Site_Visit_Q___A_0002.pdf
PDF 59 KB Posted
- Attached to
- REMODEL RAVENDALE SURPRISE BARRACKS Federal contract opportunity
- Solicitation number
- 140L1222R0006
About this file
This document contains questions and answers from a site visit for the federal contract opportunity to remodel restrooms at the Ravendale and Surprise Barracks for the Bureau of Land Management California Region. The questions addressed acceptable plumbing materials, which can include any industry standard commercial material that meets local codes such as PEX, ABS, or copper. Ball or gate valves were identified as acceptable shutoff valves, and press fittings could be used if they meet code requirements. The contract documents specify all testing procedures and requirements.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140L1222R0006_Amd_0002.pdf | ||
| B08_Updated_Solicitation_No_140L1222R0006_0001.pdf | ||
| Sol_140L1222R0006_Amd_0001.pdf | ||
| B08_Solicitation_No_140L1222R0006.pdf | ||
| Sol_140L1222R0006.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Ravendale and Surprise Restroom Remodel
Site Visit Questions and Answers
Question 1: What is the acceptable plumbing material for remodel (i.e. PEX, ABS, copper, no-hub cast)?
Answer 1: A specific material was not specified in the contract. The contractor may use any industry standard commercial plumbing material that meets county building codes and is compatible with existing plumbing.
Question 2: What are acceptable valve types (i.e. ball or gate)?
Answer 2: Ball or gate valves are acceptable for water supply shutoffs. The contractor is expected to use Industry standard valves that meet county building code. If more than one valve type meets these conditions the contractor should choose the most appropriate valve for the situation based on their professional knowledge.
Question 3: Are press fittings acceptable for material adaptation?
Answer 3: Yes, provided they meet county building code, are installed per the manufacturer’s recommendations, and function properly without limiting water flow or leaking.
Question 4: What will the testing procedures/requirements be?
Answer 4: All testing procedures and requirements are listed in the contract specifications document.