SCALE: NONE
KEY PLAN
COVER SHEET
ADD BACKUP COOLING FOR CATH LAB
09-15-2017 MA JRD
528A7-18-778
BLDG 1
GI-001
DRAWING TITLE
APPROVED PROJECT DIRECTOR
PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISIONS DATE
SYRACUSE VA
MEDICAL CENTER
ENGINEERING
DEPARTMENT
ISSUED DATE
800 IRVING AVE. SYRACUSE, NY 13210
DWG.
FRANI, CHRISTOPHER
AREA OF WORK
DISCIPLINE SHEET NO. TITLE
AutoCAD SHX Text DEPARTMENT OF VETERANS AFFAIRS PROJECT NO. 528A7-18-778 VA MEDICAL CENTER BUILDING NO.1 800 IRVING AVENUE SYRACUSE, NEW YORK, 13210
AutoCAD SHX Text
SYRACUSE VAMC ADD BACKUP COOLING FOR CATH LAB
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DRAWING SYMBOLS
XXX
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION NUMBER
DRAWING NUMBER WHERE DRAWN
XXX
KEY NOTE SYMBOL
MULTIPLE KEY NOTES APPLYING TO THE
SAME ITEM
PIPING SYMBOLS
HIGH PRESSURE STEAM CONDENSATE RETURN
HIGH PRESSURE STEAM (60 PSIG AND ABOVE)
HOT WATER HEATING SUPPLY
CONDENSATE PUMP DISCHARGE
LOW PRESSURE STEAM CONDENSATE RETURN
LOW PRESSURE STEAM (15 PSIG AND BELOW)
VENT LINE
GLYCOL-WATER HEATING RETURN
GLYCOL-WATER HEATING SUPPLY
CHILLED WATER SUPPLY
CHILLED WATER RETURN
DRAIN LINE
MAKE-UP WATER
CHILLED GLYCOL-WATER RETURN
CHILLED GLYCOL-WATER SUPPLY
HOT WATER HEATING RETURN
V
CHWR
GCR
GCS
MW
D
GLYCOL-WATER RUN AROUND SUPPLY
GLYCOL-WATER RUN AROUND RETURN
CF CHEMICAL FEED
TUBE CLEANER WATER SUPPLYTC
A
OFL
COMPRESSED AIR
OVERFLOW
COLD WATER (CITY WATER)
HW
SW
CW
HOT WATER
SOFTENED WATER
ANCHOR
REDUCER OR INCREASER
DIRECTION OF FLOW
SIDE CONNECTION
ECCENTRIC REDUCER
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
DIRECTION OF PIPE PITCH (DOWN) 1/8" PER FOOT
UNION
RISE OR DROP IN PIPE
CAPPED OUTLET
PRESSURE GAGE
THERMOMETER
FLOW ELEMENT
FLOAT & THERMOSTATIC TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
FE
PIPE UP
PIPE DOWN
REFRIGERANT SIGHT GLASS
TEST PLUG (PRESSURE/TEMPERATURE)
AUTOMATIC AIR VENT
AV
MANUAL AIR VENT
MV
THERMODYNAMIC TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
QUICK-COUPLE HOSE CONNECTOR
VALVE SYMBOLS
BALL VALVE
GATE VALVE WITH 3/4" HOSE ADAPTER
CHECK VALVE
ANGLE GLOBE VALVE
BUTTERFLY VALVE
MODULATING CONTROL VALVE
TWO POSITION CONTROL VALVE
THREE-WAY MODULATING CONTROL VALVE
AUTOMATIC BALANCING CONTROL VALVE
PRESSURE SAFETY VALVE
GATE VALVE - THREADED/FLANGED
GLOBE VALVE - THREADED/FLANGED
PRESSURE REGULATING VALVE
THREE-WAY TWO POSITION CONTROL VALVE
WYE STRAINER (WITH BALL VALVE &
FLEXIBLE CONNECTION
WATER BALANCE DEVICE
MODULATING CONTROL BUTTERFLY VALVE
CIRCUIT SETTER VALVE
GATE VALVE WITH GLOBE-VALVED BYPASS
PLUG VALVE
CONTROL VALVE (CV) - FLOAT-OPERATED
PRESSURE REDUCING VALVE (PRV)
QUICK-COUPLE HOSE CONNECTOR
WYE STRAINER WITH VALVED DRAIN AND
HOSE CONNECTION)
INSTALLATION OF NEW WORK.
LIMIT OF DEMOLITION
(WALL TYPE)
(WALL TYPE)
DN
DN
UP
UP
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
ROUND AND SQUARE 4-WAY CEILING DIFFUSERS
SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)
EXHAUST OR RETURN CEILING REGISTER OR GRILLE
EXHAUST OR RETURN BOTTOM REGISTER OR GRILLE
EXHAUST OR RETURN REGISTER OR TOP GRILLE
VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF
CONNECT NEW DUCT TO EXISTING DUCT
D
INCLINED RISE, IN DIRECTION OF AIR FLOW
INCLINED DROP, IN DIRECTION OF AIR FLOW
R
DNUP
RETURN DUCT (UP & DOWN)
SQUARE 3-WAY CEILING DIFFUSERS
SQUARE 2-WAY CEILING DIFFUSERS
SQUARE 1-WAY CEILING DIFFUSERS
FC
10x8
FLEXIBLE CONNECTION, EQUIPMENT,
VANED ELBOW (PROVIDE ALL SQUARE OR
RECTANGULAR ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
VANED ELBOW (SHORT RADIUS)
STANDARD RADIUS ELBOW (LONG RADIUS)
NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)
EXISTING DUCT TO REMAIN
VD
FLEXIBLE DUCTWORK (INSULATED)
MANUAL VOLUME DAMPER
EXISTING DUCT TO BE REMOVED
VIBRATION, OR SEISMIC
SUPPLY
RETURN
45°
RETURN, NO SPLITTER (45° TAP)
STANDARD BRANCH SUPPLY OR
45°
2 1
POINT OF CHANGE IN DUCT CONSTRUCTION BY
STATIC PRESSURE CLASS. THE NUMBER ASSIGNS
PRESSURE CLASS (IN. OF WATER) WHICH WILL
ACCOMMODATE MAXIMUM OPERATING PRESSURE
1/2
IN THE DUCT SUBSECTION. THE SYMBOL CONTINUES
THE ASSIGNMENT UNTIL THE DUCT TERMINATES OR
ANOTHER SYMBOL APPEARS. A "N" SUPERSCRIPT
INDICATES NEGATIVE PRESSURE.
AUTOMATIC CONTROL DAMPER MODULATING
AUTOMATIC CONTROL DAMPER TWO POSITION
SMOKE DETECTOR - DUCT MOUNTED
SMOKE DAMPER
SD
F/S DPR
COMBINATION FIRE/SMOKE DAMPER
REVERSE OSMOSIS
RO
EQUIPMENT TAG
EQUIPMENT ABBREVIATION (SUPPLY FAN)
EQUIPMENT NUMBER
SD
1-SF-1
AHU THAT SERVES THE EQUIPMENT
EXISTING DUCTWORK, PIPE OR EQUIPMENT TO BE REMOVED
1 HR FIRE RATED WALL
2 HR FIRE RATED WALL
SMOKE WALL
AREA OF WORK
MD
DRAWING TITLE
APPROVED PROJECT DIRECTOR
PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISIONS DATE
SYRACUSE VA
MEDICAL CENTER
ENGINEERING
DEPARTMENT
ISSUED DATE
800 IRVING AVE. SYRACUSE, NY 13210
DWG.
FRANI, CHRISTOPHER
SYMBOLS LIST, ABBREVIATIONS, & NOTES
ADD BACKUP COOLING FOR CATHLAB
09/15/2017 MA JRD
BLDG 1
MG-001
GHR
GRR
AutoCAD SHX Text
(NOTE: NOT ALL ABBREVIATIONS MAY APPEAR ON DRAWINGS)
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
S
S
R.D.
R.D.
S
S
AC-19
R.D.
SS
S
S
LADDER
RF-47
R.D.
R.D.
S
S
S
S
EXIST. DOOR
AC-47B
1 SETS
" REFRIGERANT LIQUID LINE
" REFRIGERANT SUCTION LIQUID LINE
ACCU-47
P R
E F
I L T
E R
D X
C C
H W
C
C C
UNIT
ON STEEL
DUNNAGE
REFER TO
STRUCTURAL
DRAWINGS
P R
E F
I L T
E R
SF-47AC-47
A F
T E
R
F
I L T
E R
EF3-2
EF3-4
EF3-1
EF3-3
AIR DIFFUSER SECTION
AFTER FILTER
DISCHARGE PLENUM
SARA
CONNECTOR
(TYPICAL)
FLEX
RETURN SECTION
RF-47
SF-47
CC-47
HWC-47
PRE-FILTER 2
NEW DX
COOLING COIL
NEW STAINLESS STEEL
DRAIN PAN
DRAWING TITLE
APPROVED PROJECT DIRECTOR
PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISIONS DATE
SYRACUSE VA
MEDICAL CENTER
ENGINEERING
DEPARTMENT
ISSUED DATE
800 IRVING AVE. SYRACUSE, NY 13210
DWG.
MECHANICAL REFRIGERANT PIPING ROOF PLAN
09/15/2017
MA
JRD
528A7-18-778
BLDG 1
MP-101
SCALE: 1/4" = 1'-0"
MECHANICAL EQUIPMENT PART ROOF PLAN
MP-103
SCALE: 1/4" = 1'-0"
MECHANICAL EQUIPMENT ROOF PARTS PLAN
MP-103
NOTES:
1. PROVIDE EXTERNAL PIPE ENCLOSURES TO PROTECT PIPE RUNOUTS FROM WEATHER.
ALL CONTROL VALVES TO BE LOCATED BELOW ROOF AND MADE ACCESSIBLE.
2. INSTALL NEW DX COOLING COIL, (DXCC-47), AND NEW DRAIN PAN IN LOCATION OF
PREVIOUSLY REMOVED SUPPLY HEAT RECOVERY COIL.
NOTE: INSTALL NEW ACCU-47, STRUCTURAL STEEL, SUPPORTS, DRAIN PIPING,
REFRIGERATION LINES AND ACCESSORIES PER DETAILS AND SCHEDULES ON MG-501.
AutoCAD SHX Text
AC
AutoCAD SHX Text
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NTS
DRAW THRU
BLOW THRU
2" PLUS X
1" MINIMUM
X
2X
UNIT TYPE
A B
WHERE X = STATIC PRESSURE IN PAN
DRAIN LINE SHALL BE AT LEAST THE SAME SIZE AS
THE NIPPLE ON THE DRAIN PAN
PIPING SHALL BE RIGID COPPER TYPE L OR TYPE M
UNLESS NOTE BELOW IS MET
PITCH DOWN TOWARD
DRAIN
CLEAN OUT
ROOF DRAIN
DRAIN PAN
NOTE:
1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY LOCAL VA AND IS INDOORS
AND DOES NOT PASS THROUGH RATED BARRIERS.
2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS ARE TO BE
CONNECTED.
A B
DIELECTRIC
FITTING
NTS
m m m m
M
I N m m
8"x8"x3/8"
[203x203x8.0mm] STEEL
PLATE
WELD PLATE TO
PIPE
SECURE TO ROOF SLAB WITH (4)
3/8" [8.0mm]Ø EXPANSION BOLTS
OR WELD TO STEEL DECK
CONCRETE ROOF SLAB OR
STEEL ROOF DECK
ROOF SYSTEM
INSULATION AND
MEMBRANE
PRE-MOULDED FLEXIBLE
PIPE COUNTER FLASHING
CLAMPING RING
ROOF SURFACE
WELD PIPE SADDLE
SUPPORT TO PIPE.
PROVIDE WATER TIGHT
CONNECTION
HIGH COMPRESSIVE
STRENGTH INSULATION
INSERT UNDER SHIELD
PIPE AND
INSULATION
INSULATION
PROTECTION
SHIELD
SEALANT
2" [50mm] STEEL
PIPE
2-1/2" [65mm] STEEL PIPE
PROVIDE ALUMINUM
JACKET
NOTES:
PROVIDE RESTRAINING CLAMPS 8'-0" [2438] O.C.
SHUT-OFF
VALVE
SHUT-OFF
VALVE
CHECK
VALVE
SHUT-OFF VALVE
(UNIT OPTIONAL)
NTS
NTS
DRAWING TITLE
APPROVED PROJECT DIRECTOR
PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISIONS DATE
SYRACUSE VA
MEDICAL CENTER
ENGINEERING
DEPARTMENT
ISSUED DATE
800 IRVING AVE. SYRACUSE, NY 13210
DWG.
MECHANICAL DETAILS AND SCHEDULES
BLDG 1
MG-501
AutoCAD SHX Text
AutoCAD SHX Text
AIR HANDLING UNIT DRAIN TRAP DETAIL
AutoCAD SHX Text
AutoCAD SHX Text
DETAIL FOR SUPPORTING PIPE ON ROOF
AutoCAD SHX Text
EVAPORATOR
AutoCAD SHX Text
COIL MODULE
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
CONDENSING UNIT
AutoCAD SHX Text
ACCESS PORT
AutoCAD SHX Text
4. LIQUID LINE
AutoCAD SHX Text
5. SHUT-OFF VALVE
AutoCAD SHX Text
7. LIQUID LINE FILTER DRIER
AutoCAD SHX Text
6. ACCESS PORT
AutoCAD SHX Text
5. SHUT-OFF VALVE
AutoCAD SHX Text
8. SOLENOID VALVE
AutoCAD SHX Text
9. MOISTURE AND LIQUID INDICATOR
AutoCAD SHX Text
11. EXPANSION VALVE
AutoCAD SHX Text
10. FROSTAT
AutoCAD SHX Text
12. EVAPORATOR COIL
AutoCAD SHX Text
2. SUCTION LINE FILTER
AutoCAD SHX Text
1. SUCTION SUCTION LINE
AutoCAD SHX Text
ACCESS PORT
AutoCAD SHX Text
ACCESS PORT
AutoCAD SHX Text
PRESSURE REDUCE VALVE
AutoCAD SHX Text
%%USUCTION LINE
AutoCAD SHX Text
1. INTERCONNECTED TUBING (SUCTION LINE)
AutoCAD SHX Text MAXIMUM OF 50 FEET IF CONDENSER IS ABOVE EVAPORATOR (IF RISE MORE THAN 50FEET, THE APPLICATION MUST BE VIEWED BY TRANE) REFER TO SS-APG012-EN FOR MORE
AutoCAD SHX Text
DETAILS.
AutoCAD SHX Text
2.SUCTION LINE
AutoCAD SHX Text FILTER DRIER 1 / CKT SUCTION FILTER SHOULD BE THE REPLACEABLE-CORE TYPE, AND A CLEAN CORE SHOULD BE INSTALLED AFTER THE SYSTEM IS CLEANED UP.
AutoCAD SHX Text
3.SHUT-OFF VALVE
AutoCAD SHX Text
MANUAL BALL VALVE FOR 2 1/8" TUBING.
AutoCAD SHX Text
LIQUID LINES
AutoCAD SHX Text
4.INTERCONNECTED TUBING (LIQUID LINES)
AutoCAD SHX Text REFER TO APPLICATIONS GUIDE SS-APG012-EN FOR VERTICAL & HORIZONTAL PIPING LIMITATIONS.
AutoCAD SHX Text
5.SHUT-OFF VALVE
AutoCAD SHX Text
2 MANUAL BALL VALVES
AutoCAD SHX Text
6.ACCESS PORT
AutoCAD SHX Text PORT USED TO DETERMINE SUCTION PRESSURE. THIS PORT IS USUALLY A SCHRAEDER VALVE WITH A CORE.
AutoCAD SHX Text
7.LIQUID LINE
AutoCAD SHX Text FILTER DRIER 1 / CKT LIQUID FILTER SHOULD BE THE REPLACEABLE-CORE TYPE, AND A CLEAN CORE SHOULD BE INSTALLED AFTER THE SYSTEM IS CLEANED UP.
AutoCAD SHX Text
8.SOLENOID VALVES
AutoCAD SHX Text LIQUID LINES REQUIRE A FIELD SUPPLIED AND INSTALLED ISOLATION VALVE 10 FEET OF THE EVAPORATOR. THE SUGGESTED SOLENOID USES A 120-VOLT SERVICE AND REQUIRES
AutoCAD SHX Text
CODE-COMPLIANT WIRING TO THE RAUJ CONDENSING UNIT.
AutoCAD SHX Text
9.MOISTURE AND LIQUID INDICATOR
AutoCAD SHX Text
ONE MOISTURE-INDICATING SIGHT GLASS IS TO BE INSTALLED IN THE MAIN LIQUID LINE.
AutoCAD SHX Text
AutoCAD SHX Text
REFRIGERANT PIPING DETAIL
AutoCAD SHX Text
AutoCAD SHX Text
DXCC-47 REFRIGERANT PIPING DETAIL
AutoCAD SHX Text Scale: N.T.S
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
KILOVOLT
KILOWATT
LIGHTING
KILOVOLT AMPERE
THOUSAND CIRCULAR MILS
KILOWATT HOUR
JUNCTION BOX
MAIN DISTRIBUTION PANEL
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
JB
KV
KCMIL
KW
KWH
LTG
KVA
MCMCB
MCC
MDP
MOUNTED
NEUTRAL
POLE
NORMALLY CLOSED
NORMALLY OPEN
NEW
MTD
N
NC
NO
P
(N)
PHASE
POWER
PANEL
RELOCATED EXISTING
PULL BOX
AND RETURN TO OWNER
EXISTING TO BE REMOVED
SCHEDULE
RECEPTACLE
PB
Ø
PNL
(RE)
PWR
(RRO)
RECEPT,REC
SCHED,SCH
MH MANHOLE
SINGLE POLE1P
TWO POLE
AMPERE
THREE POLE
AMERICAN WIRE GAUGE
2P
3P
A
AWG
ATS
AFF
AIC
CEILING
CIRCUIT
CABINET
CONDUIT
CIRCUIT BREAKER
COPPER
CONNECTED
CONTINUATION
CONTROL
C
CB
Cu.
CTL
CONN
CONT
CCTV
CLG
CKT
CAB
DEGREE FAHRENHEIT
DISCONNECT
DIVISION
DEGREE CELSIUS
DIAMETER
DEGREE
EACH
EXISTING TO REMAIN
ELECTRICAL
EMERGENCY
°C
°F
DP
EA
EC
EM
ELEC
(ER)
(E)
DISC
DIV
DIA
DEG
BUILDINGBLDG
CLOSED CIRCUIT TELEVISION
DISTRIBUTION PANEL BOARD
ELECTRICAL CONTRACTOR
EXISTING TO BE REMOVED
ABOVE FINISHED FLOOR
AMPERE INTERRUPTING CAPACITY
AUTOMATIC TRANSFER SWITCH
(NOT ALL ABBREVIATIONS ARE NECESSARILY
ABBREVIATIONS
SPEAKER
SWITCH
SYSTEMS
SPECIFICATIONSPEC
SP
SW
SYS
VOLT OR VOLTAGE
UNLESS OTHERWISE NOTED
TRANSFORMER
V
UON
XFMR
FIRE ALARM
EXISTING
FULL LOAD AMPERES
FLEXIBLE
FLUORESCENT
FIXTURE
FLOOR
FEEDER
FA
FL
FLA
FLEX
FLUOR
FDR
FIXT
FACP
FAP
(ERR)
EXIST,EX
HORSE POWER
HERTZ
GROUND
GENERATOR
ISOLATED GROUND
INCANDESCENT
G
HZ
IG
INCAND
GEN
GFI
HP
EXISTING TO BE REMOVED & RELOCATED
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
GROUND FAULT INTERRUPTER
CB
100/60/3
100A/3P
P
J
J
J
K
D = DOOR
a
S
POWER SYMBOLS
3 = THREE-WAY
2 = DOUBLE POLE
K = KEY OPERATED
4 = FOUR-WAY
SINGLE POLE SWITCH
a = CONTROLS SWITCH LEG 'a'
ELECTRICAL SYMBOLS LIST
(NOT ALL SYMBOLS ARE NECESSARILY USED ON THIS PROJECT)
500KVA
120/208
480V
4P
100A
ATS
100/3
MOTOR
Y
M
90/3
G
100/90/3
M
400/5
TRANSFORMER
a
S m a
GFI TYPE.
TYPE AS NOTED ON DRAWING
A
# = WATTAGE RATING
T = TIMER SWITCH
P = PILOT LIGHT
PHOTO CONTROL SWITCH
MOTOR RATED, 20A, 1P, UON
OCCUPANCY SENSOR, WALL MOUNTED. LETTER INDICATES TYPE.
OCCUPANCY SENSOR, CEILING MOUNTED. LETTER INDICATES TYPE.
MO = MOMENTARY CONTACT
DISCONNECT SWITCH - TOGGLE TYPE
20A, 125V DUPLEX RECEPTACLE - FLUSH WALL MOUNTED
CONTROLLED FROM WALL SWITCH 'a'
SINGLE RECEPTACLE - FLUSH WALL MOUNTED
20A, 125V DUPLEX RECEPTACLE FLUSH WALL MOUNTED
20A, 125V ISOLATED GROUND, DUPLEX RECEPTACLE, FLUSH
20A, 125V EMERGENCY DUPLEX RECEPTACLE
FLUSH WALL MOUNTED
WALL MOUNTED
SPECIAL PURPOSE RECEPTACLE - FLUSH WALL MOUNTED
- WITH SPECIAL PURPOSE RECEPTACLES WHERE INDICATED
20A, 125V DUPLEX RECEPTACLE FLUSH FLOOR MOUNTED
20A, 125V QUADRUPLEX RECEPTACLE FLUSH FLOOR MOUNTED
PLUG-IN SURFACE METAL RACEWAY - LETTER INDICATES TYPE
20A, 125V QUADRUPLEX RECEPTACLE - FLUSH WALL MOUNTED
WALL DIMMER - TYPE 'a'
A
VOLTAGE RATING & STARTER SIZE AS REQ'D
SWITCH AMPS / FUSE AMPS / # OF POLES,
CIRCUIT BREAKER - MOLDED CASE TYPE
VOLTAGES, WINDINGS AND SIZE AS INDICATED
AMP TRIP / # OF POLES
COMBINATION MOTOR CONTROLLER AND
RATING & STARTER SIZE AS REQ'D
TRIP AMPS / # OF POLES, VOLTAGE
CIRCUIT BREAKER
CURRENT TRANSFORMER
NUMBER AND RATIO AS INDICATED
FUSED DISCONNECT SWITCH
COMBINATION MOTOR CONTROLLER AND
DIGITAL MULTIMETER
LT = LONG TIME SETTING
ST = SHORT TIME SETTING
I = INSTANTANEOUS SETTING
SINGLE LINE DIAGRAM SYMBOLS
GROUND CONNECTION
FUSED SWITCH
GENERATOR
POLES AND RATING AS NOTED
MTS = MANUAL TRANSFER
ATS = AUTOMATIC TRANSFER
AUTOMATIC TRANSFER SWITCH
POWER TRANSFORMER
EXISTING CONDUIT/EQUIPMENT TO REMAIN
SURFACE MOUNTED DISTRIBUTION PANELBOARD - 120/208 VOLT
EPO = EM. POWER OFF
H = HOLD UP
K = KEY OPERATED
P = PANIC
PUSH BUTTON
FLEXIBLE EQUIPMENT CONNECTION
CONDUIT STUB-UP WITH FLEXIBLE
EQUIPMENT CONNECTION
CONDUIT TURNING DOWN
CONDUIT TURNING UP
NEW UNDERGROUND/IN SLAB CONDUIT
CAPPED CONDUIT
NEW EXPOSED CONDUIT
NEW CONCEALED CONDUIT
EXISTING CONDUIT TO BE REMOVED
POWER POLE
PULLBOX
FLUSH FLOOR MOUNTED JUNCTION BOX
FLUSH WALL MOUNTED JUNCTION BOX
CEILING MOUNTED JUNCTION BOX
SWITCH AMPS/# OF POLES, VOLTAGE RATING AS REQUIRED
COMBINATION MOTOR CONTROLLER AND DISCONNECT SWITCH
USE 2#12, 1#12G IN 3/4"C. HOMERUN, U.O.N.
SURFACE MOUNTED BRANCH PANELBOARD - 120/208 VOLT
SWITCH AMPS/# OF POLES, VOLTAGE RATING AS REQUIRED
TRIP AMPS/# OF POLES, VOLTAGE RATING AS REQUIRED
FUSED DISCONNECT SWITCH; SWITCH AMPS/FUSE AMPS/
# OF POLES, VOLTAGE RATING AS REQUIRED
UNFUSED DISCONNECT SWITCH
NA = NONAUTOMATIC
ENCLOSED CIRCUIT BREAKER
MOTOR CONTROLLER
SECTION A
# = DRAWING NUMBER
100 AMP SWITCH - 90 AMP FUSE - 3 POLE
UNFUSED SWITCH - 100 AMP SWITCH - 3 POLE
NEW EMERGENCY CONDUIT
SPECIAL MOUNTING HEIGHT. COORDINATE
LOCATION WITH ARCHITECTURAL ELEVATIONS
LIGHTNING ARRESTER
DIRECT BURIED GROUND CONDUCTORG G
USED ON THIS PROJECT)
SHUNT TRIPST
AC = ABOVE COUNTER
GFI = WITH GROUND FAULT INTERRUPTER
AC = ABOVE COUNTER
AC = ABOVE COUNTER
POTENTIAL TRANSFORMERSPT'S
CURRENT TRANSFORMERSCT'S
TERMINAL BLOCK
GROUND FAULT PROTECTION
ELECTRICAL INTERLOCKING
SWITCH
CURRENT POWER TRANSFORMERSCPT'S
ZONE FIRE ALARM TERMINAL CABINETZFATC
FLOOR FIRE ALARM TERMINAL CABINETFFATC
UNSWITCHED, LIGHTING BRANCH WIRING SAME ASSOCIATED BRANCH
WIRING TO POWER SOURCE UNLESS OTHERWISE INDICATED.
ABOVE FINISHED GROUNDAFG
GROUND FAULT MONITORING ONLY (NO TRIP)
IG
EG EQUIPMENT GROUND
ELECTRIC WATER COOLEREWC
MOTOR
M
MOTOR - REMOVALS
M
WEATHER PROOFWP
J
DEMO CEILING MOUNTED JUNCTION BOX
PB
SURFACE MOUNTED BRANCH PANELBOARD - 277/480 VOLT
SURFACE MOUNTED DISTRIBUTION PANELBOARD - 277/480 VOLT
VFD = VARIABLE FREQUENCY DRIVE
100A/3P
100A/3P
HOMERUN CIRCUIT TO POWER SOURCE. NUMBER OF
ARROWS INDICATE NUMBER OF CIRCUITS.
CURRENT POWER TRANSFORMER
CIRCUIT BREAKER - DRAW OUT TYPE
GFI
EM
DRAWING TITLE
APPROVED PROJECT DIRECTOR
PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISIONS DATE
SYRACUSE VA
MEDICAL CENTER
ENGINEERING
DEPARTMENT
ISSUED DATE
800 IRVING AVE. SYRACUSE, NY 13210
DWG.
ELECTRICAL GENERAL NOTES & LEGEND
ADD BACKUP COOLING FOR CATHLAB
BLDG 1
E-001
AutoCAD SHX Text 90/3
AutoCAD SHX Text 100/90/3
AutoCAD SHX Text D
AutoCAD SHX Text
PC
AutoCAD SHX Text T
AutoCAD SHX Text
TB
AutoCAD SHX Text
GF
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text W1
AutoCAD SHX Text C1
AutoCAD SHX Text
GM
AutoCAD SHX Text
CPT
AutoCAD SHX Text
1200AF
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
A429
PANEL EQPL6-4
S
R.D.
S
S
R.D.
SS
S
S
LADDER
RF-47
R.D.
S
ACCU-47
P R
E F
I L
T E
R
H W
C
C C
P R
E F
I L
T E
R
SF-47AC-47
A F
T E
R
F
I L
T E
R
A325
EXISTING 4" CONDUIT SLEEVE FROM A325 CEILING TO A429 ELECT CLOSET FLOOR. ROOMS ARE STACKED VERTICALLY.
PROVIDE NEW 3P-90A 65KAIC CKT BKR AND MOUNTING HARDWARE IN EXISTING CUTLER-HAMMER PRL4 PANELBOARD
DESIGNATION E3A-HVD
EXISTING SQD NQOB PANELBOARD DESIGNATION EQPL6-4 .
(2) EXISTING EMPTY CONDUITS STUBBED UP ON OUTSIDE WALL FROM A429. (1) 3/4" , (1) 1-1/2"
PRIVIDE NEW
" AND 1-1/2" CONDUITS FROM NEW PULL BOX TO ACCU-47. USE THE
" CONDUIT FOR 120V CONVENIENCE
OUTLET AND THE 1-1/2" CONDUIT FOR THE 480V POWER.
PROVIDE NEW PULL BOX FOR THE 1-1/2" CONDUIT IN A249.
KEYED NOTES (FOR THIS DRAWING ONLY):
SCALE: 1/4" = 1'-0"
4TH FLOOR ROOF PLAN
E-102
SCALE: 1/2" = 1'-0"
3RD FLOOR ELECTRICAL PLAN
E102
ELECTRICAL PLAN
ADD BACKUP COOLING TO CATHLAB
09/15/2017
MA
JRD
528A7-18-778
BLDG 1
E-101
NEW DX
UNIT
(ACCU-47)
CONNECT NEW UNIT
TO EXISTING LIGHTNING PROTECTION
GFI
AUXILIARY POWER HEAVY DUTY DISCONNECT
3P-100A, 480V , NEMA 3R, (FUSE AT 80A) WITH
INTEGRAL CONVEINENCE RECEPTACLE.
EATON DH361NRKA1480 OR EQUAL.
DRAWING TITLE
APPROVED PROJECT DIRECTOR
PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISIONS DATE
SYRACUSE VA
MEDICAL CENTER
ENGINEERING
DEPARTMENT
ISSUED DATE
800 IRVING AVE. SYRACUSE, NY 13210
DWG.
FRANI, CHRISTOPHER
DRAWING TITLE
APPROVED PROJECT DIRECTOR
PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISIONS DATE
SYRACUSE VA
MEDICAL CENTER
ENGINEERING
DEPARTMENT
ISSUED DATE
800 IRVING AVE. SYRACUSE, NY 13210
DWG.
FRANI, CHRISTOPHER
PROVIDE NEW 3R PULL BOX
AutoCAD SHX Text
ELECT.
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
E3A-HVD
AutoCAD SHX Text (E)
AutoCAD SHX Text (E)
AutoCAD SHX Text (E)
AutoCAD SHX Text
4" CONDUIT SLEEVE AT CEILING
AutoCAD SHX Text
ELECT.
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DRAWING TITLE
APPROVED PROJECT DIRECTOR
PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISIONS DATE
SYRACUSE VA
MEDICAL CENTER
ENGINEERING
DEPARTMENT
ISSUED DATE
800 IRVING AVE. SYRACUSE, NY 13210
DWG.
FRANI, CHRISTOPHER
STRUCTURAL PLAN ADD BACKUP COOLING FOR CATH LAB
09/15/2017 MA JRD
528A7-18-778
BLDG 1
S-101
SCALE: 3/4" = 1'-0"
STEEL BEAM (NEW)
S101
SCALE: 1/8" = 1'-0"
ROOFING STRUCTURAL PLAN (EXISTING)
S101
SCALE: 1-1/2" = 1'-0"
EXTENSION AND PLATE
S101
SCALE: 1-1/2" = 1'-0"
DETAIL CONNECTION
S101
S-101
1. DESIGN STANDARDS: AISC MANUAL OF STEEL CONSTRUCTION, 8TH EDITION.
2. STEEL ASTM A-36, SHOP PRIME, TOUCH UP IN FIELD, AND PAINT PER
SPECIFICATION 099100.
3. ALL WELDING SHALL BE IN ACCORDANCE WITH AMERICAN WELDING SOCIETY
CODES, USING E70XX ELECTRODES. ALL WELDS SHALL BE FULL PENETRATION
OR WELDED BOTH SIDES. MINIMUM THROAT OF ALL WELDS TO BE 1/4".
4. CONTRACTOR TO VERIFY EXACT LOCATION WITH EXISTING STRUCTURE.
5. COORDINATE WITH COR FOR SUPPORT STEEL WITH MECHANICAL EQUIPMENT
SUPPLIER.
6. ALL BIDDERS ARE REQUIRED TO VISIT SITE AND FAMILIARIZE THEMSELVES
WITH EXISTING CONDITIONS AND ACCESSIBILITY.
7. BEFORE MAKING ANY CUT OUT'S, HOLES, OPENING, ETC IN EXISTING
STRUCTURE NOTIFY AND REVIEW WITH RESIDENT ENGINEER.
8. REPLACE ALL CONCRETE FIREPROOFING REMOVED OR DAMAGED DURING
CONSTRUCTION. THOROUGHLY CLEAN EXISTING CONCRETE; TREAT WITH
BONDING AGENT PER MANUFACTURERS SPECIFICATIONS ; PROVIDE AND
SECURE WIRE MESH TO EXISTING STEEL.
9. NEW STEEL USE AS NOTED ON DRAWING COORDINATE WITH MANUFACTURER
SPECIFICATIONS.
GENERAL NOTES:
AutoCAD SHX Text 19'-0"
AutoCAD SHX Text 19'-0"
AutoCAD SHX Text A
AutoCAD SHX Text 19'-6"
AutoCAD SHX Text 19'-6"
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text 19'-6"
AutoCAD SHX Text 19'-6"
AutoCAD SHX Text 10'-8 "78"
AutoCAD SHX Text 10'-8 "78"
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text 19'-6"
AutoCAD SHX Text 19'-6"
AutoCAD SHX Text G
AutoCAD SHX Text H
AutoCAD SHX Text 1.1
AutoCAD SHX Text 19'-6"
AutoCAD SHX Text 19'-6"
AutoCAD SHX Text J
AutoCAD SHX Text 13'-5 "12"
AutoCAD SHX Text 13'-5 "12"
AutoCAD SHX Text 2.8
AutoCAD SHX Text 18'-9 "12"
AutoCAD SHX Text 18'-9 "12"
AutoCAD SHX Text 19'-3"
AutoCAD SHX Text 19'-3"
AutoCAD SHX Text
AutoCAD SHX Text 3.6
AutoCAD SHX Text 13'-11 "12"
AutoCAD SHX Text 13'-11 "12"
AutoCAD SHX Text
LINE OF EXIST. BUILDING
AutoCAD SHX Text 6'-11 "14"
AutoCAD SHX Text 6'-11 "14"
AutoCAD SHX Text W12x19
AutoCAD SHX Text W12x30
AutoCAD SHX Text W12x19
AutoCAD SHX Text W12x26
AutoCAD SHX Text W12x26
AutoCAD SHX Text W12x14
AutoCAD SHX Text W12x14
AutoCAD SHX Text W12x14
AutoCAD SHX Text W12x14
AutoCAD SHX Text W12x30 (-2 ")12")
AutoCAD SHX Text W12x30 (-2 ")12")
AutoCAD SHX Text REINFORCED W12x40 (-2 ")12")
AutoCAD SHX Text W8x10
AutoCAD SHX Text W8x10
AutoCAD SHX Text W12x16
AutoCAD SHX Text W12x16
AutoCAD SHX Text W12x16
AutoCAD SHX Text W12x16
AutoCAD SHX Text W10x12
AutoCAD SHX Text W10x12
AutoCAD SHX Text W12x14 (-2 )12)
AutoCAD SHX Text W12x26
AutoCAD SHX Text W18x50
AutoCAD SHX Text W12x30
AutoCAD SHX Text W12x45 (-2 ")12")
AutoCAD SHX Text W18x35
AutoCAD SHX Text W18x35
AutoCAD SHX Text W12x19 (-2 )12)
AutoCAD SHX Text W12x19
AutoCAD SHX Text W18x46
AutoCAD SHX Text W14x22
AutoCAD SHX Text W16x26 (+2'-4 ")12")
AutoCAD SHX Text W18x46
AutoCAD SHX Text W18x35
AutoCAD SHX Text W16x36 (+2'-4 ")12")
AutoCAD SHX Text W16x31
AutoCAD SHX Text W16x36 (+2'-4 ")12")
AutoCAD SHX Text W16x26 (+2'-4 ")12")
AutoCAD SHX Text W16x45 (+2'-4 ")12")
AutoCAD SHX Text W16x26 (+2'-4 ")12")
AutoCAD SHX Text W16x45 (+2'-4 ")12")
AutoCAD SHX Text W16x36 (+2'-4 ")12")
AutoCAD SHX Text W16x36 (+2'-4 ")12")
AutoCAD SHX Text W16x36 (+2'-4 ")12")
AutoCAD SHX Text W16x36 (+2'-4 ")12")
AutoCAD SHX Text W16x36 (+2'-4 ")12")
AutoCAD SHX Text W10x19
AutoCAD SHX Text W8x10
AutoCAD SHX Text W8x10
AutoCAD SHX Text W8x24 POST BRG. ON W12x45
AutoCAD SHX Text W8x24 POST BRG. ON W12x40
AutoCAD SHX Text W8x10
AutoCAD SHX Text W8x10
AutoCAD SHX Text D.8
AutoCAD SHX Text W16x26 (+2'-4 ")12")
AutoCAD SHX Text W10x19 (+2'-4 ")12")
AutoCAD SHX Text W8x10
AutoCAD SHX Text W8x10
AutoCAD SHX Text W18x35
AutoCAD SHX Text W18x35
AutoCAD SHX Text W18x35
AutoCAD SHX Text W18x35
AutoCAD SHX Text W18x35
AutoCAD SHX Text W18x35
AutoCAD SHX Text W18x35
AutoCAD SHX Text W10x19
AutoCAD SHX Text W18x35
AutoCAD SHX Text W18x35
AutoCAD SHX Text W8x10
AutoCAD SHX Text W8x10
AutoCAD SHX Text W10x19
AutoCAD SHX Text W12x19
AutoCAD SHX Text W12x19
AutoCAD SHX Text W8x10
AutoCAD SHX Text 7'-0"
AutoCAD SHX Text 7'-0"
AutoCAD SHX Text
EDGE OF ROOF DECK 1" FROM FACE OF EXIST. BUILDING U.N.O., VERIFY IN FIELD
AutoCAD SHX Text W8x10
AutoCAD SHX Text W8x10
AutoCAD SHX Text W8x10
AutoCAD SHX Text W8x10
AutoCAD SHX Text W8x10
AutoCAD SHX Text W8x10
AutoCAD SHX Text W8x10
AutoCAD SHX Text W8x10
AutoCAD SHX Text W8x10
AutoCAD SHX Text W8x10
AutoCAD SHX Text
MECHANICAL UNIT, OPERATING WT = 11,000#
AutoCAD SHX Text E.O.D. 10 "12"
AutoCAD SHX Text E.O.D. 6"
AutoCAD SHX Text E.O.D.
AutoCAD SHX Text W8x10
AutoCAD SHX Text 4x4x " ANGLE FRAMING SEE 38" ANGLE FRAMING SEE DETAIL 3/1-S2
AutoCAD SHX Text 4x4x " ANGLE 38" ANGLE FRAMING SEE DETAIL 3/1-S2
AutoCAD SHX Text
CLR.
AutoCAD SHX Text
CLR.
AutoCAD SHX Text E.O.D. 10 "12"
AutoCAD SHX Text
COL.<
AutoCAD SHX Text 6'-5"
AutoCAD SHX Text 6'-5"
AutoCAD SHX Text W6X15
AutoCAD SHX Text W6X15
AutoCAD SHX Text W6X15
AutoCAD SHX Text W6X15
AutoCAD SHX Text 14"
AutoCAD SHX Text 4"
AutoCAD SHX Text W6X15
AutoCAD SHX Text
EXISTING 18WX35
AutoCAD SHX Text
TYP.
AutoCAD SHX Text 14"
AutoCAD SHX Text 2 "X2 "X "12"X2 "X "12"X "516"
AutoCAD SHX Text
TYP.
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
| E-001 Electrical General Notes and Legend-E-001 |
| Sheets and Views |
| E-001 |
| E-101 Electrical Power Plan-E-101 |
| Sheets and Views |
| E-101 |
| GI-001 COVER SHEET-GI-001 |
| Sheets and Views |
| GI-001 |
| MG-001 SYMBOLS LIST, ABBREVIATIONS & NOTES-MG-001 |
| Sheets and Views |
| MG-001 |
| MG-501 HVAC DETAILS-MG-501 |
| Sheets and Views |
| MG-501 |
| MP-103 MECHANICAL EQUIPMENT(ROOF)-MP-103 |
| Sheets and Views |
| MP-103 |
| S-101-S-101 |
| Sheets and Views |
| S-101 |
File details come from the government source that posted it.