140L3723Q0001 x x

1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE

RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR

OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

x

LFA

BOISE ID 83705

3833 S. DEVELOPMENT AVE.

BLM FA-NTL INTRAGCY FIRE CTR(FA250)

12/08/20220001

13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

12. ACCOUNTING AND APPROPRIATION DATA (If required) is not extended.is extended, Items 8 and 15, and returning

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

FACILITY CODE CODE

10B. DATED (SEE ITEM 13)

10A. MODIFICATION OF CONTRACT/ORDER NO.

9B. DATED (SEE ITEM 11)

9A. AMENDMENT OF SOLICITATION NO.

CODE

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)

7. ADMINISTERED BY (If other than Item 6)CODE 6. ISSUED BY

PAGE OF PAGES

4. REQUISITION/PURCHASE REQ. NO.3. EFFECTIVE DATE2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO. (If applicable)

1. CONTRACT ID CODE

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

12/08/2022

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority) appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

E. IMPORTANT: Contractor is not is required to sign this document and return __________________ copies to the issuing office.

ORDER NO. IN ITEM 10A.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

PROJECT: NIFC CAMPUS FIRE SPRINKLER SYSTEM INSPECTION

The purpose of this Amendment 0001 is to:

1. Provide Site Visit roster conducted on Dec 20, 2022.

2. Provide responses to questions received before question cutoff date on Dec 28, 2022.

3. Provide inspection reports on system from most recent inspections conducted.

4. Solicitation due date remains Jan 10, 2023, at 2 PM MT.

Continued ...

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)

15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED

(Signature of person authorized to sign) (Signature of Contracting Officer)

Matthew Steele

STANDARD FORM 30 (REV. 11/2016)

Prescribed by GSA FAR (48 CFR) 53.243

Previous edition unusable

Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .

ITEM NO. SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT

NAME OF OFFEROR OR CONTRACTOR

2 61

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

140L3723Q0001/0001

All other terms and conditions set forth in this solicitation remain the same.

All amendments must be acknowledged.

Period of Performance: 02/01/2023 to 01/31/2028

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

Sponsored by GSA

FAR (48 CFR) 53.110

United States Department of the Interior

BUREAU OF LAND MANAGEMENT

Fire and Aviation 3833 S Development Ave

Boise, Idaho 83705-5354

REQUEST FOR QUOTATION (RFQ) QUESTIONS/ANSWERS JAN 4, 2022

NIFC CAMPUS FIRE SYSTEM INSPECTION

RFQ Number 140L3723Q0001

CONTRACTOR QUESTIONS GOVERNMENT RESPONSE

1. Thank‐you for taking my call – I appreciate your time. See below. Prior to the Site Survey… its it possible to provide us with the sprinkler & alarm device counts for this project?

1. See Appendix‐A of solicitation specifications for water based fire sprinkler system characteristics.

See eleven (11) attachments for buildings 100, 106, 115, 205, 215, and 300. Attachments are last years inspection records on the fire riser and the backflow preventers.

2. I have a question for page 31 of 71. The 50 Year Sprinkler Test mentions the testing status for building #205 and #110 but does not mention any of the other buildings. Does this mean that the buildings are not due for testing, or maybe it unknown when the test is due? Are you able to see when the 50 year test is due for the rest of the buildings?

2. See Appendix‐A of solicitation specifications for water based fire sprinkler system characteristics.

Appendix‐A also includes year fire sprinkler systems were installed which the contractor may derive the due date for the next 50‐year inspection.

Refer to specification section Part‐3

Execution, section “3.6. 50 Year Sprinkler Test: One percent of the sprinklers shall be submitted to a recognized testing laboratory for testing. If there are multiple types of sprinkler heads within the building, then it shall be one percent of each type sent out to be tested. Where a sprinkler is pulled for testing, another sprinkler should be put in its place.

Subsection, 3.6.1. The single building requiring 50 Year Sprinkler Test is the 205- Paraloft.

3. 3.

4. 4.

5. 5.

CUSTOMER NAME: National Interagency Fire Center BUILDING NAME: Bldg 100 Administration BUILDING ADDRESS: 3906 S Vista Ave, Boise, ID, 83705 CONTACT NAME: Ray Martinez CONTACT E-MAIL: rlmartinez@blm.gov CONTACT ROLE: Maintenance Supervisor

CONTACT PHONE: 2088035563

INSPECTION TYPE: Sprinkler FREQUENCY: Annual

WORK ORDER: 50620286

INSPECTION END DATE: 10/07/2021

INSPECTOR (s): Dmitriy Petrovich Chayka

INSPECTOR LICENSE: NICET II # 137370

ACCOUNT NAME: Johnson Controls North America OFFICE ADDRESS: 8783 W Hackamore dr, Boise ID 83709

OFFICE PHONE: 208-376-2111

OFFICE LICENSE:

TIMEZONE: MDT

SPRINKLER INSPECTION REPORT

DEVICE DEFICIENCIES

No device deficiencies in this inspection.

OTHER DEFICIENCIES

-spare head box is missing sprinkler head wrench

General

To be Answered with the Owner

1. Have there been any changes in the occupancy classification, machinery or operations since the last inspection? No

2. Have there been any changes or repairs to the fire protection systems since the last inspection? No

To be Answered by the Inspector

1. Have the sprinkler systems been extended to all areas of the building? Yes

2. Are all exterior openings protected against the entrance of cold air? Yes

3. Date Backflow Devices Were Tested 10/07/2021

4. Number Of Water Gauges 2

5. Are all Tanks, Fire Pumps, and Fire Department Connections Inspected and Tested Per NFPA 25? Yes

6. All Systems Restored To Normal Yes

Water Supplies

1. Type City

Control Valve Questions

1. Are all sprinkler system main control valves and all other valves in the appropriate open or closed position? Yes

2. Are all control valves sealed, locked, or supervised, in the appropriate open or closed position? Yes

Alarms

1. Did the electric alarms operate during testing? Yes

2. Did the supervisory alarms operate during testing? Yes

Sprinklers - Piping

1. Were All Sprinklers Made After 1920 Yes

2. Quick Response Sprinklers 20 years or older? No

3. Dry Pendent Sprinklers 10 Years Or Older No

4. Do sprinklers generally appear to be free of corrosion, paint, or loading and visible obstructions? Yes

5. Is the buildings sprinklers inventory list located within the sprinkler spare head cabinet? No

6. Are appropriate number of extra sprinklers and sprinkler wrenches available on the premises? No

Sprinkler–Annual

Customer: National Interagency Fire Center Building: Bldg 100 Administration

Address: 3906 S Vista Ave, Boise, ID, 83705

Sprinkler | 10/07/2021 Page 1 of 6

General

Sprinklers - Piping

Spare head box is missing sprinkler wrench

7.

Type of sprinkler heads

-v2710 1/2” 200* qr brass sidewall -v2708 1/2” 200* qr chrome pendent -v2704 1/2” 200* qr brass upright -v3406 3/4” 200* qr chrome pendent

8. Does there appear to be proper clearance between the top of all storage and the sprinkler deflector? Yes

9. Does the exposed exterior condition of piping, drain valves, check valves, hangers, pressure gauges, open sprinklers and strainers appear to be satisfactory?

Yes

Devices

INSPECTION RESULTS SUMMARY

DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT

Control Valve 3 3 0 0

Fire Dept. Connection 1 1 0 0

PIV 1 1 0 0

Tamper Switch 4 4 0 0

Water Flow Switch 1 1 0 0

Main Drain Test 1 1 0 0

Wet System 1 1 0 0

CONTROL VALVES AGG

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 Basement mech rm Backflow control valve

Control Valve —

Dmitriy Petrovich Chayka

10/07/2021 Passed

Type and Size 6” butterfly

Easily Accessible? Yes

Signs? No

Valve in the Appropriate Open or Closed Position? Yes

Sealed, Locked, and/or Supervised Supervised

Free from External Leaks? Yes

Control Valve Fully Exercised? Yes

2 Basement mech rm Backflow control valve

Control Valve —

Dmitriy Petrovich Chayka

10/07/2021 Passed

Type and Size 6” butterfly

Easily Accessible? Yes

Signs? Yes

Valve in the Appropriate Open or Closed Position? Yes

Sealed, Locked, and/or Supervised Supervised

Free from External Leaks? Yes

Control Valve Fully Exercised? Yes

Sprinkler–Annual

Customer: National Interagency Fire Center Building: Bldg 100 Administration

Sprinkler | 10/07/2021 Page 2 of 6

Devices

CONTROL VALVES AGG

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

3 Basement mech rm Forward flow control valve normally closed

Control Valve — Dmitriy Petrovich

Chayka 10/07/2021 Passed

Type and Size 2 1/2” butterfly

Easily Accessible? Yes

Signs? No

Valve in the Appropriate Open or Closed Position? Yes

* Normally closed

Sealed, Locked, and/or Supervised Supervised

Free from External Leaks? Yes

Control Valve Fully Exercised? Yes

FIRE DEPARTMENT CONNECTIONS

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 Outside FDC Fire Dept. Connection — Dmitriy Petrovich

Chayka 10/07/2021 Passed

Is FDC Visible / Accessible? Yes

Are Couplings / Swivels / Plugs / Caps in place? Yes

Identification Signs In Place Yes

Are Check Valve / Gaskets / Ball Drips In Place? Yes

MAIN DRAIN TESTS

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 Basement mech rm Wet sys main drain test Main Drain Test — Dmitriy Petrovich

Chayka 10/07/2021 Passed

Test pipe located On riser

Size of test pipe 2”

Previous Main Drain Test Date 07/01/2021

Previous Main Drain Static Pressure 65

Previous Main Drain Residual Pressure 62

Static supply pressure 65

Residual Pressure 55

Time to return to normal system pressure Instant

Static supply pressure after completion of test 63

Main drain opened & free of obstruction discoloration? Yes

Sprinkler–Annual

Customer: National Interagency Fire Center Building: Bldg 100 Administration

Sprinkler | 10/07/2021 Page 3 of 6

POST INDICATOR VALVES

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 Outside PIV PIV — Dmitriy Petrovich

Chayka 10/07/2021 Passed

Manufacturer and Model Mueller A20806

Type of PIV (Wall or Post) Post

Is PIV Easily Accessible? Yes

Is PIV Free From Visual Damage? Yes

Is PIV Free from External Leaks? Yes

Is PIV Open? Yes

Is PIV Sealed, Locked, and/or Supervised? Supervised, Locked

Correct Wrench Provided? Yes

Record the number of turns required to Close and Open the PIV completely. 13

Was a Main Drain Test performed after the PIV was exercised? Yes

TAMPER SWITCHES

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 Basement mech rm Backflow control valve 1 tamper Tamper Switch —

Dmitriy Petrovich Chayka

10/07/2021 Passed

2 Basement mech rm Backflow control valve 2 tamper Tamper Switch —

Dmitriy Petrovich Chayka

10/07/2021 Passed

3 Basement mech rm Forward flow control valve tamper Tamper Switch —

Dmitriy Petrovich Chayka

10/07/2021 Passed

4 Outside Piv tamper Tamper Switch — Dmitriy Petrovich

Chayka 10/07/2021 Passed

WATER FLOW SWITCHES

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 Basement mech rm Wet sys flow alarm Water Flow Switch — Dmitriy Petrovich

Chayka 10/07/2021 Passed

Time Delay (in seconds) 40

Open test connection/bypass. Did water flow activate the alarm? Yes

Sprinkler–Annual

Customer: National Interagency Fire Center Building: Bldg 100 Administration

Sprinkler | 10/07/2021 Page 4 of 6

WET SYSTEMS

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 Basement mech rm Wet sys Wet System — Dmitriy Petrovich

Chayka 10/07/2021 Passed

Make & Model 6” shotgun riser

Hydraulic Name Plate Present Yes

Record The Coverage Area Defined On The Hydraulic Plate Remote area 2 video production

580.42 gpm at 39.093 psi

Drains Leak Tight Yes

Gauges Reading Normal PSI Yes

Record The Pressure (PSI) Shown On The System Side Pressure Gauge. 65

Did alarm valves, water flow alarm devices, and retards test satisfactorily? Yes

Inspector Test Opened & Free Of Obstruction / Discoloration Yes

Notes:

• System is new was installed in 1-25-2021

Recommendations

Inspector Signature

Inspector Name Dmitriy Chayka Date 10/07/2021

Signature of the

Maintenance

Printed name of the Maintenance Ray Martinez Date 10/07/2021

Sprinkler–Annual

Customer: National Interagency Fire Center Building: Bldg 100 Administration

Sprinkler | 10/07/2021 Page 5 of 6

DEVICE NOTE IMAGE APPENDICES

Sprinkler–Annual

Customer: National Interagency Fire Center Building: Bldg 100 Administration

Sprinkler | 10/07/2021 Page 6 of 6

CUSTOMER DETAILS

Customer Name: National Interagency Fire Center Building Name: Bldg 100 Administration Building Address: 3906 S Vista Ave, Boise, ID, 83705

INSPECTION DETAILS

Work Order # 50620290 Date: 10/07/2021 Frequency: Annual

SERVICE PROVIDER INFORMATION

Name: Johnson Controls North America Office Address: 8783 West Hackamore Drive Suite 6 Boise ID 83709 Office Phone: 208-376-2111

INSPECTOR DETAILS

Name: Randy Montano License: Factory Trained

Deficiencies / Recommendations

1. List of other deficiencies you have found during this inspection. Not Applicable

2. Recommendations noted and explained to the customer. Not Applicable

INSPECTION RESULTS SUMMARY

DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT NOT INSPECTED % INSPECTED

Backflow Double Check Assembly Test

1 1 0 0 0 100

DEVICE DEFICIENCIES

No device deficiencies in this inspection.

Backflow Preventer Work Order # 50620290 c9c9d631-a920-4d18-8e44-b73cd3357a45 | 10/07/2021 Page 1 of 3

BACKFLOW DOUBLE CHECK ASSEMBLY TEST

# LOCATION DESCRIPTION MANUFACTURER MODEL SERIAL # SIZE BARCODE INSPECTOR DATE RESULT

1 — Fire Backflow riser room basement

AMES Colt 200 UD-0859 6” — Randy David

Montano 10/07/2021 Passed

Use of Backflow Fire

Type of Backflow DC

Size of Backflow 6

Manufacturer and Model of Backflow AMES Colt 200

Serial Number of Backflow UD-0859

Water Meter Manufacturer / Brand N/A

Water Meter Serial Number N/A

Water Meter Reading N/A

Test Gauge Manufacturer and Model Midwest instruments 845

Test Gauge Serial # 08061430

Test Gauge Date of Calibration 06/21/2021

Who is the Licensing Authority? Randy Montano

Inspector Certificate / License # 23748

What is the Expiration Date of the License? 03/08/2022

Authorization to turn the water off provided by: Ray Martinez

Time of Service Interruption 8:45

Time of Service Restored 9:15

Backflow Assembly Valves Locked or Sealed Open No

Did backflow pass forward flow test at the designed flow rate including the hose stream demand where hydrants or hose stations are downstream of backflow device?

Yes

Static Pressure at Time of Test? 55

Check Valve #1 Held at What PSID (Minimum 1 PSID)? 1.4

Check Valve #2 Held at What PSID (Minimum 1 PSID)? 2.0

Check Valve #2 Held Back Pressure? Yes

Number 1 Shutoff Valve Held Tight? Yes

Number 2 Shutoff Valve Held Tight? Yes

Backflow Service Restored Yes

Inspector Signature

Inspector Name Randy Montano Date 10/07/2021

Signature of the

Maintenance supervisor

Printed name of the Maintenance supervisor Ray Martinez Date 10/07/2021

Backflow Preventer Work Order # 50620290 c9c9d631-a920-4d18-8e44-b73cd3357a45 | 10/07/2021 Page 2 of 3

APPENDICES

Backflow Preventer Work Order # 50620290 c9c9d631-a920-4d18-8e44-b73cd3357a45 | 10/07/2021 Page 3 of 3

TERMS AND CONDITIONS

1. Limitation of Liability; Limitations Of Remedy. It is understood and agreed by the Customer that Company is not an insurer and that insurance coverage, if any, shall be obtained by the Customer and that amounts payable to Company hereunder are based upon the value of the services and the scope of liability set forth in this agreement and are unrelated to the value of the Customer's property and the property of others located on the premises. Customer agrees to look exclusively to the Customer's insurer to recover for injuries or damage in the event of any loss or injury and that Customer releases and waives all right of recovery against Company arising by way of subrogation. Company makes no guaranty or Warranty, including any implied warranty of merchantability or fitness for a particular purpose that equipment or services supplied by Company will detect or avert occurrences or the consequences there from that the equipment or service was designed to detect or avert.

It is impractical and extremely difficult to fix the actual damages, if any, which may proximately result from failure on the part of Company to perform any of its obligations under this agreement. Accordingly, Customer agrees that, Company shall be exempt from liability for any loss, damage or injury arising directly or indirectly from occurrences, or the consequences therefrom, which the equipment or service was designed to detect or avert. Should Company be found liable for any loss, damage or injury arising from a failure of the equipment or service in any respect, Company's liability shall be limited to an amount equal to the agreement price (as increased by the price for any additional work) or where the time and material payment term is selected, Customer's time and material payments to Company. Where this agreement covers multiple sites, liability shall be limited to the amount of the payments allocable to the site where the incident occurred. Such sum shall be complete and exclusive. If Customer desires Company to assume greater liability, the parties shall amend this agreement by attaching a rider setting forth the amount of additional liability and the additional amount payable by the Customer for the assumption by Company of such greater liability, provided however that such rider shall in no way be interpreted to hold Company as an insurer. IN NO EVENT SHALL COMPANY BE LIABLE FOR ANY DAMAGE, LOSS, INJURY, OR ANY OTHER CLAIM ARISING FROM ANY SERVICING, ALTERATIONS, MODIFICATIONS, CHANGES, OR MOVEMENTS OF THE COVERED SYSTEM(S) OR ANY OF ITS COMPONENT PARTS BY THE CUSTOMER OR ANY THIRD PARTY. COMPANY SHALL NOT BE LIABLE FOR INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND, INCLUDING BUT NOT LIMITED TO DAMAGES ARISING FROM THE USE, LOSS OF THE USE, PERFORMANCE, OR FAILURE OF THE COVERED SYSTEM(S) TO PERFORM. The limitations of liability set forth in this agreement shall inure to the benefit of all parents, subsidiaries and affiliates of Company, whether direct or indirect, Company's employees, agents, officers and directors.

2. Limited Warranty. COMPANY WARRANTS THAT ITS WORKMANSHIP AND MATERIAL FURNISHED UNDER THIS AGREEMENT WILL BE FREE FROM DEFECTS FOR A PERIOD OF NINETY (90) DAYS FROM THE DATE OF FURNISHING. Where Company provides product or equipment of others, Company will warrant the product or equipment only to the extent warranted by such third party. EXCEPT AS EXPRESSLY SET FORTH HEREIN, COMPANY DISCLAIMS ALL WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THE SERVICES PERFORMED OR THE PRODUCTS, SYSTEMS OR EQUIPMENT, IF ANY, SUPPORTED HEREUNDER. COMPANY MAKES NO WARRANTY OR REPRESENTATION, AND UNDERTAKES NO OBLIGATION TO ENSURE BY THE SERVICES PERFORMED UNDER THIS AGREEMENT, THAT COMPANY'S PRODUCTS OR THE SYSTEMS OR EQUIPMENT OF THE CUSTOMER WILL CORRECTLY HANDLE THE PROCESSING OF CALENDAR DATES BEFORE OR AFTER DECEMBER 31, 1999.

3. Indemnity. Customer agrees to indemnify, hold harmless and defend Company against any and all losses, damages, costs, including expert fees and costs, and expenses including reasonable defense costs, arising from any and all third party claims for personal injury, death, property damage or economic loss, including specifically any damages resulting from the exposure of workers to Hazardous Conditions whether or not Customer pre-notifies Company of the existence of said hazardous conditions, arising in any way from any act or omission of Customer or Company relating in any way to this agreement, including but not limited to the Services under this agreement, whether such claims are based upon contract, warranty, tort (including but not limited to active or passive negligence), strict liability or otherwise. The company reserves the right to select counsel to represent it in any such action.

4. Hazardous Materials. Customer represents that, except to the extent that Company has been given written notice of the following hazards prior to the execution of this agreement, to the best of Customer's knowledge there is no:

◦ "permit confined space," as defined by OSHA, or space in which work must be performed that, because of its construction, location, contents or work activity therein, accumulation of a hazardous gas, vapour, dust or fume or the creation of an ox

◦ risk of infectious disease,

◦ need for air monitoring, respiratory protection, or other medical risk

◦ asbestos, asbestos-containing material, formaldehyde or other potentially toxic or otherwise hazardous material contained in or on the surface of the floors, walls, ceilings, insulation or other structural components of the area of any building.

All of the above are hereinafter referred to as "Hazardous Conditions". Company shall have the right to rely on the representations listed above. If hazardous conditions are encountered by Company during the course of Company's work, the discovery of such conditions shall constitute an event beyond Company's control and Company shall have no obligation to further perform in the area where the hazardous conditions exist until the area has been made safe by Customer as certified in writing by an independent testing agency, and Customer shall pay disruption expenses and re-mobilization expenses as determined by Company. This agreement does not provide for the cost of capture, containment, or disposal of any hazardous waste materials, or hazardous materials, encountered in any of the Covered System(s) and/or during the performance of the Services. Said materials shall at all times remain the responsibility and property of Customer. The company shall not be responsible for the testing, removal or disposal of such hazardous materials.

5. Equipment Disconnections. This represents Company's notice to you that the system(s)/device(s) listed on the face of this agreement as temporarily or permanently disconnected are no longer in service and, thus, cannot detect, perform and/or report oc

6. General. Unless otherwise specified, work shall be performed during company's regular business hours,, exclusive of Saturdays, Sundays and Company holidays. All work is subject to review and rebilling in accordance with the terms and conditions of Customer's agreement/contract with Company, if one is in effect. Company shall not be responsible for failure to render services due to causes beyond its control, including but not limited to material shortages, work stoppages, fires, civil disobedience or unrest, severe weather, fire or any other cause beyond the control of Company. Customer is aware that the Limitation of Liability and other provisions set forth in any existing agreement/contract, if one is in effect, or set forth above, apply to services performed and materials supplied. The terms of this agreement shall govern notwithstanding any inconsistent or additional terms and conditions in any purchase order or other document submitted by the Customer.

Backflow Preventer Work Order # 50620290 c9c9d631-a920-4d18-8e44-b73cd3357a45 | 10/07/2021 Page 1 of 1

BUILDING NAME: Bldg 106 Owyhee BUILDING ADDRESS: 2350 Robinson Rd, Boise, ID, 83705 INSPECTION TYPE: Sprinkler FREQUENCY: Annual

WORK ORDER: 50620286

INSPECTION END DATE: 10/08/2021

INSPECTOR (s): Dmitriy Petrovich Chayka

INSPECTOR LICENSE: NICET II # 137370

ACCOUNT NAME: Johnson Controls North America OFFICE ADDRESS: 8783 W Hackamore dr, Boise ID 83709

OFFICE PHONE: 208-376-2111

OFFICE LICENSE:

TIMEZONE: MDT

SPRINKLER INSPECTION REPORT

DEVICE DEFICIENCIES

No device deficiencies in this inspection.

General

To be Answered with the Owner

1. Have there been any changes in the occupancy classification, machinery or operations since the last inspection? No

2. Have there been any changes or repairs to the fire protection systems since the last inspection? No

3. Have you had an internal pipe inspection performed in the last 5 years? Yes

4. Date the internal pipe inspection was performed? 02/11/2020

To be Answered by the Inspector

1. Have the sprinkler systems been extended to all areas of the building? Yes

2. Are all exterior openings protected against the entrance of cold air? Yes

3. Date Backflow Devices Were Tested 10/08/2021

4. Number Of Water Gauges 2

5. Are all Tanks, Fire Pumps, and Fire Department Connections Inspected and Tested Per NFPA 25? Yes

6. All Systems Restored To Normal Yes

Water Supplies

1. Type City

Control Valve Questions

1. Are all sprinkler system main control valves and all other valves in the appropriate open or closed position? Yes

2. Are all control valves sealed, locked, or supervised, in the appropriate open or closed position? Yes

Alarms

1. Did the electric alarms operate during testing? Yes

2. Did the supervisory alarms operate during testing? Yes

Sprinklers - Piping

1. Were All Sprinklers Made After 1920 Yes

2. Quick Response Sprinklers 20 years or older? No

3. Do sprinklers generally appear to be free of corrosion, paint, or loading and visible obstructions? Yes

4. Is the buildings sprinklers inventory list located within the sprinkler spare head cabinet? No

5. Are appropriate number of extra sprinklers and sprinkler wrenches available on the premises? Yes

6.

Type of sprinkler heads

-Gl5601 1/2” 155* qr white pendent -Gl5601 1/2” 200* qr brass pendent

7. Does there appear to be proper clearance between the top of all storage and the sprinkler deflector? Yes

8. Does the exposed exterior condition of piping, drain valves, check valves, hangers, pressure gauges, open sprinklers and strainers appear to be satisfactory?

Yes

Sprinkler–Annual

Customer: National Interagency Fire Center Building: Bldg 106 Owyhee

Address: 2350 Robinson Rd, Boise, ID, 83705

Sprinkler | 10/08/2021 Page 1 of 5

INSPECTION RESULTS SUMMARY

DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT

Control Valve 2 2 0 0

Fire Dept. Connection 1 1 0 0

Tamper Switch 2 2 0 0

Water Flow Switch 1 1 0 0

Main Drain Test 1 1 0 0

Wet System 1 1 0 0

CONTROL VALVES AGG

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 1011 Backflow control valve

Control Valve —

Dmitriy Petrovich Chayka

10/08/2021 Passed

Type and Size 3” butterfly

Easily Accessible? Yes

Signs? Yes

Valve in the Appropriate Open or Closed Position? Yes

Sealed, Locked, and/or Supervised Supervised

Free from External Leaks? Yes

Control Valve Fully Exercised? Yes

2 Outside 1011 Backflow control valve

Control Valve —

Dmitriy Petrovich Chayka

10/08/2021 Passed

Type and Size 3” butterfly

Easily Accessible? Yes

Signs? No

Valve in the Appropriate Open or Closed Position? Yes

Sealed, Locked, and/or Supervised Supervised

Free from External Leaks? Yes

Control Valve Fully Exercised? Yes

FIRE DEPARTMENT CONNECTIONS

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 SW corner outside FDC Fire Dept. Connection — Dmitriy Petrovich

Chayka 10/08/2021 Passed

Is FDC Visible / Accessible? Yes

Are Couplings / Swivels / Plugs / Caps in place? Yes

Identification Signs In Place Yes

Are Check Valve / Gaskets / Ball Drips In Place? Yes

* Check valve is above ceiling tile in sw corner of bldg

FDC Check Valves Internal Inspection Date 02/11/2020

Sprinkler–Annual

Customer: National Interagency Fire Center Building: Bldg 106 Owyhee

Sprinkler | 10/08/2021 Page 2 of 5

MAIN DRAIN TESTS

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 1011 Main drain test Main Drain Test — Dmitriy Petrovich

Chayka 10/08/2021 Passed

Test pipe located On riser

Size of test pipe 1 1/2”

Previous Main Drain Test Date 11/04/2019

Previous Main Drain Static Pressure 50

Previous Main Drain Residual Pressure 40

Static supply pressure 50

Residual Pressure 34

Time to return to normal system pressure Instant

Static supply pressure after completion of test 43

Main drain opened & free of obstruction discoloration? Yes

TAMPER SWITCHES

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 1011 Backflow control valve 1 tamper Tamper Switch —

Dmitriy Petrovich Chayka

10/08/2021 Passed

2 Outside 1011 Backflow control valve 2 tamper Tamper Switch —

Dmitriy Petrovich Chayka

10/08/2021 Passed

WATER FLOW SWITCHES

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 1011 Wet flow alarm Water Flow Switch — Dmitriy Petrovich

Chayka 10/08/2021 Passed

Time Delay (in seconds) 50

Open test connection/bypass. Did water flow activate the alarm? Yes

WET SYSTEMS

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 1011 Wet sys Wet System — Dmitriy Petrovich

Chayka 10/08/2021 Passed

Make & Model 3” shotgun riser

Hydraulic Name Plate Present Yes

Record The Coverage Area Defined On The Hydraulic Plate Light hazard

220.188 gpm at 30.939 psi

Drains Leak Tight Yes

Gauges Reading Normal PSI Yes

Record The Pressure (PSI) Shown On The System Side Pressure Gauge. 50

Did alarm valves, water flow alarm devices, and retards test satisfactorily? Yes

Inspector Test Opened & Free Of Obstruction / Discoloration Yes

Date the internal pipe inspection was performed? 02/11/2020

Date of Gauges Replacement 02/11/2020

Sprinkler–Annual

Customer: National Interagency Fire Center Building: Bldg 106 Owyhee

Sprinkler | 10/08/2021 Page 3 of 5

Recommendations

1. The inspector suggests the following necessary improvements. These suggestions are not the result of an engineering survey and do not reflect conditions above ceilings or in concealed spaces.

Recommend installing a lock on the Backflow control valve 2 since it’s outside.

Inspector Signature

Inspector Name Dmitriy Chayka Date 10/08/2021

Signature of the

Maintenance

Printed name of the Maintenance Ray Martinez Date 10/08/2021

Sprinkler–Annual

Customer: National Interagency Fire Center Building: Bldg 106 Owyhee

Sprinkler | 10/08/2021 Page 4 of 5

Customer: National Interagency Fire Center Building: Bldg 106 Owyhee

Sprinkler | 10/08/2021 Page 5 of 5

Building Name: Bldg 106 Owyhee Building Address: 2350 Robinson Rd, Boise, ID, 83705

INSPECTION DETAILS

Work Order # 50620290 Date: 10/08/2021 Frequency: Annual

SERVICE PROVIDER INFORMATION

Name: Johnson Controls North America Office Address: 8783 West Hackamore Drive Suite 6 Boise ID 83709 Office Phone: 208-376-2111

INSPECTOR DETAILS

Name: Randy Montano License: Factory Trained

Deficiencies / Recommendations

1. List of other deficiencies you have found during this inspection. Not Applicable

2. Recommendations noted and explained to the customer. Not Applicable

INSPECTION RESULTS SUMMARY

DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT NOT INSPECTED % INSPECTED

Backflow Double Check Assembly Test

1 1 0 0 0 100

DEVICE DEFICIENCIES

No device deficiencies in this inspection.

Backflow Preventer Work Order # 50620290 dc05dec0-6759-4a31-bf1f-21d125951ed2 | 10/08/2021 Page 1 of 3

1 — Fire Backflow AMES Colt 200 JE-0966 3” — Randy David

Montano 10/08/2021 Passed

Use of Backflow Fire

Type of Backflow DC

Size of Backflow 3

Manufacturer and Model of Backflow AMES Colt 200

Serial Number of Backflow JE-0966

Water Meter Manufacturer / Brand N/A

Water Meter Serial Number N/A

Water Meter Reading N/A

Test Gauge Manufacturer and Model Midwest instruments 845

Test Gauge Serial # 08061430

Test Gauge Date of Calibration 06/21/2021

Who is the Licensing Authority? Randy Montano

Inspector Certificate / License # 23748

What is the Expiration Date of the License? 03/08/2022

Authorization to turn the water off provided by: Ray Martinez

Time of Service Interruption 7:30

Time of Service Restored 7:50

Backflow Assembly Valves Locked or Sealed Open No

Did backflow pass forward flow test at the designed flow rate including the hose stream demand where hydrants or hose stations are downstream of backflow device?

Yes

Static Pressure at Time of Test? 55

Check Valve #1 Held at What PSID (Minimum 1 PSID)? 3.6

Check Valve #2 Held at What PSID (Minimum 1 PSID)? 4.4

Check Valve #2 Held Back Pressure? Yes

Number 1 Shutoff Valve Held Tight? Yes

Number 2 Shutoff Valve Held Tight? Yes

Backflow Service Restored Yes

Inspector Signature

Inspector Name Randy Montano Date 10/08/2021

Signature of the

Maintenance supervisor

Printed name of the Maintenance supervisor Ray Martinez Date 10/08/2021

Backflow Preventer Work Order # 50620290 dc05dec0-6759-4a31-bf1f-21d125951ed2 | 10/08/2021 Page 2 of 3

Work Order # 50620290 dc05dec0-6759-4a31-bf1f-21d125951ed2 | 10/08/2021 Page 3 of 3

1. Limitation of Liability; Limitations Of Remedy. It is understood and agreed by the Customer that Company is not an insurer and that insurance coverage, if any, shall be obtained by the Customer and that amounts payable to Company hereunder are based upon the value of the services and the scope of liability set forth in this agreement and are unrelated to the value of the Customer's property and the property of others located on the premises. Customer agrees to look exclusively to the Customer's insurer to recover for injuries or damage in the event of any loss or injury and that Customer releases and waives all right of recovery against Company arising by way of subrogation. Company makes no guaranty or Warranty, including any implied warranty of merchantability or fitness for a particular purpose that equipment or services supplied by Company will detect or avert occurrences or the consequences there from that the equipment or service was designed to detect or avert.

It is impractical and extremely difficult to fix the actual damages, if any, which may proximately result from failure on the part of Company to perform any of its obligations under this agreement. Accordingly, Customer agrees that, Company shall be exempt from liability for any loss, damage or injury arising directly or indirectly from occurrences, or the consequences therefrom, which the equipment or service was designed to detect or avert. Should Company be found liable for any loss, damage or injury arising from a failure of the equipment or service in any respect, Company's liability shall be limited to an amount equal to the agreement price (as increased by the price for any additional work) or where the time and material payment term is selected, Customer's time and material payments to Company. Where this agreement covers multiple sites, liability shall be limited to the amount of the payments allocable to the site where the incident occurred. Such sum shall be complete and exclusive. If Customer desires Company to assume greater liability, the parties shall amend this agreement by attaching a rider setting forth the amount of additional liability and the additional amount payable by the Customer for the assumption by Company of such greater liability, provided however that such rider shall in no way be interpreted to hold Company as an insurer. IN NO EVENT SHALL COMPANY BE LIABLE FOR ANY DAMAGE, LOSS, INJURY, OR ANY OTHER CLAIM ARISING FROM ANY SERVICING, ALTERATIONS, MODIFICATIONS, CHANGES, OR MOVEMENTS OF THE COVERED SYSTEM(S) OR ANY OF ITS COMPONENT PARTS BY THE CUSTOMER OR ANY THIRD PARTY. COMPANY SHALL NOT BE LIABLE FOR INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND, INCLUDING BUT NOT LIMITED TO DAMAGES ARISING FROM THE USE, LOSS OF THE USE, PERFORMANCE, OR FAILURE OF THE COVERED SYSTEM(S) TO PERFORM. The limitations of liability set forth in this agreement shall inure to the benefit of all parents, subsidiaries and affiliates of Company, whether direct or indirect, Company's employees, agents, officers and directors.

2. Limited Warranty. COMPANY WARRANTS THAT ITS WORKMANSHIP AND MATERIAL FURNISHED UNDER THIS AGREEMENT WILL BE FREE FROM DEFECTS FOR A PERIOD OF NINETY (90) DAYS FROM THE DATE OF FURNISHING. Where Company provides product or equipment of others, Company will warrant the product or equipment only to the extent warranted by such third party. EXCEPT AS EXPRESSLY SET FORTH HEREIN, COMPANY DISCLAIMS ALL WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THE SERVICES PERFORMED OR THE PRODUCTS, SYSTEMS OR EQUIPMENT, IF ANY, SUPPORTED HEREUNDER. COMPANY MAKES NO WARRANTY OR REPRESENTATION, AND UNDERTAKES NO OBLIGATION TO ENSURE BY THE SERVICES PERFORMED UNDER THIS AGREEMENT, THAT COMPANY'S PRODUCTS OR THE SYSTEMS OR EQUIPMENT OF THE CUSTOMER WILL CORRECTLY HANDLE THE PROCESSING OF CALENDAR DATES BEFORE OR AFTER DECEMBER 31, 1999.

3. Indemnity. Customer agrees to indemnify, hold harmless and defend Company against any and all losses, damages, costs, including expert fees and costs, and expenses including reasonable defense costs, arising from any and all third party claims for personal injury, death, property damage or economic loss, including specifically any damages resulting from the exposure of workers to Hazardous Conditions whether or not Customer pre-notifies Company of the existence of said hazardous conditions, arising in any way from any act or omission of Customer or Company relating in any way to this agreement, including but not limited to the Services under this agreement, whether such claims are based upon contract, warranty, tort (including but not limited to active or passive negligence), strict liability or otherwise. The company reserves the right to select counsel to represent it in any such action.

4. Hazardous Materials. Customer represents that, except to the extent that Company has been given written notice of the following hazards prior to the execution of this agreement, to the best of Customer's knowledge there is no:

◦ "permit confined space," as defined by OSHA, or space in which work must be performed that, because of its construction, location, contents or work activity therein, accumulation of a hazardous gas, vapour, dust or fume or the creation of an ox

◦ risk of infectious disease,

◦ need for air monitoring, respiratory protection, or other medical risk

◦ asbestos, asbestos-containing material, formaldehyde or other potentially toxic or otherwise hazardous material contained in or on the surface of the floors, walls, ceilings, insulation or other structural components of the area of any building.

All of the above are hereinafter referred to as "Hazardous Conditions". Company shall have the right to rely on the representations listed above. If hazardous conditions are encountered by Company during the course of Company's work, the discovery of such conditions shall constitute an event beyond Company's control and Company shall have no obligation to further perform in the area where the hazardous conditions exist until the area has been made safe by Customer as certified in writing by an independent testing agency, and Customer shall pay disruption expenses and re-mobilization expenses as determined by Company. This agreement does not provide for the cost of capture, containment, or disposal of any hazardous waste materials, or hazardous materials, encountered in any of the Covered System(s) and/or during the performance of the Services. Said materials shall at all times remain the responsibility and property of Customer. The company shall not be responsible for the testing, removal or disposal of such hazardous materials.

5. Equipment Disconnections. This represents Company's notice to you that the system(s)/device(s) listed on the face of this agreement as temporarily or permanently disconnected are no longer in service and, thus, cannot detect, perform and/or report oc

6. General. Unless otherwise specified, work shall be performed during company's regular business hours,, exclusive of Saturdays, Sundays and Company holidays. All work is subject to review and rebilling in accordance with the terms and conditions of Customer's agreement/contract with Company, if one is in effect. Company shall not be responsible for failure to render services due to causes beyond its control, including but not limited to material shortages, work stoppages, fires, civil disobedience or unrest, severe weather, fire or any other cause beyond the control of Company. Customer is aware that the Limitation of Liability and other provisions set forth in any existing agreement/contract, if one is in effect, or set forth above, apply to services performed and materials supplied. The terms of this agreement shall govern notwithstanding any inconsistent or additional terms and conditions in any purchase order or other document submitted by the Customer.

Backflow Preventer Work Order # 50620290 dc05dec0-6759-4a31-bf1f-21d125951ed2 | 10/08/2021 Page 1 of 1

BUILDING NAME: Bldg 115 National Weather Service BUILDING ADDRESS: 3807 S Development Ave, Boise, ID, 83705 CONTACT NAME: Ray Martinez CONTACT E-MAIL: rlmartinez@blm.gov CONTACT ROLE: Maintenance supervisor

CONTACT PHONE: 2088035563

INSPECTION TYPE: Sprinkler FREQUENCY: Annual

WORK ORDER: 50620286

INSPECTION END DATE: 10/08/2021

INSPECTOR (s): Dmitriy Petrovich Chayka

INSPECTOR LICENSE: NICET II # 137370

ACCOUNT NAME: Johnson Controls North America OFFICE ADDRESS: 8783 W Hackamore dr, Boise ID 83709

OFFICE PHONE: 208-376-2111

OFFICE LICENSE:

TIMEZONE: MDT

SPRINKLER INSPECTION REPORT

DEVICE DEFICIENCIES

No device deficiencies in this inspection.

OTHER DEFICIENCIES

-Conduit fitting to the Piv tamper is out of the threads

General

To be Answered with the Owner

1. Have there been any changes in the occupancy classification, machinery or operations since the last inspection? No

2. Have there been any changes or repairs to the fire protection systems since the last inspection? No

3. Have you had an internal pipe inspection performed in the last 5 years? Yes

4. Date the internal pipe inspection was performed? 02/10/2020

To be Answered by the Inspector

1. Have the sprinkler systems been extended to all areas of the building?

Only the basement is covered by sprinklers

No

2. Date Backflow Devices Were Tested 10/08/2021

3. Number Of Water Gauges 2

4. Are all Tanks, Fire Pumps, and Fire Department Connections Inspected and Tested Per NFPA 25? Yes

5. All Systems Restored To Normal Yes

Water Supplies

1. Type City

Control Valve Questions

1. Are all sprinkler system main control valves and all other valves in the appropriate open or closed position? Yes

2. Are all control valves sealed, locked, or supervised, in the appropriate open or closed position? Yes

Alarms

1. Did the electric alarms operate during testing? Yes

2. Did the supervisory alarms operate during testing? Yes

Sprinklers - Piping

1. Were All Sprinklers Made After 1920 Yes

2. Standard Response Sprinklers 50 Years Or Older No

3. Do sprinklers generally appear to be free of corrosion, paint, or loading and visible obstructions? Yes

4. Is the buildings sprinklers inventory list located within the sprinkler spare head cabinet? No

Sprinkler–Annual

Customer: National Interagency Fire Center Building: Bldg 115 National Weather Service

Address: 3807 S Development Ave, Boise, ID, 83705

Sprinkler | 10/08/2021 Page 1 of 6

5. Are appropriate number of extra sprinklers and sprinkler wrenches available on the premises? Yes

6. Type of sprinkler heads -central 1/2” 165* standard brass upright

7. Does there appear to be proper clearance between the top of all storage and the sprinkler deflector? Yes

8. Does the exposed exterior condition of piping, drain valves, check valves, hangers, pressure gauges, open sprinklers and strainers appear to be satisfactory?

Yes

Devices

INSPECTION RESULTS SUMMARY

DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT

Control Valve 2 2 0 0

Fire Dept. Connection 1 1 0 0

PIV 1 1 0 0

Pressure Switch 1 1 0 0

Tamper Switch 3 3 0 0

Main Drain Test 1 1 0 0

Wet System 1 1 0 0

CONTROL VALVES AGG

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 Basement Backflow control valve

Control Valve —

Dmitriy Petrovich Chayka

10/08/2021 Passed

Type and Size 4” os&y

Easily Accessible? Yes

Signs? No

Valve in the Appropriate Open or Closed Position? Yes

Sealed, Locked, and/or Supervised Supervised

Free from External Leaks? Yes

Control Valve Fully Exercised? Yes

2 Basement Backflow control valve

Control Valve —

Dmitriy Petrovich Chayka

10/08/2021 Passed

Type and Size 4” os&y

Easily Accessible? Yes

Signs? No

Valve in the Appropriate Open or Closed Position? Yes

Sealed, Locked, and/or Supervised Supervised

Free from External Leaks? Yes

Control Valve Fully Exercised? Yes

Sprinkler–Annual

Customer: National Interagency Fire Center Building: Bldg 115 National Weather Service

Sprinkler | 10/08/2021 Page 2 of 6

FIRE DEPARTMENT CONNECTIONS

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 In front of bldg FDC Fire Dept. Connection — Dmitriy Petrovich

Chayka 10/08/2021 Passed

Is FDC Visible / Accessible? Yes

Are Couplings / Swivels / Plugs / Caps in place? Yes

Identification Signs In Place Yes

Are Check Valve / Gaskets / Ball Drips In Place? Yes

FDC Check Valves Internal Inspection Date 02/10/2020

MAIN DRAIN TESTS

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 Basement Main drain test Main Drain Test — Dmitriy Petrovich

Chayka 10/08/2021 Passed

Test pipe located On riser

Size of test pipe 2”

Previous Main Drain Test Date 11/05/2019

Previous Main Drain Static Pressure 60

Previous Main Drain Residual Pressure 50

Static supply pressure 60

Residual Pressure 47

Time to return to normal system pressure Instant

Static supply pressure after completion of test 55

Main drain opened & free of obstruction discoloration? Yes

POST INDICATOR VALVES

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 In front of bldg Piv PIV — Dmitriy Petrovich

Chayka 10/08/2021 Passed

Manufacturer and Model Waterous A240

Type of PIV (Wall or Post) Post

Is PIV Easily Accessible? Yes

Is PIV Free From Visual Damage? Yes

Is PIV Free from External Leaks? Yes

Is PIV Open? Yes

Is PIV Sealed, Locked, and/or Supervised? Supervised, Locked

Correct Wrench Provided? Yes

Record the number of turns required to Close and Open the PIV completely. 12.75

Was a Main Drain Test performed after the PIV was exercised? Yes

Notes:

• Piv tamper conduit fitting is not connected Images: DEVICE NOTES IMAGES APPENDIX 1.1

Sprinkler–Annual

Customer: National Interagency Fire Center Building: Bldg 115 National Weather Service

Sprinkler | 10/08/2021 Page 3 of 6

SUPERVISORY POINTS

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 Basement Wet sys flow alarm Pressure Switch — Dmitriy Petrovich

Chayka 10/08/2021 Passed

TAMPER SWITCHES

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 Basement Backflow control valve 1 tamper Tamper Switch —

Dmitriy Petrovich Chayka

10/08/2021 Passed

2 Basement Backflow control valve 2 tamper Tamper Switch —

Dmitriy Petrovich Chayka

10/08/2021 Passed

3 In front of bldg Piv tamper Tamper Switch — Dmitriy Petrovich

Chayka 10/08/2021 Passed

WET SYSTEMS

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 Basement Wet sys Wet System — Dmitriy Petrovich

Chayka 10/08/2021 Passed

Make & Model 4” central alarm valve

What Size is This Wet Pipe valve? 4

Hydraulic Name Plate Present Yes

Record The Coverage Area Defined On The Hydraulic Plate Basement remote area 9207-2

229.68 gpm at 48.26 psi

Inspect Alarm Valve For Exterior Damage Yes

Drains Leak Tight Yes

Trim Piping Leak Tight Yes

Alarm Trim Valves In Normal Position Yes

Gauges Reading Normal PSI Yes

Record The Pressure (PSI) Shown On The Water Supply Pressure Gauge. 55

Record The Pressure (PSI) Shown On The System Side Pressure Gauge. 55

Retard Chamber Leak Tight And In Good Condition Yes

Did alarm valves, water flow alarm devices, and retards test satisfactorily? Yes

Inspector Test Opened & Free Of Obstruction / Discoloration Yes

Date of Internal Inspection of Strainers, Filters, Restriction Orifices 02/10/2020

Date of Check Valves Internal Inspection 02/10/2020

Date the internal pipe inspection was performed? 02/10/2020

Date of Gauges Replacement 02/10/2020

Recommendations

Sprinkler–Annual

Customer: National Interagency Fire Center Building: Bldg 115 National Weather Service

Sprinkler | 10/08/2021 Page 4 of 6

Inspector Signature

Inspector Name Dmitriy Chayka Date 10/08/2021

Signature of the

Maintenance

Printed name of the Maintenance Ray Martinez Date 10/08/2021

Sprinkler–Annual

Customer: National Interagency Fire Center Building: Bldg 115 National Weather Service

Sprinkler | 10/08/2021 Page 5 of 6

LOCATION DESCRIPTION DEVICE BARCODE IMAGES

In front of bldg Piv PIV — DEVICE NOTES IMAGES APPENDIX 1.1

Notes:

• Piv tamper conduit fitting is not connected

Sprinkler–Annual

Customer: National Interagency Fire Center Building: Bldg 115 National Weather Service

Sprinkler | 10/08/2021 Page 6 of 6

Building Name: Bldg 115 National Weather Service Building Address: 3807 S Development Ave, Boise, ID, 83705 Contact Name: Ray Martinez Contact Phone: 2088035563 Contact Email: rlmartinez@blm.gov

INSPECTION…