A06_Shop_Drawings.pdf

PDF 2 MB Posted

Attached to
FIRE SUPPRESSION SYSTEM CODE CORRECTION - ANCHORAG Federal contract opportunity
Solicitation number
140P9725Q0033
Issued by
Department of the Interior National Park Service Alaska Region

About this file

These shop drawings are for a fire suppression system modification project for the National Park Service in Anchorage, Alaska. The documents detail alterations to an existing wet pipe sprinkler system in Storage Room 132, which involves installing high-density mobile shelving. The project requires modifying the sprinkler system to accommodate mobile compact storage racks that are 10-feet high and approximately 415 square feet in area, storing non-encapsulated Class I through Class III commodities.

Key technical specifications include utilizing standard response, brass pendent-type sprinklers with a 8.0 K-factor, 1/2" thread, and 155-degree temperature rating (Viking Model VK2022), with a design density of 0.30 GPM/sq.ft over 2,500 sq.ft. The Authority Having Jurisdiction (Municipality of Anchorage Fire Marshal) requires the system to be classified as Extra Hazard Group 1 (EH1). Installation requirements mandate all sprinkler components be new, UL listed/FM approved, using Schedule 40 black steel piping, and installed per NFPA 13 standards, with the installing contractor required to provide shop drawings and hydraulic calculations to the Fire Marshal's office for review and approval.

View the file

Other files for this federal contract opportunity

Other files attached to FIRE SUPPRESSION SYSTEM CODE CORRECTION - ANCHORAG, newest first.
File Type Posted
A06_Hydraulic_Calculations.pdf PDF
A06_Specifications_DIV_01_Redacted.pdf PDF
Sol_140P9725Q0033.pdf PDF
B03_DOL_DB_WD_AK20250001_Rev_4.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N

AECC511

Surveyors 601 College Road Fairbanks AK 99701

DESIGNED BY

Architects

ISSUE DATE

COMM. NUMBER

designalaska.com

Engineers

907.452.1241

DRAWN BY

10 JULY 2024

402301

SCALE

with Retaining Strap (Beam)

Hanger No. 12S with Lock Nut or Equal Top Beam C-Clamp Model 300 Michigan

Retaining Strap

Nearest Inch Rounded to

Pipe

Rod Thread All

Swivel Ring

Bar Joist Steel I-Beam or

"A

Note on Plan: Hanger Number and "A" Dimension

Top Beam C-Clamp with Retaining Strap (Joist)

Hanger No. 13S with Lock Nut or Equal Top Beam C-Clamp Model 300 Michigan

Retaining Strap

Nearest Inch Rounded to

Pipe

Rod Thread All

Swivel Ring

Bar Joist Steel I-Beam or

"A

Note on Plan: Hanger Number and "A" Dimension

Top Beam C-Clamp

Sprinkler Legend Symbol Manufacturer Model Quantity K-Factor Type Size Response Finish Temperature Note

Central BV-QR 45 5.6 Pendent ½ Quick Brass 155 °F DEMOLISH Viking VK2022 45 8 Pendent ½ Standard Brass 155 °F NEW Central BV-QR 15 5.6 Pendent ½ Quick Brass 155 °F EXISTING TO REMAIN

Total = 105

KYLE RANKINS

NICET III: WATER-BASED SYSTEMS LAYOUT

NICET CERTIFICATION #: 140052

SOA FIRE SYS. PERMIT IIC-DO #: 190209

- PIPE ELEVATION BELOW TOP OF STEEL

- EXISTING SPRINKLER PIPE

FIRE SUPPRESSION

DEMOLITION PLAN,

NOTES, AND

DETAILS

- PIPE ELEVATION ABOVE FINISHED FLOOR

- BRANCHLINE SPRINKLER PIPE

- MAIN SPRINKLER PIPE

SYMBOL LEGEND:

- SPRINKLER PIPE SEGMENT LENGTH

X'-X"

- HYDRAULIC REFERENCE POINT

- SPRINKLER PIPE DIAMETER

- DENOTES SWAY BRACE LOCATION

- DENOTES HANGER LOCATION

X

ARO CURATORIAL

HIGH DENSITY

SHELVING

NOT TO SCALE

FIRE SPRINKLER SITE MAP

ABBREVIATIONS:

OC - ON CENTER

NO - NORMALLY OPEN

NIC - NOT IN CONTRACT DN - DOWN

FDC - FIRE DEPT. CONNECTION

RN - RISER NIPPLE

AFG - ABOVE FINISHED GRADE

UNO - UNLESS NOTED OTHERWISE

CL - CENTERLINE

AFF - ABOVE FINISHED FLOOR

TOS - TOP OF STEEL

BOR - BOTTOM OF RISER

NC - NORMALLY CLOSED

TOR - TOP OF RISER

SCALE: 1/4" = 1'

FIRE RISER DETAIL

COMMODITY CLASSIFICATION: MOBILE STORAGE RACKS, 10-FT IN

HEIGHT, APPROXIMATELY 415 SQ.FT. IN AREA, STORING

NON-ENCAPSULATED, CLASS I THRU CLASS III COMMODITIES.

COMPACT STORAGE MODULE HEIGHTS AND AREA EXCEED

MAXIMUM REQUIREMENTS FOR LIGHT HAZARD CLASSIFICATION

PER NFPA 13, SECTION 21.12.

PER AHJ DIRECTION ON SIMILAR ARRANGEMENT PROJECT,

MOBILE COMPACT STORAGE AREAS TO BE PROTECTED AS AN

EXTRA HAZARD GROUP 1 (EH1) CLASSIFICATION UTILIZING THE

DENSITY/AREA METHOD.

DESIGN DENSITY: 0.30 GPM/SQ.FT. OVER 2,500 SQ.FT.

OUTSIDE HOSE DEMAND: 500 GPM

SPRINKLER TYPE: UTILIZE STANDARD RESPONSE, BRASS

PENDENT TYPE, RETROFIT 8.0 K-FACTOR SPRINKLER WITH 1/2"

THREAD, 155 DEGREE TEMPERATURE RATING. VIKING MODEL

VK2022 USED AS BASIS OF DESIGN.

INSTALLATION NOTES:

APPLICABLE CODES:

MODIFY EXISTING WET PIPE SPRINKLER SYSTEM PROTECTING

THE NEWLY INSTALLED HIGH DENSITY MOBILE SHELVING /

COMPACT STORAGE LOCATED IN STORAGE 132.

AUTHORITY HAVING JURISDICTION NOTED AS THE MUNICIPALITY

OF ANCHORAGE FIRE MARSHAL.

INSTALLING CONTRACTOR TO PROVIDE THESE SHOP DRAWINGS

AND HYDRAULIC CALCULATIONS TO FIRE MARSHALS OFFICE FOR

REVIEW AND APPROVAL.

ALL SPRINKLER COMPONENTS TO BE NEW, UL LISTED AND/OR FM

APPROVED WHERE APPLICABLE.

ALL SPRINKLER PIPING TO BE SCHEDULE 40, BLACK STEEL.

ALL PIPING, HANGERS, AND BRACING TO BE INSTALLED PER NFPA

13 REQUIREMENTS.

COORDINATE WITH THE FACILITY MAINTENANCE FOR SPRINKLER

SYSTEM SHUTDOWN PRIOR TO PERFORMING WORK.

SPRINKLER SYSTEM TO BE BROUGHT BACK INTO SERVICE EACH

DAY, SCOPE OF WORK AREA TO REMAIN FULLY OCCUPIED AT ALL

TIMES DURING CONSTRUCTION. COMPLY WITH NFPA 25 CHAPTER

15 FOR IMPAIRMENTS.

DRAIN SYSTEM IN SUCH A WAY THAT PREVENTS SPRINKLER WATER

FROM DISCHARGING ONTO SIDEWALK ENTRYWAYS.

INSTALLING CONTRACTOR TO PROVIDE PLASTIC SHEETING OR

SIMILAR TO COVER STORAGE MODULES IN AREA OF WORK.

IBC/IFC (2018)

NFPA 13 (2019)

DESIGN CRITERIA:

FIRE SPRINKLER NOTES:

SCOPE OF WORK:

FIRE SUPPRESSION PROJECT NOTES:

SCALE: 1/8" = 1'

FIRE SPRINKLER DEMOLITION PLAN

- DEMOLISHED SPRINKLER PIPE

HYDRANT FLOW TEST DATA

Static Pressure 58.000 Residual Pressure: 20.000 Flow 3120.00 Outside Hose Flow 500.00 Test Conducted By MOA WATER MODEL Date of Test 05/16/2024

0 " FF

0 " TS

1.

1.

2.

3.

1.

2.

1.

2.

3.

4.

5.

6.

6.

5.

4.

7.

KDR

KDR

1"0"

F001

EH1 DESIGN DENSITY

2,500

43.4

MOBILE COMPACT STORAGE

0.30

REMOTE AREA #1

42 6 108 12

SCALE: 1/8" = 1'-0"

XX

EXISTING FIRE

HYDRANT

EXISTING 8-INCH

UNDERGROUNDPROJECT AREA

EXISTING 6-INCH

UNDERGROUND

FIRE RISER

LOCATION

EXISTING 12-INCH

UNDERGROUND

0' -0

25'-0"

50'-0" 625'-0"

2 630 41

SCALE: 1/4" = 1'-0"

DESIGNED BY

907.452.1241 designalaska.com

COMM. NUMBER

ISSUE DATE

402301

N

SurveyorsArchitects

DRAWN BY

10 JULY 2024

Engineers 601 College Road Fairbanks AK 99701

AECC511

SCALE

Sprinkler Legend Symbol Manufacturer Model Quantity K-Factor Type Size Response Finish Temperature Note

Central BV-QR 45 5.6 Pendent ½ Quick Brass 155 °F DEMOLISH Viking VK2022 45 8 Pendent ½ Standard Brass 155 °F NEW Central BV-QR 15 5.6 Pendent ½ Quick Brass 155 °F EXISTING TO REMAIN

Total = 105 with Retaining Strap (Beam)

Hanger No. 12S with Lock Nut or Equal Top Beam C-Clamp Model 300 Michigan

Retaining Strap

Nearest Inch Rounded to

Pipe

Rod Thread All

Swivel Ring

Bar Joist Steel I-Beam or

"A

Note on Plan: Hanger Number and "A" Dimension

Top Beam C-Clamp with Retaining Strap (Joist)

Hanger No. 13S with Lock Nut or Equal Top Beam C-Clamp Model 300 Michigan

Retaining Strap

Nearest Inch Rounded to

Pipe

Rod Thread All

Swivel Ring

Bar Joist Steel I-Beam or

"A

Note on Plan: Hanger Number and "A" Dimension

Top Beam C-Clamp

NICET CERTIFICATION #: 140052

NICET III: WATER-BASED SYSTEMS LAYOUT

KYLE RANKINS

SOA FIRE SYS. PERMIT IIC-DO #: 190209

FIRE SPRINKLER PLAN

SCALE: 1/8" = 1'

ARO CURATORIAL

HIGH DENSITY

SHELVING

FIRE SUPPRESSION

PLAN

STORAGE 130 & 131 IS OUTSIDE THE SCOPE OF THE ORIGINAL

PROJECT, HOWEVER RE-WORK OF THE EXISTING SPRINKLER

SYSTEM IS REQUIRED TO ACCOMMODATE WORK ASSOCIATED IN

STORAGE 132.

FIRE SUPPRESSION SHEET SPECIFIC NOTES:

1.

EXTRA HAZARD GROUP 1 - 0.30 GPM/SQFT OVER 2,500 SQFT

NOT IN SCOPE

WET PIPE

AREA HAZARD CLASSIFICATION - NFPA 13, FIGURE 19.3.3.1.1

0"

KDR

1"

KDR

F100

42 6 108 12

SCALE: 1/8" = 1'-0"