10 Specs.pdf
PDF 552 KB Posted
- Attached to
- INSTALL BACKUP GENERATOR FOR LAB EQUIP B986 Federal contract opportunity
- Solicitation number
- HJZH21-1409
About this file
This solicitation document is for the replacement of backup generators at Building 986 on Joint Base Elmendorf-Richardson in Alaska. The project scope of work and specifications are attached. The anticipated price range for this acquisition is between $500,000 and $1,000,000. The opportunity is set aside for small businesses according to FAR Part 19. A site visit will be held on July 9th at 2pm at Building 986; contact Clayton Hill to attend. The issuing agency is the Department of the Air Force Pacific Air Forces.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 9 SOW.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT NO. HJZH 21-1409 INSTALL BACKUP
GENERATOR FOR LAB EQUIP B986,
JOINT BASE ELMENDORF-RICHARDSON,
ALASKA
SPECIFICATIONS
14 May 2021
Prepared by:
673rd Contracting Squadron JBER, Alaska 99506-2500
INDEX
01010-1
TABLE OF
CONTENTS
DIVISION 3 – CONCRETE
03 30 00 Cast-in-Place Concrete
09 67 23.15 FUEL RESISTIVE RESINOUS FLOORING, 3-COAT SYSTEM
DIVISION 26 – ELECTRICAL
26 07 05.00 00 Electrical Identification 26 32 14.00 10 Diesel-Generator Set 26 36 00.00 10 ATS & By-Pass/Isolation Switch
-- END OF SECTION --
SECTION 03 30 00
CAST-IN-PLACE CONCRETE
PART 1 - GENERAL
1. DESCRIPTION:
1.1 Work covered in this Section includes, but is not limited to:
1.1.1 All cast-in-place concrete.
2. QUALITY ASSURANCE:
2.1 American Concrete Institute (ACI) Specifications, latest edition. Concrete work shall conform to all requirements of ACI 301 Specifications for Structural Concrete for Building, except as modified by the following Supplemental Requirements.
2.2 American Society for Testing Materials Standards and Specifications as noted in ACI 301.
2.3 Concrete Reinforcing Steel Institute: CRSI Manual of Standard Practice "Monolithic Reinforced Concrete"
2.6.1 Reinforcing Bars
a. Reinforcing bars must be deformed, except spirals, load-transfer dowels, and welded wire reinforcement, which may be plain.
b. ASTM A615/A615M with the bars marked A, Grade 60; or ASTM A996/A996M with the bars marked R, Grade 60, or marked A, Grade 60.
c. Reinforcing bars may contain post-consumer or post-industrial recycled content.
d. Plain welded wire reinforcement must conform to ASTM A1064/A1064M, with welded intersections spaced no greater than 12 in. apart in direction of principal reinforcement.
3. SUBMITTALS:
3.1 Manufacturer's Literature for:
3.1.1 Admixtures.
3.2 The selection of concrete proportions shall be in accordance with ACI 301, Article 3.8. Before any concrete is placed for the Project, the Contractor shall submit to the Contracting Officer for review all necessary data showing the method used for determining the proposed concrete mix design, including fine and coarse aggregate gradations; location of all borrow pits and stockpiles to be used in concrete production; proportions of all ingredients; water-cement ratio; slump; air content; 28-day cylinder breaks and other required data for each different concrete type specified. Mix designs and strength test results must be prepared by a qualified materials testing laboratory. (See also 8.2, Durability)
3.3 All ready-mixed concrete dispatched from a batch plant must be accompanied by dispatch slip showing concrete strength, slump, additives, time of introduction of mixing water, and must be signed by plant dispatcher. Truck driver's signature will not meet this requirement.
3.4 Placement Notification: Notify Contracting Officer’s representative 24 hours in advance of each intended concrete placement, and four days prior to scheduled first concrete pour.
3.5 Provide manufacturer's written recommendation for installation of his product.
3.6 Mix design showing entrained air content, cement content, maximum water content, slump range, cement type, and the estimated compressive strength.
3.7 Field and lab test results.
3.8 Submit an anchors design and layout plan.
4. PRODUCT HANDLING:
4.1 Storage of Materials: ACI 304.
5. ENVIRONMENTAL CONDITIONS:
5.1 Cold Weather: ACI 306R. Cold weather is defined as a period when for more than consecutive days the mean daily temperatures drop below 40 F (5 C). When temperatures above 50F (10 C) occur during more than half of any 24-hour period, the concrete should no longer be regarded as winter concrete. Heating of concrete should not exceed 90 F.
5.2 Inclement Weather: Protect freshly placed concrete against damage by infiltration of any adverse weather. When damage might occur, terminate placing against nearest construction joint bulkhead and cover at once with waterproof protection until concrete has set.
5.3 Sprayed-on Protective Coatings: Apply when air temperature is between 50 F (10 C) and 80 F (27 C), relative humidity below 80 percent. Do not apply when rain is forecast within 24 hours.
5.4 Hot weather: ACI 305. work plans must include preparation to limit the temperature affects on concrete. As the selected limiting temperatures, usually but not always between 75 F to 100 F (24C to 38 C) is approached and exceeded, it is likely that the unfavorable effects of high temperature will occur.
PART 2 - PRODUCTS
6. MATERIALS:
6.1 Concrete, General:
6.1.1 Portland Cement: ASTM C 150.
6.1.2 Aggregates: ASTM C 33.
6.1.3 Water: Potable.
6.2 Admixtures:
6.2.1 Air Entrainment: ASTM C 260.
6.2.2 Chemical Admixtures: ASTM C 494.
6.2.3 Pozzolanic Admixtures: ASTM C 494.
6.3 Expansion Joints:
6.3.1 Premolded Filler Strips: ASTM D 1751.
6.4 Control Joints: Non-Staining Material, Wood, Plastic, Metal: Formed to be removed without sampling concrete.
6.5 Curing Materials:
6.5.1 Moist Curing:
6.5.1.1 Mats.
6.5.1.2 Burlap.
6.5.2 Impervious Sheet Covering:
6.5.2.1 Polyethylene Sheeting: ASTM C 171, four (4) mil minimum thickness.
Exterior: black. Interior: white or clear.
6.5.3 Liquid Membrane-Forming Compound: ASTM C 309.
7. MIXES:
7.1 Concrete Mix:
7.1.1 Strength: Strength of concrete shall be as noted or scheduled on the plans.
Concrete shall be 5000 psi concrete minimum, at 28 days.
7.1.2 Aggregate Size:ACI 211-1.
7.1.3 Proportions: ASTM C33, Table 2.
7.1.4 Cement: Five sacks per cy minimum, type I/II or type III.
7.1.5 Maximum aggregate size to be 3/4" minus for finished slabs, 3/4 of minimum clear space between steel or between steel and forms in formed concrete, and 3/8" for grouting concrete masonry.
7.1.6 Air Entrainment: 5% to 7%.
7.1.7 Slump: 2" to 4".
7.2 Job Mixed Concrete:
7.2.1 Mix only in equipment designed for concrete mixing and capable of proportioning components by weight batching.
7.2.2 Mix in power operated drum-type mixer.
7.2.3 Proportions: Same as mix design submitted under requirements of 3.2.
8. ADMIXTURES:
8.1 General:
8.1.1 Other than specified herein, or by reference, admixtures may be used only on written approval of the Contracting Officer.
8.1.2 Submit in Writing: Brand name, description, mix of concrete (including any other admixture), purpose for which used and location in which this concrete is to be placed;
for approval.
8.1.3 All admixtures shall be used in strict conformance with manufacturer's written instructions.
8.2 Durability (ACI 302, Article 3.4):
8.2.1 Air-entrained concrete shall be obtained by the use of an approved air entraining admixture only.
8.3 Calcium Chloride: Shall not be used.
8.4 Chemical Admixtures: Must receive approval by Contracting Officer.
8.5 Pozzolanic Admixtures: Must receive approval by Contracting Officer.
PART 3 - EXECUTION
9. PREPARATION:
9.1 General: ACI 318, Chapter 6.
9.2 Forms: Complete, obtain Contracting Officer's approval before placing concrete.
9.3 Concrete shall be produced in accordance with ACI 301, Chapter 7. Concrete transported by truck mixer or agitator shall be completely discharged within one and one half (1-1/2) hours (1 hour for hot weather concreting) after water has been added to the cement or cement has been added to the aggregate.
9.4 Give Contracting Officer minimum four (4) days notice prior to scheduled first concrete pour.
10. PLACING:
10.1 General: All concrete shall be placed in accordance with ACI 304.
10.2 Construction Joint: Follow ACI 318, Section 6.4, with maximum spacing between joints to be forty (40) feet for interior concrete work where not specified otherwise on the drawings. See EXPANSION & CONTRACTION JOINTS in this Section for jointing details.
10.3 Do not add water to mix after initial mixing.
10.4 Maximum slump for concrete shall be as shown in 7.1.7 above. Where field conditions require slump to exceed that shown, Contractor shall obtain written approval from the Contracting Officer who may require an adjustment to the mix.
10.5 The temperature of the concrete as placed shall not exceed 90 F without the approval of the Contracting Officer. All costs for any precautionary measures required by the Contracting Officer shall be borne by the Contractor. Cold weather concrete must meet the requirements of ACI 301 or ACI 306.1 unless otherwise specified. Do not allow concrete temperature to decrease below 50 degrees F. Obtain approval prior to placing concrete when the ambient temperature is below 40 degrees F or when concrete is likely to be subjected to freezing temperatures within 24 hours. Cover concrete and provide sufficient heat to maintain 50 degrees F minimum adjacent to both the formwork and the structure while curing. Limit the rate of cooling to 37 degrees F in any 1 hour and 50 degrees F per 24 hours after heat application.
11. TESTS:
11.1 Contractor to make a minimum of three test cylinders for each concrete compression test set.
11.2 Cylinders will be stored at job site 24 hours in a specially prepared wooden storage box before delivery to testing laboratory. Contractor to provide wooden box and a safe storage out of direct sunlight. Do not subject cylinders to freezing temperatures.
11.3 A compressive test will be taken at the rate of one test set per 20 CY with at least one test set per day of concrete placed. In any event, not less than one test for each individual pour unless requirement is waived by the Contracting Officer. Additional tests may be required by the Contracting Officer at the Contractor's expense if, in the Contracting Officer's opinion, there appears to be excessive variation in the concrete between loads or the concrete is watered or otherwise mishandled during placement.
11.3.1 Strength tests per ACI 39.
11.3.2 Air content per ASTM C 231.
11.3.3 Slump test per ASTM C 143. Slump for all concrete to conform to ACI 211.1, Table 5.3.1(c).
11.4 Within seven (7) days following date of concrete placement, Contractor shall transport test cylinders to a testing laboratory. Use care in transporting cylinders to preclude damage.
11.5 Contractor will pay for testing cylinders.
11.6 Quality of concrete to be based on average of three 28-day-old test cylinders or two 28 day old test cylinders if a 7-day break is requested by the Contracting Officer.
11.6.1 Adjust mix quantities immediately when results show strengths less than those required.
11.6.2 Test apparent problem areas in accordance with ASTM C-39.
11.6.2.1 Load tests at Contractor's expense where serious doubt exists as to quality of material.
11.6.3 All tests for and corrections of deficiencies at Contractor's expense.
11.7 Deficiencies:
11.7.1 Strength Tests: Where testing laboratory reports on breakage of cylinders shows concrete does not comply with specifications, the Contracting Officer may request further testing of concrete to determine strength of in-place concrete. Such further testing will be obtained by the Contracting Officer and the Contractor shall pay for all such further testing.
11.7.2 Air Content and Slump Tests: Make necessary corrections to bring concrete to specification requirements before placing.
11.8 Replacement Testing: If any rejected concrete is removed, the testing of concrete placed to replace the rejected material will be obtained and paid for by the Contractor.
12. FORM REMOVAL:
12.1 General: Forms shall remain in place for time recommended per ACI 347, Article 3.6.
12.2 Removal: Remove forms with care to avoid damage to concrete.
12.3 Surface defects shall be repaired in accordance with ACI 301, Chapter 9. Proprietary compounds used for adhesion or patching ingredients shall be submitted to the Contracting Officer for approval.
13. FINISHED, FORMED SURFACED:
13.1 General: Perform finishing immediately following form removal. Keep concrete damp until finishing is complete.
13.2 Patching: (Required for all Surfaces)
13.2.1 Cut honeycomb, gravel pockets and voids over 3/4-inch diameter back to solid concrete.
13.2.2 Fill prepared voids with 1:2 cement sand patching mortar.
13.2.3 Fill form tie holes with a non-shrinking patching concrete on exposed faces, patch shall match concrete wall finish.
13.2.4 Slush wetted surface to be patched with 1:1 cement sand grout.
13.2.5 Finish patch flush to and matching adjacent wall surface.
13.2.6 Curing: Damp cure patch for 7 days.
14. FINISHING, EXTERIOR SITE WORK:
14.1 Work includes thrust blocks and anchors as required by plans.
14.2 Finish to true, even lines and leave surfaces free from defects.
15. CURING:
15.1 General:
15.1.1 Concrete shall be protected from premature drying, excessive hot or cold temperature, mechanical injury, or injury from rain or flowing water for 7 days following placing (3 days for Type III cement).
15.1.2 Maintain moist condition throughout curing period.
15.1.3 Commence curing as soon as finishing is complete and moisture has disappeared from surface.
15.2 Curing: Concrete shall be maintained in a continuously moist condition for at least 7 days after placement. Curing shall begin as soon as possible after concrete has been placed and finished. Materials and methods of curing shall be submitted to the Contracting Officer for approval. Unless specific methods are specified otherwise, any of the following curing methods will be allowed:
15.2.1 Moist Curing: Cover with burlap, mats or 1-inch sand, completely cover surface, lap sheet materials 3 inches. Thoroughly saturate cover with water and keep wet.
15.2.2 Impervious Sheet Curing: Thoroughly wet surfaces with a fine water spray.
Completely cover surfaces with waterproof sheet material. Lap all edges 4 inches or more and seal with adhesive or tape. Weight to prevent displacement. Repair or replace when damaged.
15.2.3 Liquid membrane-forming compound (not permitted where hardeners are specified unless specifically required for hardening progress).
15.2.3.1 Use only upon approval of Contracting Officer.
15.2.4 Do not allow surfaces to be alternately wet and dry.
16. CLEAN-UP: Remove all forms and materials and leave project site clear of all debris.
END OF SECTION
DESC Permitted POL Lab (Bldg 986), Fort Richardson, Alaska 03644310
SECTION 09 67 23.15
FUEL RESISTIVE RESINOUS FLOORING, 3-COAT SYSTEM
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM C 679 (2003e1; R 2009) Tack-Free Time of Elastomeric Sealants
ASTM C 884/C 884M (1998; R 2005) Thermal Compatibility between Concrete and Epoxy-Resin Overlay
ASTM D 1308 (2002; R 2007) Effect of Household Chemicals on Clear and Pigmented Organic Finishes
ASTM D 2240 (2005) Standard Test Method for Rubber Property - Durometer Hardness
ASTM D 2370 (1998e1; R 2002) Tensile Properties of Organic Coatings
ASTM D 2621 (1987; R 2005) Infrared Identification of Vehicle Solids from Solvent-Reducible Paints
ASTM D 2697 (2003; R 2008) Volume Nonvolatile Matter in Clear or Pigmented Coatings
ASTM D 3335 (1985a; R 2009) Low Concentrations of Lead, Cadmium, and Cobalt in Paint by Atomic Absorption Spectroscopy
ASTM D 3718 (1985a; R 2005) Low Concentrations of Chromium in Paint by Atomic Absorption Spectroscopy
ASTM D 3925 (2002) Sampling Liquid Paints and Related Pigmented Coatings
ASTM D 412 (2006ae1e2) Standard Test Methods for Vulcanized Rubber and Thermoplastic Elastomers - Tension
ASTM D 4541 (2009) Pull-Off Strength of Coatings Using Portable Adhesion Testers
ASTM D 6237 (2009) Painting Inspectors (Concrete and Masonry Substrates)
SECTION 09 67 23.15 Page 1
ASTM D 638 (2008) Standard Test Method for Tensile Properties of Plastics
ASTM E 11 (2009) Wire Cloth and Sieves for Testing Purposes
ASTM F 1869 (2004) Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride
INTERNATIONAL CONCRETE REPAIR INSTITUTE (ICRI)
ICRI 03732 (1997) Selecting and Specifying Concrete Surface Preparation for Sealers, Coatings, and Polymer Overlays
THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)
SSPC-TU 2 (1997) Design, Installation, and Maintenance of Coating Systems for Concrete Used in Secondary Containment
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
FED-STD-595 (Rev C) Colors Used in Government Procurement
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.1000 Air Contaminants
29 CFR 1910.134 Respiratory Protection
29 CFR 1926.59 Hazard Communication
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval and shall be submitted for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-06 Test Reports
Joint Sealant; G
Thin Film Flooring System; G
Primer; G
Urethane Topcoat; G
White Aluminum Oxide Non-Skid Grit; G
Patch Test Demonstration; G
SECTION 09 67 23.15 Page 2
Adhesion Testing; G
SD-07 Certificates
Flooring System Applicator Qualifications; G
Warranty
SD-08 Manufacturer's Instructions
Joint Sealant
Thin Film Flooring System
SD-11 Closeout Submittals
Inspection Logbook
1.3 QUALITY ASSURANCE
1.3.1 Test Reports
1.3.1.1 Joint Sealant
Submit test results that confirm sealant complies with the requirements of Table 1a. Samples must have been tested within the last three years.
1.3.1.2 Thin Film Flooring System
Submit test results that confirm the thin film flooring system complies with the requirements of Table Ib. Samples must have been tested within the last three years.
1.3.1.3 Primer
Submit test results that confirm the primer complies with the requirements of Table 1c. Samples must have been tested within the last three years.
1.3.1.4 Urethane Topcoat
Submit test results that confirm the urethane topcoat complies with the requirements of Table 1d. Samples must have been tested within the last three years.
1.3.2 Certificates
1.3.2.1 Flooring System Applicator Qualifications
Minimum requirements for the installation contractor are as follows:
Completed three or more jobs within the past two years applying the specified materials to concrete surfaces in which the total area exceeds 200,000 square feet. Submit documentation listing location of work, point of contact at job site, total square footage of applied materials, listing of both materials and equipment used, and validation from coating manufacturer documenting quality of materials purchased per job for work totaling 200,000 square feet within the past two years. In addition to the above requirements, be certified by the material manufacturer(s) to install the submitted coatings and sealant. Submit copy of certificates.
SECTION 09 67 23.15 Page 3
1.3.2.2 Warranty
Warrantee materials and workmanship for a minimum period of one year following coating and sealant application. The following terms and conditions form a part of the warranty: If the applied coating system develops either blisters (chemical), checks, softening, or lifting within one year following application, rework each area at contractor's expense.
The following conditions are excluded from the warranty: A) concrete cracking, flooring system mirrors cracks in concrete; B) cosmetic imperfections due to scratching and gouging; C) application to metallic concrete finishes ; and D) application to concrete with a rate of Moisture Vapor Emission (MVE)greater than 3.5 pounds moisture per 24 hours, 1000 square feet. If the coating system's adhesion is in question, perform one adhesion test per 100 square feet as described in the Article entitled "ADHESION TESTING." To satisfy the warranty, each adhesion test shall produce cohesive failures, concrete removal over 95 percent of each pull-off coupon, and/or adhesion no less than 400 psi. Require two additional adhesion tests to confirm results for each area failing to meet adhesion requirements. Within the warranty period, remove to sound material and rework all areas unable to meet adhesion requirements. There shall be zero percent sealant failures within one year. Within the warranty period, remove and rework all sealant material with chemically attacked surfaces and/or lifting from joint walls. Topcoat cracking over sealant is excluded from warranty.
1.3.3 Product Data
1.3.3.1 Joint Sealant
Submit manufacturer's printed instructions to include detailed application procedures, minimum and maximum application temperatures, and curing procedures. In accordance with 29 CFR 1926.59, include Material Safety Data Sheets (MSDS) for the sealant to be used at the job site.
1.3.3.2 Thin Film Flooring System
Submit manufacturer's printed instructions to include detailed mixing, minimum and maximum application temperatures, acceptable atmospheric and/or interior climatic conditions, application procedures, curing procedures, and procedures for maintenance cleaning of flooring system. Provide explicit instructions detailing surface preparation, recoat windows and remedial actions in case recoat windows are missed, and, if applicable, solvent-wiping between coats with acceptable types and grades of solvents.
In accordance with 29 CFR 1926.59, include MSDSs for the coatings to be used at the job site.
1.4 DELIVERY, STORAGE, AND HANDLING
Store coatings and sealant in spaces with temperatures from 40 degrees F to 75 degrees F. Inspect materials on site for damage prior to use. Return to manufacturer packaged materials in dented, rusty, or leaking containers. Conduct testing by manufacture of returned materials with an expired shelf life and if compliant, reissue a shelf life extension.
1.5 COATING HAZARDS
Ensure that employees are trained in all aspects of the safety plan.
Follow the coating manufacturer's written safety precautions throughout mixing, application, and curing of coatings. Comply with respiratory
SECTION 09 67 23.15 Page 4 protection requirements in 29 CFR 1910.134 and safe levels of airborne contaminants in 29 CFR 1910.1000.
1.6 JOB SITE REFERENCES
Make available to the Contracting Officer at least one copy each of ASTM D 4541, ASTM D 6237, SSPC-TU 2, and ICRI 03732, including replica standards ICRI 03732 CSP 1 through CSP 9, at the job site.
1.7 PATCH TEST DEMONSTRATION
Prior to the submitted flooring system's approval, apply the complete coating system to a 10 foot by 10 foot square section of concrete as prepared in accordance with Part 3 "EXECUTION." Within this area, perform three adhesion tests as described in the Article entitled "ADHESION TESTING." If adhesion testing produces cohesive failures within the concrete, no less than 40 mils concrete removed over 95 percent of each pull-off coupon, and/or adhesion more than400 psi, patch test adhesion is acceptable. If concrete surface preparation was insufficient, apply an additional coating system patch to properly prepared concrete followed by the above adhesion testing. If adhesion results are unacceptable for both the topcoats and the primer, submit a new coating system manufactured by a different coating vendor. Apply a patch of the new coating system and subject patch to the above requirements for adhesion prior to approval. If customer dislikes non-skid grit application, adjustments to the specifications can be made. Grit coarser than #60 aluminum oxide is not recommended.
PART 2 PRODUCTS
2.1 JOINT SEALANT
Formulate the joint sealant to exhibit the properties as listed in Table Ia.
2.2 THIN FILM FLOORING SYSTEM
A three-coat industrial flooring system consisting of primer and two urethane topcoats. Apply the coating system at a Dry Film Thickness (DFT) ranging from 13 to 20 mils and contain a broadcast of aluminum oxide non-skid grit. Formulate the complete flooring system to exhibit the properties as listed in Table Ib. Additional requirements for primer coat and urethane topcoat are listed in the following sub-paragraphs.
2.2.1 Primer Coat
In addition to the requirements of the thin film flooring system, formulate the primer coat to exhibit the properties as listed in Table Ic.
2.2.2 Urethane Topcoat
In addition to the requirements of the thin film flooring system, formulate the urethane top coat to exhibit the properties as listed in Table Id.
2.3 WHITE ALUMINUM OXIDE NON-SKID GRIT
Size #60, dust free (washed and dry), minimum 99 percent pure, having the following sieve analysis when tested using a 2.2 pound sample
(ASTM E 11):
SECTION 09 67 23.15 Page 5
Sieve No. 40 100 percent passing Sieve No. 50 15-30 percent retained Sieve No. 60 70-85 percent retained Sieve No. 70 0-15 percent retained
2.4 PREAPPROVED MATERIALS
Table II contains a listing of vendors with "preapproved materials."
PART 3 EXECUTION
3.1 COATING SAMPLE COLLECTION
The Contracting Officer and QC Manager shall witness all material sampling.
Notify the Contracting Officer a minimum of three days in advance of sampling. Obtain liquid samples of each component of primer and topcoat by random selection from sealed containers and in accordance with ASTM D 3925.
Samples may be either individual cans of liquid material or 1.0 quart quantities of properly mixed, extracted, and sealed liquid material.
Identify samples by designated name, specification number, batch number, project contract number, sample date, intended use, and quantity involved.
When the applied coating system has met the requirements defined in the Article entitled "ADHESION TESTING," return coating to the installation contractor for proper disposal.
3.2 TILE AND TILE ADHESIVE REMOVAL
Remove 100 percent of tile employing one or more of the following techniques: chipping, scraping, sanding, scarification, high-pressure water, and various hand tools. Remove 100 percent of the tile adhesive using solvents and power scrubbing. Remove residual contamination using hot potable water under a minimum of 4,000 psi. Resulting surfaces shall appear clean and display the gray color of concrete.
3.3 JOINT MATERIAL REMOVAL, RE-SAW CUTTING, CRACK CHASING
Remove 100 percent of the existing material in all joints including material bonded to joint walls and base. Rigid material may require the use of saw cutting equipment to remove. Joints may be widened up to 1/8 inch when re-saw cutting. Chase concrete cracks identified for repair and open to a minimum depth of 1/2 inch below crack surface with smooth vertical walls.
3.4 DEGREASING
On both coated and uncoated concrete, degrease entire floor by scrubbing using a solution of hot potable water, 120 degrees F to 170 degrees F, and a concentrated water-based alkaline degreaser. Perform two complete degreasing cycles on the entire floor surface. Allow solution to soak into surfaces prior to scrubbing and remove using hot potable water under a minimum of 4,000 psi. Rinsing is complete when the rinse water appears clear. If the industrial detergent is not biodegradable, collect all rinse water and dispose as hazardous waste. Squeegees and shop vacuums may be used to collect pooling rinse water. Fans may be used to aid drying of floor surfaces.
3.5 SURFACE PREPARATION
Shot blast entire floor to produce a level of coarseness equal to ICRI 03732
SECTION 09 67 23.15 Page 6
CSP 3. Overlap each pass of shot blasting by 1/4 inches to 1/2 inches. Add new shot to shot blasting equipment prior to blasting. Prepare surfaces inaccessible to shot blasting, base of perimeter walls and under secured equipment, using diamond disk grinding and/or light scarification to produce a level of coarseness equal to ICRI 03732 CSP 2 and/or ICRI 03732 CSP 4, respectively. Resulting surfaces shall appear clean and contain the appropriate level of surface coarseness. If the resulting level of cleanliness cannot be determined, place numerous drops of water on surfaces that appear contaminated. If the water drops soak into concrete, the surfaces are free of hydrocarbon contamination (oils, grease, skydrol). If the water drops bead up and do not flatten out, surfaces require additional degreasing as detailed in the Article entitled "DEGREASING." Shot blasting coarse concrete and/or broom finished concrete can produce a level of coarseness equal to ICRI 03732CSP 5: employ a best effort attempt to minimize over shot blasting of coarse concrete. If coarse concrete is encountered, shot blasting to a level of coarseness equal to ICRI 03732 CSP 5 is acceptable: however, extremely coarse concrete can require resurfacing prior to the flooring system's installation. Sweep, vacuum, and run a high powered magnet over all surfaces to be coated, including joints.
3.6 JOINT TREATMENT
Use the "Conventional Sealed Joint" as detailed in Figure 1 of SSPC-TU 2 to seal joints. Employ measures to reduce contamination from equipment and foot traffic. Limit floor access to essential contractor personnel.
Confirm joint surfaces are sufficiently clean.
3.6.1 Install Backer Rod
Install a continuous length of round, closed-cell polyethylene backer rod into each joint using a backer rod tool. For 1/2 inch, 3/8 inch, and 1/4 inch wide joints, place backer rod to a depth of 3/8 inch (depth equals the distance from the concrete's surface to the highest point on the backer rod). For joints greater than or equal to 3/4 inch width, place backer to a depth of 5/8 inch below the concrete's surface. Fit backer rod tight between joint walls (30 percent compression). Remove and reinstall all backer rod that is installed using either the incorrect size (loose fit) or at the incorrect depth. Following backer rod installation, apply painter's tape to surfaces adjacent joints to protect from sealant.
3.6.2 Sealant Application
Apply sealant directly into joints using a bulk-calking gun. At room temperature, the resulting sealant application shall exhibit a concave recess between 1/8 inch to 1/16 inch below the concrete's surface. Remove and reapply cured sealant remaining either flush or greater. Following sealant application, remove painter's tape and sealant drips on concrete surfaces. Cure sealant a minimum of 24 hours, prior to the application of coatings.
3.7 PRE-APPLICATION TESTING FOR CONTAMINATION
Spot check surfaces for oil/grease contamination using the water break test. At a rate of 5 tests per 1000 square feet, place one to two drops of water onto surfaces and observe for beading. Test all other surfaces that show visible signs of potential contamination. Apply additional degreasing techniques to surfaces displaying water beading in accordance with the Article entitled "DEGREASING."
SECTION 09 67 23.15 Page 7
3.8 COATING APPLICATION
Vacuum flooring space one additional time prior to coating application.
3.8.1 Primer Application
Apply primer to flooring space at 7.0 mils to 15.0 mils Dry Film Thickness (DFT). If the prepared concrete resembles an ICRI 03732 CSP 3 surface, apply the primer at a minimum of 7.0 mils DFT. If the prepared concrete resembles an ICRI 03732 CSP 5 surface, apply the primer at a maximum of
15.0 mils DFT. The previously applied sealant may be lightly coated.
3.8.2 Non-Skid Grit Broadcast
Broadcast non-skid grit at a rate of 1.5 pounds per 100 square feet into the second urethane top coat and backroll. Map floor into 600 square foot sections where 9.0 pounds of non-skid grit is pre-weighed, placed into clean buckets and used in its entirety per marked 600 square foot section.
3.8.3 Application of Topcoats
Apply two coats of urethane topcoat to the epoxy primer and broadcast white aluminum oxide non-skid grit directly into the second urethane topcoat.
3.8.3.1 First Topcoat
Apply a full coat of the urethane topcoat at a spreading rate from 2.5 to
3.2 mils Dry Film Thickness (DFT). Stripe coat perimeter edges and around equipment footings. Monitor and record a minimum of one Wet Film Thickness (WFT) reading per 600 square feet of floor surface. Sealant is to be lightly coated.
3.8.3.2 Second Topcoat
Apply a second coat of the urethane topcoat at a spreading rate of 2.5 to
3.2 mils DFT. Stripe coat perimeter edges and around equipment footings.
Monitor and record a minimum of one WFT reading per 600 square feet of floor surface prior to broadcasting non-skid grit. When the correct WFT has been applied per 600 square feet of area, immediately and evenly broadcast non-skid grit directly into the second topcoat of urethane and backroll in two directions. Test the adhesion of the thin film flooring system in accordance with the Article entitled "ADHESION TESTING."
3.8.3.3 Walkway Stripe and Grounding Rod Markings
Place the walkway stripe and grounding rod markings according to Government drawings, if applicable. When the second topcoat is within its recoat window, apply a walkway stripe of the red/orange urethane topcoat at 3.0 mils DFT, completely hiding the top coat, in one coat. If insufficient hiding occurs, apply one additional coat of the walkway stripe. Lightly broadcast non-skid grit into the wet walkway stripe. Use solvent resistant tape to protect the floor coating against stripe coat bleed. A thin clear coat of either epoxy or urethane may be required to prevent stripe coat bleed prior to the full application of the colored stripe coat. Apply grounding rod markings using similar procedures, urethane top coat, and colors and size according to Government drawings.
SECTION 09 67 23.15 Page 8
3.9 CURING
Cure installed materials to display performance equal to manufacturer's product literature. Remove and reapply improperly cured material.
3.10 FIELD TESTS AND INSPECTION
3.10.1 Coating Inspector
The Coating Inspector will be present during all field tests, surface preparation, flooring application, initial cure of the flooring system, and during all flooring repair work. The Coating Inspector will provide all tools/equipment necessary to perform field tests and inspection. The Coating Inspector will be responsible for field tests and specified level of inspection.
3.10.2 Inspection
Document weather conditions, job site occurrences, and report conditions and occurrences potentially detrimental to the flooring system. Prepare a project reference sheet outlining all requirements, tests, test methods, and evaluation criteria, and hold regular meetings with contractor personnel, including shot blasting operators and applicators, to review requirements/evaluation criteria for upcoming work prior to execution. At the start of coating operations and every 1.0 hour following until daily work is complete, record air temperature, substrate temperature, and relative humidity. Following the application of each coat, inspect surfaces for improperly cured material, blisters, inadequate and/or excessive coating thickness, and other defects. Document each inspection, test, non-compliant area, and location of each non-compliant area. List method of evaluation, evaluation criteria, areas requiring rework, and all other pertinent observations.
3.10.2.1 Daily Inspection Report
Submit to the Contracting Officer one copy of the daily inspection report completed each day when performing work under this Section. Use Appendix X1 "Inspection Checklist" of ASTM D 6237 to monitor daily activity and to assist in preparing the daily inspection report. Note each non-compliant issue and each issue identified for rework. Use of forms containing entry blocks for all required data is encouraged. The data shall be legible and presented in a professional format. Submit report within 24 hours of the report date.
3.10.2.2 Inspection Logbook
Record all daily activity related to this section in the Inspection Logbook, including the daily inspection reports, as well as all other pertinent observations and information. Use hard or spiral bound book with consecutively numbered pages. Prior to final payment, submit original Inspection Logbook to the Contracting Officer upon completion of project.
3.10.2.3 Inspection Equipment
Use equipment in good condition, operational within its design range, and calibrated as required by the specified standard for use with each device.
SECTION 09 67 23.15 Page 9
3.10.3 Adhesion Testing
Perform a minimum of three adhesion tests in accordance with ASTM D 4541 to the thin film flooring system. Select three random flooring locations spaced a minimum of 20 feet between each location. Prior to attaching pull-off coupons, lightly sand flooring surface and attach pull-off coupons containing a grit-blasted anchor profile. Adhere directly to the center of each sanded surface a 3/4 inch diameter pull-off coupon. When pull-off coupon adhesive has sufficiently cured, score circumference of each pull-off coupon to concrete substrate. Test adhesion and evaluate results.
If testing produces cohesive failures within the concrete, no less than 40 milsconcrete removed over 95 percent of each pull-off coupon, and/or adhesion more than 400 psi coating system's adhesion is acceptable. If the above requirements are not satisfied, then perform one adhesion test per 100 square feet using the above procedures. Perform two additional tests per non-compliant area to confirm results. Remove to sound material and rework all areas unable to meet adhesion requirements. Repair each adhesion test using a combination of primer, sand-filled epoxy mortar (for deep cohesive failures, if applicable), and two urethane topcoats. Make repairs flush with adjacent coatings and display an equivalent appearance.
3.11 FINAL CLEANUP
Following completion of the work, remove debris, equipment,and materials from the site. Remove temporary connections to Government or contractor furnished water and electrical services. Restore existing facilities in and around the work areas to their original condition.
SECTION 09 67 23.15 Page 10
TABLE I - MATERIALS REQUIREMENTS
TABLE Ia
Test Minimum Requirement (maximum where indicated)
Sealant System Polysulfide (Manganese Cure; MnO2) (two-pack: self-leveling) or Urethane
Percent Volume Solids 100 percent
Chemical Resistance to JP-8 48 hours immersion:
plus 100 Fuel at 70 degrees F 2.0 percent (max) weight increase, (ASTM D 1308) (see note 1) 5.0 percent (max) volume increase,
2.0 percent (max) weight loss
Chemical Resistance to Motor 48 hours immersion:
Oils at 70 degrees F 2.0 percent (max) weight increase (ASTM D 1308) (see note 1) 5.0 percent (max) volume increase
2.0 percent (max) weight loss
Chemical Resistance to Skydrols 48 hours immersion:
at 70 degrees F (ASTM D 1308) 2.0 percent (max) weight increase (see note 1) 5.0 percent (max) volume increase
2.0 percent (max) weight loss
Hardness (ASTM D 2240:Shore A) 20
Tensile Strength (ASTM D 412) 150 psi (or ASTM D 638)
Percent Elongation (ASTM D 412) 500 percent (or ASTM D 638)
Tack Free 12 hours maximum at 65 degrees F(ASTM C 679)
Adhesion to Concrete 140 psi
Adhesion to Urethane Topcoats 140 psi (paintable sealant)
NOTES:
(1) Immerse and test a minimum of three 2 inch by 1/2 inch by 1/2 inch section of cured sealant.
SECTION 09 67 23.15 Page 11
TABLE Ib
Test Minimum Requirement (maximum where indicated)
Tensile Strength (ASTM D 2370) 700 psi
Percent Elongation (ASTM D 2370) 5.0 percent
Adhesion to Concrete (ASTM D 4541) 400 psi or (see note 1) 100 percent failure in concrete
Thermal Compatibility between Concrete 140 degrees F
(ASTM C 884/C 884M)
Heat Resistance, continuous exposure "pass"
Chemical Resistance to JP-8 48 hours immersion:
plus 100 Fuel at 70 degrees F 2.0 percent (max) weight increase (ASTM D 1308)(see note 2) 2.0 percent (max) volume increase
2.0 percent (max) weight loss
Chemical Resistance to Motor Oils 48 hours immersion:
at 70 degrees F (ASTM D 1308)(see note 2) 2.0 percent (max) weight increase
2.0 percent (max) volume increase
2.0 percent (max) weight loss
Chemical Resistance to Skydrols 48 hours immersion:
at 70 degrees F (ASTM D 1308)(see note 2) 2.0 percent (max) weight increase
2.0 percent (max) volume increase
2.0 percent (max) weight loss
Lead (ASTM D 3335) 0.06 percent (max)
Cadmium (ASTM D 3335) 0.06 percent (max)
Chromium (ASTM D 3718) 0.00 percent
NOTES:
(1) When tested for adhesion, coating system shall display 400 psi adhesion and/or remove no less than 40 mils of concrete over 95 percent of each pull-off coupon throughout service.
(2) Immediately following immersion, in addition to the listed requirements, coating system shall be evaluated for blisters, checks, discoloration, softening, and lifting. Coating system shall be visually free of blisters, checks, discoloration, and display both substrate and intercoat adhesion no less than 350 psi (ASTM D 4541).
SECTION 09 67 23.15 Page 12
TABLE Ic
Test Minimum Requirement (maximum where indicated)
Resin System (ASTM D 2621) Epoxy (two-pack)
Percent Volume Solids (ASTM D 2697) 85 percent
Color 17925 (white) or 17875 (ultra-light gray)
Hydrolytic Stability No effect: 30 days immersion in (see note 1) Sodium Hydroxide solution with pH no less than 13.5
Moisture Insensitivity Throughout No effect: Insensitive to Service (ASTM F 1869, ASTM D 4541) moisture vapor emission at rates (see note 2) no more than 3.5 pounds moisture/24 hrs, 1000 square feet
Adhesion to Concrete Throughout 400 psi or Service (ASTM D 4541) 100 percent failure in concrete (see note 3)
NOTES:
(1) Immediately following immersion, primer shall be evaluated for blisters, checks, discoloration, softening, and substrate lifting. Primer shall appear free of blisters, checks and moderate discoloration, and display wet adhesion no less than 350 psi (ASTM D 4541).
(2) During and following application, primer shall remain unaffected by Moisture Vapor Emission (MVE) at rates no more than 3.5 pounds moisture per 24 hours, 1000 square feet: primer shall meet the requirements of Note (3).
Signs of moisture sensitivity include blisters, softening, lifting, and discoloration (whitening).
(3) When tested for in-situ adhesion, primer shall display 400 psi adhesion and/or remove no less than 40 mils of concrete over 95 percent off each pull-off coupon.
SECTION 09 67 23.15 Page 13
TABLE Id
Test Minimum Requirement (maximum where indicated)
Resin System (ASTM D 2621) Aliphatic Urethane (two-pack)
Percent Volume Solids (ASTM D 2697) 51 percent
Topcoat Color (FED-STD-595) 17925 (white) or 17875 (ultra-light gray)
Walkway Stripe Color: Red/Orange, 22197 (red/orange) semi-gloss (FED-STD-595)
Application Thickness per Coat 2.5 mils to 3.2 Dry Film Thickness(DFT)
Hiding Power: Red/Orange Complete hiding of white coatings at 3.2 mils mils DFT(one coat)
Sunlight Resistance Non-yellowing
Heat Resistance, continuous exposure 140 degrees F
Heat Resistance, intermittent exposure 200 degrees F
Chemical Resistance to JP-8 48 hours immersion:
plus 100 Fuel at 70 degrees F 1.0 percent (max) weight increase (ASTM D 1308)(see note 1) 1.0 percent (max) volume increase
1.0 percent (max) weight loss
Chemical Resistance to Motor Oils 48 hour immersion:
at 70 degrees F (ASTM D 1308)(see note 1) 1.0 percent (max) weight increase
1.0 percent (max) volume increase
1.0 percent (max) weight loss
Chemical Resistance to Skydrols 48 hours immersion:
at 70 degrees F (ASTM D 1308)(see note 1) 1.0 percent (max) weight increase
1.0 percent (max) volume increase
1.0 percent (max) weight loss
NOTES:
(1) Immediately following immersion, in addition to the listed requirements, urethane topcoat shall be evaluated for blisters, checks, discoloration, softening, and lifting. Urethane topcoat shall be visually free of blisters, checks, and discoloration, and display adhesion no less than 350 psi (
ASTM D 4541).
SECTION 09 67 23.15 Page 14
TABLE II
PREAPPROVED MATERIALS*
Vendors Materials
Polyspec Primer: 300EX
(281) 397-0033 Topcoat: Tuffrez 235 Sealant: T-2235SL
Tennant Primer: Eco-MPE (see note 1)
(800) 553-8033 Topcoat: VOC-CRU Sealant: N/A (see note 2)
Stonhard Primer: Standard Primer
(856) 779-7500 Topcoat: Stonseal GS6 Sealant: Vulkem 245
Crawford Labs Primer: Florock 4700
(800) 356-7625 Topcoat: Florock Super CRU Sealant: N/A (see note 2)
General Polymers Primer: #3578, Universal Primer
(800) 543-7694 Topcoat: #4618, Polyurethane Enamel Sealant: Cor-Seal PS
NOTES:
(*) Other products may meet specification requirements, Up to specification's date of issue, preapproved materials met specification requirements. It is the user's responsibility to confirm preapproved material formulations have not changed and specification requirements will be met.
(1) ECO-CRE primer is to be used on floors with heavy Skydrol use.
(2) Polyspec T-2235SL sealant may be used.
-- End of Section --
SECTION 09 67 23.15 Page 15
SECTION 16075
ELECTRICAL IDENTIFICATION
16075-1
SECTION 26 07 05.00 00
PART 1 GENERAL
1.1 IDENTIFICATION
A. Provide engraved nameplates, directories, termination points schedules, color-coding, and other identification as shown on Drawings and required in Specifications.
B. Provide identification labels, methods, and materials in submittals. Provide a list of all labels proposed for this Project. All items of the system shall be identified clearly with descriptions indicating purpose, origination, termination, subsystem, and characteristics.
1.2 RELATED WORK
A. Division 15: Mechanical.
PART 2 PRODUCTS
2.1 GENERAL
A. Provide all materials for complete identification of components, equipment, wire, cable, raceways, enclosures, operators, terminations, relays, contacts, controllers, etc., as noted in the following sections.
B. All materials for nameplates and other materials shall be specifically manufactured for use as identification devices.
2.2 MATERIALS
A. Nameplates:
1. Engraved nameplates of laminated plastic with black letters on a white background shall be provided for all enclosures, cabinets, and panels. Nameplates shall identify the individual enclosure, cabinet, or panel. Sizes of nameplates and text may vary depending on application, but in no case shall letters be smaller than 1/4 inch for any engraved nameplate. Nameplates shall be made from heavy-duty laminated plastic.
2.3 ACCEPTABLE MANUFACTURERS
A. Nameplates shall be manufactured by a company regularly engaged in the production of engraved plastic labels, such as Seton or Brady.
SECTION 16075
16075-2
B. Other manufacturer's products may be acceptable if characteristics, quality, appearance, etc. match those of named manufacturers.
PART 3 EXECUTION
3.1 GENERAL
A. All new panels, main, distribution, and branch circuit panelboards, cabinets, enclosures, equipment, contactors, enclosed switches for mechanical equipment, selector switches for mechanical equipment, operators, and controllers shall be labeled with engraved plastic nameplates consisting of a minimum of 3/8 inch tall letters. Affix nameplates to enclosures with countersunk machine screws with lock washers and hexhead nuts.
B. All conductors passing through pull boxes and junction boxes shall be labeled with durable tags having clearly legible data containing appropriate representation, identifying where the conductors originate and the device or equipment served by the conductors.
C. Terminals on terminal strips shall be numbered with durable printed nameplates and typed directories with clear plastic protective covers shall be provided in terminal enclosure which identifies the origin, function, and destination of each conductor.
D. Provide engraved nameplates and other identification as shown on
Drawings and specified in other Sections of this Division.
-- END OF SECTION --
Section 26 32 14.00 10 Page 1
SECTION 26 32 14.00 10
DIESEL-GENERATOR SET, STATIONARY 15-300 KW, STANDBY APPLICATIONS
02/10
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI C39.1 (1981; R 1992) Requirements for Electrical
Analog Indicating Instruments
ASME INTERNATIONAL (ASME)
ASME B16.11 (2016) Forged Fittings, Socket-Welding and
Threaded
ASME B16.3 (2011) Malleable Iron Threaded Fittings, Classes 150 and 300
ASME B16.5 (2017) Pipe Flanges and Flanged Fittings NPS
1/2 Through NPS 24 Metric/Inch Standard
ASME B31.1 (2016; Errata 2016) Power Piping
ASME BPVC SEC IX (2010) BPVC Section IX-Welding and Brazing
Qualifications
ASME BPVC SEC VIII D1 (2015) BPVC Section VIII-Rules for
Construction of Pressure Vessels Division 1
ASSOCIATION OF EDISON ILLUMINATING COMPANIES (AEIC)
AEIC CS8 (2013) Specification for Extruded Dielectric
Shielded Power Cables Rated 5 Through 46 kV
ASTM INTERNATIONAL (ASTM)
ASTM A106/A106M (2014) Standard Specification for Seamless
Carbon Steel Pipe for High-Temperature Service
ASTM A135/A135M (2009; R2014) Standard Specification for
Electric-Resistance-Welded Steel Pipe
ASTM A181/A181M (2014) Standard Specification for Carbon
Steel Forgings, for General-Purpose Piping
Section 26 32 14.00 10 Page 2
ASTM A234/A234M (2017) Standard Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and High Temperature Service
ASTM A53/A53M (2012) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
ASTM B395/B395M (2013) Standard Specification for U-Bend
Seamless Copper and Copper Alloy Heat Exchanger and Condenser Tubes
ASTM D975 (2017a) Standard Specification for Diesel
Fuel Oils
ELECTRICAL GENERATING SYSTEMS ASSOCIATION (EGSA)
EGSA 101P (1995) Performance Standard for Engine Driven
Generator Sets
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 1 (2000; R 2011) General Principles for
Temperature Limits in the Rating of Electric Equipment and for the Evaluation of Electrical Insulation
IEEE 120 (1989; R 2007) Master Test Guide for
Electrical Measurements in Power Circuits
IEEE 404 (2012) Standard for Extruded and Laminated
Dielectric Shielded Cable Joints Rated 2500 V to 500,000 V
IEEE 48 (2009) Standard for Test Procedures and
Requirements for Alternating-Current Cable Terminations Used on Shielded Cables Having Laminated Insulation Rated 2.5 kV through 765 kV or Extruded Insulation Rated 2.5 kV through 500 kV
IEEE 519 (2014) Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems
IEEE 81 (2012) Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System
IEEE C2 (2017; Errata 1-2 2017; INT 1 2017) National
Electrical Safety Code
IEEE Stds Dictionary (2009) IEEE Standards Dictionary: Glossary of
Terms & Definitions
Section 26 32 14.00 10 Page 3
MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS
INDUSTRY (MSS)
MSS SP-58 (1993; Reaffirmed 2010) Pipe Hangers and
Supports - Materials, Design and Manufacture, Selection,…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .