Attachment_2_Design_memo_for_Nez_Perce_HVAC_Duct_Replacement.pdf
PDF 5 MB Posted
- Attached to
- Improve HVAC system, Nez Perce NHP, Lapwai ID Federal contract opportunity
- Solicitation number
- 140P8319Q0054
About this file
Attachment 2: Design memo
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment_3a_Revised_Wage_Determination_(ID32,_7-19-19).pdf | ||
| site_visit_register_140P8319Q0054.pdf | ||
| Sol_140P8319Q0054_Amd_0001.pdf | ||
| forms_to_return_with_quote.docx | DOCX document | |
| Sol_140P8319Q0054.pdf | ||
| Attachment_1_Construction_Specifications_Division_1.pdf | ||
| FAQs_for_RFQ_140P8319Q0054.pdf | ||
| Attachment_3_Wage_Determination_(ID32).pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Nez Perce Historical Park Contract No. P13PC00204
Title I – Design Review Memo: Replacing Heating and Air
Conditioning Ductwork in Spalding Visitor’s Center
PMIS 194373
March 2019
Table of Contents
Executive summary……………………………………………………………1.0
Project Background……………………….……………………………………1.1
Conclusions and Recommendations…………………………………………2.0
List of Exhibits
Exhibit A Existing Duct Calculations Exhibit B Existing Mechanical Plans Exhibit C New Mechanical Plans
M0.0 - Mechanical Cover Sheet M0.1 - Mechanical Specifications M0.2 - Mechanical Specifications M1.0 - Mechanical Schedules M2.1 - Mechanical Basement Plan M2.2 - Mechanical First Floor Plan
Exhibit D Specifications
230700 - HVAC Insulation 233113 - Metal Ducts 233300 - Air Duct Accessories 233713 - Diffusers, Registers, and Grilles
1.0 Executive Summary
The objective of this report is to evaluate the suitability of retaining the existing duct sizes when the existing ductwork in the Visitor’s Center at the Nez Perce Historical Park is replaced under a separate project. There are 10 split-system fan-coil (FC) systems with electric backup heat currently serving the building. Calculations indicate that the existing duct systems are adequately sized for the equipment, except for two branch ducts connected to FC-6. Exhibit C shows the revised duct and diffuser layout, with additional notes pertaining to special construction and coordination items required for re-use of humidifiers / dehumidifiers, duct smoke detectors, dampers and carbon filters.
1.1 Project Background
In 2014, the water-source heat pumps and air handlers serving the Visitor’s Center were replaced with air-source fan-coil / heat pump systems designed to match the original systems’ capacities. Under the 2014 project, the existing ductwork was retained and re-used.
The existing ductwork has fiberglass lining which is deteriorating, necessitating more frequent filter changes and duct cleanings. The owner therefore intends to replace the existing ductwork. DC Engineering (DCE) has been tasked with evaluating whether the existing duct systems may be replaced in kind, and where duct sizes are found to be deficient, to provide corrected sizing.
The duct systems were evaluated based on SMACNA’S “HVAC Systems Duct Design” manual, along with Carrier Corporation’s “System Design Manual” air distribution volume.
General notes regarding the evaluation method:
• It is assumed that the duct sizes shown on the original drawings represented the free area.
• Calculations assume that changes in direction greater than 45° will have turning vanes. Bullhead Tees are assumed to incorporate turning vanes.
• It should be noted that the FC units 2, 5, 6 & 7 scheduled in the 2014 renovations are larger capacity units than those in the original design. The evaluations were conducted based on the 2014 CFM values.
In addition, a survey of the site indicated that the humidification and dehumidification systems serving the Storage area (002) and Exhibits area (102) are not functioning. These will require placement in order to maintain the proper humidity levels for museum collections (50% ± 10%) as requested by the owner.
2.0 Conclusions and Recommendations
All the existing duct systems may be replaced like for like and function as designed, except for two branches connected to FC-6 which require a slight increase in size. The duct static calculations for existing systems are shown in Exhibit A, and Exhibit B contains a “duct map” showing the segments corresponding to the segment names shown in the calculation sheets.
A revised mechanical plan is shown in Exhibit C. This includes the existing duct sizes and updated sizes serving the Admin Clerk Office, Room 115, and the Open Office, Room
114. It also shows new diffusers (except for custom diffusers/grilles retained in rooms 101 and 102) and airflows for balancing purposes and contains additional notes regarding the installation of ducts in the vicinity of the humidifiers, existing carbon filters, and the mixing boxes serving the Exhibits Room (Room 102). In addition to the work described above, these plans include the new humidifiers and dehumidifiers noted in the project background section. As a cost-saving measure, a deduct alternate specifying re-use of the existing grilles / diffusers may be requested.
As noted above, some HVAC units are larger than in the original design. Where this is the case, the additional airflow has been proportionally distributed between the air inlets and outlets.
Exhibit A - Existing Duct Calculations
DUCT SIZING WORKSHEET (SMACNA)
DATE: 7/31/2018
PROJECT NO.: 18HOL04 PROJECT NAME: Nez Perce National Historical Park SYSTEM: FC-1 RETURN SIDE, EXISTING PAGE: 1
A B C D E F G H I J K L M N O
DUCT SECT- SMAC- FLOW FRICTION VELOCITY VEL.PR. LOSS EQUIV. RECTANGULAR SIZE - in. ROUGHN. STR. DUCT FITTING SP. ITEM TOTAL
RUN ION LEN- FTG. NA ITEM MAIN BRANCH PER DUCT V Vp COEFF. DIA. IN OUT CORR. LOSS LOSS LOSS LOSS
GTH ANGLE FTG. cfm cfm in. w.g. fpm in. w.g. in. WIDTH HEIGHT WIDTH HEIGHT FACTOR in. w.g. in. w.g. in. w.g. in. w.g.
ft. deg. Fig. 14-3
SUM OF SUPPLY LOSSES 0.001 0.020 0.165 0.199
- INTAKE PLENUM 800 0 0 0.0000 0 1.0 0 0.000 0.1 0.100
- FILTER 800 0 0 0.0000 0 1.0 0 0.000 0.1 0.100
14.10-H ELBOW 800 0.000 480 0.0143 0.24 17.5 16 16 16 16 1.2 0.000 0.003 0.004
A 8 DUCT 800 0.002 480 0.0143 17.5 16 16 16 16 1.2 0.002 0.000 0.002
20 Carrier Man. DOUBLE-ELBOW 800 0.005 480 0.0143 17.5 16 16 16 16 1.2 0.005 0.000 0.006
B 8 DUCT 800 0.002 480 0.0143 17.5 16 16 16 16 1.2 0.002 0.000 0.002
14.10-H ELBOW 800 0.000 480 0.0143 0.24 17.5 16 16 16 16 1.2 0.000 0.003 0.004
C 4 DUCT 800 0.001 480 0.0143 17.5 16 16 16 16 1.2 0.001 0.000 0.001
GRILLE 800 0 0 0.0000 0 1.0 0 0.000 0.05 0.050
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
SUM OF LOSSES BEFORE CONTROL MARGIN 0.010 0.027 0.415 0.469
ALLOWANCE FOR CONTROL MARGIN 0.000
ALLOWANCE FOR ________________________________
STATIC PRESSURE TOTAL 0.469
PROJECT NO.: 18HOL04 PROJECT NAME: Nez Perce National Historical Park SYSTEM: FC-1 SUPPLY SIDE, EXISTING PAGE: 1
A B C D E F G H I J K L M N O
DUCT SECT- SMAC- FLOW FRICTION VELOCITY VEL.PR. LOSS EQUIV. RECTANGULAR SIZE - in. ROUGHN. STR. DUCT FITTING SP. ITEM TOTAL
RUN ION LEN- FTG. NA ITEM MAIN BRANCH PER 100' V Vp COEFF. DIA. IN OUT CORR. LOSS LOSS LOSS LOSS
GTH ANGLE FTG. cfm cfm in. w.g. fpm in. w.g. in. WIDTH HEIGHT WIDTH HEIGHT FACTOR in. w.g. in. w.g. in. w.g. in. w.g.
ft. deg. Fig. 14-3
- 90 14.1-H DISCH / ELBOW 800 0.000 480 0.0143 0.24 17.5 16 16 16 16 1.0 0.000 0.003 0.015 0.018
A 2 0 DUCT 800 0.000 480 0.0143 17.5 16 16 16 16 1.2 0.000 0.000 0.000
- - TRANSFORMATION 800 0.000 480 0.0143 0.15 17.5 16 16 24 10 1.2 0.000 0.002 0.003
B 4 - - CARBON FILTER 800 0.001 536 0.0179 16.5 24 10 24 10 1.2 0.000 0.000 0.05 0.060
- - TRANSFORMATION 800 0.000 536 0.0179 0.15 16.5 24 10 16 16 1.2 0.000 0.003 0.003
C 4 - - DUCT 800 0.001 480 0.0143 17.5 16 16 16 16 1.2 0.000 0.000 0.000
- 14.14-N BRANCH - MAIN 800 210 0.000 480 0.0143 0.02 17.5 16 16 16 16 1.2 0.000 0.000 0.000
CONTRACTION 590 0.000 354 0.0078 0.05 17.5 16 16 12 12 1.2 0.000 0.000 0.000
D 4 - - DUCT 590 0.002 629 0.0247 13.1 12 12 12 12 1.2 0.000 0.000 0.000
14.1-H ELBOW 590 0.000 629 0.0247 0.24 13.1 12 12 12 12 1.2 0.000 0.006 0.007
E 2 - - DUCT 590 0.001 629 0.0247 13.1 12 12 12 12 1.2 0.000 0.000 0.000
- 14.14-N BRANCH - MAIN 590 210 0.000 629 0.0247 0.02 13.1 12 12 12 12 1.2 0.000 0.000 0.001
14.12-A CONTRACTION 380 0.000 405 0.0102 0.05 13.1 12 12 11 11 1.2 0.000 0.001 0.001
F 4 - - DUCT 380 0.001 482 0.0145 12.0 11 11 11 11 1.2 0.000 0.000 0.000
14.1-H ELBOW 380 0.000 482 0.0145 0.24 12.0 11 11 11 11 1.2 0.000 0.003 0.004
G 4 - - DUCT 380 0.001 482 0.0145 12.0 11 11 11 11 1.2 0.000 0.000 0.000
14.14-N BRANCH - MAIN 380 190 0.000 482 0.0145 0.05 12.0 11 11 11 11 1.2 0.000 0.001 0.001
14.12-A CONTRACTION 190 0.000 241 0.0036 0.05 12.0 11 11 8 8 1.0 0.000 0.000 0.000
H 8 - - DUCT 190 0.004 456 0.0129 8.7 8 8 8 8 1.0 0.000 0.000 0.000
DIFFUSER 190 190 0 0 0.0000 0 1.0 0.000 0.000 0.1 0.100
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0.0000 0 1.0 0.000 0.000 0.000
SUM OF LOSSES BEFORE CONTROL MARGIN 0.001 0.020 0.165 0.199
ALLOWANCE FOR CONTROL MARGIN 0.000 0.000 0.000 0.000
SAFETY FACTOR ALLOWANCE ______________
STATIC PRESSURE TOTAL 0.199
PROJECT NO.: 18HOL04 PROJECT NAME: Nez Perce National Historical Park SYSTEM: FC-2 RETURN SIDE PAGE: 1
A B C D E F G H I J K L M N O
DUCT SECT- SMAC- FLOW FRICTION VELOCITY VEL.PR. LOSS EQUIV. RECTANGULAR SIZE - in. ROUGHN. STR. DUCT FITTING SP. ITEM TOTAL
RUN ION LEN- FTG. NA ITEM MAIN BRANCH PER DUCT V Vp COEFF. DIA. IN OUT CORR. LOSS LOSS LOSS LOSS
GTH ANGLE FTG. cfm cfm in. w.g. fpm in. w.g. in. WIDTH HEIGHT WIDTH HEIGHT FACTOR in. w.g. in. w.g. in. w.g. in. w.g.
ft. deg. Fig. 14-3
SUM OF SUPPLY LOSSES 0.004 0.027 0.215 0.249
- INTAKE PLENUM 1,600 0 0 0.0000 0 1.0 0 0.000 0.1 0.100
- FILTER 1,600 0 0 0.0000 0 1.0 0 0.000 0.1 0.100
A 6 DUCT 1,600 0.004 884 0.0487 18.2 20 14 20 14 1.2 0.004 0.000 0.005
14.10-H ELBOW 1,600 0.000 884 0.0487 0.24 18.2 20 14 20 14 1.2 0.000 0.012 0.014
B 4 DUCT 1,600 0.003 884 0.0487 18.2 20 14 20 14 1.2 0.003 0.000 0.003
14.10-H ELBOW 1,600 0.000 884 0.0487 0.24 18.2 20 14 20 14 1.2 0.000 0.012 0.014
C Carrier Man. ABRUPT ENTRANCE 1,600 0.000 884 0.0487 0.35 18.2 20 14 20 14 1.2 0.000 0.017 0.020
GRILLE 1,600 0 0 0.0000 0 1.0 0 0.000 0.05 0.050
0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
SUM OF LOSSES BEFORE CONTROL MARGIN 0.011 0.067 0.465 0.556
ALLOWANCE FOR CONTROL MARGIN 0.000
ALLOWANCE FOR ________________________________
STATIC PRESSURE TOTAL 0.556
, EXISTING
PROJECT NO.: 18HOL04 PROJECT NAME: Nez Perce National Historical Park SYSTEM: FC-2 SUPPLY SIDE PAGE: 1
A B C D E F G H I J K L M N O
DUCT SECT- SMAC- FLOW FRICTION VELOCITY VEL.PR. LOSS EQUIV. RECTANGULAR SIZE - in. ROUGHN. STR. DUCT FITTING SP. ITEM TOTAL
RUN ION LEN- FTG. NA ITEM MAIN BRANCH PER 100' V Vp COEFF. DIA. IN OUT CORR. LOSS LOSS LOSS LOSS
GTH ANGLE FTG. cfm cfm in. w.g. fpm in. w.g. in. WIDTH HEIGHT WIDTH HEIGHT FACTOR in. w.g. in. w.g. in. w.g. in. w.g.
ft. deg. Fig. 14-3
- 90 14.1-H DISCH / ELBOW 1,600 0.000 884 0.0487 0.24 18.2 20 14 20 14 1.0 0.000 0.012 0.015 0.027
A 8 0 DUCT 1,600 0.005 884 0.0487 18.2 20 14 20 14 1.2 0.001 0.000 0.001
20 Carrier Man. DOUBLE-ELBOW 800 0.009 627 0.0245 15.3 14 14 14 14 1.2 0.002 0.000 0.003
B 8 - - DUCT 800 0.004 627 0.0245 15.3 14 14 14 14 1.2 0.000 0.000 0.000
- 14.1-H ELBOW 800 0.000 627 0.0245 0.24 15.3 14 14 14 14 1.2 0.000 0.006 0.007
C 8 - - DUCT 800 0.004 627 0.0245 15.3 14 14 14 14 1.2 0.000 0.000 0.000
- 14.1-H ELBOW 800 0.000 627 0.0245 0.24 15.3 14 14 14 14 1.2 0.000 0.006 0.007
8 - DUCT 800 0.004 627 0.0245 15.3 14 14 14 14 1.2 0.000 0.000 0.000
D - 14.14-N BRANCH - MAIN 800 400 0.000 627 0.0245 15.3 14 14 16 10 1.2 0.000 0.000 0.000
14.12-A CONTRACTION 400 0.000 389 0.0094 0.24 13.7 16 10 10 10 1.2 0.000 0.002 0.003
E 4 - - DUCT 400 0.003 614 0.0235 10.9 10 10 1.0 10 1.2 0.000 0.000 0.000
- 14.1-H ELBOW 400 0.000 614 0.0235 0.05 10.9 10 10 1.0 10 1.2 0.000 0.001 0.001
14.12-A DIFFUSER 400 400 0.000 614 0.0235 10.9 10 10 1.0 10 1.0 0.000 0.000 0.1 0.100
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0.24 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0.05 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.1 0.100
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0.0000 0 1.0 0.000 0.000 0.000
SUM OF LOSSES BEFORE CONTROL MARGIN 0.004 0.027 0.215 0.249
ALLOWANCE FOR CONTROL MARGIN 0.000 0.000 0.000 0.000
SAFETY FACTOR ALLOWANCE ______________
STATIC PRESSURE TOTAL 0.249
PROJECT NO.: 18HOL04 PROJECT NAME: Nez Perce National Historical Park SYSTEM: FC-4 RETURN SIDE PAGE: 1
A B C D E F G H I J K L M N O
DUCT SECT- SMAC- FLOW FRICTION VELOCITY VEL.PR. LOSS EQUIV. RECTANGULAR SIZE - in. ROUGHN. STR. DUCT FITTING SP. ITEM TOTAL
RUN ION LEN- FTG. NA ITEM MAIN BRANCH PER DUCT V Vp COEFF. DIA. IN OUT CORR. LOSS LOSS LOSS LOSS
GTH ANGLE FTG. cfm cfm in. w.g. fpm in. w.g. in. WIDTH HEIGHT WIDTH HEIGHT FACTOR in. w.g. in. w.g. in. w.g. in. w.g.
ft. deg. Fig. 14-3
SUM OF SUPPLY LOSSES 0.001 0.014 0.125 0.142
- INTAKE PLENUM 800 0 0 0.0000 0 1.0 0 0.000 0.1 0.100
- FILTER 800 0 0 0.0000 0 1.0 0 0.000 0.1 0.100
0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
SUM OF LOSSES BEFORE CONTROL MARGIN 0.001 0.014 0.325 0.342
ALLOWANCE FOR CONTROL MARGIN 0.000
ALLOWANCE FOR ________________________________
STATIC PRESSURE TOTAL 0.342
PROJECT NO.: 18HOL04 PROJECT NAME: Nez Perce National Historical Park SYSTEM: FC-4 SUPPLY SIDE PAGE: 1
A B C D E F G H I J K L M N O
DUCT SECT- SMAC- FLOW FRICTION VELOCITY VEL.PR. LOSS EQUIV. RECTANGULAR SIZE - in. ROUGHN. STR. DUCT FITTING SP. ITEM TOTAL
RUN ION LEN- FTG. NA ITEM MAIN BRANCH PER 100' V Vp COEFF. DIA. IN OUT CORR. LOSS LOSS LOSS LOSS
GTH ANGLE FTG. cfm cfm in. w.g. fpm in. w.g. in. WIDTH HEIGHT WIDTH HEIGHT FACTOR in. w.g. in. w.g. in. w.g. in. w.g.
ft. deg. Fig. 14-3
- 90 14.1-H DISCH / ELBOW 800 0.000 546 0.0186 16.4 15 15 15 15 1.0 0.000 0.000 0.025 0.025
45 14.10-D ELBOW 800 0.000 546 0.0186 0.34 16.4 15 15 15 15 1.2 0.000 0.006 0.008
A 7 - - DUCT 800 0.002 546 0.0186 16.4 15 15 15 15 1.2 0.000 0.000 0.000
- 14.14-N BRANCH - MAIN 800 200 0.000 546 0.0186 0.22 16.4 15 15 15 15 1.2 0.000 0.004 0.005
B 3 - - DUCT 600 0.001 409 0.0104 16.4 15 15 15 15 1.2 0.000 0.000 0.000
- 14.14-N BRANCH - MAIN 600 200 0.000 409 0.0104 0.09 16.4 15 15 15 15 1.2 0.000 0.001 0.001
C 3 - DUCT 400 0.000 273 0.0046 16.4 15 15 15 15 1.2 0.000 0.000 0.000
14.12-A CONTRACTION 400 0.000 273 0.0046 0.05 16.4 15 15 11 11 1.2 0.000 0.000 0.000
D 10 - - DUCT 400 0.004 507 0.0161 12.0 11 11 11 11 1.2 0.000 0.000 0.001
- 14.14-N BRANCH - MAIN 400 200 0.000 507 0.0161 0.03 12.0 11 11 11 11 1.2 0.000 0.000 0.001
14.12-A CONTRACTION 200 0.000 254 0.0040 0.05 12.0 11 11 11 11 1.2 0.000 0.000 0.000
- 14.1-H ELBOW 200 0.000 254 0.0040 0.34 12.0 11 11 11 11 1.2 0.000 0.001 0.002
14.12-A GRILLE 200 200 0.000 254 0.0040 0.00 12.0 11 11 11 11 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.1 0.100
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0.0000 0 1.0 0.000 0.000 0.000
SUM OF LOSSES BEFORE CONTROL MARGIN 0.001 0.014 0.125 0.142
ALLOWANCE FOR CONTROL MARGIN 0.000 0.000 0.000 0.000
SAFETY FACTOR ALLOWANCE ______________
STATIC PRESSURE TOTAL 0.142
PROJECT NO.: 18HOL04 PROJECT NAME: Nez Perce National Historical Park SYSTEM: FC-5 RETURN SIDE, EXISTING PAGE: 1
A B C D E F G H I J K L M N O
DUCT SECT- SMAC- FLOW FRICTION VELOCITY VEL.PR. LOSS EQUIV. RECTANGULAR SIZE - in. ROUGHN. STR. DUCT FITTING SP. ITEM TOTAL
RUN ION LEN- FTG. NA ITEM MAIN BRANCH PER DUCT V Vp COEFF. DIA. IN OUT CORR. LOSS LOSS LOSS LOSS
GTH ANGLE FTG. cfm cfm in. w.g. fpm in. w.g. in. WIDTH HEIGHT WIDTH HEIGHT FACTOR in. w.g. in. w.g. in. w.g. in. w.g.
ft. deg. Fig. 14-3
SUM OF SUPPLY LOSSES 0.004 0.075 0.115 0.311
- INTAKE GRILLE 2,000 0 0 0.0000 0 1.0 0 0.000 0.05 0.050
3 DUCT 2,000 0.001 808 0.0407 21.3 20 19 20 19 1.2 0.001 0.000 0.002
ELBOW 2,000 0.000 808 0.0407 0.17 21.3 20 19 20 19 1.2 0.000 0.007 0.008
15 DUCT 2,000 0.007 808 0.0407 21.3 20 19 20 19 1.2 0.007 0.000 0.009
- INTAKE 2,000 0 0 0.0000 0 1.0 0 0.000 0.05 0.050
- FILTER 2,000 0 0 0.0000 0 1.0 0 0.000 0.1 0.100
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
SUM OF LOSSES BEFORE CONTROL MARGIN 0.013 0.082 0.315 0.529
ALLOWANCE FOR CONTROL MARGIN 0.000
STATIC PRESSURE TOTAL 0.529
PROJECT NO.: 18HOL04 PROJECT NAME: Nez Perce National Historical Park SYSTEM: FC-5 SUPPLY SIDE, EXISTING PAGE: 1
A B C D E F G H I J K L M N O
DUCT SECT- SMAC- FLOW FRICTION VELOCITY VEL.PR. LOSS EQUIV. RECTANGULAR SIZE - in. ROUGHN. STR. DUCT FITTING SP. ITEM TOTAL
RUN ION LEN- FTG. NA ITEM MAIN BRANCH PER 100' V Vp COEFF. DIA. IN OUT CORR. LOSS LOSS LOSS LOSS
GTH ANGLE FTG. cfm cfm in. w.g. fpm in. w.g. in. WIDTH HEIGHT WIDTH HEIGHT FACTOR in. w.g. in. w.g. in. w.g. in. w.g.
ft. deg. Fig. 14-3
- - 14.1-H DISCH 2,000 0.000 948 0.0560 19.7 18 18 18 18 1.0 0.000 0.000 0.015 0.015
A 3 - - DUCT 2,000 0.002 948 0.0560 19.7 18 18 18 18 1.2 0.000 0.000 0.000
- 14.14-N BRANCH - MAIN 2,000 335 0.000 948 0.0560 0.02 19.7 18 18 18 18 1.2 0.000 0.001 0.001
- 14.1-H ELBOW 1,665 0.000 789 0.0388 0.24 19.7 18 18 18 18 1.2 0.000 0.009 0.011
B 10 - - DUCT 1,665 0.005 789 0.0388 19.7 18 18 18 18 1.2 0.001 0.000 0.001
- 14.14-N BRANCH - MAIN 1,665 250 0.000 789 0.0388 0.02 19.7 18 18 18 18 1.2 0.000 0.001 0.001
14.12-A CONTRACTION 1,415 0.000 670 0.0280 0.05 19.7 18 18 18 18 1.2 0.000 0.001 0.002
C 3 - - DUCT 1,415 0.003 965 0.0581 0.05 16.4 15 15 15 15 1.2 0.000 0.003 0.004
- 14.1-H ELBOW 1,415 0.000 965 0.0581 0.17 16.4 15 15 15 15 1.2 0.000 0.010 0.012
- 14.14-N BRANCH - MAIN 1,415 250 0.000 965 0.0581 0.02 16.4 15 15 15 15 1.2 0.000 0.001 0.001
D 12 - - DUCT 1,165 0.008 795 0.0394 0.05 16.4 15 15 15 15 1.2 0.001 0.002 0.004
- 14.1-H ELBOW 1,165 0.000 795 0.0394 0.17 16.4 15 15 15 15 1.2 0.000 0.007 0.008
E 5 - - DUCT 1,165 0.003 795 0.0394 0.00 16.4 15 15 15 15 1.2 0.000 0.000 0.000
- 14.14-N BRANCH - MAIN 1,165 250 0.000 795 0.0394 0.03 16.4 15 15 15 15 1.2 0.000 0.001 0.001
14.12-A CONTRACTION 915 0.000 975 0.0593 0.05 13.1 12 12 12 12 1.2 0.000 0.003 0.004
F 6 - - DUCT 915 0.007 975 0.0593 13.1 12 12 12 12 1.2 0.001 0.000 0.001
- 14.14-N BRANCH - MAIN 915 250 0.000 975 0.0593 0.05 13.1 12 12 12 12 1.2 0.000 0.003 0.004
G 14 - - DUCT 665 0.009 709 0.0313 13.1 12 12 12 12 1.2 0.002 0.000 0.002
- 14.14-N BRANCH - MAIN 665 250 0.000 709 0.0313 0.09 13.1 12 12 12 12 1.2 0.000 0.003 0.003
14.12-A CONTRACTION 415 0.000 442 0.0122 0.05 13.1 12 12 12 12 1.2 0.000 0.001 0.001
H 3 - - DUCT 415 0.003 786 0.0386 9.8 9 9 9 9 1.2 0.000 0.000 0.000
- 14.14-N BRANCH -BRANCH 415 250 0.000 786 0.0386 0.74 9.8 9 9 9 9 1.2 0.000 0.029 0.034
I 3 - - DUCT 165 0.001 313 0.0061 9.8 9 9 9 9 1.2 0.000 0.000 0.100
- 14.1-H ELBOW 165 0.000 313 0.0061 0.17 9.8 9 9 9 9 1.2 0.000 0.001 0.001
J 4 - - DUCT 165 0.001 313 0.0061 9.8 9 9 9 9 1.2 0.000 0.000 0.000
GRILLE 165 0 0 0.0000 0 1.0 0.000 0.000 0.1 0.100
0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0.0000 0 1.0 0.000 0.000 0.000
SUM OF LOSSES BEFORE CONTROL MARGIN 0.004 0.075 0.115 0.311
ALLOWANCE FOR CONTROL MARGIN 0.000 0.000 0.000 0.000
STATIC PRESSURE TOTAL 0.311
PROJECT NO.: 18HOL04 PROJECT NAME: Nez Perce National Historical Park SYSTEM: FC-6 RETURN SIDE, EXISTING PAGE: 1
A B C D E F G H I J K L M N O
DUCT SECT- SMAC- FLOW FRICTION VELOCITY VEL.PR. LOSS EQUIV. RECTANGULAR SIZE - in. ROUGHN. STR. DUCT FITTING SP. ITEM TOTAL
RUN ION LEN- FTG. NA ITEM MAIN BRANCH PER DUCT V Vp COEFF. DIA. IN OUT CORR. LOSS LOSS LOSS LOSS
GTH ANGLE FTG. cfm cfm in. w.g. fpm in. w.g. in. WIDTH HEIGHT WIDTH HEIGHT FACTOR in. w.g. in. w.g. in. w.g. in. w.g.
ft. deg. Fig. 14-3
SUM OF SUPPLY LOSSES 0.004 0.188 0.115 0.346
- INTAKE GRILLE 1,980 0 0 0.0000 0 1.0 0 0.000 0.05 0.050
ELBOW 1,980 0.000 547 0.0186 0.24 25.8 28 20 28 20 1.2 0.000 0.004 0.005
5 DUCT 1,980 0.001 547 0.0186 25.8 28 20 28 20 1.2 0.001 0.000 0.001
ELBOW 1,980 0.000 547 0.0186 0.24 25.8 28 20 28 20 1.2 0.000 0.004 0.005
5 DUCT 1,980 0.001 547 0.0186 25.8 28 20 28 20 1.2 0.001 0.000 0.001
ELBOW 1,980 0.000 547 0.0186 0.24 25.8 28 20 28 20 1.2 0.000 0.004 0.05 0.065
- INTAKE 0 0 0 0.0000 0 1.0 0 0.000 0.1 0.100
- FILTER 0 0 0 0.0000 0 1.0 0 0.000 0.1 0.100
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
SUM OF LOSSES BEFORE CONTROL MARGIN 0.006 0.202 0.415 0.674
ALLOWANCE FOR CONTROL MARGIN 0.000
STATIC PRESSURE TOTAL 0.674
PROJECT NO.: 18HOL04 PROJECT NAME: Nez Perce National Historical Park SYSTEM: FC-6 SUPPLY SIDE, EXISTING PAGE: 1
A B C D E F G H I J K L M N O
DUCT SECT- SMAC- FLOW FRICTION VELOCITY VEL.PR. LOSS EQUIV. RECTANGULAR SIZE - in. ROUGHN. STR. DUCT FITTING SP. ITEM TOTAL
RUN ION LEN- FTG. NA ITEM MAIN BRANCH PER 100' V Vp COEFF. DIA. IN OUT CORR. LOSS LOSS LOSS LOSS
GTH ANGLE FTG. cfm cfm in. w.g. fpm in. w.g. in. WIDTH HEIGHT WIDTH HEIGHT FACTOR in. w.g. in. w.g. in. w.g. in. w.g.
ft. deg. Fig. 14-3
- - 14.1-H DISCH 1,980 0.000 845 0.0445 20.7 20 18 20 18 1.0 0.000 0.000 0.015 0.015
A 2 - - DUCT 1,980 0.001 845 0.0445 20.7 20 18 20 18 1.2 0.000 0.000 0.000
- 14.1-H ELBOW 1,980 0.000 845 0.0445 0.24 20.7 20 18 20 18 1.2 0.000 0.011 0.013
B 5 - - DUCT 1,980 0.003 845 0.0445 20.7 20 18 20 18 1.2 0.000 0.000 0.000
- 14.1-H ELBOW 1,980 990 0.000 845 0.0445 0.24 20.7 20 18 20 18 1.2 0.000 0.011 0.013
C 5 - - DUCT 990 0.001 422 0.0111 20.7 20 18 20 18 1.2 0.000 0.000 0.000
14.12-A CONTRACTION 990 0.000 422 0.0111 0.05 20.7 20 18 14 14 1.2 0.000 0.001 0.001
- 14.1-H ELBOW 990 0.000 775 0.0375 0.24 15.3 14 14 14 14 1.2 0.000 0.009 0.011
D 7 - - DUCT 990 0.005 775 0.0375 15.3 14 14 14 14 1.2 0.000 0.000 0.000
- 14.1-H DOUBLE-ELBOW 990 0.000 775 0.0375 3.40 15.3 14 14 14 14 1.2 0.000 0.127 0.153
E 10 - - DUCT 990 0.007 775 0.0375 15.3 14 14 14 14 1.2 0.001 0.000 0.001
- 14.1-H ELBOW 990 0.000 775 0.0375 0.24 15.3 14 14 14 14 1.2 0.000 0.009 0.011
F 7 - - DUCT 990 0.005 775 0.0375 15.3 14 14 14 14 1.2 0.000 0.000 0.000
- 14.14-N BRANCH - MAIN 990 330 0.000 775 0.0375 0.17 15.3 14 14 14 14 1.2 0.000 0.006 0.008
14.12-A CONTRACTION 660 0.000 517 0.0167 0.05 15.3 14 14 11 11 1.2 0.000 0.001 0.001
G 10 - - DUCT 660 0.010 837 0.0437 12.0 11 11 11 11 1.2 0.001 0.000 0.001
- 14.14-N BRANCH - MAIN 660 330 0.000 837 0.0437 0.09 12.0 11 11 11 11 1.2 0.000 0.004 0.005
H 4 - - DUCT 330 0.001 419 0.0109 12.0 11 11 11 11 1.2 0.000 0.000 0.000
14.12-A CONTRACTION 330 0.000 419 0.0109 0.05 12.0 11 11 8 8 1.2 0.000 0.001 0.001
I 7 - - DUCT 330 0.009 792 0.0391 8.7 8 8 8 8 1.2 0.001 0.000 0.001
- 14.1-H ELBOW 330 0.000 792 0.0391 0.24 8.7 8 8 8 8 1.2 0.000 0.009 0.011
GRILLE 330 0.000 792 0.0391 8.7 8 8 8 8 1.0 0.000 0.000 0.1 0.100
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0.0000 0 1.0 0.000 0.000 0.000
0 0 0.0000 0 1.0 0.000 0.000 0.000
SUM OF LOSSES BEFORE CONTROL MARGIN 0.004 0.188 0.115 0.346
ALLOWANCE FOR CONTROL MARGIN 0.000 0.000 0.000 0.000
STATIC PRESSURE TOTAL 0.346
PROJECT NO.: 18HOL04 PROJECT NAME: Nez Perce National Historical Park SYSTEM: FC-7 RETURN SIDE, EXISTING PAGE: 1
A B C D E F G H I J K L M N O
DUCT SECT- SMAC- FLOW FRICTION VELOCITY VEL.PR. LOSS EQUIV. RECTANGULAR SIZE - in. ROUGHN. STR. DUCT FITTING SP. ITEM TOTAL
RUN ION LEN- FTG. NA ITEM MAIN BRANCH PER DUCT V Vp COEFF. DIA. IN OUT CORR. LOSS LOSS LOSS LOSS
GTH ANGLE FTG. cfm cfm in. w.g. fpm in. w.g. in. WIDTH HEIGHT WIDTH HEIGHT FACTOR in. w.g. in. w.g. in. w.g. in. w.g.
ft. deg. Fig. 14-3
SUM OF SUPPLY LOSSES 0.003 0.167 0.115 0.319
- INTAKE GRILLE 1,600 0 0 0.0000 0 1.0 0 0.000 0.05 0.050
90 ELBOW 1,600 0.000 884 0.0487 0.24 18.2 14 20 14 20 1.2 0.000 0.012 0.014
3 DUCT 1,600 0.002 884 0.0487 18.2 14 20 14 20 1.2 0.002 0.000 0.002
90 ELBOW 1,600 0.000 884 0.0487 0.24 18.2 14 20 14 20 1.2 0.000 0.012 0.014
3 DUCT 1,600 0.002 884 0.0487 18.2 14 20 14 20 1.2 0.002 0.000 0.002
90 ELBOW 1,600 0.000 884 0.0487 0.24 18.2 14 20 14 20 1.2 0.000 0.012 0.014
8 DUCT 1,600 0.005 884 0.0487 18.2 14 20 14 20 1.2 0.005 0.000 0.006
INTAKE 1,600 0.000 884 0.0487 18.2 14 20 14 20 1.2 0.000 0.000 0.05 0.060
FILTER 1,600 0 0 0.0000 0 1.0 0 0.000 0.1 0.100
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
SUM OF LOSSES BEFORE CONTROL MARGIN 0.013 0.202 0.315 0.583
ALLOWANCE FOR CONTROL MARGIN 0.000
STATIC PRESSURE TOTAL 0.583
PROJECT NO.: 18HOL04 PROJECT NAME: Nez Perce National Historical Park SYSTEM: FC-7 SUPPLY SIDE, EXISTING PAGE: 1
A B C D E F G H I J K L M N O
DUCT SECT- SMAC- FLOW FRICTION VELOCITY VEL.PR. LOSS EQUIV. RECTANGULAR SIZE - in. ROUGHN. STR. DUCT FITTING SP. ITEM TOTAL
RUN ION LEN- FTG. NA ITEM MAIN BRANCH PER 100' V Vp COEFF. DIA. IN OUT CORR. LOSS LOSS LOSS LOSS
GTH ANGLE FTG. cfm cfm in. w.g. fpm in. w.g. in. WIDTH HEIGHT WIDTH HEIGHT FACTOR in. w.g. in. w.g. in. w.g. in. w.g.
ft. deg. Fig. 14-3
- - 14.1-H DISCH 1,600 0.000 758 0.0358 19.7 18 18 18 18 1.0 0.000 0.000 0.015 0.015
A 7 - - DUCT 1,600 0.003 758 0.0358 19.7 18 18 18 18 1.2 0.000 0.000 0.000
90 14.1-H ELBOW 1,600 0.000 758 0.0358 0.24 19.7 18 18 18 18 1.2 0.000 0.009 0.010
B 12 - - DUCT 1,600 0.006 758 0.0358 19.7 18 18 18 18 1.2 0.001 0.000 0.001
90 14.1-H ELBOW 1,600 0.000 854 0.0454 0.24 18.5 18 16 20 16 1.2 0.000 0.011 0.013
C 3 - - DUCT 1,600 0.001 770 0.0370 19.5 20 16 20 16 1.2 0.000 0.000 0.000
90 14.1-H ELBOW 1,600 0.000 770 0.0370 0.24 19.5 20 16 20 16 1.2 0.000 0.009 0.011
D 10 - - DUCT 1,600 0.005 770 0.0370 19.5 20 16 20 16 1.2 0.001 0.000 0.001
90-90 14.1-H DOUBLE-ELBOW 1,600 0.000 770 0.0370 3.40 19.5 20 16 18 18 1.2 0.000 0.126 0.151
E 5 - - DUCT 1,600 0.002 758 0.0358 19.7 18 18 18 18 1.2 0.000 0.000 0.000
- 14.14-N BRANCH - MAIN 1,600 530 0.000 758 0.0358 0.02 19.7 18 18 18 18 1.2 0.000 0.001 0.001
F 11 - - DUCT 1,070 0.002 507 0.0160 19.7 18 18 18 18 1.2 0.000 0.000 0.000
- 14.14-N BRANCH - MAIN 1,070 150 0.000 507 0.0160 0.02 19.7 18 18 18 18 1.2 0.000 0.000 0.000
14.12-A CONTRACTION 920 0.000 436 0.0118 0.05 19.7 18 18 15 15 1.2 0.000 0.001 0.001
G 11 - - DUCT 920 0.004 628 0.0246 16.4 15 15 15 15 1.2 0.001 0.000 0.001
- 14.14-N BRANCH - MAIN 920 300 0.000 628 0.0246 0.04 16.4 15 15 15 15 1.2 0.000 0.001 0.001
14.12-A CONTRACTION 620 0.000 423 0.0112 0.05 16.4 15 15 12 12 1.2 0.000 0.001 0.001
H 5 - - DUCT 620 0.003 661 0.0272 13.1 12 12 12 12 1.2 0.000 0.000 0.000
45 14.1-H ELBOW 620 0.000 661 0.0272 0.17 13.1 12 12 12 12 1.2 0.000 0.005 0.006
I 4 - - DUCT 620 0.002 661 0.0272 13.1 12 12 12 12 1.2 0.000 0.000 0.000
- 14.14-N BRANCH - MAIN 620 270 0.000 661 0.0272 0.06 13.1 12 12 12 12 1.2 0.000 0.002 0.002
J 4 - - DUCT 350 0.001 373 0.0087 13.1 12 12 12 12 1.2 0.000 0.000 0.000
14.12-A CONTRACTION 350 0.000 373 0.0087 0.05 13.1 12 12 12 12 1.2 0.000 0.000 0.001
K 8 - - DUCT 350 0.002 373 0.0087 13.1 12 12 10 10 1.2 0.000 0.000 0.000
45 14.1-H ELBOW 350 0.000 537 0.0180 0.17 10.9 10 10 10 10 1.2 0.000 0.003 0.004
GRILLE 350 0.000 537 0.0180 10.9 10 10 10 10 1.0 0.000 0.000 0.1 0.100
0.000 0.000 0.000
0.000 0.000 0.000
SUM OF LOSSES BEFORE CONTROL MARGIN 0.003 0.167 0.115 0.319
ALLOWANCE FOR CONTROL MARGIN 0.000 0.000 0.000 0.000
STATIC PRESSURE TOTAL 0.319
PROJECT NO.: 18HOL04 PROJECT NAME: Nez Perce National Historical Park SYSTEM: FC-8 RETURN SIDE PAGE: 1
A B C D E F G H I J K L M N O
DUCT SECT- SMAC- FLOW FRICTION VELOCITY VEL.PR. LOSS EQUIV. RECTANGULAR SIZE - in. ROUGHN. STR. DUCT FITTING SP. ITEM TOTAL
RUN ION LEN- FTG. NA ITEM MAIN BRANCH PER DUCT V Vp COEFF. DIA. IN OUT CORR. LOSS LOSS LOSS LOSS
GTH ANGLE FTG. cfm cfm in. w.g. fpm in. w.g. in. WIDTH HEIGHT WIDTH HEIGHT FACTOR in. w.g. in. w.g. in. w.g. in. w.g.
ft. deg. Fig. 14-3
SUM OF SUPPLY LOSSES 0.002 0.021 0.115 0.143
- INTAKE GRILLE 1,600 0 0 0.0000 0 1.0 0 0.000 0.05 0.050
3 DUCT 1,600 0.003 978 0.0597 17.3 14 18 14 18 1.2 0.003 0.000 0.003
90 ELBOW 1,600 0.000 978 0.0597 0.24 17.3 14 18 14 18 1.2 0.000 0.014 0.017
3 DUCT 1,600 0.003 978 0.0597 17.3 14 18 14 18 1.2 0.003 0.000 0.003
90 ELBOW 1,600 0.000 978 0.0597 0.24 17.3 14 18 14 18 1.2 0.000 0.014 0.017
INTAKE 1,600 0 0 0.0000 0 1.0 0 0.000 0.05 0.050
FILTER 1,600 0 0 0.0000 0 1.0 0 0.000 0.1 0.100
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
1,600 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
SUM OF LOSSES BEFORE CONTROL MARGIN 0.007 0.050 0.315 0.383
ALLOWANCE FOR CONTROL MARGIN 0.000
ALLOWANCE FOR ________________________________
STATIC PRESSURE TOTAL 0.383
PROJECT NO.: 18HOL04 PROJECT NAME: Nez Perce National Historical Park SYSTEM: FC-8 SUPPLY SIDE PAGE: 1
A B C D E F G H I J K L M N O
DUCT SECT- SMAC- FLOW FRICTION VELOCITY VEL.PR. LOSS EQUIV. RECTANGULAR SIZE - in. ROUGHN. STR. DUCT FITTING SP. ITEM TOTAL
RUN ION LEN- FTG. NA ITEM MAIN BRANCH PER 100' V Vp COEFF. DIA. IN OUT CORR. LOSS LOSS LOSS LOSS
GTH ANGLE FTG. cfm cfm in. w.g. fpm in. w.g. in. WIDTH HEIGHT WIDTH HEIGHT FACTOR in. w.g. in. w.g. in. w.g. in. w.g.
ft. deg. Fig. 14-3
- - 14.1-H DISCH 1,200 0.000 617 0.0237 18.9 20 15 20 15 1.0 0.000 0.000 0.015 0.015
A 3 - - DUCT 1,200 0.001 617 0.0237 18.9 20 15 20 15 1.2 0.000 0.000 0.000
90 14.1-H ELBOW 1,200 0.000 617 0.0237 0.24 18.9 20 15 20 15 1.2 0.000 0.006 0.007
B 10 - - DUCT 1,200 0.003 617 0.0237 18.9 20 15 20 15 1.2 0.000 0.000 0.000
- 14.14-N BRANCH - MAIN 1,200 310 0.000 617 0.0237 0.04 18.9 20 15 20 15 1.2 0.000 0.001 0.001
- - CONTRACTION 890 0.000 458 0.0131 0.05 18.9 20 15 17 15 1.2 0.000 0.001 0.001
C 5 - - DUCT 890 0.001 536 0.0179 17.4 17 15 17 15 1.2 0.000 0.000 0.000
90 14.1-H ELBOW 890 0.000 536 0.0179 0.24 17.4 17 15 17 15 1.2 0.000 0.004 0.005
D 5 - - DUCT 890 0.001 536 0.0179 17.4 17 15 17 15 1.2 0.000 0.000 0.000
- 14.14-N BRANCH - MAIN 890 430 0.000 536 0.0179 0.06 17.4 17 15 17 15 1.2 0.000 0.001 0.001
- - CONTRACTION 460 0.000 277 0.0048 0.05 17.4 17 15 12 12 1.2 0.000 0.000 0.000
E 9 - - DUCT 460 0.003 490 0.0150 13.1 12 12 12 12 1.2 0.000 0.000 0.000
- 14.14-N BRANCH - MAIN 460 180 0.000 490 0.0150 0.09 13.1 12 12 12 12 1.2 0.000 0.001 0.002
14.12-A CONTRACTION 280 0.000 298 0.0056 0.05 13.1 12 12 8 8 1.2 0.000 0.000 0.000
F 10 - - DUCT 280 0.010 672 0.0281 8.7 8 8 8 8 1.2 0.001 0.000 0.001
- 14.14-N BRANCH - MAIN 280 260 0.000 672 0.0281 0.22 8.7 8 8 8 8 1.2 0.000 0.006 0.007
14.12-A CONTRACTION 20 0.000 48 0.0001 0.05 8.7 8 8 6 6 1.2 0.000 0.000 0.000
G 5 - - DUCT 20 0.000 85 0.0005 6.6 6 6 6 6 1.2 0.000 0.000 0.000
90 14.1-H ELBOW 20 0.000 85 0.0005 0.24 6.6 6 6 6 6 1.2 0.000 0.000 0.000
GRILLE 20 20 0.000 85 0.0005 6.6 6 6 6 6 1.0 0.000 0.000 0.1 0.100
SUM OF LOSSES BEFORE CONTROL MARGIN 0.002 0.021 0.115 0.143
ALLOWANCE FOR CONTROL MARGIN 0.000 0.000 0.000 0.000
SAFETY FACTOR ALLOWANCE ______________
STATIC PRESSURE TOTAL 0.143
PROJECT NO.: 18HOL04 PROJECT NAME: Nez Perce National Historical Park SYSTEM: FC-9 RETURN SIDE PAGE: 1
A B C D E F G H I J K L M N O
DUCT SECT- SMAC- FLOW FRICTION VELOCITY VEL.PR. LOSS EQUIV. RECTANGULAR SIZE - in. ROUGHN. STR. DUCT FITTING SP. ITEM TOTAL
RUN ION LEN- FTG. NA ITEM MAIN BRANCH PER DUCT V Vp COEFF. DIA. IN OUT CORR. LOSS LOSS LOSS LOSS
GTH ANGLE FTG. cfm cfm in. w.g. fpm in. w.g. in. WIDTH HEIGHT WIDTH HEIGHT FACTOR in. w.g. in. w.g. in. w.g. in. w.g.
ft. deg. Fig. 14-3
SUM OF SUPPLY LOSSES 0.004 0.044 0.115 0.196
- INTAKE GRILLE 800 0 0 0.0000 0 1.0 0 0.000 0.05 0.050
90 ELBOW 800 0.000 442 0.0122 0.24 18.2 14 20 14 20 1.2 0.000 0.003 0.004
A 4 DUCT 800 0.001 442 0.0122 18.2 14 20 14 20 1.2 0.001 0.000 0.001
90 ELBOW 800 0.000 442 0.0122 0.24 18.2 14 20 14 20 1.2 0.000 0.003 0.004
B 3 DUCT 800 0.001 442 0.0122 18.2 14 20 14 20 1.2 0.001 0.000 0.001
90 ELBOW 800 0.000 442 0.0122 0.24 18.2 14 20 14 20 1.2 0.000 0.003 0.004
C 10 DUCT 800 0.002 442 0.0122 18.2 14 20 14 20 1.2 0.002 0.000 0.002
90 ELBOW 800 0.000 442 0.0122 0.24 18.2 14 20 14 20 1.2 0.000 0.003 0.004
D 4 DUCT 800 0.001 442 0.0122 18.2 14 20 14 20 1.2 0.001 0.000 0.001
INTAKE 800 0 0 0.0000 0 1.2 0 0.000 0.05 0.060
FILTER 800 0 0 0.0000 0 1.0 0 0.000 0.1 0.100
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
800 0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
0 0 0.0000 0 1.0 0 0.000 0.000
SUM OF LOSSES BEFORE CONTROL MARGIN 0.008 0.056 0.315 0.425
ALLOWANCE FOR CONTROL MARGIN 0.000
ALLOWANCE FOR ________________________________
STATIC PRESSURE TOTAL 0.425
PROJECT NO.: 18HOL04 PROJECT NAME: Nez Perce National Historical Park SYSTEM: FC-9 SUPPLY SIDE PAGE: 1
A B C D E F G H I J K L M N O
DUCT SECT- SMAC- FLOW FRICTION VELOCITY VEL.PR. LOSS EQUIV. RECTANGULAR SIZE - in. ROUGHN. STR. DUCT FITTING SP. ITEM TOTAL
RUN ION LEN- FTG. NA ITEM MAIN BRANCH PER 100' V Vp COEFF. DIA. IN OUT CORR. LOSS LOSS LOSS LOSS
GTH ANGLE FTG. cfm cfm in. w.g. fpm in. w.g. in. WIDTH HEIGHT WIDTH HEIGHT FACTOR in. w.g. in. w.g. in. w.g. in. w.g.
ft. deg. Fig. 14-3
- - 14.1-H DISCH 800 0.000 853 0.0453 13.1 12 12 12 12 1.2 0.000 0.000 0.015 0.018
90 14.1-H ELBOW 800 0.000 853 0.0453 0.24 13.1 12 12 12 12 1.2 0.000 0.011 0.013
A 17 - - DUCT 800 0.016 853 0.0453 13.1 12 12 12 12 1.2 0.003 0.000 0.004
- 14.14-N BRANCH - BRANCH 800 400 0.000 853 0.0453 0.74 13.1 12 12 10 8 1.2 0.000 0.034 0.040
B 8 - - DUCT 400 0.009 770 0.0370 9.8 8 10 8 10 1.2 0.001 0.000 0.001
GRILLE 400 0.000 770 0.0370 9.8 8 10 8 10 1.2 0.000 0.000 0.1 0.120
SUM OF LOSSES BEFORE CONTROL MARGIN 0.004 0.044 0.115 0.196
ALLOWANCE FOR CONTROL MARGIN 0.000 0.000 0.000 0.000
SAFETY FACTOR ALLOWANCE ______________
STATIC PRESSURE TOTAL 0.196
Exhibit B - Existing Mechanical Plans
2T
2T
5T
5T
4T
3T
2T
ABCD
A
B
C
D
E F G H
I
J
A
B
C
D up
A
B C up
A
B
C
D
E F G
A
B
A
B
C VERTICAL
D
EXHIBIT B - EXISTING DUCT LAYOUT
BASEMENT
LETTERED SECTIONS CORRESPOND WITH DUCT SEGMENTS IN
ASSOCIATED DUCT CALCULATIONS - SEE EXHIBIT A
(E) 9x9
(E) 6x7
(E) 6x7
(E) 6x7
4T
A
C B
D E
F
G H
ABC
A
B
C
DE
B
E - VERTICAL
FGI H
D - VERTICAL
FGH
I
J
K
E
EXHIBIT B - EXISTING DUCT LAYOUT
FIRST FLOOR
LETTERED SECTIONS CORRESPOND WITH DUCT SEGMENTS IN
ASSOCIATED DUCT CALCULATIONS - - SEE EXHIBIT A
Exhibit C - New Mechanical Plans
Exhibit D - Specifications
Nez Perce National Historical Park
Evaluation of Ductwork Replacement in Spalding Visitor’s Center
HVAC INSULATION 230700-1
SECTION 230700 - HVAC INSULATION
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Insulation Materials:
a. Flexible elastomeric.
b. Mineral fiber.
2. Fire-rated insulation systems.
3. Insulating cements.
4. Adhesives.
5. Mastics.
6. Lagging adhesives.
7. Sealants.
8. Factory-applied jackets.
9. Tapes.
10. Securements.
11. Corner angles.
1.3 SUBMITTALS
A. Product Data: For each type of product indicated. Include thermal conductivity, thickness, and jackets (both factory and field applied, if any).
B. Qualification Data: For qualified Installer.
C. Material Test Reports: From a qualified testing agency acceptable to authorities having jurisdiction indicating, interpreting, and certifying test results for compliance of insulation materials, sealers, attachments, cements, and jackets, with requirements indicated. Include dates of tests and test methods employed.
1.4 QUALITY ASSURANCE
A. Fire-Test-Response Characteristics: Insulation and related materials shall have fire-test-response characteristics indicated, as determined by testing identical products per ASTM E 84, by a testing and inspecting agency acceptable to authorities having jurisdiction. Factory label insulation and jacket materials and adhesive, mastic, tapes, and cement material containers, with appropriate markings of applicable testing and inspecting agency.
1. Flame-spread index of 25 or less, and smoke-developed index of 50 or less.
2. Insulation Installed Outdoors: Flame-spread index of 75 or less, and smoke-developed.
HVAC INSULATION 230700-2
1.5 DELIVERY, STORAGE, AND HANDLING
A. Packaging: Insulation material containers shall be marked by manufacturer with appropriate ASTM standard designation, type and grade, and maximum use temperature.
1.6 COORDINATION
A. Coordinate size and location of supports, hangers, and insulation shields specified in Division 23 Section "Hangers and Supports for HVAC Piping and Equipment."
B. Coordinate clearance requirements with piping Installer for piping insulation application, duct Installer for duct insulation application, and equipment Installer for equipment insulation application. Before preparing piping and ductwork Shop Drawings, establish and maintain clearance requirements for installation of insulation and field-applied jackets and finishes and for space required for maintenance.
C. Coordinate installation and testing of heat tracing.
1.7 SCHEDULING
A. Schedule insulation application after pressure testing systems and, where required, after installing and testing heat tracing. Insulation application may begin on segments that have satisfactory test results.
PART 2 - PRODUCTS
2.1 INSULATION MATERIALS
A. Comply with requirements in Part 3 schedule articles for where insulating materials shall be applied.
B. Products shall not contain asbestos, lead, mercury, or mercury compounds.
C. Foam insulation materials shall not use CFC or HCFC blowing agents in the manufacturing process.
D. Flexible Elastomeric: Closed-cell, sponge- or expanded-rubber materials. Comply with ASTM C 534, Type I for tubular materials and Type II for sheet materials.
1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:
a. Aeroflex USA Inc.; Aerocel.
b. Armacell LLC; AP Armaflex.
c. RBX Corporation; Insul-Sheet 1800 and Insul-Tube 180.
E. Mineral-Fiber Blanket Insulation: Mineral or glass fibers bonded with a thermosetting resin.
Comply with ASTM C 553, Type II and ASTM C 1290, Type II with factory-applied vinyl jacket.
Factory-applied jacket requirements are specified in "Factory-Applied Jackets" Article.
1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:
HVAC INSULATION 230700-3
a. CertainTeed Corp.; Duct Wrap.
b. Johns Manville; Microlite.
c. Knauf Insulation; Duct Wrap.
d. Manson Insulation Inc.; Alley Wrap.
e. Owens Corning; All-Service Duct Wrap.
F. Mineral-Fiber Board Insulation: Mineral or glass fibers bonded with a thermosetting resin.
Comply with ASTM C 612, Type IA or Type IB. For duct and plenum applications, provide insulation with factory-applied ASJ. For equipment applications, provide insulation with factory-applied ASJ. Factory-applied jacket requirements are specified in "Factory-Applied Jackets" Article.
1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:
a. CertainTeed Corp.; Commercial Board.
b. Fibrex Insulations Inc.; FBX.
c. Johns Manville; 800 Series Spin-Glas.
d. Knauf Insulation; Insulation Board.
e. Manson Insulation Inc.; AK Board.
f. Owens Corning; Fiberglas 700 Series.
2.2 INSULATING CEMENTS
A. Mineral-Fiber Insulating Cement: Comply with ASTM C 195.
1. Products: Subject to compliance with requirements available products that may be incorporated into the Work include, but are not limited to, the following:
a. Insulco, Division of MFS, Inc.; Triple I.
b. P. K. Insulation Mfg. Co., Inc.; Super-Stik.
B. Expanded or Exfoliated Vermiculite Insulating Cement: Comply with ASTM C 196.
1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:
a. P. K. Insulation Mfg. Co., Inc.; Thermal-V-Kote.
C. Mineral-Fiber, Hydraulic-Setting Insulating and Finishing Cement: Comply with
ASTM C 449/C 449M.
1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:
a. Insulco, Division of MFS, Inc.; SmoothKote.
b. P. K. Insulation Mfg. Co., Inc.; PK No. 127, and Quik-Cote.
c. Rock Wool Manufacturing Company; Delta One Shot.
2.3 ADHESIVES
A. Materials shall be compatible with insulation materials, jackets, and substrates and for bonding insulation to itself and to surfaces to be insulated, unless otherwise indicated.
B. Flexible Elastomeric and Polyolefin Adhesive: Comply with MIL-A-24179A, Type II, Class I.
1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:
a. Aeroflex USA Inc.; Aeroseal.
b. Armacell LCC; 520 Adhesive.
HVAC INSULATION 230700-4
c. Foster Products Corporation, H. B. Fuller Company; 85-75.
d. RBX Corporation; Rubatex Contact Adhesive.
C. Mineral-Fiber Adhesive: Comply with MIL-A-3316C, Class 2, Grade A.
1. Products: Subject to compliance with requirements available products that may be incorporated into the Work include, but are not limited to, the following:
a. Childers Products, Division of ITW; CP-82.
b. Foster Products Corporation, H. B. Fuller Company; 85-20.
c. ITW TACC, Division of Illinois Tool Works; S-90/80.
d. Marathon Industries, Inc.; 225.
e. Mon-Eco Industries, Inc.; 22-25.
D. ASJ Adhesive, and FSK and PVDC Jacket Adhesive: Comply with MIL-A-3316C, Class 2, Grade A for bonding insulation jacket lap seams and joints.
1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:
a. Childers Products, Division of ITW; CP-82.
b. Foster Products Corporation, H. B. Fuller Company; 85-20.
c. ITW TACC, Division of Illinois Tool Works; S-90/80.
d. Marathon Industries, Inc.; 225.
e. Mon-Eco Industries, Inc.; 22-25.
2.4 MASTICS
A. Materials shall be compatible with insulation materials, jackets, and substrates; comply with MIL-C-19565C, Type II.
B. Vapor-Barrier Mastic: Water based; suitable for indoor and outdoor use on below ambient services.
1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:
a. Childers Products, Division of ITW; CP-35.
b. Foster Products Corporation, H. B. Fuller Company; 30-90.
c. ITW TACC, Division of Illinois Tool Works; CB-50.
d. Marathon Industries, Inc.; 590.
e. Mon-Eco Industries, Inc.; 55-40.
f. Vimasco Corporation; 749.
2. Water-Vapor Permeance: ASTM E 96, Procedure B, 0.013 perm at 43-mil dry film thickness.
3. Service Temperature Range: Minus 20 to plus 180 deg F.
4. Solids Content: ASTM D 1644, 59 percent by volume and 71 percent by weight.
5. Color: White.
C. Vapor-Barrier Mastic: Solvent based; suitable for outdoor use on below ambient services.
1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:
a. Childers Products, Division of ITW; Encacel.
b. Foster Products Corporation, H. B. Fuller Company; 60-95/60-96.
c. Marathon Industries, Inc.; 570.
d. Mon-Eco Industries, Inc.; 55-70.
2. Water-Vapor Permeance: ASTM F 1249, 0.05 perm at 30-mil dry film thickness.
3. Service Temperature Range: Minus 50 to plus 220 deg F.
HVAC INSULATION 230700-5
4. Solids Content: ASTM D 1644, 33 percent by volume and 46 percent by weight.
5. Color: White.
D. Breather Mastic: Water based; suitable for indoor and outdoor use on above ambient services.
1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:
a. Childers Products, Division of ITW; CP-10.
b. Foster Products Corporation, H. B. Fuller Company; 35-00.
c. ITW TACC, Division of Illinois Tool Works; CB-05/15.
d. Marathon Industries, Inc.; 550.
e. Mon-Eco Industries, Inc.; 55-50.
f. Vimasco Corporation; WC-1/WC-5.
2. Water-Vapor Permeance: ASTM F 1249, 3 perms at 0.0625-inch dry film thickness.
3. Service Temperature Range: Minus 20 to plus 200 deg F.
4. Solids Content: 63 percent by volume and 73 percent by weight.
5. Color: White.
2.5 LAGGING ADHESIVES
A. Description: Comply with MIL-A-3316C Class I, Grade A and shall be compatible with insulation materials, jackets, and substrates.
1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:
a. Childers Products, Division of ITW; CP-52.
b. Foster Products Corporation, H. B. Fuller Company; 81-42.
c. Marathon Industries, Inc.; 130.
d. Mon-Eco Industries, Inc.; 11-30.
e. Vimasco Corporation; 136.
2. Fire-resistant, water-based lagging adhesive and coating for use indoors to adhere fire-resistant lagging cloths over duct, equipment, and pipe insulation.
3. Service Temperature Range: Minus 50 to plus 180 deg F.
4. Color: White.
2.6 SEALANTS
A. Joint Sealants:
1. Joint Sealants for Cellular-Glass Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:
a. Childers Products, Division of ITW; CP-76.
b. Foster Products Corporation, H. B. Fuller Company; 30-45.
c. Marathon Industries, Inc.; 405.
d. Mon-Eco Industries, Inc.; 44-05.
e. Pittsburgh Corning Corporation; Pittseal 444.
f. Vimasco Corporation; 750.
B. ASJ Flashing Sealants:
1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:
a. Childers Products, Division of ITW; CP-76.
2. Materials shall be compatible with insulation materials, jackets, and substrates.
HVAC INSULATION 230700-6
3. Fire- and water-resistant, flexible, elastomeric sealant.
4. Service Temperature Range: Minus 40 to plus 250 deg F.
5. Color:…
This is the start of the file's text. The full file is on GovTribe.