This document is a specification section outlining requirements for emergency and exit lighting upgrades for a Bureau of Land Management facility. Key requirements include the installation of new emergency lighting units, exit signs, and remote emergency lighting units capable of connecting to an existing monitoring system. The emergency lighting units must operate LED lamps continuously during power outages from either internal or external emergency power supplies. Exit signs must meet UL924 standards and also connect to the monitoring system. Support components for all lighting must comply with section 260529. The contractor will be responsible for providing connections and testing to verify functionality with the existing monitoring system. Products must be submitted for approval, along with shop drawings and manuals. The contractor will perform startup, testing, inspections, and training and provide a two-year warranty on all lighting equipment.

View the file

Other files for this federal contract opportunity

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MAY 2023 LED INTERIOR LIGHTING

BDO MAIN BLDG. EMERGENCY EXIT DEVICES & 265119 - 1

EMERGENCY LIGHTING UPGRADE

SECTION 265213 - EMERGENCY AND EXIT LIGHTING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary

Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Emergency lighting units.

2. Exit signs.

3. Luminaire supports.

1.3 DEFINITIONS

A. CCT: Correlated color temperature.

B. CRI: Color Rendering Index.

C. Emergency Lighting Unit: A lighting unit with internal or external emergency battery powered supply and the means for controlling and charging the battery and unit operation.

D. Fixture: See "Luminaire" Paragraph.

E. Lumen: Measured output of lamp and luminaire, or both.

F. Luminaire: Complete lighting unit, including lamp, reflector, and housing.

1.4 ACTION SUBMITTALS

A. Product Data: For each type of emergency lighting unit, exit sign, and emergency lighting support.

1. Include data on features, accessories, and finishes.

2. Include physical description of the unit and dimensions.

3. Battery and charger for light units.

4. Include life, output of luminaire (lumens, CCT, and CRI), and energy-efficiency data.

5. Include photometric data and adjustment factors based on laboratory tests, complying with IES LM-45, for each luminaire type.

B. Shop Drawings: For nonstandard or custom luminaires.

BDO MAIN BLDG. EMERGENCY EXIT DEVICES & 265119 - 2

EMERGENCY LIGHTING UPGRADE

1. Include plans, elevations, sections, and mounting and attachment details.

2. Include details of equipment assemblies. Indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.

3. Include diagrams for power, signal, and control wiring.

1.5 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For luminaires and lighting systems to include in emergency, operation, and maintenance manuals.

1.6 QUALITY ASSURANCE

A. Luminaire Photometric Data Testing Laboratory Qualifications: Luminaire manufacturer's laboratory that is accredited under the National Volunteer Laboratory Accreditation Program for

Energy Efficient Lighting Products.

B. FM Global Compliance: Luminaires for hazardous locations shall be listed and labeled for indicated class and division of hazard by FM Global.

1.7 DELIVERY, STORAGE, AND HANDLING

A. Protect finishes of exposed surfaces by applying a strippable, temporary protective covering before shipping.

1.8 WARRANTY

A. Warranty: Manufacturer and Installer agree to repair or replace components of luminaires that fail in materials or workmanship within specified warranty period.

1. Warranty Period: Two year(s) from date of Substantial Completion.

B. Special Warranty for Emergency Lighting Batteries: Manufacturer's standard form in which manufacturer of battery-powered emergency lighting unit agrees to repair or replace components of rechargeable batteries that fail in materials or workmanship within specified warranty period.

1. Warranty Period for Emergency Power Unit Batteries: Five years from date of

Substantial Completion. Full warranty shall apply for the entire warranty period.

2. Warranty Period for Self-Powered Exit Sign Batteries: Two years from date of

Substantial Completion. Full warranty shall apply for the entire warranty period.

BDO MAIN BLDG. EMERGENCY EXIT DEVICES & 265119 - 3

EMERGENCY LIGHTING UPGRADE

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Seismic Performance: Luminaires shall withstand the effects of earthquake motions determined according to ASCE/SEI 7.

1. The term "withstand" means "the luminaire will remain in place without separation of any parts when subjected to the seismic forces specified and the luminaire will be fully operational during and after the seismic event."

2.2 GENERAL REQUIREMENTS FOR EMERGENCY LIGHTING

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. All emergency lighting provided shall be capable of connecting to the existing Nexus

Monitoring System. Contractor is responsible to provide connections and testing as required to verify functionality of new devices with existing system

C. NRTL Compliance: Fabricate and label emergency lighting units, exit signs, and batteries to comply with UL 924.

D. Comply with NFPA 70 and NFPA 101.

E. Comply with NEMA LE 4 for recessed luminaires.

F. Lamp Base: Comply with ANSI C81.61 or IEC 60061-1.

G. Bulb Shape: Complying with ANSI C79.1.

H. Internal Type Emergency Power Unit: Self-contained, modular, battery-inverter unit, factory mounted within luminaire body.

1. Emergency Connection: Operate one lamp(s) continuously at an output of 1100 lumens each upon loss of normal power. Connect unswitched circuit to battery-inverter unit and switched circuit to luminaire ballast.

2. Operation: Relay automatically turns lamp on when power-supply circuit voltage drops to

80 percent of nominal voltage or below. Lamp automatically disconnects from battery when voltage approaches deep-discharge level. When normal voltage is restored, relay disconnects lamps from battery, and battery is automatically recharged and floated on charger.

3. Environmental Limitations: Rate equipment for continuous operation under the following conditions unless otherwise indicated:

a. Ambient Temperature: Less than 0 deg F or exceeding 104 deg F, with an average value exceeding 95 deg F over a 24-hour period.

BDO MAIN BLDG. EMERGENCY EXIT DEVICES & 265119 - 4

EMERGENCY LIGHTING UPGRADE

b. Ambient Storage Temperature: Not less than minus 4 deg F and not exceeding 140 deg F.

c. Humidity: More than 95 percent (condensing).

d. Altitude: Exceeding 3300 feet.

4. Nightlight Connection: Operate lamp continuously at 40 percent of rated light output.

5. Test Push-Button and Indicator Light: Visible and accessible without opening luminaire or entering ceiling space.

a. Push Button: Push-to-test type, in unit housing, simulates loss of normal power and demonstrates unit operability.

b. Indicator Light: LED indicates normal power on. Normal glow indicates trickle charge; bright glow indicates charging at end of discharge cycle.

6. Battery: Sealed, maintenance-free, nickel-cadmium type.

7. Charger: Fully automatic, solid-state, constant-current type with sealed power transfer relay.

8. Remote Test: Switch in handheld remote device aimed in direction of tested unit initiates coded infrared signal. Signal reception by factory-installed infrared receiver in tested unit triggers simulation of loss of its normal power supply, providing visual confirmation of either proper or failed emergency response.

9. Integral Self-Test: Factory-installed electronic device automatically initiates code-required test of unit emergency operation at required intervals. Test failure is annunciated by an integral audible alarm and a flashing red LED.

I. External Type: Self-contained, modular, battery-inverter unit, suitable for powering one or more lamps, remote mounted from luminaire.

1. Emergency Connection: Operate LED lamp continuously. Connect unswitched circuit to battery-inverter unit and switched circuit to luminaire.

2. Operation: Relay automatically turns lamp on when power-supply circuit voltage drops to

80 percent of nominal voltage or below. Lamp automatically disconnects from battery when voltage approaches deep-discharge level. When normal voltage is restored, relay disconnects lamps from battery, and battery is automatically recharged and floated on charger.

3. Nightlight Connection: Operate lamp in a remote luminaire continuously.

4. Battery: Sealed, maintenance-free, nickel-cadmium type.

5. Charger: Fully automatic, solid-state, constant-current type.

6. Housing: NEMA 250, Type 1 enclosure listed for installation inside, on top of, or remote from luminaire. Remote assembly shall be located no less than half the distance recommended by the emergency power unit manufacturer, whichever is less.

7. Test Push Button: Push-to-test type, in unit housing, simulates loss of normal power and demonstrates unit operability.

8. LED Indicator Light: Indicates normal power on. Normal glow indicates trickle charge;

bright glow indicates charging at end of discharge cycle.

9. Remote Test: Switch in handheld remote device aimed in direction of tested unit initiates coded infrared signal. Signal reception by factory-installed infrared receiver in tested unit triggers simulation of loss of its normal power supply, providing visual confirmation of either proper or failed emergency response.

BDO MAIN BLDG. EMERGENCY EXIT DEVICES & 265119 - 5

EMERGENCY LIGHTING UPGRADE

10. Integral Self-Test: Factory-installed electronic device automatically initiates code-required test of unit emergency operation at required intervals. Test failure is annunciated by an integral audible alarm and a flashing red LED.

2.3 EMERGENCY LIGHTING

A. General Requirements for Emergency Lighting Units: Self-contained units.

B. Emergency Luminaires:

1. Emergency Luminaires: as indicated on Drawings, with the following additional features:

a. Operating at nominal voltage of 120 V ac.

b. Internal emergency power unit.

c. Rated for installation in damp locations, and for sealed and gasketed luminaires in wet locations.

C. Emergency Lighting Unit:

1. Emergency Lighting Unit: as indicated on Drawings.

2. Operating at nominal voltage of 120 V ac.

3. Wall or ceiling with universal junction box adaptor.

4. UV stable thermoplastic housing.

5. Two LED lamp heads.

6. Internal emergency power unit.

D. Remote Emergency Lighting Units:

1. Emergency Lighting Unit: as indicated on Drawings.

2. Operating at nominal voltage of 120 V ac.

3. Wall or ceiling with universal junction box adaptor.

4. UV stable thermoplastic housing.

5. One or Two LED lamp heads.

6. External emergency power unit.

2.4 EXIT SIGNS

A. General Requirements for Exit Signs: Comply with UL 924; for sign colors, visibility, luminance, and lettering size, comply with authorities having jurisdiction.

B. All exit signs provided shall be capable of connecting to the existing Nexus Monitoring System.

Contractor is responsible to provide connections and testing as required to verify functionality of new devices with existing system

C. Internally Lighted Signs:

1. Operating at nominal voltage of 120 V ac.

2. Lamps for AC Operation: LEDs; 50,000 hours minimum rated lamp life.

BDO MAIN BLDG. EMERGENCY EXIT DEVICES & 265119 - 6

EMERGENCY LIGHTING UPGRADE

3. Self-Powered Exit Signs (Battery Type): Internal emergency power unit.

2.5 LUMINAIRE SUPPORT COMPONENTS

A. Comply with requirements in Section 260529 "Hangers and Supports for Electrical Systems" for channel and angle iron supports and nonmetallic channel and angle supports.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for conditions affecting performance of luminaires.

B. Examine roughing-in for luminaire to verify actual locations of luminaire and electrical connections before luminaire installation.

C. Examine walls, floors, roofs, and ceilings for suitable conditions where emergency lighting luminaires will be installed.

D. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 INSTALLATION

A. Comply with NECA 1.

B. Install luminaires level, plumb, and square with ceilings and walls unless otherwise indicated.

C. Install lamps in each luminaire.

D. Supports:

1. Sized and rated for luminaire and emergency power unit weight.

2. Able to maintain luminaire position when testing emergency power unit.

3. Provide support for luminaire and emergency power unit without causing deflection of ceiling or wall.

4. Luminaire-mounting devices shall be capable of supporting a horizontal force of 100 percent of luminaire and emergency power unit weight and vertical force of 400 percent of luminaire weight.

E. Wall-Mounted Luminaire Support:

1. Attached to structural members in walls.

2. Do not attach luminaires directly to gypsum board.

BDO MAIN BLDG. EMERGENCY EXIT DEVICES & 265119 - 7

EMERGENCY LIGHTING UPGRADE

3.3 IDENTIFICATION

A. Identify system components, wiring, cabling, and terminals. Comply with requirements for identification specified in Section 260553 "Identification for Electrical Systems."

3.4 FIELD QUALITY CONTROL

A. Perform the following tests and inspections:

1. Test for Emergency Lighting: Interrupt power supply to demonstrate proper operation.

Verify transfer from normal power to battery power and retransfer to normal.

B. Luminaire will be considered defective if it does not pass operation tests and inspections.

C. Prepare test and inspection reports.

3.5 STARTUP SERVICE

A. Perform startup service:

1. Charge emergency power units and batteries minimum of 24 hours and conduct one-hour discharge test.

3.6 ADJUSTING

A. Adjustments: Within 12 months of date of Substantial Completion, provide on-site visit to do the following:

1. Inspect all luminaires. Replace lamps, emergency power units, batteries, signs, or luminaires that are defective.

a. Parts and supplies shall be manufacturer's authorized replacement parts and supplies.

2. Conduct short-duration tests on all emergency lighting.

END OF SECTION 265213