36C24218B0069-00001001.pdf

PDF 5 MB Posted

Attached to
BACKUP COOLING FOR CATH LAB Federal contract opportunity
Solicitation number
36C24218B0069
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

36C24218B0069 00001 528A7-18-778 Drawings.pdf

View the file

Other files for this federal contract opportunity

Other files attached to BACKUP COOLING FOR CATH LAB, newest first.
File Type Posted
36C24218C0040-000.docx DOCX document
36C24218B0069-00001000.docx DOCX document
36C24218B0069-002.pdf PDF
36C24218B0069-001.docx DOCX document
36C24218B0069-003.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SCALE: NONE

KEY PLAN

COVER SHEET

ADD BACKUP COOLING FOR CATH LAB

09-15-2017 MA JRD

528A7-18-778

BLDG 1

GI-001

DRAWING TITLE

APPROVED PROJECT DIRECTOR

PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

DRAWING NUMBER

BUILDING NUMBER

PROJECT NUMBER

REVISIONS DATE

SYRACUSE VA

MEDICAL CENTER

ENGINEERING

DEPARTMENT

ISSUED DATE

800 IRVING AVE. SYRACUSE, NY 13210

DWG.

FRANI, CHRISTOPHER

AREA OF WORK

DISCIPLINE SHEET NO. TITLE

AutoCAD SHX Text DEPARTMENT OF VETERANS AFFAIRS PROJECT NO. 528A7-18-778 VA MEDICAL CENTER BUILDING NO.1 800 IRVING AVENUE SYRACUSE, NEW YORK, 13210

AutoCAD SHX Text

SYRACUSE VAMC ADD BACKUP COOLING FOR CATH LAB

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DRAWING SYMBOLS

XXX

DETAIL NUMBER

DRAWING NUMBER WHERE SHOWN

SECTION NUMBER

DRAWING NUMBER WHERE DRAWN

XXX

KEY NOTE SYMBOL

MULTIPLE KEY NOTES APPLYING TO THE

SAME ITEM

PIPING SYMBOLS

HIGH PRESSURE STEAM CONDENSATE RETURN

HIGH PRESSURE STEAM (60 PSIG AND ABOVE)

HOT WATER HEATING SUPPLY

CONDENSATE PUMP DISCHARGE

LOW PRESSURE STEAM CONDENSATE RETURN

LOW PRESSURE STEAM (15 PSIG AND BELOW)

VENT LINE

GLYCOL-WATER HEATING RETURN

GLYCOL-WATER HEATING SUPPLY

CHILLED WATER SUPPLY

CHILLED WATER RETURN

DRAIN LINE

MAKE-UP WATER

CHILLED GLYCOL-WATER RETURN

CHILLED GLYCOL-WATER SUPPLY

HOT WATER HEATING RETURN

V

CHWR

GCR

GCS

MW

D

GLYCOL-WATER RUN AROUND SUPPLY

GLYCOL-WATER RUN AROUND RETURN

CF CHEMICAL FEED

TUBE CLEANER WATER SUPPLYTC

A

OFL

COMPRESSED AIR

OVERFLOW

COLD WATER (CITY WATER)

HW

SW

CW

HOT WATER

SOFTENED WATER

ANCHOR

REDUCER OR INCREASER

DIRECTION OF FLOW

SIDE CONNECTION

ECCENTRIC REDUCER

BOTTOM CONNECTION, 45° OR 90°

TOP CONNECTION, 45° OR 90°

DIRECTION OF PIPE PITCH (DOWN) 1/8" PER FOOT

UNION

RISE OR DROP IN PIPE

CAPPED OUTLET

PRESSURE GAGE

THERMOMETER

FLOW ELEMENT

FLOAT & THERMOSTATIC TRAP SET INCLUDING

PIPING ACCESSORIES SEE DETAIL

FE

PIPE UP

PIPE DOWN

REFRIGERANT SIGHT GLASS

TEST PLUG (PRESSURE/TEMPERATURE)

AUTOMATIC AIR VENT

AV

MANUAL AIR VENT

MV

THERMODYNAMIC TRAP SET INCLUDING

PIPING ACCESSORIES SEE DETAIL

QUICK-COUPLE HOSE CONNECTOR

VALVE SYMBOLS

BALL VALVE

GATE VALVE WITH 3/4" HOSE ADAPTER

CHECK VALVE

ANGLE GLOBE VALVE

BUTTERFLY VALVE

MODULATING CONTROL VALVE

TWO POSITION CONTROL VALVE

THREE-WAY MODULATING CONTROL VALVE

AUTOMATIC BALANCING CONTROL VALVE

PRESSURE SAFETY VALVE

GATE VALVE - THREADED/FLANGED

GLOBE VALVE - THREADED/FLANGED

PRESSURE REGULATING VALVE

THREE-WAY TWO POSITION CONTROL VALVE

WYE STRAINER (WITH BALL VALVE &

FLEXIBLE CONNECTION

WATER BALANCE DEVICE

MODULATING CONTROL BUTTERFLY VALVE

CIRCUIT SETTER VALVE

GATE VALVE WITH GLOBE-VALVED BYPASS

PLUG VALVE

CONTROL VALVE (CV) - FLOAT-OPERATED

PRESSURE REDUCING VALVE (PRV)

QUICK-COUPLE HOSE CONNECTOR

WYE STRAINER WITH VALVED DRAIN AND

HOSE CONNECTION)

INSTALLATION OF NEW WORK.

LIMIT OF DEMOLITION

(WALL TYPE)

(WALL TYPE)

DN

DN

UP

UP

SUPPLY DUCT (UP & DOWN)

EXHAUST DUCT (UP & DOWN)

ROUND AND SQUARE 4-WAY CEILING DIFFUSERS

SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)

EXHAUST OR RETURN CEILING REGISTER OR GRILLE

EXHAUST OR RETURN BOTTOM REGISTER OR GRILLE

EXHAUST OR RETURN REGISTER OR TOP GRILLE

VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF

CONNECT NEW DUCT TO EXISTING DUCT

D

INCLINED RISE, IN DIRECTION OF AIR FLOW

INCLINED DROP, IN DIRECTION OF AIR FLOW

R

DNUP

RETURN DUCT (UP & DOWN)

SQUARE 3-WAY CEILING DIFFUSERS

SQUARE 2-WAY CEILING DIFFUSERS

SQUARE 1-WAY CEILING DIFFUSERS

FC

10x8

FLEXIBLE CONNECTION, EQUIPMENT,

VANED ELBOW (PROVIDE ALL SQUARE OR

RECTANGULAR ELBOWS WITH VANES EVEN IF

SYMBOL IS MISSING)

VANED ELBOW (SHORT RADIUS)

STANDARD RADIUS ELBOW (LONG RADIUS)

NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)

EXISTING DUCT TO REMAIN

VD

FLEXIBLE DUCTWORK (INSULATED)

MANUAL VOLUME DAMPER

EXISTING DUCT TO BE REMOVED

VIBRATION, OR SEISMIC

SUPPLY

RETURN

45°

RETURN, NO SPLITTER (45° TAP)

STANDARD BRANCH SUPPLY OR

45°

2 1

POINT OF CHANGE IN DUCT CONSTRUCTION BY

STATIC PRESSURE CLASS. THE NUMBER ASSIGNS

PRESSURE CLASS (IN. OF WATER) WHICH WILL

ACCOMMODATE MAXIMUM OPERATING PRESSURE

1/2

IN THE DUCT SUBSECTION. THE SYMBOL CONTINUES

THE ASSIGNMENT UNTIL THE DUCT TERMINATES OR

ANOTHER SYMBOL APPEARS. A "N" SUPERSCRIPT

INDICATES NEGATIVE PRESSURE.

AUTOMATIC CONTROL DAMPER MODULATING

AUTOMATIC CONTROL DAMPER TWO POSITION

SMOKE DETECTOR - DUCT MOUNTED

SMOKE DAMPER

SD

F/S DPR

COMBINATION FIRE/SMOKE DAMPER

REVERSE OSMOSIS

RO

EQUIPMENT TAG

EQUIPMENT ABBREVIATION (SUPPLY FAN)

EQUIPMENT NUMBER

SD

1-SF-1

AHU THAT SERVES THE EQUIPMENT

EXISTING DUCTWORK, PIPE OR EQUIPMENT TO BE REMOVED

1 HR FIRE RATED WALL

2 HR FIRE RATED WALL

SMOKE WALL

AREA OF WORK

MD

DRAWING TITLE

APPROVED PROJECT DIRECTOR

PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

DRAWING NUMBER

BUILDING NUMBER

PROJECT NUMBER

REVISIONS DATE

SYRACUSE VA

MEDICAL CENTER

ENGINEERING

DEPARTMENT

ISSUED DATE

800 IRVING AVE. SYRACUSE, NY 13210

DWG.

FRANI, CHRISTOPHER

SYMBOLS LIST, ABBREVIATIONS, & NOTES

ADD BACKUP COOLING FOR CATHLAB

09/15/2017 MA JRD

BLDG 1

MG-001

GHR

GRR

AutoCAD SHX Text

(NOTE: NOT ALL ABBREVIATIONS MAY APPEAR ON DRAWINGS)

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

S

S

R.D.

R.D.

S

S

AC-19

R.D.

SS

S

S

LADDER

RF-47

R.D.

R.D.

S

S

S

S

EXIST. DOOR

AC-47B

1 SETS

" REFRIGERANT LIQUID LINE

" REFRIGERANT SUCTION LIQUID LINE

ACCU-47

P R

E F

I L T

E R

D X

C C

H W

C

C C

UNIT

ON STEEL

DUNNAGE

REFER TO

STRUCTURAL

DRAWINGS

P R

E F

I L T

E R

SF-47AC-47

A F

T E

R

F

I L T

E R

EF3-2

EF3-4

EF3-1

EF3-3

AIR DIFFUSER SECTION

AFTER FILTER

DISCHARGE PLENUM

SARA

CONNECTOR

(TYPICAL)

FLEX

RETURN SECTION

RF-47

SF-47

CC-47

HWC-47

PRE-FILTER 2

NEW DX

COOLING COIL

NEW STAINLESS STEEL

DRAIN PAN

DRAWING TITLE

APPROVED PROJECT DIRECTOR

PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

DRAWING NUMBER

BUILDING NUMBER

PROJECT NUMBER

REVISIONS DATE

SYRACUSE VA

MEDICAL CENTER

ENGINEERING

DEPARTMENT

ISSUED DATE

800 IRVING AVE. SYRACUSE, NY 13210

DWG.

MECHANICAL REFRIGERANT PIPING ROOF PLAN

09/15/2017

MA

JRD

528A7-18-778

BLDG 1

MP-101

SCALE: 1/4" = 1'-0"

MECHANICAL EQUIPMENT PART ROOF PLAN

MP-103

SCALE: 1/4" = 1'-0"

MECHANICAL EQUIPMENT ROOF PARTS PLAN

MP-103

NOTES:

1. PROVIDE EXTERNAL PIPE ENCLOSURES TO PROTECT PIPE RUNOUTS FROM WEATHER.

ALL CONTROL VALVES TO BE LOCATED BELOW ROOF AND MADE ACCESSIBLE.

2. INSTALL NEW DX COOLING COIL, (DXCC-47), AND NEW DRAIN PAN IN LOCATION OF

PREVIOUSLY REMOVED SUPPLY HEAT RECOVERY COIL.

NOTE: INSTALL NEW ACCU-47, STRUCTURAL STEEL, SUPPORTS, DRAIN PIPING,

REFRIGERATION LINES AND ACCESSORIES PER DETAILS AND SCHEDULES ON MG-501.

AutoCAD SHX Text

AC

AutoCAD SHX Text

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

NTS

DRAW THRU

BLOW THRU

2" PLUS X

1" MINIMUM

X

2X

UNIT TYPE

A B

WHERE X = STATIC PRESSURE IN PAN

DRAIN LINE SHALL BE AT LEAST THE SAME SIZE AS

THE NIPPLE ON THE DRAIN PAN

PIPING SHALL BE RIGID COPPER TYPE L OR TYPE M

UNLESS NOTE BELOW IS MET

PITCH DOWN TOWARD

DRAIN

CLEAN OUT

ROOF DRAIN

DRAIN PAN

NOTE:

1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY LOCAL VA AND IS INDOORS

AND DOES NOT PASS THROUGH RATED BARRIERS.

2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS ARE TO BE

CONNECTED.

A B

DIELECTRIC

FITTING

NTS

m m m m

M

I N m m

8"x8"x3/8"

[203x203x8.0mm] STEEL

PLATE

WELD PLATE TO

PIPE

SECURE TO ROOF SLAB WITH (4)

3/8" [8.0mm]Ø EXPANSION BOLTS

OR WELD TO STEEL DECK

CONCRETE ROOF SLAB OR

STEEL ROOF DECK

ROOF SYSTEM

INSULATION AND

MEMBRANE

PRE-MOULDED FLEXIBLE

PIPE COUNTER FLASHING

CLAMPING RING

ROOF SURFACE

WELD PIPE SADDLE

SUPPORT TO PIPE.

PROVIDE WATER TIGHT

CONNECTION

HIGH COMPRESSIVE

STRENGTH INSULATION

INSERT UNDER SHIELD

PIPE AND

INSULATION

INSULATION

PROTECTION

SHIELD

SEALANT

2" [50mm] STEEL

PIPE

2-1/2" [65mm] STEEL PIPE

PROVIDE ALUMINUM

JACKET

NOTES:

PROVIDE RESTRAINING CLAMPS 8'-0" [2438] O.C.

SHUT-OFF

VALVE

SHUT-OFF

VALVE

CHECK

VALVE

SHUT-OFF VALVE

(UNIT OPTIONAL)

NTS

NTS

DRAWING TITLE

APPROVED PROJECT DIRECTOR

PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

DRAWING NUMBER

BUILDING NUMBER

PROJECT NUMBER

REVISIONS DATE

SYRACUSE VA

MEDICAL CENTER

ENGINEERING

DEPARTMENT

ISSUED DATE

800 IRVING AVE. SYRACUSE, NY 13210

DWG.

MECHANICAL DETAILS AND SCHEDULES

BLDG 1

MG-501

AutoCAD SHX Text

AutoCAD SHX Text

AIR HANDLING UNIT DRAIN TRAP DETAIL

AutoCAD SHX Text

AutoCAD SHX Text

DETAIL FOR SUPPORTING PIPE ON ROOF

AutoCAD SHX Text

EVAPORATOR

AutoCAD SHX Text

COIL MODULE

AutoCAD SHX Text

(TYPICAL)

AutoCAD SHX Text

CONDENSING UNIT

AutoCAD SHX Text

ACCESS PORT

AutoCAD SHX Text

4. LIQUID LINE

AutoCAD SHX Text

5. SHUT-OFF VALVE

AutoCAD SHX Text

7. LIQUID LINE FILTER DRIER

AutoCAD SHX Text

6. ACCESS PORT

AutoCAD SHX Text

5. SHUT-OFF VALVE

AutoCAD SHX Text

8. SOLENOID VALVE

AutoCAD SHX Text

9. MOISTURE AND LIQUID INDICATOR

AutoCAD SHX Text

11. EXPANSION VALVE

AutoCAD SHX Text

10. FROSTAT

AutoCAD SHX Text

12. EVAPORATOR COIL

AutoCAD SHX Text

2. SUCTION LINE FILTER

AutoCAD SHX Text

1. SUCTION SUCTION LINE

AutoCAD SHX Text

ACCESS PORT

AutoCAD SHX Text

ACCESS PORT

AutoCAD SHX Text

PRESSURE REDUCE VALVE

AutoCAD SHX Text

%%USUCTION LINE

AutoCAD SHX Text

1. INTERCONNECTED TUBING (SUCTION LINE)

AutoCAD SHX Text MAXIMUM OF 50 FEET IF CONDENSER IS ABOVE EVAPORATOR (IF RISE MORE THAN 50FEET, THE APPLICATION MUST BE VIEWED BY TRANE) REFER TO SS-APG012-EN FOR MORE

AutoCAD SHX Text

DETAILS.

AutoCAD SHX Text

2.SUCTION LINE

AutoCAD SHX Text FILTER DRIER 1 / CKT SUCTION FILTER SHOULD BE THE REPLACEABLE-CORE TYPE, AND A CLEAN CORE SHOULD BE INSTALLED AFTER THE SYSTEM IS CLEANED UP.

AutoCAD SHX Text

3.SHUT-OFF VALVE

AutoCAD SHX Text

MANUAL BALL VALVE FOR 2 1/8" TUBING.

AutoCAD SHX Text

LIQUID LINES

AutoCAD SHX Text

4.INTERCONNECTED TUBING (LIQUID LINES)

AutoCAD SHX Text REFER TO APPLICATIONS GUIDE SS-APG012-EN FOR VERTICAL & HORIZONTAL PIPING LIMITATIONS.

AutoCAD SHX Text

5.SHUT-OFF VALVE

AutoCAD SHX Text

2 MANUAL BALL VALVES

AutoCAD SHX Text

6.ACCESS PORT

AutoCAD SHX Text PORT USED TO DETERMINE SUCTION PRESSURE. THIS PORT IS USUALLY A SCHRAEDER VALVE WITH A CORE.

AutoCAD SHX Text

7.LIQUID LINE

AutoCAD SHX Text FILTER DRIER 1 / CKT LIQUID FILTER SHOULD BE THE REPLACEABLE-CORE TYPE, AND A CLEAN CORE SHOULD BE INSTALLED AFTER THE SYSTEM IS CLEANED UP.

AutoCAD SHX Text

8.SOLENOID VALVES

AutoCAD SHX Text LIQUID LINES REQUIRE A FIELD SUPPLIED AND INSTALLED ISOLATION VALVE 10 FEET OF THE EVAPORATOR. THE SUGGESTED SOLENOID USES A 120-VOLT SERVICE AND REQUIRES

AutoCAD SHX Text

CODE-COMPLIANT WIRING TO THE RAUJ CONDENSING UNIT.

AutoCAD SHX Text

9.MOISTURE AND LIQUID INDICATOR

AutoCAD SHX Text

ONE MOISTURE-INDICATING SIGHT GLASS IS TO BE INSTALLED IN THE MAIN LIQUID LINE.

AutoCAD SHX Text

AutoCAD SHX Text

REFRIGERANT PIPING DETAIL

AutoCAD SHX Text

AutoCAD SHX Text

DXCC-47 REFRIGERANT PIPING DETAIL

AutoCAD SHX Text Scale: N.T.S

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

KILOVOLT

KILOWATT

LIGHTING

KILOVOLT AMPERE

THOUSAND CIRCULAR MILS

KILOWATT HOUR

JUNCTION BOX

MAIN DISTRIBUTION PANEL

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

JB

KV

KCMIL

KW

KWH

LTG

KVA

MCMCB

MCC

MDP

MOUNTED

NEUTRAL

POLE

NORMALLY CLOSED

NORMALLY OPEN

NEW

MTD

N

NC

NO

P

(N)

PHASE

POWER

PANEL

RELOCATED EXISTING

PULL BOX

AND RETURN TO OWNER

EXISTING TO BE REMOVED

SCHEDULE

RECEPTACLE

PB

Ø

PNL

(RE)

PWR

(RRO)

RECEPT,REC

SCHED,SCH

MH MANHOLE

SINGLE POLE1P

TWO POLE

AMPERE

THREE POLE

AMERICAN WIRE GAUGE

2P

3P

A

AWG

ATS

AFF

AIC

CEILING

CIRCUIT

CABINET

CONDUIT

CIRCUIT BREAKER

COPPER

CONNECTED

CONTINUATION

CONTROL

C

CB

Cu.

CTL

CONN

CONT

CCTV

CLG

CKT

CAB

DEGREE FAHRENHEIT

DISCONNECT

DIVISION

DEGREE CELSIUS

DIAMETER

DEGREE

EACH

EXISTING TO REMAIN

ELECTRICAL

EMERGENCY

°C

°F

DP

EA

EC

EM

ELEC

(ER)

(E)

DISC

DIV

DIA

DEG

BUILDINGBLDG

CLOSED CIRCUIT TELEVISION

DISTRIBUTION PANEL BOARD

ELECTRICAL CONTRACTOR

EXISTING TO BE REMOVED

ABOVE FINISHED FLOOR

AMPERE INTERRUPTING CAPACITY

AUTOMATIC TRANSFER SWITCH

(NOT ALL ABBREVIATIONS ARE NECESSARILY

ABBREVIATIONS

SPEAKER

SWITCH

SYSTEMS

SPECIFICATIONSPEC

SP

SW

SYS

VOLT OR VOLTAGE

UNLESS OTHERWISE NOTED

TRANSFORMER

V

UON

XFMR

FIRE ALARM

EXISTING

FULL LOAD AMPERES

FLEXIBLE

FLUORESCENT

FIXTURE

FLOOR

FEEDER

FA

FL

FLA

FLEX

FLUOR

FDR

FIXT

FACP

FAP

(ERR)

EXIST,EX

HORSE POWER

HERTZ

GROUND

GENERATOR

ISOLATED GROUND

INCANDESCENT

G

HZ

IG

INCAND

GEN

GFI

HP

EXISTING TO BE REMOVED & RELOCATED

FIRE ALARM CONTROL PANEL

FIRE ALARM ANNUNCIATOR PANEL

GROUND FAULT INTERRUPTER

CB

100/60/3

100A/3P

P

J

J

J

K

D = DOOR

a

S

POWER SYMBOLS

3 = THREE-WAY

2 = DOUBLE POLE

K = KEY OPERATED

4 = FOUR-WAY

SINGLE POLE SWITCH

a = CONTROLS SWITCH LEG 'a'

ELECTRICAL SYMBOLS LIST

(NOT ALL SYMBOLS ARE NECESSARILY USED ON THIS PROJECT)

500KVA

120/208

480V

4P

100A

ATS

100/3

MOTOR

Y

M

90/3

G

100/90/3

M

400/5

TRANSFORMER

a

S m a

GFI TYPE.

TYPE AS NOTED ON DRAWING

A

# = WATTAGE RATING

T = TIMER SWITCH

P = PILOT LIGHT

PHOTO CONTROL SWITCH

MOTOR RATED, 20A, 1P, UON

OCCUPANCY SENSOR, WALL MOUNTED. LETTER INDICATES TYPE.

OCCUPANCY SENSOR, CEILING MOUNTED. LETTER INDICATES TYPE.

MO = MOMENTARY CONTACT

DISCONNECT SWITCH - TOGGLE TYPE

20A, 125V DUPLEX RECEPTACLE - FLUSH WALL MOUNTED

CONTROLLED FROM WALL SWITCH 'a'

SINGLE RECEPTACLE - FLUSH WALL MOUNTED

20A, 125V DUPLEX RECEPTACLE FLUSH WALL MOUNTED

20A, 125V ISOLATED GROUND, DUPLEX RECEPTACLE, FLUSH

20A, 125V EMERGENCY DUPLEX RECEPTACLE

FLUSH WALL MOUNTED

WALL MOUNTED

SPECIAL PURPOSE RECEPTACLE - FLUSH WALL MOUNTED

- WITH SPECIAL PURPOSE RECEPTACLES WHERE INDICATED

20A, 125V DUPLEX RECEPTACLE FLUSH FLOOR MOUNTED

20A, 125V QUADRUPLEX RECEPTACLE FLUSH FLOOR MOUNTED

PLUG-IN SURFACE METAL RACEWAY - LETTER INDICATES TYPE

20A, 125V QUADRUPLEX RECEPTACLE - FLUSH WALL MOUNTED

WALL DIMMER - TYPE 'a'

A

VOLTAGE RATING & STARTER SIZE AS REQ'D

SWITCH AMPS / FUSE AMPS / # OF POLES,

CIRCUIT BREAKER - MOLDED CASE TYPE

VOLTAGES, WINDINGS AND SIZE AS INDICATED

AMP TRIP / # OF POLES

COMBINATION MOTOR CONTROLLER AND

RATING & STARTER SIZE AS REQ'D

TRIP AMPS / # OF POLES, VOLTAGE

CIRCUIT BREAKER

CURRENT TRANSFORMER

NUMBER AND RATIO AS INDICATED

FUSED DISCONNECT SWITCH

COMBINATION MOTOR CONTROLLER AND

DIGITAL MULTIMETER

LT = LONG TIME SETTING

ST = SHORT TIME SETTING

I = INSTANTANEOUS SETTING

SINGLE LINE DIAGRAM SYMBOLS

GROUND CONNECTION

FUSED SWITCH

GENERATOR

POLES AND RATING AS NOTED

MTS = MANUAL TRANSFER

ATS = AUTOMATIC TRANSFER

AUTOMATIC TRANSFER SWITCH

POWER TRANSFORMER

EXISTING CONDUIT/EQUIPMENT TO REMAIN

SURFACE MOUNTED DISTRIBUTION PANELBOARD - 120/208 VOLT

EPO = EM. POWER OFF

H = HOLD UP

K = KEY OPERATED

P = PANIC

PUSH BUTTON

FLEXIBLE EQUIPMENT CONNECTION

CONDUIT STUB-UP WITH FLEXIBLE

EQUIPMENT CONNECTION

CONDUIT TURNING DOWN

CONDUIT TURNING UP

NEW UNDERGROUND/IN SLAB CONDUIT

CAPPED CONDUIT

NEW EXPOSED CONDUIT

NEW CONCEALED CONDUIT

EXISTING CONDUIT TO BE REMOVED

POWER POLE

PULLBOX

FLUSH FLOOR MOUNTED JUNCTION BOX

FLUSH WALL MOUNTED JUNCTION BOX

CEILING MOUNTED JUNCTION BOX

SWITCH AMPS/# OF POLES, VOLTAGE RATING AS REQUIRED

COMBINATION MOTOR CONTROLLER AND DISCONNECT SWITCH

USE 2#12, 1#12G IN 3/4"C. HOMERUN, U.O.N.

SURFACE MOUNTED BRANCH PANELBOARD - 120/208 VOLT

SWITCH AMPS/# OF POLES, VOLTAGE RATING AS REQUIRED

TRIP AMPS/# OF POLES, VOLTAGE RATING AS REQUIRED

FUSED DISCONNECT SWITCH; SWITCH AMPS/FUSE AMPS/

# OF POLES, VOLTAGE RATING AS REQUIRED

UNFUSED DISCONNECT SWITCH

NA = NONAUTOMATIC

ENCLOSED CIRCUIT BREAKER

MOTOR CONTROLLER

SECTION A

# = DRAWING NUMBER

100 AMP SWITCH - 90 AMP FUSE - 3 POLE

UNFUSED SWITCH - 100 AMP SWITCH - 3 POLE

NEW EMERGENCY CONDUIT

SPECIAL MOUNTING HEIGHT. COORDINATE

LOCATION WITH ARCHITECTURAL ELEVATIONS

LIGHTNING ARRESTER

DIRECT BURIED GROUND CONDUCTORG G

USED ON THIS PROJECT)

SHUNT TRIPST

AC = ABOVE COUNTER

GFI = WITH GROUND FAULT INTERRUPTER

AC = ABOVE COUNTER

AC = ABOVE COUNTER

POTENTIAL TRANSFORMERSPT'S

CURRENT TRANSFORMERSCT'S

TERMINAL BLOCK

GROUND FAULT PROTECTION

ELECTRICAL INTERLOCKING

SWITCH

CURRENT POWER TRANSFORMERSCPT'S

ZONE FIRE ALARM TERMINAL CABINETZFATC

FLOOR FIRE ALARM TERMINAL CABINETFFATC

UNSWITCHED, LIGHTING BRANCH WIRING SAME ASSOCIATED BRANCH

WIRING TO POWER SOURCE UNLESS OTHERWISE INDICATED.

ABOVE FINISHED GROUNDAFG

GROUND FAULT MONITORING ONLY (NO TRIP)

IG

EG EQUIPMENT GROUND

ELECTRIC WATER COOLEREWC

MOTOR

M

MOTOR - REMOVALS

M

WEATHER PROOFWP

J

DEMO CEILING MOUNTED JUNCTION BOX

PB

SURFACE MOUNTED BRANCH PANELBOARD - 277/480 VOLT

SURFACE MOUNTED DISTRIBUTION PANELBOARD - 277/480 VOLT

VFD = VARIABLE FREQUENCY DRIVE

100A/3P

100A/3P

HOMERUN CIRCUIT TO POWER SOURCE. NUMBER OF

ARROWS INDICATE NUMBER OF CIRCUITS.

CURRENT POWER TRANSFORMER

CIRCUIT BREAKER - DRAW OUT TYPE

GFI

EM

DRAWING TITLE

APPROVED PROJECT DIRECTOR

PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

DRAWING NUMBER

BUILDING NUMBER

PROJECT NUMBER

REVISIONS DATE

SYRACUSE VA

MEDICAL CENTER

ENGINEERING

DEPARTMENT

ISSUED DATE

800 IRVING AVE. SYRACUSE, NY 13210

DWG.

ELECTRICAL GENERAL NOTES & LEGEND

ADD BACKUP COOLING FOR CATHLAB

BLDG 1

E-001

AutoCAD SHX Text 90/3

AutoCAD SHX Text 100/90/3

AutoCAD SHX Text D

AutoCAD SHX Text

PC

AutoCAD SHX Text T

AutoCAD SHX Text

TB

AutoCAD SHX Text

GF

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text W1

AutoCAD SHX Text C1

AutoCAD SHX Text

GM

AutoCAD SHX Text

CPT

AutoCAD SHX Text

1200AF

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

A429

PANEL EQPL6-4

S

R.D.

S

S

R.D.

SS

S

S

LADDER

RF-47

R.D.

S

ACCU-47

P R

E F

I L

T E

R

H W

C

C C

P R

E F

I L

T E

R

SF-47AC-47

A F

T E

R

F

I L

T E

R

A325

EXISTING 4" CONDUIT SLEEVE FROM A325 CEILING TO A429 ELECT CLOSET FLOOR. ROOMS ARE STACKED VERTICALLY.

PROVIDE NEW 3P-90A 65KAIC CKT BKR AND MOUNTING HARDWARE IN EXISTING CUTLER-HAMMER PRL4 PANELBOARD

DESIGNATION E3A-HVD

EXISTING SQD NQOB PANELBOARD DESIGNATION EQPL6-4 .

(2) EXISTING EMPTY CONDUITS STUBBED UP ON OUTSIDE WALL FROM A429. (1) 3/4" , (1) 1-1/2"

PRIVIDE NEW

" AND 1-1/2" CONDUITS FROM NEW PULL BOX TO ACCU-47. USE THE

" CONDUIT FOR 120V CONVENIENCE

OUTLET AND THE 1-1/2" CONDUIT FOR THE 480V POWER.

PROVIDE NEW PULL BOX FOR THE 1-1/2" CONDUIT IN A249.

KEYED NOTES (FOR THIS DRAWING ONLY):

SCALE: 1/4" = 1'-0"

4TH FLOOR ROOF PLAN

E-102

SCALE: 1/2" = 1'-0"

3RD FLOOR ELECTRICAL PLAN

E102

ELECTRICAL PLAN

ADD BACKUP COOLING TO CATHLAB

09/15/2017

MA

JRD

528A7-18-778

BLDG 1

E-101

NEW DX

UNIT

(ACCU-47)

CONNECT NEW UNIT

TO EXISTING LIGHTNING PROTECTION

GFI

AUXILIARY POWER HEAVY DUTY DISCONNECT

3P-100A, 480V , NEMA 3R, (FUSE AT 80A) WITH

INTEGRAL CONVEINENCE RECEPTACLE.

EATON DH361NRKA1480 OR EQUAL.

DRAWING TITLE

APPROVED PROJECT DIRECTOR

PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

DRAWING NUMBER

BUILDING NUMBER

PROJECT NUMBER

REVISIONS DATE

SYRACUSE VA

MEDICAL CENTER

ENGINEERING

DEPARTMENT

ISSUED DATE

800 IRVING AVE. SYRACUSE, NY 13210

DWG.

FRANI, CHRISTOPHER

DRAWING TITLE

APPROVED PROJECT DIRECTOR

PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

DRAWING NUMBER

BUILDING NUMBER

PROJECT NUMBER

REVISIONS DATE

SYRACUSE VA

MEDICAL CENTER

ENGINEERING

DEPARTMENT

ISSUED DATE

800 IRVING AVE. SYRACUSE, NY 13210

DWG.

FRANI, CHRISTOPHER

PROVIDE NEW 3R PULL BOX

AutoCAD SHX Text

ELECT.

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

E3A-HVD

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text (E)

AutoCAD SHX Text

4" CONDUIT SLEEVE AT CEILING

AutoCAD SHX Text

ELECT.

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DRAWING TITLE

APPROVED PROJECT DIRECTOR

PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

DRAWING NUMBER

BUILDING NUMBER

PROJECT NUMBER

REVISIONS DATE

SYRACUSE VA

MEDICAL CENTER

ENGINEERING

DEPARTMENT

ISSUED DATE

800 IRVING AVE. SYRACUSE, NY 13210

DWG.

FRANI, CHRISTOPHER

STRUCTURAL PLAN ADD BACKUP COOLING FOR CATH LAB

09/15/2017 MA JRD

528A7-18-778

BLDG 1

S-101

SCALE: 3/4" = 1'-0"

STEEL BEAM (NEW)

S101

SCALE: 1/8" = 1'-0"

ROOFING STRUCTURAL PLAN (EXISTING)

S101

SCALE: 1-1/2" = 1'-0"

EXTENSION AND PLATE

S101

SCALE: 1-1/2" = 1'-0"

DETAIL CONNECTION

S101

S-101

1. DESIGN STANDARDS: AISC MANUAL OF STEEL CONSTRUCTION, 8TH EDITION.

2. STEEL ASTM A-36, SHOP PRIME, TOUCH UP IN FIELD, AND PAINT PER

SPECIFICATION 099100.

3. ALL WELDING SHALL BE IN ACCORDANCE WITH AMERICAN WELDING SOCIETY

CODES, USING E70XX ELECTRODES. ALL WELDS SHALL BE FULL PENETRATION

OR WELDED BOTH SIDES. MINIMUM THROAT OF ALL WELDS TO BE 1/4".

4. CONTRACTOR TO VERIFY EXACT LOCATION WITH EXISTING STRUCTURE.

5. COORDINATE WITH COR FOR SUPPORT STEEL WITH MECHANICAL EQUIPMENT

SUPPLIER.

6. ALL BIDDERS ARE REQUIRED TO VISIT SITE AND FAMILIARIZE THEMSELVES

WITH EXISTING CONDITIONS AND ACCESSIBILITY.

7. BEFORE MAKING ANY CUT OUT'S, HOLES, OPENING, ETC IN EXISTING

STRUCTURE NOTIFY AND REVIEW WITH RESIDENT ENGINEER.

8. REPLACE ALL CONCRETE FIREPROOFING REMOVED OR DAMAGED DURING

CONSTRUCTION. THOROUGHLY CLEAN EXISTING CONCRETE; TREAT WITH

BONDING AGENT PER MANUFACTURERS SPECIFICATIONS ; PROVIDE AND

SECURE WIRE MESH TO EXISTING STEEL.

9. NEW STEEL USE AS NOTED ON DRAWING COORDINATE WITH MANUFACTURER

SPECIFICATIONS.

GENERAL NOTES:

AutoCAD SHX Text 19'-0"

AutoCAD SHX Text 19'-0"

AutoCAD SHX Text A

AutoCAD SHX Text 19'-6"

AutoCAD SHX Text 19'-6"

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text 19'-6"

AutoCAD SHX Text 19'-6"

AutoCAD SHX Text 10'-8 "78"

AutoCAD SHX Text 10'-8 "78"

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text 19'-6"

AutoCAD SHX Text 19'-6"

AutoCAD SHX Text G

AutoCAD SHX Text H

AutoCAD SHX Text 1.1

AutoCAD SHX Text 19'-6"

AutoCAD SHX Text 19'-6"

AutoCAD SHX Text J

AutoCAD SHX Text 13'-5 "12"

AutoCAD SHX Text 13'-5 "12"

AutoCAD SHX Text 2.8

AutoCAD SHX Text 18'-9 "12"

AutoCAD SHX Text 18'-9 "12"

AutoCAD SHX Text 19'-3"

AutoCAD SHX Text 19'-3"

AutoCAD SHX Text

AutoCAD SHX Text 3.6

AutoCAD SHX Text 13'-11 "12"

AutoCAD SHX Text 13'-11 "12"

AutoCAD SHX Text

LINE OF EXIST. BUILDING

AutoCAD SHX Text 6'-11 "14"

AutoCAD SHX Text 6'-11 "14"

AutoCAD SHX Text W12x19

AutoCAD SHX Text W12x30

AutoCAD SHX Text W12x19

AutoCAD SHX Text W12x26

AutoCAD SHX Text W12x26

AutoCAD SHX Text W12x14

AutoCAD SHX Text W12x14

AutoCAD SHX Text W12x14

AutoCAD SHX Text W12x14

AutoCAD SHX Text W12x30 (-2 ")12")

AutoCAD SHX Text W12x30 (-2 ")12")

AutoCAD SHX Text REINFORCED W12x40 (-2 ")12")

AutoCAD SHX Text W8x10

AutoCAD SHX Text W8x10

AutoCAD SHX Text W12x16

AutoCAD SHX Text W12x16

AutoCAD SHX Text W12x16

AutoCAD SHX Text W12x16

AutoCAD SHX Text W10x12

AutoCAD SHX Text W10x12

AutoCAD SHX Text W12x14 (-2 )12)

AutoCAD SHX Text W12x26

AutoCAD SHX Text W18x50

AutoCAD SHX Text W12x30

AutoCAD SHX Text W12x45 (-2 ")12")

AutoCAD SHX Text W18x35

AutoCAD SHX Text W18x35

AutoCAD SHX Text W12x19 (-2 )12)

AutoCAD SHX Text W12x19

AutoCAD SHX Text W18x46

AutoCAD SHX Text W14x22

AutoCAD SHX Text W16x26 (+2'-4 ")12")

AutoCAD SHX Text W18x46

AutoCAD SHX Text W18x35

AutoCAD SHX Text W16x36 (+2'-4 ")12")

AutoCAD SHX Text W16x31

AutoCAD SHX Text W16x36 (+2'-4 ")12")

AutoCAD SHX Text W16x26 (+2'-4 ")12")

AutoCAD SHX Text W16x45 (+2'-4 ")12")

AutoCAD SHX Text W16x26 (+2'-4 ")12")

AutoCAD SHX Text W16x45 (+2'-4 ")12")

AutoCAD SHX Text W16x36 (+2'-4 ")12")

AutoCAD SHX Text W16x36 (+2'-4 ")12")

AutoCAD SHX Text W16x36 (+2'-4 ")12")

AutoCAD SHX Text W16x36 (+2'-4 ")12")

AutoCAD SHX Text W16x36 (+2'-4 ")12")

AutoCAD SHX Text W10x19

AutoCAD SHX Text W8x10

AutoCAD SHX Text W8x10

AutoCAD SHX Text W8x24 POST BRG. ON W12x45

AutoCAD SHX Text W8x24 POST BRG. ON W12x40

AutoCAD SHX Text W8x10

AutoCAD SHX Text W8x10

AutoCAD SHX Text D.8

AutoCAD SHX Text W16x26 (+2'-4 ")12")

AutoCAD SHX Text W10x19 (+2'-4 ")12")

AutoCAD SHX Text W8x10

AutoCAD SHX Text W8x10

AutoCAD SHX Text W18x35

AutoCAD SHX Text W18x35

AutoCAD SHX Text W18x35

AutoCAD SHX Text W18x35

AutoCAD SHX Text W18x35

AutoCAD SHX Text W18x35

AutoCAD SHX Text W18x35

AutoCAD SHX Text W10x19

AutoCAD SHX Text W18x35

AutoCAD SHX Text W18x35

AutoCAD SHX Text W8x10

AutoCAD SHX Text W8x10

AutoCAD SHX Text W10x19

AutoCAD SHX Text W12x19

AutoCAD SHX Text W12x19

AutoCAD SHX Text W8x10

AutoCAD SHX Text 7'-0"

AutoCAD SHX Text 7'-0"

AutoCAD SHX Text

EDGE OF ROOF DECK 1" FROM FACE OF EXIST. BUILDING U.N.O., VERIFY IN FIELD

AutoCAD SHX Text W8x10

AutoCAD SHX Text W8x10

AutoCAD SHX Text W8x10

AutoCAD SHX Text W8x10

AutoCAD SHX Text W8x10

AutoCAD SHX Text W8x10

AutoCAD SHX Text W8x10

AutoCAD SHX Text W8x10

AutoCAD SHX Text W8x10

AutoCAD SHX Text W8x10

AutoCAD SHX Text

MECHANICAL UNIT, OPERATING WT = 11,000#

AutoCAD SHX Text E.O.D. 10 "12"

AutoCAD SHX Text E.O.D. 6"

AutoCAD SHX Text E.O.D.

AutoCAD SHX Text W8x10

AutoCAD SHX Text 4x4x " ANGLE FRAMING SEE 38" ANGLE FRAMING SEE DETAIL 3/1-S2

AutoCAD SHX Text 4x4x " ANGLE 38" ANGLE FRAMING SEE DETAIL 3/1-S2

AutoCAD SHX Text

CLR.

AutoCAD SHX Text

CLR.

AutoCAD SHX Text E.O.D. 10 "12"

AutoCAD SHX Text

COL.<

AutoCAD SHX Text 6'-5"

AutoCAD SHX Text 6'-5"

AutoCAD SHX Text W6X15

AutoCAD SHX Text W6X15

AutoCAD SHX Text W6X15

AutoCAD SHX Text W6X15

AutoCAD SHX Text 14"

AutoCAD SHX Text 4"

AutoCAD SHX Text W6X15

AutoCAD SHX Text

EXISTING 18WX35

AutoCAD SHX Text

TYP.

AutoCAD SHX Text 14"

AutoCAD SHX Text 2 "X2 "X "12"X2 "X "12"X "516"

AutoCAD SHX Text

TYP.

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

E-001 Electrical General Notes and Legend-E-001
Sheets and Views
E-001
E-101 Electrical Power Plan-E-101
Sheets and Views
E-101
GI-001 COVER SHEET-GI-001
Sheets and Views
GI-001
MG-001 SYMBOLS LIST, ABBREVIATIONS & NOTES-MG-001
Sheets and Views
MG-001
MG-501 HVAC DETAILS-MG-501
Sheets and Views
MG-501
MP-103 MECHANICAL EQUIPMENT(ROOF)-MP-103
Sheets and Views
MP-103
S-101-S-101
Sheets and Views