Statement of work

Location:

USDA ARS WRPIS Central Ferry research Farm

639 Hastings Hill Rd

Pomeroy Wa 99347.

Contacts:

Contracting Officer: Brian Fien 509-335-3349

Farm Manager: Kurt Tetrick 509-843-3580

Description of Work:

Greenhouse requirement:

2 – 175,000 BTU UDAS sealed combustion unit propane heaters hung from the bow’s and purlen’s; wall vents kits, all gas piping interior and underground, all necessary hardware, and low voltage control wiring to the greenhouse controls.

Pex tube was installed in the floor of the greenhouse for floor heat. Contractor is required to provide the all the necessary heating components for this structure for floor heating including but not limited too.

Boiler unit or units, temperature controls, underground insulated piping connecting to the installed loops, valves and pumps, expansion tank, concentric venting, back flow, pressure regulator, low water cutoff, propane piping, and all necessary high and low voltage electrical. This unit will be housed beside the greenhouse in what we believe to be a 6x6 portable building to house the boiler unit that is anchored down for high winds.

Work Shop Heating Requirement:

Complete installation of a commercial grade 5 Ton Heat pump system with 15KW electrical backup heat adequate for industrial repair shop application.

All electrical wiring (high and Low voltage) with thermostat

All metal framing, filtering, and spiral ducting to evenly distribute air across the 50’ X30’ building.

Removal and disposal of the old heating system and repair the shop roof where the exhaust pipe is now.

** A site visit is not required but highly recommended. For a site visit please contact Brian Fien at 509-335-3349 or Brian.Fien@ars.usda.gov; or our site manager Kurt Tetrick at 509-843-3580 or Kurt.Tertick@ars.usda.gov.