Questions_and_Answers_0001.pdf

PDF 51 KB Posted

Attached to
REPLACEMENT REVERSE OSMOSIS DESALINATORS Federal contract opportunity
Solicitation number
140P5424Q0058
Issued by
Department of the Interior National Park Service Southeast Region

About this file

This document contains Questions and Answers related to Solicitation 140P5424Q0058 for the Replacement of Reverse Osmosis Desalinators at Dry Tortugas National Park. The key details are:

The solicitation is for the replacement of reverse osmosis desalinators. The high pressure pump specification has been changed from a belt-driven pulley system to a direct drive, non-belt driven pump. The feed water source is 100% raw seawater from the southeastern Gulf of Mexico, with an average temperature range of 70-90 degrees Fahrenheit. No pretreatment equipment is required. A variable frequency drive for the high pressure pump is not required. The unit dimensions of 65" W x 43" D x 30" H will be acceptable. The due date for quotes has been extended to September 3, 2024 at 4:00 p.m. ET.

View the file

Other files for this federal contract opportunity

Other files attached to REPLACEMENT REVERSE OSMOSIS DESALINATORS, newest first.
File Type Posted
Sol_140P5424Q0058_Amd_0001.pdf PDF
Statement_of_Work.pdf PDF
Sol_140P5424Q0058.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions and Answers

140P5424Q0058

Replace Reverse Osmosis Desalinators

Dry Tortugas National Park

1. In the SOW one requirement is “unit must have a belt driven pulley motor system, positive displacement pumps.” Can this be substituted for a direct drive, non-belt driven pump?

Response: Interested bidders should disregard “unit must have a belt driven pulley motor system.” The specification is now for a “direct drive, non-belt driven pump.”

2. Is this referring to the feed water or a re-pressurization pump after the RO system?

Response: Feed water high pressure pump.

3. Can you provide any information regarding the feedwater source or its characteristics? TDS levels, mineral content, etc.?

Response: Feed water source is 100% raw sea water with origin from the southeastern Gulf of Mexico with the characteristics common to such.

4. The system may require pretreatment equipment to function properly, should this be included in quote, or should the quote only focus on the RO units as specified?

Response: No pretreatment equipment is specified.

5. Do you know what the expected temperature range for the feed water will be?

Response: Year-round temp range of feed water averages 70-90 degrees F.

6. Is a variable frequency drive desired/required for the high-pressure pump?

Response: Variable frequency drive high pressure pump not required.

7. Will approximate unit dimensions of 65” W x 43” D x 30” H be acceptable?

Response: Dimensions in SOW allow min-max for doorway access into interior of equipment room.

8. May we get an extension on this project?

Response: Due date for quotes is being extended to September 3, 2024, at 4:00 p.m. ET.