Amendment -01 - RFI Questions and Answers.pdf

PDF 291 KB Posted

Attached to
Install Boiler Controls Federal contract opportunity
Solicitation number
12405B24R0006
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery

About this file

This document provides details for a federal contract solicitation to install boiler controls. The solicitation seeks proposals to remove existing controls and install a new Fireye Nexus micro modulation control system on two 350 HP Cleaver-Brooks boilers located at the USDA Agricultural Research Service National Poultry Research Center in Athens, Georgia. Offerors must provide labor, supervision, equipment, and materials for the work. Proposals are due by 3:00 pm Central Standard Time on February 27, 2024. Award will be made to the lowest price technically acceptable offer. The contract will have a firm fixed price and result from this solicitation to the responsible offeror whose offer is most advantageous to the government.

View the file

Other files for this federal contract opportunity

Other files attached to Install Boiler Controls, newest first.
File Type Posted
12405B24R0006 - SF-30 Amendment 01.pdf PDF
SOW Boiler Controls.pdf PDF
12405B24R0006 - SF-1449-Request for Proposal.pdf PDF
S C Wage Determination-2015-4469.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

12405B24R0006: RFI Ques ons and Answers

1. In execu ng this project, can one superintendent fulfill the supervision, safety, and QAQC roles?

YES

2. Are contractors required to issue a contract specific QA/QC Plan? NO

3. Are contractors required to issue a contract specific Safety Plan? YES

4. Is this project tax exempt? THE FEDERAL GOVERNMENT IS TAX EXWMPT; CONTRACTORS ARE

NOT.

5. There are only 3 servos on the Statement of Work Packet, a 4th servo is required for the FGR.

The system must have all components required for proper opera on. It is the contractor’s responsibility to provide all items necessary to ensure a complete, fully func onal system that meets this requirement.

6. Will we be conver ng the feedwater pumps to con nuous run pumps? All the Nexus water level control components and daughter board are for a con nuous run system. During the site visit, we learned the pumps are on/off pumps. The system must func on as designed and meet all applicable code requirements. It is the contractor’s responsibility to provide all items necessary to ensure a fully func onal system that meets this requirement.

7. The boiler on the le has a Cleaver Brooks water level control system, the one on the right has a McDonnell Miller level control system, the McDonnell Miller will work fine for this applica on. I would suggest replacing the Cleaver Brooks control system with a McDonnell Miller control system. This will have to be completed to be within the code. The complete system must meet code requirements. It is the contractor’s responsibility to provide all items necessary to ensure a fully func onal system that meets this requirement.

File details come from the government source that posted it. Updated .