36C24119Q0268-000.docx

DOCX document 20 KB Posted

Attached to
Pneumatic Controls Service Federal contract opportunity
Solicitation number
36C24119Q0268
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1

About this file

36C24119Q0268 36C24119Q0268_1.docx

View the file

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FedBizOpps Presolicitation Notice

CLASSIFICATION CODE

SUBJECT

CONTRACTING OFFICE'S

ZIP-CODE

SOLICITATION NUMBER

RESPONSE DATE (MM-DD-YYYY)

ARCHIVE

DAYS AFTER THE RESPONSE DATE

RECOVERY ACT FUNDS

SET-ASIDE

NAICS CODE

CONTRACTING OFFICE

ADDRESS

POINT OF CONTACT

(POC Information Automatically Filled from User Profile Unless Entered)

DESCRIPTION

See Attachment

AGENCY'S URL

URL DESCRIPTION

AGENCY CONTACT'S EMAIL

ADDRESS

EMAIL DESCRIPTION

ADDRESS

POSTAL CODE

COUNTRY

ADDITIONAL INFORMATION

GENERAL INFORMATION

PLACE OF PERFORMANCE

* = Required Field FedBizOpps Presolicitation Notice Rev. March 2010 J Pneumatic Controls Service 06516 36C24119Q0268 06-27-2019 N 811310 Department of Veterans Affairs VA Connecticut 950 Campbell Avenue West Haven CT 06516 Cory Dionne Contracting Officer Department of Veterans Affairs Connecticut HCS West Haven Campus 950 Campbell Avenue West Haven, CT 06516

USA

https://va.gov Official VA Web Site cory.dionne@va.gov email address Pursuant to Federal Acquisition Regulation (FAR) 8.405-6(a)(1)(i)(B), The Connecticut Health Care System for the Department of Veterans Affairs intends to issue a sole source contract award to Quincy Compressor LLC 14500 Lochridge blvd Ste A Covington, GA 30014-4941.

The contract will include Preventive Maintenance & Repair Service for Medical Air Compressors and Vacuum Pumps for Connecticut HCS Facilities and Maintenance 950 Campbell Avenue West Haven, CT 06516. The applicable NAICS code will be 811310 with an applicable small business size standard of $7.5 Million. The performance period is for a 1-year period with an option of four years and will provide all equipment, labor, materials; to include tools, parts, transportation, supervision, permits and disposal necessary to service all medical air, medical vacuum, and compressed air for pneumatic controls with all associated dryers, sensors and monitors at the West Haven VA Medical Center, 950 Campbell Ave., West Haven, CT 06516. Contractor to be responsible for obtaining mfg. Spec’s as needed with copies for engineering dept. The Connecticut HCS has warranties currently being serviced by Quincy Compressor and use of another vendor would void these warranties.

THIS NOTICE OF INTENT IS NOT A REQUEST FOR COMPETITIVE PROPOSALS. It is a market research tool being used to determine the availability of other qualified sources that can meet the requirements identified above and inherent with the referenced product. The Government is not obligated to and will not pay for any information received from potential sources as a result of this notice of intent. All responses received within 15 days of the posting of this notice will be considered by the Government. A determination by the Government to require services for The Connecticut HCS, acquisition based on this notice is solely within the discretion of the Government. Information received will normally be considered solely for the purposes of determining whether to allow alternate service providers.

Submit any responses within 4 days of the posting of the notice of intent via email to:

cory.dionne@va.gov.

THIS NOTICE OF INTENT IS NOT A REQUEST FOR PROPOSALS OR QUOTATIONS. No solicitation package will be issued. A determination by the Government not to compete this proposed action based upon responses to this notice is solely within the discretion of the Government. Information received will be considered solely for the purpose of determining whether conducting a competitive procurement is in the best interest of the Government. All responses received by 13:00 EST on 26 June 2019 will be considered by the Government. This notice is not a request for competitive proposals/quotes. All information submitted should support the offeror's capability to provide the items required and shall be furnished at no cost or obligation to the Government. Responses must be in writing and must provide clear and concise documentation indicating an offeror's capability to provide these services. Verbal responses are not acceptable and will not be considered. Responses and questions shall be submitted via email to: cory.dionne@va.gov.

The Government will issue a Limited Sources Justification (LSJ) to support the need for a sole source award. The LSJ will post to the GPE at http://www.fedbizopps.gov, within fourteen (14) days after award of the task order.

Statement of Work

Preventive Maintenance & Repair Service for Medical Air Compressors and Vacuum Pumps for VA Connecticut Healthcare System West Haven, CT

Contractor shall provide all equipment, labor, materials; to include tools, parts, transportation, supervision, permits and disposal necessary to service all medical air, medical vacuum, and compressed air for pneumatic controls with all associated dryers, sensors and monitors at the West Haven VA Medical Center, 950 Campbell Ave., West Haven, CT 06516. Contractor to be responsible for obtaining mfg. Spec’s as needed with copies for engineering dept.

Preventive Maintenance The contractor shall provide a monthly walk-through to inspect all equipment listed on bid spec on the equipment listed below:

QTYMFG Description / Medical Air / Medical VacuumBldg/Location
1Beacon Medical Vacuum / Model # OV8A-ITBS-TC001 SER# 655031-SG182
1Quincy Medical Vacuum / Model # QSVB10 SER# UNO640101- 5th Floor
1Quincy Medical Vacuum / Model# QSVB10 SER# UNO6400091-5th Floor
1Busch Medical Vacuum / Model# MM1104AB SER# 0500441092-7-100
1Airtech Dental Vacuum / Model# 1-DV-7620-5-TANV #9592-G-139
1Chemtron Medical Vacuum / Model# LPHR 50518 BN11 70202-G-139
SER# 348618 SER# 3448619
1Airtech Research Vacuum / Model# 2BL2061-1AH50-4AS2004-Basement
1Power-X Medical Air / Model# SPL3471698 Cat Number M3218T1-5th Floor
1Power-x Medical Air / Model# SPL3485304 Cat Number MS218T1-SG-182
1Power-X Medical Air / Model# SET1507401-SG-177
1Power-X Dental Air / Model# SET150740E2-G-139
1Power-X Medical Air / Model# SPL29237352-G-139
1Speed Air Pneumatic Air / Model# 4YN50A SER# 2008-000402-2-113
(Wood Shop)
1Quincy Pneumatic Air / Model# PLT-5 SER# 200301120-019562-2-113
1Quincy Pneumatic Air / Model# PLT-5 SER# 61444162-2-113
1Quincy Pneumatic Air / Model# 390 SER# 3399312-G-139
1Quincy Pneumatic Air / Model# 390L103 SER# 400451RL2-G-139
1Quincy Pneumatic Air / Model# 310 SER# 20041018-00132-G-139
1Quincy Pneumatic Air / Model# QT5QCB SER# 200601124-Basement
1Quincy Pneumatic Air / Model# QT5QCB SER# 200602240057Bldg 34
1Quincy Pneumatic Air / Model# 310 SER# 20041018-00111-SG-101
1Hitachi Pneumatic Air / Model# 5-5OU-8.5CH SER# OC8588371-SG-170
1Quincy Pneumatic Air / Model# QSB15ANA11SQ SER# 97726H1-SG-182
1Kobelco Pneumatic Air / Model# KNWA00-A/L SER# 01A01061-SG-182
1Quincy Pneumatic Air / Model# QSB15ANA11SQ SER# 97725H1-10th Floor
1Quincy Pneumatic Air / Model# 390101 SER# 3399321-10th Floor
1Johnson Control Pneumatic Air / Model# AD030 SER# 050692L-2090941-5th Floor
1Ingersol Pneumatic Air / Model# BS15 SER# 100309Boiler Plant
QTYMFG Description / Pneumatic Control Air/Fire SuppressionBldg/Location
1Quincy Pneumatic Air / Model# 390 QRV-ROCOBoiler Plant
1Quincy Pneumatic Air / Model# QT5QCB SER# 20060224-0055Bldg 21
1Jenny Fire Suppression / Model FIS-BS SER# G072JJ4020Boiler Plant
1Jenny Fire Suppression / Model# K SER# F1222110253-Basement
1Magnetech Fire Suppression / Model 8-164550-237-Basement

Reciprocating compressors will be serviced as follows:

• Air filter element replacement

• Change oil

• Change oil filter

• Replace Belts one time per year

• Replace unloader diaphragms one time per year

• Inspect dryer- air clean exterior of condenser with compressed air

• Check temps/ pressures

• Check drain trap operations

Powerex Systems will be serviced as follows:

• Change air filters one time per year

• Change floats in water separators

• Change line filter element and floats

• Change belts

• Change dryer exhaust filters two times per year

• Change HC elements once per four years

The Rotary screw compressors and vacuum pumps will be serviced as follows:

• Oil sample taken

• Change oil filters

• Replace Separators (Every 4000 hours of operation)

• Check belts (Change belts every 4000 hours of operation)

• Change air filter elements

• Check safeties

• Clean Exterior of coolers with compressed air

• Clean entire unit

Airtec Vacuum Pumps will be serviced as follows:

• Change water filters two times per year

• Change air filter elements two times per year

• Dryers- install overhaul kits and desiccant (every 2 years)

• Three emergency (after hours) callouts for labor only

• Six dew point probes to be on a two-year calibration schedule Parts

• Contractor shall include a list of all parts covered by Preventive Maintenance with the cost mark up.

• Contractor shall provide the cost mark up for parts not included in the Preventive Maintenance.

Additional Equipment

• Additional equipment may be added or existing equipment removed from the list when necessary to meet the changing needs of the facility which may be required throughout the life of the contract and shall be considered within the scope.

Written Reports

• Written reports for the work completed and recommendations on repairs shall be required with a cost quote included after each PM and/or service call.

Emergency & Repair Service Work

• The contractor will be required to provide 24/7 response to emergency air compressor and vacuum pump system problems. Response time will be with-in 2 hour time frame.

• The contractor will provide a straight time hurly rate and an overtime hourly rate for emergency call-ins and routine repair service.

• In the event of a major breakdown a suitable rental must be available within 24 hours.

Performance Work Statement Tasks

• The contractor shall be available to perform the semi-annual preventive maintenance on a schedule that is satisfactory to the hospital.

• The contractor shall work continuously on preventive maintenance once the work has started until all the units specified in the contract are completed.

• The contractor shall provide legible and complete reports on all equipment that received preventive maintenance including the repairs required and a cost proposal to perform the repair.

• The contractor shall respond to all emergency repair call ins within the 2 hour time frame specified.

• The contractor shall provide highly qualified technicians with adequate training to resolve all repair issues encountered.

Infectious Control

• The Contractor shall conform to the infection control measures as specified in the attached Construction Specification for Infection Control.

• Preventive Maintenance Service will normally but not always is performed in a separate work area not subject to all the infection control procedures.

• Repairs and emergency repairs may be conducted in patient rooms and other hospital areas that are subject to infection control encountered.

Work Hours and Project Sequence

Routine PM and repair work can start as early as 7:00am and work past 4:30pm week days.

Weekend work needs to be approved by the Mechanical Maintenance Supervisor. Emergency service work will occur as conditions dictate.

Duration

This service contract will be for a Base Year and four (4) one (1) year options renewable at the discretion of the VA.