This document specifies requirements for fire hose assemblies with nylon outer covers to be procured through solicitation number SPMYM223Q2015, issued by the Defense Logistics Agency Land and Maritime. The hose assemblies are to have 1-3/4 inch inside diameters, be made of woven nylon jackets, measure 50 feet in length including brass rocker lug couplings per specification A-A-59227, and be color orange. Each hose assembly must pass a hydrostatic test of 250 psi for 10 minutes and be marked in accordance with NFPA 1961. Packaging is to be in accordance with MIL-H-775.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SPMYM223Q2015 EXTENSION SAM.pdf | ||
| SPMYM223Q2015.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ENCLOSURE 1
MIL/FED SPECIFICATION ORDERING DATA
NIIM/SMIC = 4210/4720- 1-3/4” FIRE HOSE, NYLON OUTER COVER
(A) TITLE, NUMBER, AND DATE OF THIS SPECIFICATION: COMMERICAL ITEM DESCRIPTION HOSE
ASSEMBLY, NONMETALLIC, FIRE FIGHTING, WITH COUPLINGS; A-A-59226 MAY 18, 1998.
(B) TYPE, SIZE, STYLE OF HOSE REQUIRED: FIRE HOSE, WOVEN NYLON JACKETED OUTER LAYER. TYPE:
TYPE II, SYNTHETIC NYLON JACKET. CLASS: CLASS A, DOUBLE JACKETED. SIZE; 1-3/4 INCH INSIDE
DIAMETER
(C) SERVICE PRESSURE: 300 P.S.I. (TEST PREESURE 600 P.S.I. AND 900 P.S.I. BURST)
(D) WHEN INNER RUBBER IS REQUIRED TO CONFORM TO FEDERAL FDA; INVOKE PAR. 3.2.1 FOR HOSE
LINING TO MEET THE REQUIREMENTS OF FDA 21 CFR 177.2600.
(E) WHEN THE OUTER JACKET IS REQUIRED TO BE IMPREGNATED WITH SYNTHETIC RUBBER: N/A
SYNTHETIC NYLON JACKET
(F) COLOR OF HOSE: COLOR OF HOSE TO BE ORANGE
NOTE: YELLOW IS NOT ACCEPTABLE.
(G) CERTIFICATION HYDRO TEST; VENDOR/MANUFACTURER TO PROVIDE CERTIFICATION THAT EACH HOSE ASSEMBLY HAS BEEN HYDROSTATICALLY TESTED USING POTABLE WATER TEST MEDIUM, 250 PSI
(+20, -0) PSI FOR 10 MINUTES.
NO LEAKS, TWISTING, KINKING, DAMAGED OR FAULTY FITTINGS, HAIRLINE CUTS, BREAKS, ABRASIONS, SOFT SPOTS, BULGES OF SLIPPAGE OF HOSE OUT OF END FITTINGS.
(H) LENGTH OF HOSE: 50 FEET, INCLUDING COUPLINGS.
(I) WHEN EACH LENGTH OF HOSE IS TO BE FITTED WITH A SET OF COUPLINGS. THIS HOSE ASSEBLY TO BE FITTED WITH ONE MALE AND ONE FEMALE HOSE COUPLING. BOTH END FITTINGS TO BE MADE OF BRASS. BOTH END FITTINGS TO BE ROCKER LUG TYPE. THE FEMALE END FITTING TO BE A SWIVEL
ROCKER TYPE. END FITTINGS TO BE AS PER COMMERICAL ITEM DESCRIPTION A-A-59227.
(J) N/A
(K) WHEN COUPLINGS ARE TO HAVE OTHER THAN (NH) THREAD CONNECTIONS: N/A
END COUPLINGS TO BE 1-1/2” BRASS, NATIONAL STANDARD THREAD TYPE (1-1/2” INCH HOSE, 9 THREADS PER INCH, 1.985 INCH OUTSIDE DIAMETER MALE THREAD, AKA 1-1/2" NH or NST). END FITTINGS TO BE AS
PER COMMERICAL ITEM DESCRIPTION A-A-59227.
(L) WHEN TYPES I & II HOSE JACKETS AND RUBBER COATED FABRIC LININGS ARE TO BE TREATED
FOR MILDEW RESISTANCE: INVOKE MILDEW TREATMENT AS PER PAR.3.5 AND NFPA 1961.
(M) WHEN FIRST ARTICLE INSPECTION REQUIRED: N/A NOT REQUIRED
(N) WHEN ADDITIONAL MARKING REQUIRED: INVOKE PAR. 3.6. MARKING SHALL BE IN ACCORDANCE OF
NFPA 1961
(O) PACKAGING REQUIREMENTS: PRESERVED AND MARKED LEVEL C, COMMERICAL, IN ACCORDANCE
WITH MIL-H-775.
7.3 PART IDENTIFICATION NUMBER (PIN) A-A-59226-2-A-4-50