This document is a combined synopsis/solicitation for the procurement of an air and vacuum compressor for the Pinon Health Center, which is part of the Navajo Area Indian Health Service. The solicitation is a Buy Indian set-aside, meaning only offers from Buy Indian small businesses will be accepted. The key details are:

The solicitation is for the delivery of an air and vacuum compressor in strict accordance with the attached specifications. The government has identified a specific brand name but will accept brand-name or equal descriptions. Offers should be submitted via email to the Contracting Officer. Quotations must include completed pricing, specifications of the offered product, and evidence that the offered product meets the specifications. The government will evaluate offers and award on a Lowest Price Technically Acceptable basis. The resultant contract will include standard FAR and HHSAR clauses for commercial item acquisitions.

View the file

Other files for this federal contract opportunity

Other files attached to Air and Vacuum Compressor at PHC, newest first.
File Type Posted
IHS IEE Representation Form.pdf PDF
RFQ - Supplies FAR 13 - Fee Schedule.xlsx XLSX spreadsheet

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Aeras 3 Aeras 5 Aeras 8 Aeras 12 Aeras 18

(C3-12) (C5-12) (C8-2) (C12-2) (C18-2)

ATTENTION: It is recommended that this equipment be installed by a licensed electrical/ plumbing contractor only. All installations must conform to local and national standards.

Check Compressor Model Being Installed:

Doctor:

Address:

Phone No.:

Dealer:

Address:

NOTICE

This information is not intended to replace the information found in the User Manual. Refer to the User Manual for full installation, safety and precautions.

PREINSTALLATION GUIDE

MODELS:

C3, C5, C8, C12 & C18

COMPRESSOR

PLACEMENT

• Indoor use only, in a dust-free room.

• Ventilation required for room to remain between 35°F to 100°F (2°C to 38°C). Additional forced air and HVAC must be used if ambient temperatures do not fall into this range.

• Do not install on surfaces with more than a 5 degree incline.

• Allow 12" minimum clearance on all sides for all units.

• If unit is placed in an area adjacent to office space, sound eliminating techniques should be considered for the unit.

PLUMBING

• Connect drain hose to fitting on bottom of coalescing filter and direct it into floor drain/purge bowl for disposal of water.

• Connect compressor air outlet to facility plumbing with provided supply hose (3/8" MPT × 3/8" MPT × 6' long).

• Connect fresh air manifold to controlled fresh air source.

• Connect only equipment suitable for listed maximum pressure of the compressor.

PREINSTALLATION GUIDE

EQUIPMENT ROOM LAYOUT

FRESH AIR INTAKE KITS

Model

AERAS 3

(C3-12)

AERAS 3

(C3-12SS)

AERAS 5

(C5-12)

AERAS 5

(C5-12SS)

AERAS 8

(C8-2)

AERAS 12

(C12-2)

AERAS 18

(C18-2)

Part Number 8658-009 8658-014 8658-010 8658-015 8658-012 8658-012 8658-013

FILTER DRAIN HOSE TO

FLOOR SINK/PURGE BOWL

ELECTRICAL DISCONNECT

BOX (SUPPLIED BY

ELECTRICIAN). POSITION

WITHIN LIMITS OF 6'

ELECTRICAL CONDUIT WHIP.

FRESH AIR INTAKE

(OPTIONAL)

FACILITY SUPPLY

HOSE (6' LONG)

REMOTE

SWITCHING

CONNECTIONS

SOUND COVER

POWER

CONNECTOR

(C8, C12 & C18)

1" × 12' LONG FLEX AIR INTAKE

HOSE TO CONTROLLED FRESH AIR

(SUPPLIED WITH INTAKE)

12" MINIMUM

CLEARANCE

(ALL SIDES)

PREINSTALLATION GUIDE

ELECTRICAL

HIGH VOLTAGE

• Install a dedicated electrical circuit of sufficient capacity (see SPECIFICATIONS & SITE REQUIREMENTS table).

• Any means provided to isolate this device from the supply mains shall isolate all poles simultaneously. The disconnection means and overcurrent protection are to be provided by the installer. This device should always be attached to a dedicated circuit with appropriate wiring and circuit protection.

• All Aeras Compressor models are factory set to run on 230 volts mains power. Aeras Compressor models C3-12 and C5-12 are dual voltage capable and can run on 115 volts or 230 volts mains power. (See compressor manual MAINS VOLTAGE SWITCHING for setting voltage procedure.)

LOW-VOLTAGE REMOTE SWITCHING (RECOMMENDED)

• Maximum wire length for low-voltage, 18-gauge wire is 500 feet.

RAMVAC

Remote Panel (or

Equivalent) with

Illuminated

24V DC

Switch

F

G

H

Aeras

Control

Terminals

F

H

G

LOW-VOLTAGE REMOTE SWITCHING (ALTERNATIVE)

Toggle Switch or Other Non-

Illuminated Switch

(Optional)

F

H

Aeras

Control

Terminals

F

H

Switch

Light

Common

+24V DC

+24V DC

DC Common

F

G

H

Illuminated Remote Switch

REMOTE

SWITCH

FGH

CONNECTOR

AERAS CONTROL PANEL

Conforms to:

ANSI/AAMI STD ES60601

Certified to:

CAN/CSA STD C22.2 NO. 60601-1

ETL CLASSIFIED

4007136

DENTALEZ

2500 Highway 31 South Bay Minette, AL 36507

Phone: 866-DTE-INFO Fax: 251-937-0461 dentalez.com

PN: 7565-098A

August, 2022

SPECIFICATIONS & SITE REQUIREMENTS

PREINSTALLATION GUIDE

© 2022 DentalEZ Alabama, Inc. DENTALEZ and Aeras are registered trademarks of DentalEZ, Inc. Ramvac is a registered trademark of Ramvac Dental Products, Inc.

AERAS 3

(C3-12)

AERAS 5

(C5-12)

AERAS 8

(C8-2)

AERAS 12

(C12-2)

AERAS 18

(C18-2)

Max Users 3 5 8 12 18

Voltage (AC) 115/230

(103-126/ 208-253)

115/230 (103-126/ 208-253)

(208-253)

(208-253)

(208-253)

Power Consumption (Amps) 12/6.1 17.6/9 16 21 30.5

Breaker Size (Amps) 15/15 20/15 20 30 40

Fusetron Size FRN 15/10 FRN 20/15 FRN 20 FRN 25 FRN 40

Number of Motor Heads 2 3 2 2 3

HP Per Motor Head .50 .50 2 2 2

Pressure 85 PSI/586 kPa to 115 PSI/793 kPa with ± 2% Total Error Band

High-Pressure Mode* 105 PSI/724 kPA to 125 PSI/862 kPA

Weight (lbs) 136 149 230 230 335

Dimensions W×D×H (in) 30×21×26 30×21×26 35×25×30 35×25×30 41×29×32

Dimensions (with Sound Cover) N/A N/A 35×29×34 35×29×34 41.1×33×36

Dimensions (with Sound Shield) 30×20×26 30×20×26 N/A N/A N/A

Pump Up Cycle Time, 85 to 115 PSI (Sec) 60 45 45 35 30

Tank Size (Gal) 12 12 20 20 30

Filtration (microns) 0.3 Coalescing; 0.01 Final Particulate

Dryer Duty Cycle 100%

Dryer Dew Point (PDP) -40°F/-40°C dBA Levels (with/without Sound Cover) N/A N/A 76/82 76/82 78/84 dBA Levels (with/without Sound Shield) 63/67 66/70 N/A N/A N/A

BTU/HR (Heat Released to Room) 1,820 2,725 2,000 3,072 4,608

NOTES: *High-pressure mode should only be used with a compatible milling machine; not for use in general dentistry.

USER MANUALCOMPRESSOR

MODELS:

C3, C5, C8, C12 & C18 i

TABLE OF CONTENTS

SECTION I - INTRODUCTION

Product Overview Product Features Specifications (Compressor) Specifications (LTE Radio) Recommended Environmental Conditions Classifications Explanation of Symbols & Signs Safety Precautions

SECTION II - PREINSTALLATION

Packaging Placement Site Requirements

SECTION III - INSTALLATION

Feet Kit Filter Drain Kit Mains Voltage Low-voltage Wiring Connections Outlet Plumbing Kit

SECTION IV - OPERATION

How the System Works Getting Started Aeras Control Panel Home Screen Information Screen Technical Screen Settings Screen

SECTION V - CARE & MAINTENANCE

Overview Key Points for Trouble-Free Operation Cleaning Instructions Preventive Maintenance Schedule Check Filter Element Service Indicator Test for Air Leaks Depressurize Air System Replace Intake Filter Replace Coalescing Filter Replace Particulate Filter ii

COMPRESSOR USER MANUAL

866-DTE-INFO

dentalez.com

PN: 7717-007B

SECTION VI - USER SERVICE INFO

Service Instruction Disposal of Equipment

SECTION VII - PARTS

DENTALEZ Parts Online

EMC INFORMATION

LIMITED WARRANTY

TABLE OF CONTENTS

PRODUCT OVERVIEW

This manual contains installation, operation, care and user service information for the Ramvac® Aeras® dental compressor. To view the latest manual, go to DENTALEZ.COM to download a digital (PDF) copy.

The Aeras compressors are designed to provide trouble-free service when installed, operated and cared for according to the procedures set forth in this manual. They compressors are NFPA 99 Healthcare Facility Code compliant.

To ensure proper installation, carefully read all the instructions contained in this manual prior to installing, operating, and servicing. For safety, pay close attention to all warnings, cautions, notices and notes.

Before starting installation procedures, review the illustration to become familiar with the components of the compressor (FIGURE 1).

After the compressor is installed, review the features, operation procedures and care guidelines with the doctor’s staff.

LEAVE THIS MANUAL IN THE DOCTOR’S OFFICE.

NOTICE

Installation by an authorized Ramvac dealer service technician is recommended.

For any questions about an order, please contact a Ramvac customer service representative at 866-DTE-INFO.

SECTION I - INTRODUCTION

FIGURE 1. MAIN COMPONENTS OF THE AERAS COMPRESSOR (SIDE AND FRONT VIEWS)

COMPRESSOR

MOTOR HEADS

TOUCH

SCREEN

CONTROL

PANEL COALESCING FILTER

RUBBER

HAND

GRIPS (4)

HEAT

EXCHANGER

& FAN (NOT

AVAILABLE ON

C3-12 &

C5-12 MODELS)

DUAL COLUMN

DESICCANT TOWER

INTAKE

FILTER(S)

TANK

FEET (4)

PARTICULATE

FILTER FILTER

DRAIN

BOWL

FILTER

DRAIN

TANK

PETCOCK

FGH

CONNECTOR

SAFETY

VALVE

SHUT-

OFF

VALVE

www.dentalez.com

866-DTE-INFO

dentalez.com

PN: 7717-007B

PRODUCT FEATURES

The Aeras® Compressor by Ramvac® offers increased productivity while decreasing downtime. The compressor is dependable, quiet and simple to operate. In order to achieve the most efficient use in the operatory and understand what the compressor offers, here is a compilation of some of those features and benefits.

STANDARD FEATURES

Aeras features the latest cloud-based technology that offers active monitoring with data streaming from embedded sensors. The smart monitoring service automatically detects potential issues and diagnostic information is relayed to the appropriate person, helping to prevent downtime. Information can be accessed via a web browser on any device. Users also can remotely schedule the equipment to power ON and OFF.

Dual column desiccant tower provides 100% continuous supply of dry, clean air. While one column is drying, the other is in operation. Solenoid valve activates as needed and the chambers switch processes immediately to ensure an uninterrupted supply of air for your practice.

Design allows for easy desiccant cartridge replacement.

Stores air at -40°C, preventing growth of harmful bacteria.

Industry leading 6-year warranty (see LIMITED WARRANTY section of this manual).

Models available suited for 3 to 18 users.

OPTIONAL FEATURES

Optional fresh air intake kit is used when room temperatures are beyond operating temperature range and/or when air has contaminants.

Optional sound cover lowers decibel ratings for the Aeras Compressor models C8-2, C12-2 and C18-2.

Optional Sound Shield technology lowers decibel ratings and improves sound quality for the Aeras Compressor models C3-12SS and C5-12SS.

SECTION I - INTRODUCTION

SPECIFICATIONS (COMPRESSOR)

SECTION I - INTRODUCTION

AERAS 3

(C3-12)

AERAS 5

(C5-12)

AERAS 8

(C8-2)

AERAS 12

(C12-2)

AERAS 18

(C18-2)

Max Users 3 5 8 12 18

Voltage (AC) 115/230

(103-126/ 208-253)

115/230 (103-126/ 208-253)

(208-253)

(208-253)

(208-253)

Power Consumption (Amps) 12/6.1 17.6/9 16 21 30.5

Breaker Size (Amps) 15/15 20/15 20 30 40

Fusetron Size FRN 15/10 FRN 20/15 FRN 20 FRN 25 FRN 40

Number of Motor Heads 2 3 2 2 3

HP Per Motor Head .50 .50 2 2 2

Pressure 85 PSI/586 kPa to 115 PSI/793 kPa with ± 2% Total Error Band

High-Pressure Mode* 105 PSI/724 kPA to 125 PSI/862 kPA

Weight (lbs) 136 149 230 230 335

Dimensions W×D×H (in) 30×21×26 30×21×26 35×25×30 35×25×30 41×29×32

Dimensions (with Sound Cover) N/A N/A 35×29×34 35×29×34 41.1×33×36

Dimensions (with Sound Shield) 30×20×26 30×20×26 N/A N/A N/A

Pump Up Cycle Time, 85 to 115 PSI (Sec) 60 45 45 35 30

Tank Size (Gal) 12 12 20 20 30

Filtration (microns) 0.3 Coalescing; 0.01 Final Particulate

Dryer Duty Cycle 100%

Dryer Dew Point (PDP) -40°F/-40°C dBA Levels (with/without Sound Cover)

N/A N/A 76/82 76/82 78/84 dBA Levels (with/without Sound Shield)

63/67 66/70 N/A N/A N/A

NOTES: *High-pressure mode should only be used with a compatible milling machine; not for use in general dentistry.

866-DTE-INFO

dentalez.com

PN: 7717-007B

SECTION I - INTRODUCTION

ITEM DESCRIPTION

Modulation

QPSK

16-QAM

Frequencies

Band 2 (1900 MHz) Band 4 (1700 MHz) Band 5 (850 MHz) Band 12 (700 MHz)

Power Class Class 3 (23 dBm)

Radiation Pattern Omnidirectional antenna

Certifications

FCC ID: 2AEMI-BRN404 https://www.fcc.gov/oet/ea/fccid FCC Compliance Statement (e.g., products subject to Part 15): This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

Operating Temperature Normal operating temperature -20 to +65 C Extended operating temperature -40 to +85 C

Mounting SMT

Power

Nominal 3.8V at:

Minimum Average Peak during Tx

110 mA 190 mA 500 mA

SPECIFICATIONS (LTE RADIO)

The LTE radio of the DENTALEZ products use the U-blox SARA R410-02B LTE Cat M1* modem for use in North America.

*SARA-R4 series modules comply with the Directive 2011/65/EU of the European Parliament and the Council on the Restriction of Use of certain Hazardous Substances in Electrical and Electronic Equipment (EU RoHS 2) and its amendment Directive (EU) 2015/863 (EU RoHS 3). SARA-R4 series modules are RoHS 3 compliant. No natural rubbers, hygroscopic materials, or materials containing asbestos are employed.

TRANSPORTATION AND STORAGE

Temperature range: -20°F to 165°F (-29°C to 74°C)

Relative humidity range: 0% to 95%

OPERATION

Temperature range: 35°F to 100°F (2°C to 38°C)

Relative humidity range: 0% to 95%

INDOOR USE

Altitude up to 9,000 ft (2,743 m)

RECOMMENDED ENVIRONMENTAL CONDITIONS

CLASSIFICATIONS

Conforms to:

ANSI/AAMI STD ES60601-1:2005 (R2012)

Certified to:

CAN/CSA C22.2 NO. 60601-1-08

Complies with NFPA 99 Healthcare Facility Code.

Manufactured in a FDA registered ISO 13485:2016 certified facility.

Ramvac compressors meet the most current and highest safety standards.

Type of Protection Against Electric Shock:

Class 1 Equipment.

Degree of Protection Against Ingress of Water: IPXO.

Flammable Gases: Equipment not suitable for use in the presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.

Not intended for use in an oxygen rich environment.

Mode of Operation: Continuous

= Caution

= Warning

= Biohazard

= Warning - Dangerous Voltage

= Hot Surface

= General Mandatory Action

= Refer to Manual (Follow Instructions)

= Refer to Accompanying Documents

= Alternating Current

= Direct Current

= Protective Earth (Ground)

= Type B Applied Part

= Serial Number

= Manufacture Date

= Manufacturer

= Electromagnetic Radiation

= Box Must Remain Upright

= Do Not Place Box on Unlevel Surface

= Do Not Stack Box

= Box Contents Safe Temperature Range

= Box Contents Safe Humidity Range

EXPLANATION OF SYMBOLS &

SIGNS

SECTION I - INTRODUCTION

C

ETL CLASSIFIED

4010684

866-DTE-INFO

dentalez.com

PN: 7717-007B

SAFETY PRECAUTIONS

To ensure that the safety potential of this equipment is achieved, make sure equipment is installed according to written instructions.

SECTION I - INTRODUCTION

WARNING Do not modify this equipment without permission from Ramvac. Unauthorized modification will void the warranty and could result in serious injury. If this equipment is modified, appropriate inspection and testing must be conducted to ensure continued safe use of equipment.

Electrical shock could occur as a result of improper grounding. This product must be grounded according to NEC regulations and local codes.

Portable RF communications equipment (including peripherals such as antenna cables and external antennas) should be used no closer than 30 cm (12") to any part of the compressor, including cables specified by the manufacturer. Otherwise, degradation of the performance of this equipment could result.

Property damage and/or personal injury may result if directions are not followed or OEM parts are not used.

Always turn off compressor and remove power from compressor when servicing. (Turn off power at disconnect or service breaker.)

Danger of fire or explosion when using flammable substances.

Never leave children unattended when compressor is in use.

CAUTION The compressor has several guards designed to protect against accidental contact with dangerous components. Do not remove these guards until power has been disconnected/turned off from the equipment. If service is required with the guard removed and the power on, it should only be performed by a qualified service technician. Always replace any guards that have been removed for service or that may have been damaged.

During installation, always ensure all electrical, plumbing or other utilities are properly located to avoid possible tripping or falling hazards. Always follow all local, state and national building codes, as well as any applicable workplace safety regulations.

Use of a plug for electrical service is not recommended. Incorrect connections will cause a drop in line voltage and/or loss of power. Overheating could result.

Connect only equipment suitable for listed maximum pressure of the compressor.

The EMISSIONS characteristics of this equipment make it suitable for use in industrial areas and hospitals (CISPR 11 class A). If it is used in a residential environment (for which CISPR 11 class B is normally required) this equipment might not offer adequate protection to radio-frequency communication services. The user might need to take mitigation measures, such as relocating or re-orienting the equipment.

SAFETY PRECAUTIONS (CONTINUED)

SECTION I - INTRODUCTION

NOTICE Medical electrical equipment needs special precautions regarding electromagnetic (EMC) compatibility and needs to be installed according to EMC information. (See EMC INFORMATION provided in this manual.)

The use of accessories, transducers, and cables other than those specified, with the exception of transducers and cables sold by the manufacturer of this device as replacement parts for internal components, may result in increased emissions or decreased immunity of the compressor.

Portable and mobile radio frequency (RF) communications equipment can affect medical electrical equipment.

There may be an instance, in low humidity environments, that the user of the dental compressed air system may cause the compressor to stop as a result of electrostatic discharge (ESD) energy. To remedy this issue, cycle the ON/OFF switch on the side of the control.

An air leakage test should be conducted on the facility air system to ensure no air leaks are present. Excessive air leakage will impact the performance and life expectancy of your compressor. See SECTION V - CARE & MAINTENANCE > TEST FOR AIR LEAKS instructions provided in this manual.

866-DTE-INFO

dentalez.com

PN: 7717-007B

PACKAGING

TOOLS REQUIRED

7/16" Wrench

UNPACKING COMPRESSOR CARTON

1. Carefully remove the shipping carton from the pallet containing the compressor.

2. Visually inspect the entire compressor for any shipping damage.

Visually inspect the motor isolator mounts for tearing.

If shipping damage is found, immediately contact the freight carrier and supplier.

3. Using a 7/16" wrench, remove the nuts that secure the compressor to the shipping pallet.

4. For easier handling, four rubber grips have been installed on the frame of the compressor for lifting (FIGURE 2).

NOTE: Lifting the compressor assembly by any other part or location could result in damage to the compressor.

5. Verify additional parts shipped with the compressor for use at installation:

Outlet Plumbing Kit

Filter Drain Kit/Purge Bowl

Feet Kit

Doctor’s Packet

Maintenance Chart and Head Service Kit

Low-voltage Wiring Connectors (Installed on Aeras Control)

NOTE: The compressor is shipped with the shut-off valve in the CLOSED position to limit exposure of the system to humidity. OPEN the valve after installation.

SECTION II - PREINSTALLATION

WARNING To prevent tipping during transport, securely fasten unit to shipping pallet until final destination has been reached.

FIGURE 2. RUBBER GRIPS (4) FOR LIFTING

COMPRESSOR

RUBBER

GRIPS

RUBBER

GRIPS

This device must not be stacked during transport and storage and must be oriented right side up during transport and storage.

The compressor unit should not be used adjacent to or stacked with other equipment. If adjacent or stacked use is necessary, the compressor should be observed to verify normal operation in the configuration in which it will be used.

Locate the compressor on a level hard surface capable of supporting the compressor weight. If a level surface is not available, the compressor is equipped with height adjustable feet to level the device. Install four adjustable rubber feet supplied to ensure unit stands firmly on the floor (see SECTION

III - INSTALLATION > FEET KIT).

Floors should be wood, concrete or ceramic tile. It is highly recommended that a higher than 30% relative humidity be established and the operator wear a ground strap before physical contact is attempted.

Compressor is for indoor use only, in a dust free, climate controlled room.

DO NOT install in a enclosed area where ambient temperature could exceed temperature specifications of below 35°F (2°C) or above 100°F (38°C) while the compressor is running.

Maintain minimum 12" clearance on all sides and on top of all compressors.

A source of conditioned fresh air is required for safe operation of this compressor. The air source must be located outside of the utility room and away from potential air contaminants.

Do not locate this device or it’s air intake opening in an area that is prone to flooding or has previously flooded.

Water can damage components, reduce life expectancy of the compressor or cause serious personal injury.

PLACEMENT

SECTION II - PREINSTALLATION

WARNING DO NOT install on surfaces with more than a 5° incline.

CAUTION The compressor is front heavy. When moving with handles, be sure to hold it securely to prevent it from tipping and possible dropping of the device, which could result in damage to the compressor.

866-DTE-INFO

dentalez.com

PN: 7717-007B

SITE REQUIREMENTS

Before the compressor can be properly installed, the following utilities must be supplied.

ELECTRICAL

A licensed electrician should always complete the electrical portion of the installation process. This device requires proper electrical grounding for safe operation.

Follow NEC, NFPA 99C, and all local codes.

Compressors are shipped with a 6-foot electrical whip of the appropriate size for the compressor.

Qualified personnel must install a dedicated electrical circuit of sufficient capacity. See SECTION I - INTRODUCTION > SPECIFICATIONS (COMPRESSOR) in this manual for additional electrical information.

Any means provided to isolate this device from the supply mains shall isolate all poles simultaneously.

The disconnection means and over-current protection are to be provided by the installer (qualified electrician) in accordance with applicable local and national electric codes. This device should always be attached to a dedicated circuit with appropriate wiring and circuit protection. If this device is being installed as a replacement, always have a licensed electrician inspect the existing facility electrical and complete the electrical portion of the device installation.

PLUMBING

Attach drain tubing to fitting on bottom of coalescing filter and direct it into floor drain for proper disposal of water. If floor drain plumbing is an issue, water can be disposed into the supplied purge bowl.

Connect compressor air outlet to facility plumbing with provided supply hose (3/8" MPT × 3/8" MPT, 6 feet in length).

Install particulate filter to the facility shut-off valve using plumbing kit connectors provided.

Install fresh air manifold and connect fresh air intake kit supplied to external air source per NFPA 99C recommendations.

This device should always be installed with the appropriate plumbing and fresh air intake systems. If this device is being installed as a replacement, always have a licensed plumber inspect the existing facility plumbing and complete the plumbing portion of the device installation.

SECTION II - PREINSTALLATION

NOTICE This air compressor has been designed to operate within the following voltage ranges; 115V systems, 103 to 126V AC; 230V systems, 208 to 253V AC. Failure to provide sufficient voltage to this device could result in damage to electrical components and reduced service life.

CAUTION During the performance of any service procedures that may involve the disconnection of a ground wire, take extra precautions to verify the ground wire has been properly re-connected. Never leave a ground wire disconnected, since this can create a significant safety issue.

WARNING To avoid risk of electric shock, this equipment must only be connected to a supply mains with protective earth.

FEET KIT

TOOLS REQUIRED

7/16" Wrench

1/2" Wrench

PARTS INCLUDED

Foot (4 Pieces)

Flanged Nut (4 Pieces)

ASSEMBLY

1. Remove the four nuts (7/16" wrench) from the bolts that secure the Aeras compressor legs to the wooden shipping pallet. At this point, the bolts can be removed from the legs and the compressor can be removed from the pallet. Do not attempt to install the feet while the compressor is on the pallet; tipping of the pallet and subsequent loss of control may occur.

2. Lift one end of the compressor using the integrated handles and place blocking under the end of the tank to support the compressor. Be careful not to damage the drain valve under the center of the tank. Never work under a compressor that is not supported with adequate blocking (FIGURE 3).

FIGURE 3. BLOCK THE COMPRESSOR TANK

TO INSTALL FEET

FOOT (4) FLANGED NUT (4)

SECTION III - INSTALLATION

(Continued on the next page.)

WARNING Prior to starting this assembly, read, understand and follow the safety information and the assembly instructions in this user manual.

Handles for lifting the compressor assembly are provided on each end of the device. Lifting the compressor assembly by any other part or location could result in damage to the compressor.

The weight distribution of this compressor is unbalanced to the front of the device. Exercise care when lifting to avoid accidental tipping and possible dropping of the device, which could result in damage to the compressor or severe injuries to the installer.

Compressor assemblies are very heavy and may require multiple people to safely lift. Prior to lifting, check the user manual for the weight of this model. Over-exertion could result in serious injuries to the installer.

This procedure may not comply with all safety requirements of federal, state or local agencies or safety requirements of the installer’s employer. If a conflict does exist, follow the requirements set forth by the other organizations.

866-DTE-INFO

dentalez.com

PN: 7717-007B

FIGURE 4. INSTALL FLANGED NUT

FEET KIT (CONTINUED)

3. Thread feet into the two elevated legs from the bottom side of the leg.

4. Adjust each foot to approximately the same height, then thread a flanged nut (flange side toward the leg) onto each foot (FIGURE 4).

NOTE: It is not necessary to tighten the flanged nuts at this time. The feet will require further adjustment once the compressor has been placed in its permanent location in the utility room.

5. Lift the compressor and remove the blocking from under the tank end. Repeat steps 2 through 4 for the opposite end of the compressor.

6. After the compressor is in its permanent location in the utility room, adjust each foot using a 7/16" wrench until the compressor is setting level. After adjusting the feet, tighten the flanged nut with a 1/2" wrench to lock the foot into position.

FILTER DRAIN KIT

PARTS INCLUDED

Drain Hose

Elbow Fitting

SECTION III - INSTALLATION

(Continued from the previous page.)

ELBOW

FITTING

DRAIN

HOSE

Prior to starting this assembly, read, understand and follow the safety information and the assembly instructions in this user manual.

The bowl on the coalescing filter assembly is under high pressure while the system is running. Allow the compressor to stop running and release the pressure prior to removing the bowl. Failure to allow the system to properly de-pressurize could result in severe injuries.

Always disconnect the compressor from the electrical power source prior to conducting any maintenance or service of the equipment. The compressor could start unexpectedly, resulting in possible injury to the service technician.

This procedure may not comply with all safety requirements of federal, state or local agencies or safety requirements of the installer’s employer. If a conflict does exist, follow the requirements set forth by the other organizations.

WARNING

ASSEMBLY

1. To help in determining the routing of the drain hose, read the following tips on proper installation.

The connection at the bottom of the coalescing filter is designed to work with either the elbow fitting or the 3/8" hose provided in the kit, depending on space constraints in the utility room.

The drain hose will require a steady downward slope to the drain.

Never route the drain hose assembly across traffic areas in the utility room. This could create tripping or falling hazards that could result in injury to personnel.

2. The connections for installing the filter drain are a “push-to-connect” style of fitting and do not require any tools to install. After determining proper routing, simply insert either the hose end or the elbow fitting into the fitting on the bottom of the coalescing filter bowl. Apply light force until the item stops. Gently pull the opposite direction on the hose or fitting to determine if they have properly seated into the connection. If the fitting or hose comes out with light force, then the hose was not fully seated into the connection and can be re-inserted again.

3. If, for some reason, the fitting or hose needs to be released from the connection, depressing the colored plastic ring (while gently pulling on the hose or fitting) releases the hose or fitting from the connection (FIGURE 5).

NOTE: If drain plumbing is not accessible, the supplied purge bowl can be used instead to catch disposal water. The water should be manually emptied daily.

FILTER DRAIN KIT (CONTINUED)

SECTION III - INSTALLATION

FIGURE 5. ELBOW FITTING INSTALLED IN

COALESCING FILTER DRAIN

COLORED

RING:

PUSH IN

TO RELEASE

ELBOW

FROM DRAIN

FITTING

ELBOW

FITTING

866-DTE-INFO

dentalez.com

PN: 7717-007B

MAINS VOLTAGE

SECTION III - INSTALLATION

All Aeras Compressor models are factoy set to run on 230 (208-253) volts mains power. Aeras Compressor models C3-12 and C5-12 are dual voltage capable and can run on 115 (103-126) volts or 230 (208-253) volts mains power.

WARNING Prior to starting this assembly, read, understand and follow the safety information and the assembly instructions in this user manual.

Always disconnect the compressor from the electrical power source prior to conducting any electrical service of the equipment. The compressor could start unexpectedly resulting in possible injury to the service technician.

This procedure may not comply with all safety requirements of federal, state or local agencies or safety requirements of the installer’s employer. If a conflict does exist, follow the requirements set forth by the other organizations.

MAINS VOLTAGE SWITCH (MODELS C3-12 AND C5-12 ONLY)

Aeras Compressor models C3-12 and C5-12 are shipped from the factory pre-set to 230 volts. Before turning on power to the compressor, be sure the mains voltage switch is set to the proper voltage. If the facility mains power is 115 (103-

126) volts, slide the mains voltage switch to 115 volts on each compressor head. If the facility mains power is 230 volts, verify the mains voltage switch is set to 230 (208-253) volts on each compressor head (FIGURE 6).

FIGURE 6. MAINS VOLTAGE SWITCH

MAINS VOLTAGE

SWITCH

MAINS VOLTAGE SWITCH

(2 OR 3 COMPRESSOR

HEADS)

LOW-VOLTAGE WIRING CONNECTIONS

PARTS INCLUDED

Remote Switch FGH Connector - Used to control power state of this compressor from a remote location (see SECTION III - INSTALLATION > LOW-VOLTAGE WIRING CONNECTIONS > LOW-VOLTAGE REMOTE

SWITCHING).

Auxiliary Connector - Used to control power state of a non-Aeras vacuum, water control valve, or another non- Aeras compressor (see SECTION III - INSTALLATION > LOW-VOLTAGE WIRING CONNECTIONS > LOW-

VOLTAGE AUXILIARY DEVICE CONNECTION).

Building Maintenance Connector - Used to connect to building maintenance system.

SECTION III - INSTALLATION

REMOTE SWITCH

FGH CONNECTOR

AUXILIARY

DEVICE

CONNECTOR

BUILDING

MAINTENANCE

CONNECTOR

WARNING Prior to starting this assembly, read, understand and follow the safety information and the assembly instructions in this user manual.

Always disconnect the compressor from the electrical power source prior to conducting any electrical service of the equipment. The compressor could start unexpectedly resulting in possible injury to the service technician.

This procedure may not comply with all safety requirements of federal, state or local agencies or safety requirements of the installer’s employer. If a conflict does exist, follow the requirements set forth by the other organizations.

FIGURE 7. AERAS CONTROL PANEL LOW-VOLTAGE WIRING CONNECTIONS

FRONT VIEW

BUILDING

MAINTENANCE

CONNECTOR

AUXILIARY

CONNECTOR

REMOTE SWITCH

FGH CONNECTOR

SIDE VIEW

CONTROL PANEL CONNECTOR LOCATIONS

866-DTE-INFO

dentalez.com

PN: 7717-007B

LOW-VOLTAGE WIRING CONNECTIONS (CONTINUED)

SECTION III - INSTALLATION

CONTROL PANEL CONNECTOR LOCATIONS

AERAS CONTROL BOX

(RIGHT SIDE VIEW)

AERAS CONTROL BOX

(LEFT SIDE VIEW)

AERAS CONTROL BOX

(FRONT VIEW)

Building maintenance connector

Auxiliary device connector

Remote switch FGH connector

Dryer 1

Dryer 2

Tank Pressure (PSI/kPa)

Head 1 temperature

Head 2 temperature

Head 3 temperature

Tank temperature/humidity

Ambient temperature/humidity

NON-ILLUMINATED REMOTE SWITCHES

Non-illuminated switches provide no indication for system status.

ILLUMINATED REMOTE PANELS

Switch light is steady on when system is running normally.

Switch light flashes for maintenance or one of the heads has been disabled by the disable button on the control panel.

Recommended Switching

Alternative Switching

Toggle Switch or Other Non-

Illuminated Switch

(Option)

Aeras Control

Terminals

F

H

Air Switch

+24V DC

+24V DC

DC Common

F

G

H

Air Light

Common

Ramvac Remote Panel (or

Equivalent) with

Illuminated

24V DC

Switch

Aeras Control

Terminals

F

H

G

AIR

LOW-VOLTAGE REMOTE SWITCHING

NOTICE Maximum wire length for 18-gauge wire is 500 feet.

Low-voltage remote switching is used to turn the system on and off from a remote location. Your Aeras compressor is manufactured to continuously cycle as required throughout the workday. Power the compressor off at end of day.

LOW-VOLTAGE WIRING CONNECTIONS (CONTINUED)

SECTION III - INSTALLATION

AERAS CONTROL PANEL

REMOTE

SWITCH

FGH

CONNECTOR

(Continued on the next page.)

866-DTE-INFO

dentalez.com

PN: 7717-007B

SECTION III - INSTALLATION

LOW-VOLTAGE WIRING CONNECTIONS (CONTINUED)

LOW-VOLTAGE AUXILIARY DEVICE CONNECTION

NOTICE Maximum wire length for 18-gauge wire is 500 feet.

Low-voltage auxiliary connection is used to connect a non-Aeras vacuum, master water control valve, or another non-Aeras compressor to this Aeras compressor. The auxiliary power state will match the power state of this Aeras compressor (ON/STANDBY).

Auxiliary Wiring

Aeras Control

Terminals

S2 Control Terminals or

C2 Control Terminals or

Water Control Valve

Terminals

F

H

AUXILIARY

CONNECTOR

AERAS CONTROL PANEL

Switch

Common

Alternative Switching

(Continued from the previous page.)

OWL Touch OWL Hub OWL Interface Aeras Control Panel

OUTLET PLUMBING KIT

PARTS INCLUDED

Final Filter (Particulate)

Facility Supply Hose

Fittings

Thread Sealer

FITTINGS

THREAD

SEALER

FACILITY

SUPPLY

HOSE

SECTION III - INSTALLATION

FINAL FILTER

(PARTICULATE)

WARNING Prior to starting this assembly, read, understand and follow the safety information and the assembly instructions in this user manual.

Never route the facility supply hose across traffic areas in the utility room. This could create tripping or falling hazards that could result in injury to personnel.

The compressor system may be pressurized; follow the discharge procedures in the user manual prior to conducting any repairs or maintenance. Working on pressurized components could result in severe injuries or even death. It is recommended any repairs or service be performed by a qualified service technician.

When installing air lines in a new facility, always follow NFPA 99 standards (or local codes) and maintain cleanliness throughout.

Prior to or during the replacement of compressors, always verify the cleanliness of the existing air lines in the facility. Old or malfunctioning compressors can cause unhealthy deposits of mold, dust or dirt.

This compressor is designed for dental procedures and powering dental equipment and can be safely used in the oral cavity for such purposes. Under no circumstances should it be supplied or considered as medical/breathing air for a patient.

Installation of this device should be conducted by licensed electrical and plumbing contractors and should always follow the instructions found in the various manuals, unless local state or national building codes specify otherwise. Failure to comply with all applicable codes and installation procedures may result in personal injury, damaged components or reduced life expectancy of this product.

Never direct the air stream toward any portion of the body or others in the vicinity. Pressurized air streams can be extremely hazardous to your health and can result in death in certain circumstances.

This procedure may not comply with all safety requirements of federal, state or local agencies or safety requirements of the installer’s employer. If a conflict does exist, follow the requirements set forth by the other organizations.

866-DTE-INFO

dentalez.com

PN: 7717-007B

ASSEMBLY

1. Determine the best routing for the facility supply hose and the filter assembly. The filter can be mounted in two different directions, depending on the safest and easiest route for the hose (FIGURE 8).

Always use the hose assembly provided to connect the compressor to the facility airlines. If a longer hose is required, be certain the product used is rated to an adequate pressure level and is intended for compressed air systems.

2. Utilize the fittings provided to mount the filter assembly in the orientation determined in step 1. A small tube of thread sealer has been provided in the kit. Do not over-apply the thread sealer; just a couple of drops on the male threads of all the fittings will provide an adequate seal. Tighten fittings as needed.

3. Thread the final filter onto the fittings and tighten it into the desired position (FIGURE 8).

NOTE: The final filter has to be installed in the correct flow orientation.

4. Thread the facility supply hose into the final filter and tighten. Both ends of the hose have swivel fittings to make installation easier.

5. Attach the other end of the hose to the facility piping. The kit contains an adapter bushing to adapt the 3/8 pipe thread on the end of the hose to a 1/2 pipe thread on the facility piping if it is required.

6. Upon completion of the air compressor installation, always check to ensure the shut-off valve on the pressure manifold is in the open position.

7. After the system has been pressurized, perform the following checks: (SECTION V - CARE & MAINTENANCE > TEST

FOR AIR LEAKS)

Check each joint for leaks using a soap and water mixture. Tighten any joints that may be leaking.

Check the facility plumbing for leaks, either by inspection or by completing a pressure decay test. Repair any leaks in the facility plumbing.

OUTLET PLUMBING KIT (CONTINUED)

SECTION III - INSTALLATION

FIGURE 8. FILTER MOUNTING OPTIONS

FLOW

ARROW

FLOW

ARROW

SHUT-

OFF

VALVE

SHUT-

OFF

VALVE

HOW THE SYSTEM WORKS

When power is applied, fresh air is taken in through air filters and compressed by the pump pistons. The compressed air is very warm and is cooled for use by the heat exchanger and fan. Air is then delivered to the coalescing filter to remove most of the moisture.

The coalescing filter is equipped with an automatic draining feature that allows the draining of the excess moisture.

The cool air enters the desiccant-style dryer assembly to complete the moisture removal by removing 99.7% of the water vapor from the air.

Air is directed into the dryer (desiccant) cartridges, from one to the other, by electronically controlled solenoid valves.

The timing for the solenoid valves is provided by the Aeras control.

While the air is moving through one cartridge, the desiccant in the other cartridge is being dried by air directed through an orifice in the outlet shuttle valve. This valve cycle will be noticeable by a short burst of air from the purge valves. The air is then collected in the tank where it is stored for future use.

The Aeras control panel LCD display shows the tank air pressure. When air is called for to run equipment in the facility, it goes through a particulate filter to remove any remaining particulates from the air.

The tank pressure is monitored by the Aeras control, using a pressure transducer sensor on the manifold block, which runs the motors on demand. Pressure is factory set from 85 PSI/586 kPa to 115 PSI/793 kPa.

GETTING STARTED

SECTION IV - OPERATION

CAUTION DO NOT attempt to operate the compressor at ambient temperature below 35°F/2°C or above 100°F/38°C.

WARNING Never direct the air stream toward any portion of the body or others in the vicinity. Pressurized air streams can be extremely hazardous to your health and can result in death in certain circumstances.

The Aeras compressor is easy to operate and maintain.

1. Verify the compressor is connected to a dedicated circuit. For models C3-12 and C5-12, verify mains power switch voltage on each compressor head matches facility mains voltage (SECTION III - INSTALLATION > MAINS VOLTAGE)

2. Verify the compressor is properly connected to the facility plumbing and a fresh air source.

3. Verify the shut-off valve is closed.

4. For optimal signal strength, put the antenna (located on the right side of the control panel) in the upright (verticle) position.

5. Push the Aeras control panel power switch to the ON position.

6. To switch the compressor from STANDBY to ON, press the orange STANDBY switch on the HOME screen. The switch will turn green and display ON.

7. Test for leaks (SECTION V - CARE & MAINTENANCE > TEST FOR AIR LEAKS).

8. Turn the shut-off valve to OPEN.

9. The compressor installation is complete.

NOTE: Periodically during startup from 0 PSI, the dryer shuttle valve may be out of sync from the previous cycle. This is noted by the sound of air being released out of the dryer purge valves. This minor interruption causes no harm to the dryer or air system. The dryer shuttle valve will relocate itself to the correct position after 35 seconds, and after which the dryer will cycle normally.

866-DTE-INFO

dentalez.com

PN: 7717-007B

SECTION IV - OPERATION

FIGURE 9. AERAS COMPRESSOR CONTROL PANEL

Settings

Technical

Info

Home

3 hrs Equipment Runtime

70.3 F

Ambient Temp

-40.0 F Pressure Dew Point

85 PSI

Tank Pressure

On Alerts Settings

Technical

Info

Home

3 hrs Equipment Runtime

70.3 F

Ambient Temp

-40.0 F Pressure Dew Point

85 PSI

Tank Pressure

On Alerts

By selecting “Accept”, you consent and agree to our Privacy Policy available at https://www.dentalez.com/privacy-policy and our

Terms of Use available at www.dentalez.com/terms.

Accept

CONTROL

PANEL

POWER

SWITCH

PRIVACY POLICY

ACCEPTANCE SCREEN

SHOWN AT INITIAL SYSTEM

START-UP

HOME

Tank Pressure Pressure Dew Point Ambient Temperature Equipment Runtime Update (only appears when a new firmware/software update is available) System Switch (ON/STANDBY) Alerts (when alerts are present)

INFORMATION

Firmware Version Hardware Version Brand Model Serial Number DentalEZ Support Contact Number Service Provider Contact Number

TECHNICAL

Maintenance Mode Switch Alerts Motors Sensors Tandem (Web App Enabled) Runtimes Network Advanced Service (Maintenance Mode ON)

SETTINGS

Smart Schedule Switch Metric Display Switch Schedule Date & Time Restore System Defaults (Reset)

MAIN NAVIGATION MENU

AERAS CONTROL PANEL

The Aeras compressor control platform utilizes state-of-the-art technology solid state relays to control cycling of the compressor. When the Aeras control panel is first turned on, a Privacy Policy screen will be shown. Press ACCEPT to consent and agree to the privacy policy and continue (FIGURE 9). Aeras compressor models C3-12 and C5-12 (dual voltage) will have an additional Voltage screen. Press VERIFIED after checking that the mains voltage switch on each compressor head matches the voltage on the screen (FIGURE 9). If mains voltage does not match, see SECTION III - INSTALLATION > MAINS VOLTAGE to set proper voltage .

VOLTAGE VERIFICATION SCREEN

SHOWN AT INITIAL SYSTEM START-UP

(MODELS C3-12 AND C5-12 ONLY)

Settings

Technical

Info

Home

3 hrs Equipment Runtime

70.3 F

Ambient Temp

-40.0 F Pressure Dew Point

85 PSI

Tank Pressure

On Alerts Settings

Technical

Info

Home

Model

Brand

Hardware

Firmware

Serial Number

DENTALEZ Support Contact

Service Provider Contact v34 v5

Aeras

C4-1

ACR0000000

(866) 383-4636

(000) 000-0000 s

Technical

Info

Home

3 hrs Equipment Runtime

70.3 F

Ambient Temp

-40.0 F Pressure Dew Point

85 PSI

Tank Pressure

On Alerts SettingsSettingsSettings

TechnicalTechnicalTechnical

InfoInfoInfo

HomeHomeHome

ModelMo

Brandandan

HardwareHa

Firmware

Serial Number85 PSI85 PSI

DENTALEZ Support Contact Pressure Dew Pore

Service Provider Contact v34 v5v5

AerasraAAe

C4-14-1

ACR00000003 hrs3 hrs

(866) 383-4636 Equipment RuntiEquipment Runti

(000) 000-0000

Current voltage reading is 209V. Please verify the voltage switch on each motor head is in the correct position.

Verified

CONTROL

PANEL

LCD

DISPLAY

SECTION IV - OPERATION

Software Update Available 07:33:14 PMLTE

Settings

Technical

Info

Home

20 hrs Equipment Runtime

70.3 F

Ambient Temp

-40.0 F Pressure Dew Point

85 PSI

Tank Pressure

Standby AlertsUpdate

SYSTEM SWITCH

(STANDBY)

TANK

PRESSURE

PRESSURE

DEW POINT

AMBIENT

TEMPERATURE

WIRELESS SIGNAL STRENGTH

TIME OF DAY

EQUIPMENT

RUNTIME

HOME LINK

(ACTIVE)

INFO LINK

TECHNICAL LINK

SETTINGS LINK

FIGURE 10. HOME SCREEN

The Aeras control panel LCD display uses simple touch controls and is easy to navigate. The Home screen of the control panel displays the following information (FIGURE 10):

Main navigational menu links: HOME, INFO, TECHNICAL, and SETTINGS

Wireless signal strength indicator (for detailed wireless status, go to TECHNICAL > MAINTENANCE MODE >

NETWORK)

Time of day (to set/reset time, go to SETTINGS > DATE & TIME >)

Tank pressure reading (normal reading is 85 PSI/586 kPa to 115 PSI/793 kPa)*

Pressure dew point reading*

Ambient temperature reading*

Equipment runtime reading

UPDATE (only appears when a new firmware/software update is available)

SYSTEM switch (ON/STANDBY)

NOTES: * Temperature (°F) and pressure (PSI) can be set to view in metric mode (°C and kPa) by going to

SETTINGS > METRIC DISPLAY SWITCH).

HOME SCREEN

ALERTS

SOFTWARE UPDATE AVAILABLE

SOFTWARE

UPDATE

AVAILABLE

866-DTE-INFO

dentalez.com

PN: 7717-007B

SYSTEM SWITCH (ON/STANDBY)

HOME SCREEN (CONTINUED)

SECTION IV - OPERATION

While performing maintenance operations on the compressor, the system should be in STANDBY mode. Motor heads of the compressor will not run while in this mode. The compressor may also be in kept in STANDBY mode during extended periods of non-use in order to conserve energy.

To switch the compressor system from STANDBY mode to ON, from the Home screen, press the orange STANDBY switch. The switch will turn green and display ON. Pressing the green ON switch will return the compressor to STANDBY mode (FIGURE 11).

07:33:14 PMLTE

Settings

Technical

Info

Home

20 hrs Equipment Runtime

70.3 F

Ambient Temp

-40.0 F Pressure Dew Point

85 PSI

Tank Pressure

On

SYSTEM SWITCH (ON)

07:33:14 PMLTE

Settings

Technical

Info

Home

20 hrs Equipment Runtime

70.3 F

Ambient Temp

-40.0 F Pressure Dew Point

85 PSI

Tank Pressure

Standby

SYSTEM SWITCH (STANDBY)

FIGURE 11. HOME SCREENS SHOWING SYSTEM IN “STANDBY” AND “ON”

HOME SCREEN (CONTINUED)

UPDATE (SOFTWARE)

When a new firmware/software version has been released and is ready to download and install, a green UPDATE button will be shown on the Home screen. To update the software, press the green UPDATE button. This will open a new screen asking to install the pending update. Pressing OK will start download and installation of software. Pressing CANCEL will cancel the software update and return to the Home screen (FIGURE 12).

If the UPDATE button is not pressed, the update will occur automatically overnight.

NOTE: The device may be inoperable during the update to the software.

FIGURE 12. HOME SCREEN SHOWING SOFTWARE UPDATE AVAILABLE

Software Update Available 07:33:14 PMLTE

Settings

Technical

Info

Home

20 hrs Equipment Runtime

70.3 F

Ambient Temp

-40.0 F Pressure Dew Point

85 PSI

Tank Pressure

Standby AlertsUpdate

SOFTWARE

UPDATE

AVAILABLE

HEADER:

SOFTWARE

UPDATE

AVAILABLE

Software Update Available 07:33:14 PMLTE tings hnical nfo ome

20 hrs Equipment Runt

70.3 F

Ambient Temp

-40.0 F Pressure Dew Point

85 PSI

Tank Pressure

Standby AlertsUpdate

Software Update Available 07:33:14 PMLTE tings hnical nfo ome

20 hrs Equipment Runt

70.3 F

Ambient Temp

-40.0 F Pressure Dew Point

85 PSI

Tank Pressure

Standby AlertsUpdate

Install pending update? Device may be inoperable until update complete.

OK Cancel

Software Update Available 07:33:14 PMLTE

Settings

Technical

Info

Home

20 hrs Equipment Runtime

70.3 F

Ambient Temp

-40.0 F Pressure Dew Point

85 PSI

Tank Pressure

Standby AlertsUpdate

07:33:14 PMLTE

34Firmware

Line Voltage

Ambient Temp

Downloading icons

75%

866-DTE-INFO

dentalez.com

PN: 7717-007B

INFORMATION SCREEN

SECTION IV - OPERATION

The Information screen of the control panel displays the following information (FIGURE 13):

Main navigational menu links: HOME, INFO, TECHNICAL, and SETTINGS

Wireless signal strength indicator

Time of day

Firmware (current version of software installed)

Hardware (current version of hardware installed)

Brand (Aeras)

Model of compressor (C3-12, C5-12, C12-2, etc.)

Serial Number of the compressor (set at factory)

DENTALEZ Support Contact phone number (set at factory)

Service Provider Contact phone number (set manually by user)

SERVICE PROVIDER CONTACT phone number screen link

FIGURE 13. INFORMATION SCREEN

07:33:14 PMLTE

Settings

Technical

Info

Home

Model

Brand

Hardware

Firmware

Serial Number

DENTALEZ Support Contact

Service Provider Contact v34 v5

Aeras

C12-2

ACR0000000

(866) 383-4636

(000) 000-0000

HOME LINK

INFO LINK

(ACTIVE)

TECHNICAL LINK

SETTINGS LINK

WIRELESS SIGNAL STRENGTH

TIME OF DAY

FIRMWARE

HARDWARE

BRAND

MODEL

SERIAL

NUMBER

DENTALEZ

SUPPORT

CONTACT

SERVICE PROVIDER CONTACT

PHONE NUMBER

SERVICE PROVIDER

CONTACT SCREEN LINK

SERVICE PROVIDER CONTACT

INFORMATION SCREEN (CONTINUED)

SECTION IV - OPERATION

To manually enter the service provider contact phone number, on the Info screen, press SERVICE PROVIDER

CONTACT > (FIGURE 14).

This will open a new screen for entering the service provider's phone number. Using the numeric key pad, enter the phone number (area code included) and press SAVE key (FIGURE 15).

Press < INFO to return to the previous screen.

FIGURE 14. ON THE INFO SCREEN, PRESS SERVICE PROVIDER CONTACT >

07:33:14 PMLTE

Settings

Technical

Info

Home

Model

Brand

Hardware

Firmware

Serial Number

DENTALEZ Support Contact

Service Provider Contact v34 v5

Aeras

C12-2

ACR0000000

(866) 383-4636

(000) 000-0000

SERVICE PROVIDER

CONTACT PHONE NUMBER

SERVICE

PROVIDER

CONTACT

SCREEN

LINK

FIGURE 15. ENTER PHONE NUMBER AND PRESS SAVE KEY

5 6

7 8 9

0DEL SAV

Info

Please enter service provider contact number

1 2 3

123-456-7890

PHONE

NUMBER

SAVE

KEY

DELETE

KEY

NUMERIC

KEY PAD

PRESS

< INFO

TO

RETURN TO

PREVIOUS

SCREEN

866-DTE-INFO

dentalez.com

PN: 7717-007B

TECHNICAL SCREEN

SECTION IV - OPERATION

The Technical screen of the control panel displays the following information (FIGURE 16):

Main navigational menu links: HOME, INFO, TECHNICAL, and SETTINGS

Wireless signal strength indicator

Time of day

MAINTENANCE MODE switch

ALERTS screen link

MOTORS screen link

SENSORS screen link

TANDEM screen link (Web app enabled)

RU…