEL
PLATE TO EXISTING BEAM (IN 2" INCREMENTS). ALLOW
SECTION TO COOL BEFORE CONTINUING.
3. ALL ANGLE IRON TO BE ASTM A-36 OR GREATER.
4. USE E70 SERIES WELDING ELECTRODES.
5. CONTRACTOR TO INSTALL BOLTS PER MANUFACTURER
INSTRUCTIONS.
6. BOLTS TO BE GRADE 50 OR APPROVED EQUIVALENT.
7. W8X24 BEAM TO BE GRADE 60 STEEL OR APPROVED
EQUIVALENT.
STEEL NOTES:
1. WELD TO ADJOINING ANGLE AND BOLT ANGLE IRON TO
EXISTING STEEL BEAM.
2. CONTRACTOR TO CONTINUOUSLY WELD PROPOSED STEEL
PLATE TO EXISTING BEAM (IN 2" INCREMENTS). ALLOW
SECTION TO COOL BEFORE CONTINUING.
3. ALL ANGLE IRON TO BE ASTM A-36 OR GREATER.
4. USE E70 SERIES WELDING ELECTRODES.
5. CONTRACTOR TO INSTALL BOLTS PER MANUFACTURER
INSTRUCTIONS.
6. BOLTS TO BE GRADE 60 OR APPROVED EQUIVALENT.
7. W8X24 BEAM TO BE GRADE 60 STRUCTURAL STEEL OR
APPROVED EQUIVALENT.
NOTES:
1. EXISTING BEAM DIMENSIONS ARE DRAWN BASED OFF OF AS-BUILT DRAWINGS PROVIDED BY
GOVERNMENT. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS FOR EXISTING BEAMS. IF
THERE ANY DEVIATION FROM THE DIMENSIONS OR DETAILS SHOWN ON THESE DRAWINGS,
CONTACT THE COR IMMEDIATELY.
2. CONTRACTOR TO CONTINUOUSLY WELD PROPOSED ANGLE IRON TO EXISTING BEAM.
3. CONTRACTOR TO MATCH EXISTING FINISH FLOOR ELEVATION.
4. CONTRACTOR TO VERIFY THAT THERE IS SUFFICIENT CONCRETE COVERAGE (3") FROM TOP
OF EXISTING BEAM TO EXISTING FINISH FLOOR ELEVATION.
5. CONTRACTOR TO SAW CUT ENTIRE PERIMETER OF NEW DEPRESSED SLAB LOCATION.
6. CONTRACTOR TO PROVIDE TEMPORARY SHORING UNIT UNTIL PROPOSED CONCRETE HAS
ADEQUATE TIME TO CAST.
7. CONCRETE F'C = 5,000 P.S.I. @ 28 DAYS WITH 5.0% - 9.0% ENTRAINED AIR.
8. CONTRACTOR TO USE STEEL FIBERS PER SECTION SDI C-2011 OF IBC 2015.
9. USE CONCRETE FIBER SOLUTIONS CFS 150-5 OR APPROVED EQUIVALENT.
10. CONTRACTOR TO ADD 6 X 6 - W1.4 X W1.4 REINFORCING MESH IN UPPER THIRD OF
CONCRETE ABOVE THE COMPOSITE DECK PER MANUFACTURES RECOMMENDATIONS.
1 1/2"
EXISTING 5" CONCRETE SLAB
AutoCAD SHX Text
3VLI18 FLOOR DECK
AutoCAD SHX Text
ESTCODE
ESTCODE
NOTES:
1. EXISTING BEAM DIMENSIONS ARE DRAWN BASED OFF OF AS-BUILT
DRAWINGS PROVIDED BY GOVERNMENT. CONTRACTOR TO FIELD VERIFY
ALL DIMENSIONS AND LOCATIONS FOR EXISTING BEAMS. IF THERE ANY
DEVIATION FROM THE DIMENSIONS OR DETAILS SHOWN ON THESE
DRAWINGS, CONTACT THE COR IMMEDIATELY.
2. CONCRETE F'C = 5,000 P.S.I. @ 28 DAYS WITH 5.0% - 9.0% ENTRAINED AIR.
3. CONTRACTOR TO FIELD VERIFY LOCATION OF EXISTING SLAB REBAR AND
ENSURE PROPER DOWELING CONNECTION BETWEEN EXISTING AND
PROPOSED CONCRETE SLABS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
P
M
100% SUBMISSION
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEER
WATSON ENGINEERING, PC
1112 STATE ROUTE 434
OWEGO, NY 13827
0: 607-223-4334
CANTEEN FREEZER SLAB REPAIR
AND WALK-IN FREEZER
REPLACEMENT
SYRACUSE VAMC, RM CL06
528A7-17-720
Project Director
4-27-18 JWE MPLRevisions: Date:
STRUCTURAL SECTION
VIEWS
S502
SCALE: 3/4" = 1'-0"
B-B SECTION VIEW OF EXISTING SLAB
C5
SCALE: 3/4" = 1'-0"
A-A SECTION VIEW OF EXISTING SLAB
C1
SCALE: 3/4" = 1'-0"
B-B SECTION VIEW OF PROPOSED SLAB
F5
RIBBED COMPOSITE DECKING. USE
VULCRAFT 3VLI18 OR APPROVED
EQUIVALENT. SEE DETAIL D1/S501.
EXISTING 5" CONCRETE SLAB
EXISTING CONCRETE SLAB
5,000 PSI CONCRETE
NOTES:
1. CONCRETE F'C = 5,000 P.S.I. @ 28 DAYS WITH 5.0% - 9.0% ENTRAINED
AIR.
2. VULCRAFT EXTERIOR BEARING LENGTH OF 2.5 INCHES.
3. VULCRAFT INTERIOR BEARING LENGTH OF 5 INCHES.
4. SHEET STEEL FOR GALVANIZED DECK SHALL CONFORM TO ASTM A653
(A653M) STRUCTURAL QUALITY, WITH MINIMUM YIELD STRENGTH OF 33
PSI (230 MPa).
5. CONTRACTOR TO ADD 6 X 6 - W1.4 X W1.4 REINFORCING MESH IN
UPPER THIRD OF CONCRETE ABOVE THE COMPOSITE DECK PER
MANUFACTURES RECOMMENDATIONS.
6. CONTRACTOR TO FIELD VERIFY LOCATION OF EXISTING SLAB REBAR
AND ENSURE PROPER DOWELING CONNECTION BETWEEN EXISTING
AND PROPOSED CONCRETE SLABS.
7. PROPOSED FREEZER FLOOR SHALL BE NOTCHED OVER EXISTING
I-BEAM, AS REQUIRED.
MANUFACTURER APPROVED MOISTURE
PROOF MEMBRANE
6"
PROPOSED W8X24 BEAM. SEE
DETAIL C5/S501 FOR CONNECTION.
PROPOSED 4" FREEZER FLOOR
1'-9 7/8"
SCALE: 3/4" = 1'-0"
A-A SECTION VIEW OF PROPOSED SLAB
F1
RIBBED COMPOSITE DECKING. USE VULCRAFT
3VLI18 OR APPROVED EQUIVALENT. SEE DETAIL
D1/S501.
EXISTING CONCRETE SLAB
PROPOSED L5 1/2" X 5 1/2" X
1/2". SEE DETAIL F5/S501 FOR
CONNECTION (TYP.)
PROPOSED 5" CONCRETE SLAB
NOTES:
1. CONCRETE F'C = 5,000 P.S.I. @ 28 DAYS WITH 5.0% - 9.0%
ENTRAINED AIR.
2. VULCRAFT EXTERIOR BEARING LENGTH OF 2.5 INCHES.
3. VULCRAFT INTERIOR BEARING LENGTH OF 5 INCHES.
4. SHEET STEEL FOR GALVANIZED DECK SHALL CONFORM TO
ASTM A653 (A653M) STRUCTURAL QUALITY, WITH MINIMUM
YIELD STRENGTH OF 33 PSI (230 MPa).
5. CONTRACTOR TO ADD 6 X 6 - W1.4 X W1.4 REINFORCING
MESH IN UPPER THIRD OF CONCRETE ABOVE THE
COMPOSITE DECK PER MANUFACTURES
RECOMMENDATIONS.
6. CONTRACTOR TO FIELD VERIFY LOCATION OF EXISTING
SLAB REBAR AND ENSURE PROPER DOWELING
CONNECTION BETWEEN EXISTING AND PROPOSED
CONCRETE SLABS.
7. CONTRACTOR SHALL VERIFY FREEZER FLOOR DIMENSIONS
PRIOR TO CASTING CONCRETE.
MANUFACTURER APPROVED
MOISTURE PROOF MEMBRANE
PROPOSED L5 1/2" X 5 1/2" X 1/2". SEE
DETAIL F5/S501 FOR CONNECTION (TYP.)
PROPOSED 4" FREEZER FLOOR
12'-5"
5"
1/2" NEOPRENE MEMBRANE OR
APPROVED EQUIVALENT (TYP.)
1/2" NEOPRENE MEMBRANE
OR APPROVED EQUIVALENT
EXISTING CONCRETE SLAB TO REMAIN
EXISTING CONCRETE BEAM
WITH 18WF114 EMBEDDED
EXISTING CONCRETE BEAM
WITH 18WF95 EMBEDDED
EXISTING CONCRETE SLAB TO REMAIN
5"
5"
EXISTING CONCRETE BEAM WITH 16WF60
EMBEDDED; CONTRACTOR SHALL DEMOLISH
CONCRETE ON INTERIOR SIDE OF BEAM, AS SHOWN
EXISTING CONCRETE BEAM
WITH 16WF64 EMBEDDED
PROPOSED W8X24 TO SPAN ACROSS
CENTER OF SECTION. SEE DETAIL
C5/S501 FOR CONNECTION.
5"
5"
PROPOSED 7/8" X 12" PSD12/#6TX
SPEED DOWEL OR APPROVED
EQUIVALENT @ 12" SPACING O.C.
5"
PROPOSED 18'-3
" X 9'-7
" CONCRETE SLAB
CONTRACTOR SHALL
DEMOLISH EXISTING
CONCRETE AROUND BEAM
CONTRACTOR SHALL DEMOLISH
EXISTING CONCRETE AROUND
INTERIOR SIDE OF BEAMS (TYP.)
EXISTING CONCRETE BEAM WITH
16WF60 EMBEDDED; CONTRACTOR
SHALL DEMOLISH CONCRETE ON
INTERIOR SIDE OF BEAM, AS SHOWN
5'-5 1/2" 3'-9"
264'-4"
M
D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
P
M
100% SUBMISSION
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEER
WATSON ENGINEERING, PC
1112 STATE ROUTE 434
OWEGO, NY 13827
0: 607-223-4334
CANTEEN FREEZER SLAB REPAIR
AND WALK-IN FREEZER
REPLACEMENT
SYRACUSE VAMC, RM CL06
528A7-17-720
Project Director
4-27-18 JWE MPLRevisions: Date:
SCALE: 1/4" = 1'-0"
MECHANICAL DUCTWORK DEMOLITION FLOOR PLAN
F2
CORRIDOR 30A
WALK-IN
FREEZER CL06
EQUIPMENT
STORAGE ROOM
CL08
CL04
BL04
BL06A
CL09
EQUIPMENT
STORAGE ROOM
CL08A
M N O
M N O
SCALE: 1/4" = 1'-0"
PROPOSED MECHANICAL DUCTWORK FLOOR PLAN
F5
CORRIDOR 30A
WALK-IN
FREEZER CL06
EQUIPMENT
STORAGE ROOM
CL08
CL04
BL04
BL06A
CL09
EQUIPMENT
STORAGE ROOM
CL08A
M N O
M N O
RELOCATE EXISTING SUPPLY AND
RETURN DUCTWORK THROUGH ROOM
CL06 AT A BOTTOM OF DUCT ELEVATION
NO LESS THAN 8'-8" AFF TO ALLOW FOR
FREEZER/ COOLER INSTALLATION.
EXISTING DUCTWORK SHALL
BE CUT AND REROUTED TO
ALLOW FOR INSTALLATION
OF FREEZER/ COOLER. SEE
VIEW F5 FOR PROPOSED
DUCTWORK ROUTING AND
ELEVATION.
MECHANICAL DEMOLITION NOTES:
1. ALL AREAS OF THE BUILDING AFFECTED BY MECHANICAL DEMOLITION WORK SHALL BE
PATCHED AND REPAIRED TO MATCH ADJACENT FINAL FINISHES. THE REPAIR WORK SHALL BE
DONE TO THE OWNER'S SATISFACTION.
2. DEMOLITION WORK SHALL INCLUDE REMOVAL OF EXISTING BUILDING CONSTRUCTION TO
EXTENT REQUIRED TO PERFORM NEW CONSTRUCTION ACTIVITIES INDICATED.
3. REMOVE ALL EXISTING MECHANICAL SYSTEM COMPONENTS, MATERIALS , APPARATUS, AND
APPLIANCES WITHIN THE DESIGNATED PROJECT AREA, UNLESS OTHERWISE NOTED.
COORDINATE WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, FIRE PROTECTION, AND
PLUMBING CONTRACT DOCUMENTS FOR ADDITIONAL SCOPE OF WORK FOR SYSTEMS TO BE
REMOVED OR RETAINED TO EXTENT REQUIRED TO PERFORM NEW CONSTRUCTION
ACTIVITIES INDICATED.
4. THE DEMOLITION PROCEDURES SHALL PROVIDE FOR SAFE CONDUCT OF THE WORK,
PROTECTION OF PERSONNEL, CAREFUL REMOVAL AND OTHER DISPOSITION OF MATERIALS
SPECIFIED TO BE SALVAGED. PROTECTION OF PROPERTY TO REMAIN UNDISTURBED,
COORDINATION WITH OTHER WORK IN PROGRESS, AND TIMELY DISCONNECTION OF UTILITY
SERVICES.
5. EXISTING WORK SHALL BE CUT, DRILLED, ALTERED, REMOVED, OR TEMPORARILY REMOVED
AND REPLACED FOR PERFORMANCE OF WORK UNDER THE CONTRACT. WORK REPLACED
SHALL MATCH SIMILAR EXISTING WORK. STRUCTURAL MEMBERS OF CONCRETE OR
STRUCTURAL STEEL SHALL NOT BE CUT OR ALTERED, EXCEPT AS SHOWN, WITHOUT
AUTHORIZATION OF THE ENGINEER. WORK REMAINING IN PLACE DAMAGED OR DEFACED
DURING THIS CONTRACT SHALL BE RESTORED TO THE CONDITION AT TIME OF AWARD OF
CONTRACT. CUT, ALTER, REMOVE, OR TEMPORARILY REMOVE AND REPLACE EXISTING WORK
FOR INSTALLATION OF ELECTRICAL WORK.
GENERAL MECHANICAL NOTES:
1. ALL MECHANICAL WORK SHALL BE DONE IN ACCORDANCE WITH ALL LOCAL AND STATE
REGULATIONS FOR THE STATE OF NEW YORK.
2. CONTRACTOR SHALL COORDINATE EXACT LOCATION OF DUCTWORK AND DIFFUSERS WITH
LIGHTS, EQUIPMENT, AND CEILING GRID.
3. DRAWINGS ARE DIAGRAMMATIC AND GENERALLY INDICATIVE OF THE WORK. ALL SYSTEMS
SHALL FOLLOW ARRANGEMENT AS MUCH AS POSSIBLE, HOWEVER, ACTUAL FIELD
CONDITIONS SHALL DICTATE. PROVIDE NECESSARY MODIFICATIONS TO MEET FIELD
CONDITIONS AND AVOID CONFLICT WITH OTHER TRADES. IF RESOLUTION CANNOT BE
REACHED WITHOUT COMPROMISING THE DESIGN, THESE CONFLICTS SHALL BE PRESENTED
TO THE ENGINEER FOR RESOLUTION. IN CONFLICT AREAS, COMPLETE ONLY WORK NOT
AFFECTED BY THE CONFLICT PRIOR TO RESOLUTION.
4. CONNECTIONS TO EQUIPMENT SHALL CONFORM TO MANUFACTURER'S SPECIFICATIONS.
5. ALL HANGER SYSTEMS FOR PIPING AND EQUIPMENT SHALL BE SECURED TO BUILDING
STRUCTURAL SYSTEM.
6. ALL DUCT DIMENSIONS SHALL BE FIELD VERIFIED.
7. PROVIDE AIR TURNING VANES IN ALL SQUARE ELBOWS.
8. PROVIDE ACCESS PANELS IN DUCTWORK AND CEILINGS WHERE REQUIRED FOR OPERATION
AND MAINTENANCE OF ALL FANS, DAMPERS, AIR-DEFLECTING DEVICES, AND OTHER
MECHANICAL EQUIPMENT.
9. PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTS CONNECTING TO FANS AND ALL
OTHER MECHANICAL EQUIPMENT INCORPORATING FANS.
10. PROVIDE A MANUAL VOLUME DAMPER ON SUPPLY AND RETURN DUCTS AT THE CONNECTION
POINT TO THE EXISTING SYSTEM.
12x6
13x7 x x
EXISTING FAN COIL
TO BE DEMOLISHED.
ALL ASSOCIATED
PIPING SHALL BE CUT
AND CAPPED.
x x
PROVIDE AND INSTALL
TROX RN-125 DAMPER
ON SUPPLY AND
RETURN DUCTS. (SET
TO 200 CFM EACH)
PROVIDE AND INSTALL
TROX RN-160 DAMPER
ON SUPPLY AND
RETURN DUCTS. (SET
TO 300 CFM EACH)
MECHANICAL
DUCTWORK PLAN
M101
P.1
SS SS SS SS SS SS
SS SS SS
S S
SS
S S
S S
S S
FD
1/8" / 1'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
P
M
100% SUBMISSION
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEER
WATSON ENGINEERING, PC
1112 STATE ROUTE 434
OWEGO, NY 13827
0: 607-223-4334
CANTEEN FREEZER SLAB REPAIR
AND WALK-IN FREEZER
REPLACEMENT
SYRACUSE VAMC, RM CL06
528A7-17-720
Project Director
4-27-18 JWE MPLRevisions: Date:
SCALE: 1/4" = 1'-0"
PROPOSED MECHANICAL REFRIGERATION FLOOR PLAN
F2
PROPOSED MECHANICAL
REFRIGERATION PLAN
M102
PROPOSED
EVAPORATOR
COIL FOR
FREEZER
LOCATION OF EXISTING
FREEZER COMPRESSOR
TO BE REPLACED.
LOCATION OF EXISTING
COMPRESSOR TO REMAIN.
EXISTING REFRIGERANT SUCTION
AND LIQUID LINES TO BE
REPLACED PER MANUFACTURER
SPECIFICATIONS
Room Data
Room Temp:
· Freezer: -12° F with 90% RH
· Cooler: 35° F with 90% RH
Dimensions
· Freezer: 18'-2 3/8" X 12'-5" X 8'-1"
· Cooler: 8'-0" X 12'-5" X 8'-1"
Doors: 48"W X 76"H
Ambient Temp.: 85° F DB
Ceiling Insulation: 4" Extruded Polystyrene
Ceiling K Factor: 0.15
Ceiling Temperature: 85° F
Wall Insulation: 4" Extruded Polystyrene
Wall K Factor: 0.15
Wall Temperature: 85° F
Floor Insulation: 4" Extruded Polystyrene
Floor K Factor: 0.15
Floor Temperature: 60° F
Infiltration Data
Air Flow: Based on 1.5 ASHRAE averages.
Infil. Temp.: 85° F DB (60% RH) infiltrating air.
Product Data
Description: Misc
Max. Load:
· Freezer: 1,808 lbs./8 hrs.
· Cooler: 0 lbs./8 hrs.
Enter Temp.: 35° F
Spec. Heats: 0.9 above freeze/0.45 below freeze
Lat. Ht. Fusion: 100
Packaging: Varies
Pulldown in: 24 hrs.
Final Temp.:
· Freezer: -12° F
· Cooler: 35° F
Freeze: 27° F
Respiration: 0 lbs. (0 BTU/LB/Day)
Miscellaneous Data
Personnel: 0.0 person(s)
Lighting: 1 watt(s) per square foot
Motors: 0.0 equiv. horsepower
Calculation Results
Wall Heat Gains
· Freezer: 81,626 BTU/day
· Cooler: 18,544 BTU/day
Air Change
· Freezer: 61,700 BTU/day
· Cooler: 26,240 BTU/day
Product Load
· Freezer: 277,300 BTU/day
· Cooler: 0 BTU/day
Misc. Load
· Freezer: 56,360 BTU/day
· Cooler: 45,700 BTU/day
Daily Load
· Freezer: 524,700 BTU/day
· Cooler: 90,484 BTU/day
Required Capacity
· Freezer: 29,150 BTUH at 18 hours per day runtime.
· Cooler: 5,026 BTUH at 18 hours per day runtime.
Notes:
1. All proposed walls, floors, and ceilings of freezer and cooler sections shall have a maximum K-factor of 0.15.
REFRIGERATION SIZING CRITERIA
CORRIDOR 30A
WALK-IN
FREEZER CL06
EQUIPMENT
STORAGE ROOM
CL08
CL04
BL04
CL03
BL06A
CL09
RECEIVING AREA
CL10
HIGH VOLTAGE
SUBSTATION ROOM
CL15
NOTES FOR WATER COOLED REFRIGERATION SYSTEM
1. UNIT COOLER FAN(S) SHALL RUN CONTINUOUSLY, EXCEPT WHEN IT IS TURNED "OFF" BY A SWITCH
MOUNTED ON THE UNIT COOLER. THIS SAME SWITCH SHALL ALSO DE-ENERGIZE THE LIQUID-LINE
SOLENOID VALVE WHEN THE UNIT IS IN THE "OFF" POSITION.
2. ROOM THERMOSTAT FOR WALK-IN COOLER OR FREEZER SHALL AUTOMATICALLY CONTROL THE
LIQUID-LINE SOLENOID VALVE.
3. COMPRESSOR OPERATION SHALL BE CONTROLLED BY THE LOW PRESSURE SWITCH: HIGH PRESSURE
CUTOUT SWITCH SHALL PREVENT THE COMPRESSOR FROM OPERATING UNDER EXCESSIVELY HIGH
HEAD PRESSURE.
4. FLOW OF WATER THROUGH CONDENSER SHALL BE CONTROLLED BY WATER REGULATING VALVE
INSTALLED IN THE CONDENSER DISCHARGE LINE AND SHALL MODULATE IN RESPONSE TO
REFRIGERANT CONDENSING PRESSURE.
5. WHEN EQUIPMENT SCHEDULE INDICATES ELECTRIC DEFROST, THE FOLLOWING CONTROLS SHALL
ALSO BE PROVIDED:
A. DEFROST TYPE UNIT COOLER WITH HEATING ELEMENTS FOR EVAPORATOR COIL, DRAIN PAN AND
DRAIN PIPING WITHIN THE LOW TEMPERATURE ROOM. DEFROST CYCLE SHALL BE AUTOMATICALLY
CONTROLLED BY AN ELECTRIC CLOCK AND SHALL INCLUDE A SAFETY THERMOSTAT IN THE
CONTROL CIRCUIT TO PREVENT OVERHEATING THE EVAPORATOR COIL.
B. THE AUTOMATIC TIMER FOR ELECTRIC DEFROST SHALL ALSO DE-ENERGIZE THE SOLENOID VALVE
IN THE LIQUID REFRIGERANT LINE SERVING THE UNIT COOLER AND SHALL STOP THE UNIT COOLER
FAN(S) DURING THE DEFROST CYCLE.
6. PROVIDE ADDITIONAL TEMPERATURE TRANSMITTER THAT SENDS HIGH TEMPERATURE ALARM
INDICATION TO ECC.
7. EVAPORATOR DRAIN LINE SHALL BE SIZED BASED ON MANUFACTURER RECOMMENDATIONS. DRAIN
LINE FOR WALK-IN FREEZER SHALL BE INSTALLED WITH HEAT TRACING TO PROVIDE FREEZE
PROTECTION.
VA DESIGN REQUIREMENTS
ARCHITECTURAL (PER VA ARCHITECTURAL DESIGN MANUAL):
1. ALL FREEZER DOORS SHALL BE A MINIMUM OF 48" WIDE
2. FREEZER FLOOR SHALL BE FLUSH WITH THE FLOOR OF ADJOINING ROOM. FLOOR FINISH SHALL BE
NON-SLIP QUARRY TILE ON TILE SETTING BED. FLOOR INSULATION SHALL BE LOAD BEARING TYPE.
MECHANICAL (PER VA HVAC DESIGN MANUAL):
1. COORDINATE EQUIPMENT INSTALLATION AND DESIGN WITH SPECIFICATION SECTION 11.41.21 - WALK-IN
COOLERS AND FREEZERS.
2. PROVIDE EMERGENCY POWER FOR THE EQUIPMENT AND CONTROLS SERVING REFRIGERATORS AND
FREEZERS.
3. HEAT GAIN FACTORS, LOAD CALCULATIONS, AND COMPRESSOR RUNNING TIME SHALL BE BASED ON
ASHRAE RECOMMENDATIONS FOR THE FOLLOWING TYPE OF FREEZER AND ASSOCIATED DESIGN
TEMPERATURE:
A. MIXED VEGETABLES: -12 F [-24 C]
L M N O
L M N O P
PROPOSED LOCATION OF
COMPRESSOR FOR
COOLER SECTION
PROPOSED
EVAPORATOR
COIL FOR
COOLER
EVAPORATOR
DRAIN DOWN TO
CRAWLSPACE
BELOW
SCALE: 1/4" = 1'-0"
PROPOSED MECHANICAL REFRIGERATION FLOOR PLAN
F2
PROPOSED MECHANICAL
REFRIGERATION PLAN
M102
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
P
M
100% SUBMISSION
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEER
WATSON ENGINEERING, PC
1112 STATE ROUTE 434
OWEGO, NY 13827
0: 607-223-4334
CANTEEN FREEZER SLAB REPAIR
AND WALK-IN FREEZER
REPLACEMENT
SYRACUSE VAMC, RM CL06
528A7-17-720
Project Director
4-27-18 JWE MPLRevisions: Date:
SCALE: NTS
CONTROL SYSTEM SCHEMATIC, POINTS LIST, AND SEQUENCE OF OPERATION
F1
MECHANICAL SCHEDULES,
NOTES, AND DETAILS
M601
FS FS
C H
W S
D C
W
C H
W R
F R
E E
Z E
R
C O
N D
E N
S E
R
F R
E E
Z E
R
E V
A P
O R
A T
O R
COMP.
DI
DI
DI
DO
DI
DO
T
AI
AO
FS FS COMP.
DI
DI
DI
DO
DI
DO
T
AI
AO
BYPASS
BYPASS
NOTES:
1. ALARMS ON FLOW DETECTION SENSORS SHALL SEND AN
ALERT SIGNAL TO THE BAS SYSTEM IF THERE IS AN
UNEXPECTED LACK OF FLOW THROUGH THE SENSOR.
2. ALL VALVES SHALL EITHER BE FULLY OPEN OR FULLY CLOSED.
3. THREE-WAY CONTROL VALVES SHALL FAIL "OPEN" TO ALLOW
THE FLOW OF DOMESTIC WATER AS AN EMERGENCY SOURCE
OF WATER.
4. IF THE TEMPERATURE RISES TO 5°F (ADJUSTABLE) ABOVE THE
SETPOINT TEMPERATURE FOR EITHER SPACE, AN ALARM SHALL
BE SENT TO THE BAS SYSTEM.
REFRIGERATION SYSTEM SEQUENCE OF OPERATIONS
NORMAL OPERATION
1. DURING NORMAL OPERATION, THE THREE-WAY CONTROL VALVE SHALL BE IN THE "OPEN" POSITION TO ALLOW FLOW OF CHILLED WATER, THE THREE-WAY MANUAL VALVE SHALL BE SET TO THE "OPEN" POSITION TO
ALLOW FLOW OF DOMESTIC WATER TO THE THREE-WAY CONTROL VALVE, IF REQUIRED, AND ALL MANUAL SERVICE ISOLATION VALVES SHALL BE SET TO THE "OPEN" POSITION.
2. UPON A RISE IN THE SPACE TEMPERATURE OF THE WALK-IN FREEZER OR COOLER TO 2°F ABOVE THE SETPOINT TEMPERATURE (ADJUSTABLE), AS DETECTED BY THE WALL-MOUNTED THERMOSTAT LOCATED WITHIN
EACH REFRIGERATED SPACE, THE EVAPORATOR, CONDENSER, AND COMPRESSOR SHALL POWER "ON" SIMULTANEOUSLY, AND CHILLED WATER SHALL FLOW THRU THE CONDENSER.
3. UPON A DROP IN THE SPACE TEMPERATURE OF THE WALK-IN FREEZER OR COOLER TO 2°F BELOW THE SETPOINT TEMPERATURE (ADJUSTABLE), AS DETECTED BY THE WALL-MOUNTED THERMOSTAT LOCATED WITHIN
EACH SPACE, THE EVAPORATOR, CONDENSER, AND COMPRESSOR SHALL POWER "OFF" SIMULTANEOUSLY.
4. IF THE FLOW DETECTION SENSOR UPSTREAM OF THE THREE-WAY CONTROL VALVE IN EITHER SYSTEM DETECTS AN UNEXPECTED LACK OF FLOW, THE AFFECTED SYSTEM SHALL FOLLOW THE SEQUENCE OF
OPERATION FOR "EMERGENCY OPERATION," AS OUTLINED BELOW.
EMERGENCY OPERATION
1. UPON A DETECTION OF "NO FLOW" THROUGH THE FLOW DETECTION SENSOR UPSTREAM OF THE THREE-WAY CONTROL VALVE FOR EITHER SYSTEM, AN ALARM SHALL ALERT THE BAS SYSTEM AND THE THREE-WAY
CONTROL VALVE FOR THE AFFECTED SYSTEM SHALL ACTUATE TO A POSITION TO ALLOW THE SYSTEM TO BE TEMPORARILY FED BY THE DOMESTIC COLD WATER SYSTEM INSTEAD OF THE CHILLED WATER SYSTEM.
THE THREE-WAY DRAIN VALVE SHALL SIMULTANEOUSLY ACTUATE TO A POSITION TO ALLOW THE SYSTEM RETURN WATER TO BE DIRECTED TO THE BUILDING SANITARY SYSTEM.
1.1. ONCE FLOW HAS BEEN RESTORED THROUGH THE FLOW DETECTION SENSOR UPSTREAM OF THE THREE-WAY CONTROL VALVE , THE THREE-WAY CONTROL VALVE SHALL ACTUATE BACK TO THE NORMAL
OPERATING POSITION, THE ALARM TO THE BAS SHALL TURN OFF, AND THE SYSTEM SHALL FOLLOW THE SEQUENCE OF OPERATION FOR "NORMAL OPERATION," AS OUTLINED ABOVE.
2. UPON A DETECTION OF "NO FLOW" THROUGH THE FLOW DETECTION SENSOR DOWNSTREAM OF THE THREE-WAY CONTROL VALVE FOR EITHER SYSTEM, AN ALARM SHALL ALERT THE BAS SYSTEM, THE EVAPORATOR, CONDENSER, AND COMPRESSOR SHALL POWER "OFF," AND THE TWO-WAY CONTROL VALVE UPSTREAM OF THE EVAPORATOR SHALL ACTUATE TO THE "CLOSED" POSITION.
2.1. UPON A DETECTION OF "FLOW" THROUGH THE FLOW DETECTION SENSOR DOWNSTREAM OF THE THREE-WAY CONTROL VALVE, THE EVAPORATOR, CONDENSER, AND COMPRESSOR SHALL POWER "ON," AND THE
TWO-WAY CONTROL VALVE UPSTREAM OF THE EVAPORATOR SHALL ACTUATE TO THE "OPEN" POSITION.
2.2. ONCE FLOW HAS BEEN RESTORED THROUGH THE FLOW DETECTION SENSOR DOWNSTREAM OF THE THREE-WAY CONTROL VALVE, REFER BACK TO SECTION 1.1 OF THE "EMERGENCY OPERATION" SEQUENCE OF
OPERATION ABOVE TO BRING THE SYSTEM(S) BACK TO NORMAL OPERATING CONDITIONS.
MAINTENANCE OPERATION
1. DURING ROUTINE MAINTENANCE OF ANY COMPONENT OF EITHER REFRIGERATION SYSTEM, THE TWO MANUAL THREE-WAY VALVES ON THE ASSOCIATED SYSTEM SHALL BE TURNED TO ALLOW DOMESTIC COLD
WATER TO FLOW FREELY TO THE EVAPORATOR, AND ANY MANUAL SHUT-OFF VALVES SHALL BE TURNED TO THE "CLOSED" POSITION, AS REQUIRED, TO ISOLATE THE COMPONENT REQUIRING MAINTENANCE.
2. UPON COMPLETION OF MAINTENANCE TO ANY COMPONENT OF THE REFRIGERATION SYSTEM, THE TWO MANUAL THREE-WAY VALVES ON THE ASSOCIATED SYSTEM(S) SHALL BE RETURNED TO THEIR NORMAL
OPERATING POSITIONS TO ALLOW CHILLED WATER TO FLOW FREELY TO THE EVAPORATOR, AND ANY MANUAL SHUT-OFF VALVES THAT WERE TURNED TO THE "CLOSED" POSITION TO ISOLATE A COMPONENT SHALL BE
RETURNED TO THE "OPEN" POSITION.
DDC POINTS LIST
POINT TYPE POINT # DESCRIPTION ALARM
TO BAS
AI
1 FREEZER TEMPERATURE YES
2 COOLER TEMPERATURE YES
AO
1 FREEZER TEMPERATURE SETPOINT
2 COOLER TEMPERATURE SETPOINT
DI
1 THREE-WAY VALVE POSITION
2 EVAPORATOR STATUS
3 FLOW DETECTION SENSOR YES
4 FLOW DETECTION SENSOR YES
5 THREE-WAY VALVE POSITION
6 EVAPORATOR STATUS
7 FLOW DETECTION SENSOR YES
8 FLOW DETECTION SENSOR YES
9 THREE-WAY VALVE POSITION
10 THREE-WAY VALVE POSITION
DO
1 VALVE OPEN/CLOSE
2 EVAPORATOR ON/OFF
3 VALVE OPEN/CLOSE
EVAPORATOR ON/OFF
5 VALVE OPEN/CLOSE
6 VALVE OPEN/CLOSE
C O
O L E
R
C O
N D
E N
S E
R
C O
O L E
R
E V
A P
O R
A T
O R
MANUAL GATE VALVE
UNION
FLOW DETECTION SENSORFS
THREE-WAY CONTROL VALVE
MANUAL THREE-WAY VALVE
THERMOSTATIC EXPANSION VALVE
DOMESTIC COLD WATERDCW
CHILLED WATER RETURNCHWR
CHILLED WATER SUPPLYCHWS
T
THERMOSTAT
SYMBOLS LEGEND
WATER COOLED CONDENSING UNIT SCHEDULE
SPACE DESIGN SYSTEM DESIGN EVAPORATOR BASIS OF DESIGN ELECTRICAL
UNIT CLASSIFICATION
DESIGN
TEMPERATURE
DAILY
TOTAL CAPACITY RUN TIME
REFRIGERANT
NUMBER OF
EVAPORATORS
UPPER
SUCTION
TEMP
UPPER
SUCTION
CAPACITY
LOWER
SUCTION
TEMP
LOWER
SUCTION
CAPACITY
SUCTION
TEMPERATURE VOLTAGE
PHASE
FREQ.
(°F) (BTU/DAY) (BTUH) (HRS/DAY) (°F) (BTUH) (°F) (BTUH) (°F) VOLTS Hz
COOLER REFRIGERATED
VESTIBULE 35 104490 5805 18 R404A 1 30 6480 20 5270 24 208 3 60
FREEZER MIXED VEGETABLES -12 524700 29150 18 R404A 1 -10 36440 -20 27930 -15 208 3 60
NOTES:
1. SPACE CLASSIFICATIONS ARE BASED ON ASHRAE HANDBOOK
2. SEE DETAILED CALCULATIONS FOR SPACE AND SYSTEM DESIGN RESULTS
3. CONTRACTOR SHALL PROVIDE CALCULATIONS FROM MANUFACTURER TO SUPPORT FINAL…