Specification Sheet.pdf
PDF 177 KB Posted
- Attached to
- BLDG 374 TSI Controller Replacements Federal contract opportunity
- Solicitation number
- 12305B24Q0200
About this file
This document is a Specification Sheet for a federal contract opportunity to replace aging TSI Adaptive Offset Controllers and Room Pressure monitors throughout the Foreign Disease-Weed Science Research Unit facility at Fort Detrick, Maryland.
The United States Department of Agriculture (USDA), Agricultural Research Service (ARS) is seeking a contractor to provide 14 TSI SureFlow Adaptive Offset Controller Digital Interface Modules (DIMs), 4 TSI SureFlow DIMs, and 4 TSI PresSura premium room pressure monitor DIMs. The equipment must integrate with the building's BACnet-based automation system. This is a total small business set-aside with a NAICS code of 238210 and a $19M size standard. Offers are due by September 5, 2024 and the contract will be awarded on a Lowest Price Technically Acceptable basis. The Government intends to award a Firm Fixed-Price contract without discussions, but reserves the right to conduct discussions if deemed necessary.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| CLAUSES_PROVISIONS.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPECIFICATON SHEET
1. PROJECT TITLE: Building 374 TSI controller/monitor Digital Interface Module (DIM) Replacement
2. PROJECT LOCATION: Foreign Disease-Weed Science Research Unit
1301 Ditto Avenue Fort Detrick, Md 21702
3. INTRODUCTION
The USDA, Agricultural Research Service, Foreign Disease-Weed Science Research Unit has two distinct missions united by a common relationship to plant pathology and the unit’s unique Biosafety Level 3 (BSL-3) plant pathogen containment laboratory and greenhouse facilities.
The mission of the foreign disease program is to develop techniques for the rapid detection and identification of new and emerging crop pathogens, and to provide fundamental information on the biology and epidemiology of emerging pathogens for risk assessment and disease management strategies including the development of resistant plants.
The mission of the weed biological control program is to collect foreign pathogens overseas from weeds in their native habitat, and to evaluate, characterize and release the pathogens in the U.S.
for biological control of introduced weeds, leading to improved, sustainable weed control practices in agricultural systems with reduced dependence on chemical herbicides.
4. BACKGROUND
Building 374, the Plant Pathogen Containment Headhouse/Greenhouse at Fort Detrick, Maryland, is a BSL-3 high containment facility with change-in/change-out protocols. The building consists of laboratory and office space areas. Scientists study high impact domestic and foreign pathogens in the laboratories of Building 374. The building was originally constructed in the mid-1950s and it was last renovated in 2015. The TSI Adaptive Offset Controllers and Room Pressure monitors that were installed during the renovations are scheduled to become obsolete and the units will not be available. The TSI controllers and monitors are an integral part of the buildings automation system and must be functional at all times.
5. PROJECT SUMMARY
The United States Department of Agriculture (USDA), Agricultural Research Service (ARS), Foreign Disease-Weed Science Research Unit intends to replace all aging TSI Adaptive Offset Controllers and Room Pressure monitors throughout the facility.
6. TECHNICAL REQUIREMENTS
Units must integrate to the building automation system using digital communication system BACnet™
Adaptive Offset Controllers Digital Interface Module (DIM) Specifications brand name or equal to:
TSI SureFlow Adaptive Offset Controller DIM (8681-VV-LF-BAC) – Qty 14 TSI SureFlow DIM (8681-TP-BAC) Qty 4 TSI PresSura premium room pressure monitor DIM (RPM20-BAC) Qty 4
• Low Supply Alarm 0 to 30,000 cfm (0 to 14.158 lps)
• High Exhaust Alarm 0 to 30,000 cfm (0 to 14.158 lps)
• Alarm Contacts SPST (NO)* Max Current 5A
• Max voltage 150 VDC, 250 VAC Min switch load 10 mA, 5DC
• Flow Inputs (1) 0 to 10 VDC Supply Flow
• 0 to 10 VDC Exhaust Flow
• (2) 0 to 10 VDC Fume Hood Flow (1 Flow on 8681-BAC)
• Temperature Input 1000 Ω platinum RTD
• Control Outputs 0 to 10 VDC Supply, General
• Exhaust, Reheat
• Operating Temperature 32 to 120˚F (0 to 48.8˚C)
• Input Power 24 VAC, 5W max
• Size (H x W x D) 4.90 in. x 4.90 in. x 1.35 in. (124.5 x124.5 x 34.3 mm)
• Weight 0.7 lb (0.3 kg)
Sensor Specifications
• Range -0.20000 to +0.20000 in. H2O (-50 to + 50 Pa)
• Accuracy ±10% of reading ±0.00001 in. H2O (±0.0025 Pa)
• Resolution 5% of reading
• Temp. Comp. Range 55 to 95˚F (12.7 to 35˚C)
• Power Dissipation 0.16 W at 0 in. H2O 0.20 W at 0.00100 in. H2O (0.25 Pa)
• Size (H x W x D) 3.34 in. x 5.58 in. x 1.94 in. (84.8 x 141.7 x 49.3 mm)
• Weight 0.2 lb (0.1 kg)