4 - Drawings REV F-001.pdf
PDF 982 KB Posted
- Attached to
- Fire Alarm Replacement at FCC Coleman Federal contract opportunity
- Solicitation number
- 15B30221B00000001
About this file
This document includes a federal contract opportunity solicitation and related file. The solicitation is for a firm-fixed-price construction contract valued between $1 million to $5 million to remove an existing fire alarm system and install a new one at the Federal Correctional Complex in Coleman, Florida. The performance period is 365 calendar days from notice to proceed. Interested vendors must be registered as a small business in SAM.gov under NAICS code 238210 with a $16.5 million size standard. The solicitation and any amendments will be distributed solely through SAM.gov. The related file provides drawings and notes for the fire alarm replacement, including project scope, demolition requirements, new equipment to be installed, and other technical details.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Bid Abstract.pdf | ||
| AMEND 0007 COL.pdf | ||
| AMEND 0006 COL.pdf | ||
| 5 - Construction Wage Rate 9242021.pdf | ||
| AMEND 0005 COL.pdf | ||
| AMEND 0004 COL.pdf | ||
| Site Visit Meeting Minutes.pdf | ||
| Questions and Answers FCC Coleman.pdf | ||
| AMEND 0003 COL.pdf | ||
| 5 - Construction Wage Rate 7092021.pdf | ||
| AMEND 0002 COL.pdf | ||
| AMEND 0001 COL.pdf | ||
| 2 - Solicitation.pdf | ||
| 4 - Drawings.pdf | ||
| 3 - Specification.pdf | ||
| 1 - Instructions to Bidders.pdf | ||
| 7 - Criminal History Check Form.pdf | ||
| 6 - SF24 Bid Bond.pdf | ||
| 5 - Construction Wage Rate.pdf |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE WITH FBOP
ADOPTED CODES AND STARDNARDS AND THE FOLLOWING: NFPA 70,
"NATIONAL ELECTRIC CODE", 2020 EDITION; NFPA 70, "NATIONAL
ELECTRICAL CODE", 2020 EDITION; NFPA 101, "LIFE SAFETY CODE"' 2018
EDITION; NFPA 241, "SAFEGUARDING CONSTRUCTION, ALTERATION, AND
DEMOLITION OPERATIONS" 2019 EDITION, INTERNATIONAL BUILDING
CODE, 2018 EDITION.
CONTRACTOR SHALL VISIT JOB SITE PRIOR TO BID WITH THE PROJECT
DOCUMENTS AND SPECIFICATIONS TO BECOME FAMILIAR WITH THE
SITE AND SCOPE OF WORK. NOTIFY CONTRACTING OFFICER'S
REPRESENTATIVE WITH ANY DISCREPANCIES OUTSIDE THIS DESIGN
INTENT. ANY CHANGE ORDER REQUEST AS A RESULT OF
COORDINATION BETWEEN TRADES SHALL BE DENIED.
ADHERE TO AND OBTAIN ALL PERMITS, LICENSES, FOR BOTH LOCAL
AND FEDERAL GOVERNMENT REQUIREMENTS.
DO NOT SCALE PLANS FOR THE PURPOSE OF ESTABLISHING
DIMENSIONS. FIELD DIMENSION GOVERN.
FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE PARTITIONS. FIRE
STOPPING SHALL BE OF UL LISTED ASSEMBLY.
IF ASBESTOS OR LEAD BASED PAINT IS FOUND, SUB-CONTRACTOR
IMMEDIATELY STOP WORK AND NOTIFY OWNER. OWNER IS
RESPONSIBLE FOR ABATEMENT OF LEAD BASED PAINT AND ASBESTOS.
1.
2.
3.
4.
5.
6.
GENERAL NOTES
UNLESS OTHERWISE NOTED, DEMOLISH EXISTING FIRE DETECTION, FIRE
ALARM, AND OCCUPANT NOTIFICATION SYSTEM IN ITS ENTIRETY INSIDE
THE INDICATED PROJECT SCOPE AREA UNLESS OTHERWISE NOTED.
CONTRACTOR SHALL REPAIR IN KIND ANY DAMAGES THE BUILDING
SUSTAINS DURING DEMOLITION.
CONTRACTOR SHALL DISPOSE OF ALL DEMOLISHED COMPONENTS AND
MATERIALS IN ACCORDANCE WITH ALL LOCAL AND FEDERAL
REGULATIONS.
EXISTING FIRE ALARM AND OCCUPANT NOTIFICATION SYSTEM IS TO
REMAIN IN OPERATION AT ALL TIMES TO THE FULLEST EXTENT POSSIBLE,
UNTIL NEW FIRE ALARM DEVICES ARE INSTALLED AND TESTED. PLANNED
SYSTEM IMPAIRMENTS SHALL COMPLY WITH NFPA 72 REQUIREMENTS. A
FIRE WATCH WILL BE PROVIDED FOR SYSTEM IMPAIRMENTS AT THE
DISCRETION OF THE SITE/ FACILITY AHJ.
MAINTAIN THE EXISTING FIRE ALARM EQUIPMENT FULLY OPERATIONAL
UNTIL THE NEW EQUIPMENT HAS BEEN TESTED AND ACCEPTED BY THE
CONTRACTING OFFICER'S REPRESENTATIVE (COR). AS NEW EQUIPMENT IS
INSTALLED, LABEL IT "NOT IN SERVICE" UNTIL THE NEW EQUIPMENT IS
ACCEPTED. ONCE THE NEW SYSTEM IS COMPLETED, TESTED, AND
ACCEPTED BY THE COR, IT SHALL BE PLACED IN SERVICE AND
CONNECTED TO THE STATION FIRE ALARM SYSTEM. REMOVE TAGS FROM
NEW EQUIPMENT AND TAG THE EXISTING EQUIPMENT "NOT IN SERVICE"
UNTIL REMOVED FROM THE BUILDING. REFERENCE THE SPECIFICATIONS
FOR FURTHER DETAIL.
REFER TO PLAN DRAWINGS AND PROJECT DOCUMENTS FOR
APPROXIMATE FIRE ALARM SYSTEM QUANTITIES AND LOCATIONS, NOT ALL
SITE CONDITIONS ARE SHOWN. FIRE ALARM CONTRACTOR SHALL VISIT
JOB SITE WITH ALL PROJECT DOCUMENTS PRIOR TO BID TO BECOME
FAMILIAR WITH PROJECT DESIGN, INSTALLATION, TESTING AND
COMMISSIONING REQUIREMENTS, SITE CONDITIONS FOR NEW SYSTEM
INSTALLATION, IN ORDER TO PROVIDE A COMPREHENSIVE AND COMPLETE
BID, CODE COMPLIANT SYSTEM DESIGN, INSTALLATION, TESTING,
COMMISSIONING AND APPROVAL.
CONTRACTOR SHALL SUBMIT COMPLETE BATTERY CALCULATIONS,
VOLTAGE DROP CALCULATIONS, MATERIAL DATA SHEETS, AND SHOP
DRAWINGS TO OWNER'S TECHNICAL REPRESENTATIVE FOR REVIEW
PRIOR TO COMMENCING FABRICATION AND INSTALLATION. FAILURE TO
COMPLY IS AT THE RISK OF THE CONTRACTOR.
FIRE ALARM FLOOR PLANS AND RISER DIAGRAM ARE DIAGRAMMATIC AND
NOT INTENDED TO SHOW EACH AND EVERY COMPONENT, DEVICE,
APPLIANCE, ETC. CONDUIT PATHWAYS AND INTERCONNECTIONS SHALL BE
DETERMINED BY THE BUILDING FEATURES, NFPA 70, NFPA 72, SYSTEM
MANUFACTURER REQUIREMENTS AND RECOMMENDATIONS.
FIRE ALARM SIGNALS AND EMERGENCY COMMUNICATIONS SHALL TAKE
PRECEDENCE OVER ALL OTHER SIGNALS, SUCH AS BUT NOT LIMITED TO
PUBLIC ADDRESS SYSTEMS.
CONTRACTOR SHALL PROVIDE ALL NECESSARY AND REQUIRED SYSTEM
PROGRAMMING TO MEET THE DESIGN INTENT AND CODE COMPLIANCE.
FIRE ALARM NOTIFICATION APPLIANCES SHALL BE 15 CANDELA UNLESS
OTHERWISE NOTED.
ALL NOTIFICATION APPLIANCES CIRCUITS (NAC) SHALL PERFORM TO
CLASS "B" AS DEFINED BY NFPA 70 AND NFPA 72.
ALL SIGNALING LINE CIRCUITS (SLC) SHALL PERFORM TO CLASS "B" AS
DEFINED BY NFPA 70 AND NFPA 72.
ALL INDICATING DEVICE CIRCUITS SHALL PERFORM TO CLASS "B" AS
DEFINED BY NFPA 70 AND NFPA 72.
THE INSTALLATION OF WIRING BETWEEN THE FACP AND RELAY MODULES
OR APPLIANCES SHALL PERFORM TO CLASS "B" AS DEFINED BY NFPA 70
AND NFPA 72.
FIRE ALARM MANUAL PULL STATIONS AT DOOR OPENINGS SHALL BE
WITHIN 5' - 0" HORIZONTALLY OF THE DOOR OPENING.
ALL CONDUCTORS FOR THE FIRE ALARM SYSTEM SHALL BE INSTALLED IN
CONDUIT AND IN ACCORDANCE WITH NFPA 70. THE CONDUCTORS SHALL
NOT BE INSTALLED WITH CONDUCTORS OF LIGHTING OR POWER
SYSTEMS. THE SUM OF THE CROSS-AREA OF INDIVIDUAL CONDUCTORS
SHALL NOT EXCEED 40% OF THE INTERIOR CROSS SECTION OF THE
CONDUIT. ALL FIRE ALARM SYSTEM CONDUIT SHALL NOT BE LESS THAN
3/4".
WALL MOUNTED FIRE ALARM DEVICES IN UNFINISHED AREAS MAY BE
SURFACED MOUNTED, THE CONDUIT MAY BE INSTALLED EXPOSED ON
WALLS AND ON CEILINGS.
IN FINISHED AREAS, WALL MOUNTED DEVICES SHALL BE FLUSH MOUNTED.
THE CONDUIT SHALL BE INSTALLED CONCEALED IN THE WALLS AND
CEILINGS UNLESS REFERENCED AS CEILING MOUNTED.
ALL NEW CONDUIT IS TO BE FACTORY FINISHED RED OR PAINTED RED
THROUGHOUT THE SYSTEM, FOR BOTH EXPOSED AND CONCEALED
CONDUIT.
ELECTRICAL AND FIRE ALARM CONTRACTORS SHALL COORDINATE WITH
FIRE ALARM VENDOR FOR SYSTEM OPERATING INSTRUCTIONS AND
WIRING DIAGRAMS.
CONTRACTOR SHALL PROVIDE PATHWAY SURVIVABILITY OF LEVEL 1.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
FIRE ALARM NOTES
FIRE ALARM DUCT MOUNTED SMOKE DETECTOR
MANUAL FIRE ALARM PULL STATION, MOUNT 42" - 48" AFF TO
TOP OF HANDLE
VALVE SUPERVISORY SWITCH; TO REMAIN AND BE
CONNECTED TO NEW FIRE ALARM SYSTEM
WATER FLOW DETECTOR/SWITCH; TO REMAIN AND
BE CONNECTED TO NEW FIRE ALARM SYSTEM
FIRE ALARM CONTROL PANEL
NOTIFICATION APPLIANCE BOOSTER PANEL
FIRE ALARM ANNUNCIATOR
SMOKE DETECTOR - PHOTOELECTRIC
ER= ELEVATOR RECALL
R=DOOR RELEASE
ALARM INDICATING AND REMOTE TEST SWITCH;
MOUNT IN AN ACCESSIBLE LOCATION
FACP
NAC
ANN
F
FIRE ALARM CLEAR VISUAL STROBE AND SPEAKER. WALL
MOUNT AT 80" AFF TO BOTTOM OF LENS OR 6" BELOW
CEILING, WHICHEVER IS LOWER AND NOT GREATER THAN 96".
C = CEILING MOUNTED DEVICE.
WP = WEATHERPROOF
C/WP
S
S
HEAT DETECTOR
ER= ELEVATOR RECALL
ST=SHUNT TRIP
FIRE ALARM SPEAKER. WALL MOUNT AT 80" AFF TO TOP OF
DEVICE OR 6" BELOW CEILING, WHICHEVER IS LOWER AND NOT
GREATER THAN 96".
C = CEILING MOUNTED DEVICE.
S C
FIRE ALARM LEGEND
RTS
VS
WF
FIRE ALARM CLEAR VISUAL STROBE. WALL MOUNT AT 80" AFF
TO BOTTOM OF LENS OR 6" BELOW CEILING, WHICHEVER IS
LOWER AND NOT GREATER THAN 96"
PROJECT SCOPE INCLUDES THE FOLLOWING: FULL REPLACEMENT OF
THE EXISTING FIRE ALARM SYSTEM IN A FACILITY. DETECTION
DEVICES, WIRING, NOTIFICATION APPLIANCES, ANNUNCIATORS, FIRE
ALARM PANELS, POWER SUPPLIES, AREA SMOKE DETECTORS, DUCT
DETECTORS, HEAT DETECTORS, ELEVATOR RECALL INITIATION
DEVICES, ETC. WILL BE REPLACED IN THEIR ENTIRETY; WITH THE
EXCEPTION OF THOSE LISTED IN SCOPE OF WORK NOTE 11. THE
PROJECT WILL BE PHASED TO ACCOMMODATE THE ACTIVE FACILITY
AND TO MINIMIZE SYSTEM DOWNTIME. THE NEW FIRE ALARM SYSTEM
COMPONENTS WILL BE INSTALLED AND BROUGHT ONLINE PRIOR TO
THE REMOVAL OF THE EXISTING COMPONENTS.
ALL PHASING SHALL BE DETERMINED BY THE CONTRACTOR WITH
GUIDANCE FROM THE CONTRACTING OFFICER'S REPRESENTATIVE/
USER.
THE NEW SYSTEM COMPONENTS WILL BE INSTALLED TO MEET THE
CURRENT EDITION OF NFPA 72, & NFPA 101.
DEMOLITION: THE EXISTING FIRE ALARM EQUIPMENT WILL BE
REMOVED IN A PHASED PROCESS OVER THE COURSE OF THE
PROJECT AS THE NEW EQUIPMENT IS BROUGHT ONLINE. DUE TO THE
PHASING, SOME MAIN INFRASTRUCTURE EQUIPMENT WILL NEED TO
BE ACTIVE FROM THE START OF THE PROJECT (NEW FIBER LOOP,
NEW DACT, FACP, ETC.). CEILINGS, WALLS, AND FLOORS THAT
CONDUIT IS CURRENTLY PASSING THROUGH AND WALLS AND CEILING
THAT DEVICES AND APPLIANCES ARE CURRENTLY ATTACHED TO, WILL
BE IMPACTED DURING DEMOLITION AND WILL REQUIRE FILLING AND
PATCHING ON A CASE BY CASE BASIS. WALLS, CEILING, AND FLOORS
WILL BE REPAIRED TO MATCH THE EXISTING CONSTRUCTION AND/OR
FIRE/SMOKE RATINGS AS APPLICABLE.
AREAS WHERE SMOKE DETECTION IS CURRENTLY INSTALLED AND NO
LONGER REQUIRED PER CURRENT REQUIREMENTS WILL BE REMOVED
AND WILL NOT BE REINSTALLED.
NEW NOTIFICATION APPLIANCES SHALL BE ADDED TO PROVIDE
COMPLETE AND CODE COMPLIANT OCCUPANT NOTIFICATION
THROUGHOUT THE FACILITY.
THE EXISTING FIRE ALARM ZONES SHALL BE MATCHED FOR THE NEW
SYSTEM. ADD ADDITIONAL DEVICES TO THE EXISTING ZONES AS
NEEDED.
ELECTRICAL POWER FEEDS THAT CURRENTLY SUPPLIES THE FIRE
ALARM SYSTEMS WILL BE RE-USED FOR NEW FIRE ALARM PANELS.
ALL FIRE ALARM CONTROL PANELS SHALL BE REPLACED WITH NEW
ADDRESSABLE FIRE ALARM CONTROL PANELS THAT ARE COMPATIBLE
WITH EXISTING FIRE ALARM RECEIVING EQUIPMENT.
NEW FIRE ALARM CONTROL PANELS SHALL BE REPORT TO THE
ASSOCIATED FIRE ALARM RECEIVING STATION VIA EXISTING FIBER
OPTIC LINE. CONTRACTOR IS RESPONSIBLE FOR CONNECTING FIRE
ALARM CONTROL PANELS TO THE EXISTING FIBER LOCATED IN EACH
BUILDING. THE CONTRACTOR SHALL COORDINATE WHICH CENTRAL
RECEIVING LOCATION EACH PANEL REPORTS TO PRIOR TO START OF
INSTALLATION/ PROGRAMMING.
THE EXISTING RELAYS FOR FACP CONNECTION TO SMOKE CONTROL,
FIRE SUPPRESSION SYSTEMS, HVAC SHUTDOWN, GAS SHUTOFF, AND
SPRINKLER MONITORING DEVICES ARE SIEMENS TRI-R AND TRI-60R
DEVICES. (APPROXIMATELY 825 RELAYS). IF NEW SIEMENES PANELS
ARE UTILIZED, RELAYS MAY BE REUSED AND CONNECTED TO NEW
FIRE ALARM CONTROL PANELS. WHERE OTHER MANUFACTURE FACPS
ARE UTILIZED ALL EXISTING SIEMENS RELAYS MUST BE REMOVED AND
REPLACED WITH NEW INTELLIGENT INITIATING DEVICES INTERFACE
MODULES COMPATIBLE WITH THAT SELECTED SYSTEM.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
SCOPE OF WORK
CONTROL MODULECM
FIRE ALARM CLEAR STROBE. CEILING MOUNTED.
FIRE ALARM CONTRACTOR SHALL PROVIDE POWER PANEL
INFORMATION, BREAKER LOCKING AND IDENTIFICATION
REQUIREMENTS IN ACCORDANCE WITH NFPA 70 AND 72
REQUIREMENTS.
THE FIRE ALARM SYSTEM SHALL NOT BE COMBINED WITH ANY
OTHER BUILDING SYSTEM, SUCH AS BUT NOT LIMITED TO,
AUTOMATION, ENERGY, SECURITY, ETC.
REFER TO FIRE ALARM RELATED SPECIFICATION SECTIONS: 28 05
00, 28 05 13, 28 05 26, 28 05 29, & 28 31 00 FOR ADDITIONAL
REQUIREMENTS AND INFORMATION.
COORDINATION LOCATION OF ALL NEW FIRE ALARM APPLIANCES
WITH EXISTING BUILDING CONDITIONS.
NEW DUCT SMOKE DETECTORS SHALL BE PROVIDED IN SUPPLY
AIR SYSTEMS WITH A DESIGN CAPACITY GREATER THAT 2,000-CFM.
ACCESS TO DETECTORS SHALL BE PROVIDED FOR INSPECTION
AND MAINTENANCE PURPOSES. ACTIVATION OF THE DUCT
DETECTOR SYSTEM SHALL SHUT DOWN ALL OPERATIONAL
CAPABILITIES OF THE AFFECTED UNIT. COORDINATE LOCATION OF
ALL NEW REPLACED DUCT DETECTORS WITH EXISTING DETECTOR
LOCATIONS. DUCT SMOKE SENSORS SHALL BE IN ACCORDANCE
WITH NFPA 72, AND INTERNATIONAL MECHANICAL CODE.
ALL DUCT DETECTORS SHALL BE PROVIDED WITH REMOVE STATUS
INDICATION. PROVIDE INDICATING LAMP FOR ALL CONCEALED
DETECTORS.
INSTALL SMOKE DETECTORS NO CLOSER THAN 3'-0" TO HVAC AIR
SUPPLY DIFFUSERS.
22.
23.
24.
25.
26.
27.
28.
FIRE ALARM NOTES CONT.
MONITOR MODULEMM
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y L a n e
S u it e
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
Copyright © 2020 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the express written agreement of Pond & Company.
ORIGINAL SHEET SIZE 22" X 34"
N D
S
J K
C
B T
H
C A
D
J O
B N
O
/2
/2
:5 :1
P
M B
IM
/1
F
C I C o le m a n /1
F
C I_
C o le m a n F
P v .r v t
F-001
100% BID SET
F
IR
E A
L A
R M
G E
N E
R A
L N
O T
E S
L
E G
E N
D
N
E
T
H T
E R
R A
C E
C
O L E
M A
N
F L
F B
O P
F
C C
C O
L E
M A
N F
IR
E
A L A
R M
R E
P L A
C E
M E
N T
M A
R K
D E
S C
R
IP
T I O
N D
A T
E
F
B O
P C
O M
M E
N T
S .2
.2
O
W N
E R
R E
V
IS
IO
N
S .2
.2
| Sheets |
| F-001 - FIRE ALARM GENERAL NOTES & LEGEND |
File details come from the government source that posted it. Updated .