36C24125Q0602_1.docx
DOCX document 17 KB Posted
- Attached to
- J059--Newington Replacement Breakers Federal contract opportunity
- Solicitation number
- 36C24125Q0602
About this file
This document is an Amendment to a Combined Solicitation for the Department of Veterans Affairs, specifically for the VA Medical Center in Newington, Connecticut. The solicitation (36C24125Q0602) seeks a vendor to test, inspect, and replace electrical breaker equipment, specifically targeting two Eaton breakers (Catalog # MDN4083XEA0552N) with a Frame Type K600-AR-600NM and 800 Frame Size. The procurement is set-aside for Veteran-Owned Small Businesses (VOSB) under NAICS code 811210 for Electronic and Precision Equipment Repair and Maintenance, with a small business size standard of $34 Million. The critical requirements include replacing one molded case breaker, refurbishing one breaker trip unit, providing a temporary unit to minimize hospital CT scanner downtime, and generating secondary injection testing reports to verify equipment functionality. The response deadline is 08-25-2025 at 17:00 Eastern Time, with the solicitation being issued as a Request for Quote (RFQ).
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24125Q0602 Final.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Amendment to a Previous Combined Solicitation
Amendment to a Previous Combined Solicitation
| SUBJECT* |
| Newington Replacement Breakers |
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 06516 |
| SOLICITATION NUMBER* |
| 36C24125Q0602 |
| RESPONSE DATE/TIME/ZONE |
| 08-25-2025 17:00 EASTERN TIME, NEW YORK, USA |
| ARCHIVE |
| 30 DAYS AFTER THE RESPONSE DATE |
| RECOVERY ACT FUNDS |
| N |
| SET-ASIDE |
| VSA |
| PRODUCT SERVICE CODE* |
| J059 |
| NAICS CODE* |
| 811210 |
| CONTRACTING OFFICE ADDRESS |
| Department of Veterans Affairs |
VA Connecticut
950 Campbell Avenue West Haven CT 06516
POINT OF CONTACT*
Contract Specialist Shawn Lawrence Shawn.Lawrence@va.gov
PLACE OF PERFORMANCE
| ADDRESS |
| VA Medical Center Newington |
555 WILLARD AVENUE
Newington CT
| POSTAL CODE |
| 06111 |
COUNTRY
ADDITIONAL INFORMATION
AGENCY’S URL
URL DESCRIPTION
| AGENCY CONTACT’S EMAIL ADDRESS |
| Shawn.Lawrence@va.gov |
EMAIL DESCRIPTION
DESCRIPTION
36C241-25-AP-4384 Newington Replacement Breakers – Q and A
1. Can you please advise part # of breaker needed / pictures of existing breaker?
a. There are 2 breakers noted in the solicitation. The first of which cannot be racked out for information due to the support bracket being damaged. This is the breaker that needs to be replaced. Here is the information I have available to me:
· MFR: EATON
· Catalog # MDN4083XEA0552N
· Frame Type: K600-AR-600NM
· Frame Size: 800
· Voltage Rating: 480
· Trip Unit: DIGITRIP 520
· Trip Rating: 250
2. Can you please send us the catalog number for this breaker and information on the trip unit? If you have any pictures, that would help.
a. The second breaker failed a trip test and will need the trip unit replaced. Here is the information I have available from the second breaker.
· MFR: EATON
· Catalog # MDN4083XEA0552N
· Frame Type: K600-AR-600NM
· Frame Size: 800
· Voltage Rating: 480
· Trip Unit: DIGITRIP 520
· Trip Rating: NA (This will need to be dialed in as best you can)
b. Please note as stated in the SOW, this breaker will need a temporary unit for use until the trip unit is rebuilt, and the breaker can be racked back in. This unit supports the hospital’s CT scanners and downtime is not acceptable.
c. Please also note that each breaker will require a testing report via secondary injection testing to verify functionality.
36C241-25-AP-4384 Newington Replacement Breakers – Q and A
3. Can you please advise part # of breaker needed / pictures of existing breaker?
a. There are 2 breakers noted in the solicitation. The first of which cannot be racked out for information due to the support bracket being damaged. This is the breaker that needs to be replaced. Here is the information I have available to me:
· MFR: EATON
· Catalog # MDN4083XEA0552N
· Frame Type: K600-AR-600NM
· Frame Size: 800
· Voltage Rating: 480
· Trip Unit: DIGITRIP 520
· Trip Rating: 250
4. Can you please send us the catalog number for this breaker and information on the trip unit? If you have any pictures, that would help.
a. The second breaker failed a trip test and will need the trip unit replaced. Here is the information I have available from the second breaker.
· MFR: EATON
· Catalog # MDN4083XEA0552N
· Frame Type: K600-AR-600NM
· Frame Size: 800
· Voltage Rating: 480
· Trip Unit: DIGITRIP 520
· Trip Rating: NA (This will need to be dialed in as best you can)
b. Please note as stated in the SOW, this breaker will need a temporary unit for use until the trip unit is rebuilt, and the breaker can be racked back in. This unit supports the hospital’s CT scanners and downtime is not acceptable.
c. Please also note that each breaker will require a testing report via secondary injection testing to verify functionality.